ALTV2432UL Series
CCTV Power Supplies
Installation Guide
Models Include:
• ALTV2432UL • ALTV2432ULCB
- 24VAC @ 7 amp (175VA) - 24VAC @ 7 amp (175VA)
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
• ALTV2432300UL • ALTV2432300ULCB
- 24VAC @ 12.5 amp (300VA) - 24VAC @ 12.5 amp (300VA)
or 28VAC @ 10 amp (280VA). or 28VAC @ 10 amp (280VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
• ALTV2432600UL • ALTV2432600ULCB
- 24VAC @ 25 amp (600VA) - 24VAC @ 25 amp (600VA)
or 28VAC @ 20 amp (560VA). or 28VAC @ 20 amp (560VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
Rev. 020604
Overview:
These Altronix CCTV Power Supplies provide 24VAC/28VAC, (ALTV2432UL and ALTV2432ULCB provide 24VAC),
distributed via thirty-two (32) fuse or PTC protected outputs for powering CCTV Cameras, heaters and other video
accessories.
Thirty-two (32) Output ALTV2432UL Reference Chart:
wer limited)
Altronix
Model Number
ALTV2432UL 24VAC 7 amp 32 - x 3.5 amp 3.5 amp 250V 2.9 amp
ALTV2432ULCB 24VAC 7 amp 32 x - 2.5 amp 3.5 amp 250V 2.9 amp
ALTV2432300UL
ALTV2432300ULCB
Output Voltage
24VAC 12.5 amp
28VAC 10 amp
24VAC 12.5 amp
28VAC 10 amp
(Power)
Total Output Current
Outputs
Number of
32 - x 3.5 amp - 2.7 amp
32 x - 2.5 amp - 2.7 amp
PTC Protected Outputs
(Class 2 po
Outputs
Fuse Protected
(max per output)
Output Current
Main Fuse Ratings
115VAC
50/60Hz Input
Current
24VAC 25 amp
ALTV2432600UL
28VAC 20 amp
24VAC 25 amp
ALTV2432600ULCB
28VAC 20 amp
32 - x 3.5 amp - 5.4 amp
32 x - 2.5 amp - 5.4 amp
Specifications:
• UL Listed for Commercial CCTV Equipment (UL2044).
CUL Listed - CSA Standard C22.2 No.1-98, Audio,
Video and Similar Equipment.
• Surge suppression.
• AC power LED indicator.
ower ON/OFF switch / circuit-breaker.
P
•
• Unit maintains camera synchronization.
• Ease of installation saves time & eliminates costly labor.
• Spare fuses included (on fuse protected models).
Enclosure Dimensions:
13"H x 13.5"W x 3.5"D
Installation Instructions:
1. Mount unit in desired location.
2. Turn OFF main switch on unit.
All units are factory set for 24VAC operation.
3.
For 28VAC operation (where available) adjust unit prior to mounting and applying power as follows: Change the wire
position so that the black wire [28V] is connected to the terminal marked [P] and the yellow wire [24V] is connected
to the terminal marked [S]
Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1-3, pgs. 4-6)
4.
WG or lar
round. Use 18
th g
ear
Keep power limited (PTC protected outputs only) wiring separate from non-power limited wiring.
Minimum .25” spacing must be provided. Use separate knockouts.
5. Measure output voltage before connecting devices. This helps avoid potential damage.
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting
the output voltage.
6. Connect devices to terminals marked [1P - 1N through 16P - 16N] on PD16W/PD16WCB board
(Figs. 1-3, pgs. 4-6), carefull
A
(Figs. 1-3, pgs. 4-6).
.
, secure g
ger for all power connections.
y observing polarity. Terminals marked [1P - 16P] are of the same polarity.
- 2 -
reen lead to
7. Turn main switch on unit to the ON (RESET) position (Figs. 1-3, pgs. 4-6).
8.
Green LED(s) will illuminate when unit is powered.
9.
Upon completion of wiring, secure enclosure door with screws (supplied).
Caution:
Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes
and in accordance with the National Electrical Code. Use 75 C or higher rated UL insulated wiring for
connecting the unit to the mains. Replace fuses only with the same type and rating (3.5 amp/250V).
Terminal Identification:
PD16W - Power Distribution Module
1P - 16P AC output.
1N - 16N AC output.
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated “DANGEROUS VOLTAGE” within the products enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.