Altronix ALTV2432350, ALTV2432350CB, ALTV2432600, ALTV2432600CB Installation Guide

ALTV2432 Series
CCTV Power Supplies
Installation Guide
Models Include:
• ALTV2432 • ALTV2432CB
- 24VAC @ 8A (200VA) - 24VAC @ 8A (200VA) or 28VAC @ 7A (200VA). or 28VAC @ 7A (200VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
- 24VAC @ 14A (350VA) - 24VAC @ 14A (350VA) or 28VAC @ 12.5A (350VA). or 28VAC @ 12.5A (350VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
• ALTV2432600 • ALTV2432600CB
- 24VAC @ 28A (700VA) - 24VAC @ 28A (700VA) or 28VAC @ 25A (700VA). or 28VAC @ 25A (700VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
Rev. 021704
Overview:
ALTV2432 Series CCTV Power Supplies provide 24VAC/28VAC distributed via thirty-two (32) fuse or PTC protected outputs for powering CCTV Cameras, heaters and other video accessories.
Thirty-two (32) Output ALTV2432 Reference Chart:
Total
Output Altronix Model Number
ALTV2432
ALTV2432CB
ALTV2432350
ALTV2432350CB
ALTV2432600
ALTV2432600CB
Output
Voltage
24VAC 8A 28VAC 7A 24VAC 8A 28VAC 7A 24VAC 14A 28VAC 12.5A 24VAC 14A 28VAC 12.5A 24VAC 28A 28VAC 25A 24VAC 28A 28VAC 25A
Current (Power)
Input:
• 115VAC, 50/60Hz.
Output:
• Thirty-Two (32) fuse or PTC protected outputs.
• 24VAC or 28VAC supply current
• Outputs are rated @ 3.5A (fuse) or 2.5A (PTC).
• Surge suppression.
PTC
Number of
Outputs
32
Protected
Outputs
Specifications:
Features:
• Secondary fuse rated @ 10A/250V.
• AC power LED.
• Power ON/OFF switch.
• Spare fuses provided. (all models w/primary and/or secondary fuses).
Mechanical:
• Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
P
P
P
Output
Fuse
Protected
Outputs
-
-
-
P
- 2.5A
P
- 2.5A
P
- 2.5A
Current
(max per
output)
3.5A
3.5A
3.5A
115VAC
50/60Hz Input
Current
2.9A
2.7A
5.4A
Installation Instructions:
1. Mount unit in the desired location.
2. Turn main switch on the unit OFF (Figs. 1-3, pgs. 4-6).
3. All units are factory set for 24VAC operation. For 28VAC operation, adjust unit prior to mounting and applying power as follows: Change the wire position so that the black wire [28V] is connected to the terminal marked [P] and the yellow wire [24V] is connected to the terminal marked [S].
4. Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1-3, pgs. 4-6), secure green lead to earth ground. Use 18 AWG or larger for all power connections.
5. Measure output voltage before connecting devices. This helps avoiding potential damage. CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage.
6. Connect devices to the terminals marked [1P - 1N] through [16P - 16N] on PD16W/PD16WCB board (Figs. 1-3, pgs. 4-6), carefully observing polarity. Terminals marked [1P - 16P] are of the same polarity.
7. Turn main switch on the unit to the ON (RESET) position (Figs. 1-3, pgs. 4-6).
8. Green LED(s) will illuminate when unit is powered.
9. Upon completion of the wiring secure enclosure door with screws (supplied). CAUTION: Equipment to be installed/serviced by authorized / trained personnel only. Shut branch circuit power before installing/servicing equipment.
- 2 - ALTV2432 Series
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes. Use 75 C or higher rated UL insulated wiring for connecting the unit to the mains.
Terminal Identification:
PD16W - Power Distribution Module
1P - 16P AC output. 1N - 16N AC output.
ALTV2432 Series - 3 -
Loading...
+ 5 hidden pages