ALTV2432UL Series
CCTV Power Supplies
Installation Guide
Models Include:
• ALTV2432UL • ALTV2432ULCB
- 24VAC @ 7A (175VA) - 24VAC @ 7A (175VA)
or 28VAC @ 6.25A (175VA). or 28VAC @ 6.25A (175VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
• ALTV2432300UL • ALTV2432300ULCB
- 24VAC @ 12.5A (300VA) - 24VAC @ 12.5A (300VA)
or 28VAC @ 10A (280VA). or 28VAC @ 10A (280VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
• ALTV2432600UL • ALTV2432600ULCB
- 24VAC @ 25A (600VA) - 24VAC @ 25A (600VA)
or 28VAC @ 20A (560VA). or 28VAC @ 20A (560VA).
- Thirty-two (32) Fuse Protected Outputs. - Thirty-two (32) PTC Protected Outputs.
Rev. 040506
Overview:
Altronix ALTV2432UL Series CCTV Power Supplies provide 24VAC/28VAC distributed via thirty-two (32) fuse or PTC
protected outputs for powering CCTV cameras, heaters and other video accessories.
Thirty-two (32) Output ALTV2432UL Reference Chart:
Altronix
Model Number
ALTV2432UL
ALTV2432ULCB
ALTV2432300UL
ALTV2432300ULCB
ALTV2432600UL
ALTV2432600ULCB
Output Voltage
24VAC 7A
28VAC 6.25A
24VAC 7A
28VAC 6.25A
24VAC 12.5A
28VAC 10A
24VAC 12.5A
28VAC 10A
24VAC 25A
28VAC 20A
24VAC 25A
28VAC 20A
Total Output Current
(Power)
Number of Outputs
32 -
32
32 -
32
32 -
32
PTC Protected Outputs
(Class 2 power-limited)
P
P
P
Fuse Protected Outputs
P
- 2.5A
P
- 2.5A - 2.7A
P
- 2.5A - 5.4A
Output Current
(max per output)
3.5A
3.5A - 2.7A
3.5A - 5.4A
Main Fuse Ratings
3.5A
250V
3.5A
250V
115VAC
50/60Hz Input
2.9A
2.9A
Current
Agency Listings
Specifications:
Agency Listings:
• UL Listed for Commercial CCTV Equipment (UL2044).
CUL Listed - CSA Standard C22.2 No.1-98, Audio,
Video and Similar Equipment.
• CE European Conformity.
Input:
• 115VAC, 50/60Hz.
Output:
• Thirty-two (32) fuse or PTC protected outputs.
• 24VAC or 28VAC outputs.
• Outputs are rated @ 3.5A (fused) or 2.5A (PTC).
• Surge suppression.
Features:
• AC power LED indicator.
• Illuminated power disconnect circuit breaker
with manual reset (all other models).
• Unit maintains camera synchronization.
• Ease of installation saves time & eliminates costly labor.
• Spare fuses included (on fuse protected models).
Enclosure Dimensions (H x W x D approx.):
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm).
- 2 - ALTV2432ULseries
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 7).
Secure enclosure to earth ground.
2. Turn OFF main switch on the unit (Figs. 1 - 3, pgs. 4 - 6).
3. All units are factory set for 24VAC operation.
For 28VAC operation (where available) adjust unit prior to mounting and applying power as follows: Change the
wire position so that the black wire [28V] is connected to the terminal marked [P] and the yellow wire [24V] is
connected to the terminal marked [S].
4. Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1 - 3, pgs. 4 - 6), secure green
lead to earth ground. Use 18 AWG or larger for all power connections.
Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring.
Minimum 0.25” spacing must be provided. Use separate knockouts.
5. Measure output voltage before connecting devices. This helps avoid potential damage.
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting
the output voltage.
6. Connect devices to terminals marked [1P - 1N] through [16P - 16N] on PD16W/PD16WCB board
(Figs. 1 - 3, pgs. 4 - 6), carefully observing polarity. Terminals marked [1P - 16P] are of the same polarity.
7. Turn main switch on unit to the ON (RESET) position (Figs. 1 - 3, pgs. 4 - 6).
8. Green LED(s) will illuminate when unit is powered.
9. Upon completion of the wiring secure enclosure door with screws (supplied).
CAUTION: Equipment to be installed/serviced by authorized / trained personnel only.
Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This
installation should be made by qualified service personnel and should conform to all local codes and in
accordance with the National Electrical Code. Use 75 C or higher rated UL insulated wiring for connecting
the unit to the mains. Replace fuses only with the same type and rating (3.5A/250V).
Terminal Identification:
PD16W - Power Distribution Module
1P - 16P AC output.
1N - 16N AC output.
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.
ALTV2432ULseries - 3 -