ALTV2416UL Series CCTV Power Supplies provide 24VAC/28VAC distributed via sixteen (16) fuse or PTC protected
outputs for powering CCTV cameras, heaters, and other video accessories.
ALTV2416ULX, ALTV2416ULCBX,
ALTV2416300UL, ALTV2416300ULCB,
ALTV2416600UL and ALTV2416600ULCB:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 11 - 12).
Secure enclosure to earth ground.
2. Set power switch on power distribution board marked [PD] to OFF position for models ALTV2416ULX or
ALTV2416ULCBX (Figs. 1, 2, pgs. 4, 5). Set power disconnect circuit breaker to OFF position for all other models (Figs. 3a - 8a, pgs. 6 - 10).
3. All units are factory set for 24VAC operation.
For 28VAC operation, adjust unit prior to mounting and applying power as follows:
Change the wire position so that the wire marked [28V] is connected to the terminal marked [P] and
the wire marked [24V] is connected to the terminal marked [S].
Note: ALTV2416ULCBX set for 28VAC operation is not Class 2 Rated, not power-limited.
4. Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1 - 8, pgs. 4 - 10).
Use 18 AWG or larger for all power connections.
Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring. Minimum 0.25” spacing must be provided.Use separate knockouts.
5. Set power switch on power distribution board marked [PD] to ON position for models ALTV2416ULX or
ALTV2416ULCBX (Figs. 1, 2, pgs. 4, 5). Set power disconnect circuit breaker to RESET (ON) position for all other models (Figs. 3a-8a, pgs. 6-10).
6. Measure output voltage before connecting devices. This helps avoiding potential damage.
Terminals marked [1P - 16P] are of the same polarity.
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting
the output voltage.
7. Set power switch on power distribution board marked [PD] to OFF position for models ALTV2416ULX or
ALTV2416ULCBX (Figs. 1, 2, pgs. 4, 5). Set power disconnect circuit breaker to OFF position for all other models (Figs. 3a - 8a, pgs. 6-10).
8. Connect devices to terminals marked [1P - 1N] through [8P - 8N] on PD8 board (Figs. 1 - 4, pgs. 4 - 7,
Figs. 7 - 8, pgs. 9 - 10), or terminals marked [1P - 1N] through [16P - 16N] on PD16W/PD16WCB board
(Figs. 5 - 6, pg. 8), carefully observing polarity.
9. Set power switch on power distribution board marked [PD] to ON position for models ALTV2416ULX or
ALTV2416ULCBX (Figs. 1, 2, pgs. 4, 5). Set power disconnect circuit breaker to RESET (ON) position for all other models (Figs. 3a - 8a, pgs. 6 - 10).
10. Green LED will illuminate when power is present.
11. Upon completion of the wiring, secure enclosure door with screws (supplied). Installation of cam lock is optional.
CAUTION: Equipment to be installed/serviced by authorized/trained personnel only.
Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to all local codes and in accordance with
the National Electrical Code. Use 75º C or higher rated UL insulated wiring for connecting the unit to the mains.
Replace fuses only with the same type and rating (refer to Sixteen (16) Output ALTV2416UL Reference Chart, pg. 2).
Terminal Identification:
PD8 - Power Distribution Module
Terminal LegendFunction/Description
1P - 8PAC output.
1N - 8NAC output.
PD16W - Power Distribution Module
Terminal LegendFunction/Description
1P - 16PAC output.
1N - 16NAC output.
ALTV2416UL Series - 3 -
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
Fig. 1
ALTV2416ULX
Connected
to Door
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.
24VAC or 28VAC output 1
(Follow same procedure using
terminals 2P & N through 8P & N
outputs 2 through 8)
N
COMMON POWER OUTPUTS
P
1 2 3 4 5 6 7 8
FUSED POWER OUTPUTS
FUSE
MAIN
ON OFF
INPUT
LED
Class 1 Outputs
Primary
In-line
Fuse
Ground
115VAC input,
60 Hz.
Black
Lead
D1
R1
NPS
Class 1
NPS
R1
D1
LED
INPUT
ON OFF
MAIN
FUSE
24VAC or 28VAC output 1
(Follow same procedure using
terminals 2P & N through 8P & N
outputs 2 through 8)
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
P
Outputs
COMMON POWER OUTPUTS
N
non-power limited
non-power limited
White
Lead
Black
Lead
XFMR
XFMR
- 4 - ALTV2416UL Series
Fig. 2
ALTV2416ULCBX
Connected
to Door
24VAC configuration
Class 2 Not Wet/
Class 3 Wet
28VAC configuration
Class 1
24VAC or 28VAC
output 1 (Follow same
procedure using terminals 2P & N
through 8P & N outputs 2 through 8)
N
COMMON POWER OUTPUTS
NPS
P
F1F2 F3F4 F5F6F7F8
R1
D1
FUSE
MAIN
ON OFF
SW1
INPUT
LED
D1
R1
NPS
24VAC
configuration
Class 2 Not Wet/
Class 3 Wet
28VAC
configuration
Class 1
Primary
In-line
Fuse
Ground
115VAC input,
60 Hz.
Black
Lead
LED
INPUT
SW1
ON OFF
non-power limited
MAIN
FUSE
F1F2 F3F4 F5F6F7F8
P
24VAC or 28VAC
output 1 (Follow same
procedure using terminals 2P & N
through 8P & N outputs 2 through 8)
COMMON POWER OUTPUTS
N
non-power limited
White
Lead
Black
Lead
XFMR
XFMR
ALTV2416UL Series - 5 -
Fig. 3
ALTV2416300UL
Connected
to Door
Class 1 Outputs
Ground
24VAC or 28VAC output 1
(Follow same procedure using
terminals 2P & N through 8P & N
outputs 2 through 8)
P
N
COMMON POWER OUTPUTS
NPS
INPUT
1 2 3 4 5 6 7 8
FUSED POWER OUTPUTS
R1
D1
LED
non-power limited
MAIN FUSE
non-power limited
MAIN FUSE
LED
D1
R1
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
P
24VAC or 28VAC output 1
(Follow same procedure using
terminals 2P & N through 8P & N
outputs 2 through 8)
INPUT
NPS
Class 1
Outputs
COMMON POWER OUTPUTS
N
Fig. 3a
Black Lead
115VAC input,
60 Hz
White Lead
XFMR*
Illuminated Power Disconnect
Circuit Breaker with manual reset
- 6 - ALTV2416UL Series
Fig. 4
ALTV2416300ULCB
Connected
to Door
24VAC configuration
Class 2 Not Wet/
Class 3 Wet
Ground
24VAC or 28VAC
output 1 (Follow same
procedure using terminals 2P & N
through 8P & N outputs 2 through 8)
R1
LED
P
D1
ON OFF
F1 F2 F3 F4 F5F6 F7 F8
SW1
MAIN
N
COMMON POWER OUTPUTS
NPS
INPUT
non-power limited
FUSE
FUSE
F1 F2 F3 F4 F5F6 F7 F8
non-power limited
MAIN
24VAC or 28VAC
output 1 (Follow same
procedure using terminals 2P & N
through 8P & N outputs 2 through 8)
ON OFF
SW1
INPUT
LED
D1
R1
NPS
COMMON POWER OUTPUTS
P
N
24VAC
configuration
Class 2 Not Wet/
Class 3 Wet
Fig. 4a
Black Lead
115VAC input
60 Hz
White Lead
XFMR*
Illuminated Power Disconnect
Circuit Breaker with manual reset
ALTV2416UL Series - 7 -
p
Fig. 5
p
ALTV2416300ULM
Fig. 5a
Illuminated Power Disconnect
Circuit Breaker with manual reset
Transformer
underneath
ower supply
Fig. 6
ALTV2416300ULCBM
board
12345678
XFMR*
3.5A 250V
common
outputs
protected
outputs
For continuous protection against risk of fire
replace fuses with same type and rating.
9 10 11 12 13 14 15 16
N
P
NPS
PN
XFMR Input
Fig. 6a
Illuminated Power Disconnect
Circuit Breaker with manual reset
12345678
common
outputs
protected
outputs
9 10 11 12 13 14 15 16
N
P
NP
NPS
Transformer
underneath
ower supply
board
XFMR Input
- 8 - ALTV2416UL Series
Fig. 7
ALTV2416600UL
Connected
to Door
Class 1 Outputs
24VAC or 28VAC output 1
(Follow same procedure using
terminals 2P & N through 8P & N
outputs 2 through 8)
N
COMMON POWER OUTPUTS
NPS
INPUT
P
1 2 3 4 5 6 7 8
FUSED POWER OUTPUTS
R1
D1
LED
MAIN FUSE
MAIN FUSE
LED
D1
R1
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
P
24VAC or 28VAC output 1
(Follow same procedure using
terminals 2P & N through 8P & N
outputs 2 through 8)
INPUT
NPS
Class 1
Outputs
COMMON POWER OUTPUTS
N
Ground
115VAC input,
60 Hz.
Black
Lead
White
Lead
non-power limited
non-power limited
XFMR*
non-power limited
XFMR*
Fig. 7a
Illuminated Power Disconnect
Circuit Breaker with manual reset
ALTV2416UL Series - 9 -
Fig. 8
ALTV2416600ULCB
Connected
to Door
24VAC configuration
Class 2 Not Wet/
Class 3 Wet
24VAC or 28VAC
output 1 (Follow same
procedure using terminals 2P & N
through 8P & N outputs 2 through 8)
N
COMMON POWER OUTPUTS
NPS
INPUT
P
R1
D1
LED
MAIN
MAIN
F1 F2 F3 F4 F5F6 F7 F8
FUSE
FUSE
D1
F1 F2 F3 F4 F5F6 F7 F8
P
24VAC or 28VAC
output 1 (Follow same
procedure using terminals 2P & N
through 8P & N outputs 2 through 8)
INPUT
LED
R1
NPS
24VAC
configuration
Class 2 Not Wet/
Class 3 Wet
COMMON POWER OUTPUTS
N
Ground
115VAC input,
60 Hz.
Black
Lead
White
Lead
non-power limited
non-power limited
XFMR*
non-power limited
XFMR*
Fig. 8a
Illuminated Power Disconnect
Circuit Breaker with manual reset
- 10 - ALTV2416UL Series
Enclosure Dimensions (H x W x D approximate) for
(
)
• ALTV2416300ULM
• ALTV2416300ULCBM
8.5” x 7.5” x 3.75” (215.9mm x 190.5mm x 97.9mm)
0.6”
(15.24mm)
0.9”
(22.86mm)
1”
(25.4mm)
1.25”
(31.75mm)
7.25”
(184.15mm)
3.63”
(92.2mm)
0.6”
(15.24mm)
1.25”
(31.75mm)
3.85”
(97.79mm)
0.9”
(22.86mm)
1.25”
(31.75mm)
1”
(25.4mm)
8.13”
(206.5mm)
(25.4mm)
1”
1.25”
(31.75mm)
3.85”
(97.79mm)
0.6”
(15.24mm)
1”
(25.4mm)
7.25”
184.15mm
0.6”
(15.24mm)
(206.5mm)
1”
(25.4mm)
1”
(25.4mm)
8.13”
3.85”
(97.79mm)
1.75”
(44.45mm)
1”
(25.4mm)
ALTV2416UL Series - 11 -
Enclosure Dimensions (H x W x D approximate) for
(
)
(
)
(
)
• ALTV2416ULX • ALTV2416ULCBX
• ALTV2416300UL • ALTV2416300ULCB
• ALTV2416600UL • ALTV2416600ULCB
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)
1.40”
(36mm)
5.10”
(130mm)
1.20”
(31mm)
13.0”
(330mm)
(36mm)
0.75”
(19mm)
1.40”
4.85”
(123mm)
12.5”
(318mm)
11.0”
(279mm)
4.85”
(123mm)
1.40”
(36mm)
0.75”
(19mm)
1.20”
(31mm)
0.9375”
(24mm)
3.25”
(83mm)
1.20”
(31mm)
1.40”
(36mm)
5.10”
(130mm)
5.10”
(130mm)
6.5625”
(167mm)
0.9375”
(24mm)
3.25”
(83mm)
1.0”
(25mm)
1.0”
25mm
10.5”
267mm
1.0”
25mm
1.0”
(25mm)
3.25”
(83mm)
3.25”
(83mm)
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: info@altronix.com. Lifetime Warranty, Made in U.S.A.
II1ALTV2416ULSeries C18P
MEMBER
- 12 - ALTV2416UL Series