![](/html/2d/2ded/2ded92ed8f9adf7b809db69270e6ed744797b01996764a0f99df19f40a419ffb/bg1.png)
AL400ULACMJ, AL400ULACMCBJ
Power Supply/Chargers w/Multi-Output
ev. DSAL400ULACMJ - J19F
Access Power Controllers
Overview
• The AL400ULACMJ / AL400ULACMCBJ converts an 115VAC 60Hz input
into eight (8) independently controlled 12VDC or 24VDC Fail-Safe and/or
Fail-Secure outputs with a total of 4 amp @ 12VDC or 3 amp @ 24VDC
continuous supply current. These power outputs can be converted to dry
form "C" contacts (AL400ULACMJ only). Outputs are activated by an open
collector sink or normally open (NO) dry trigger input from an Access
Control System, Card Reader, Keypad, Push Button, PIR, etc. These units will
route power to a variety of access control hardware devices including Mag
Locks, Electric Strikes, Magnetic Door Holders, etc. The outputs will operate
in both Fail-Safe and/or Fail-Secure modes. The units are designed to be
powered by one common power source (factory installed) which will provide
power for both the board operation and locking devices, or two (2) totally
independent power sources, one (1) providing power for board operation and
the other for lock / accessory power. The FACP Interface enables Emergency
Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices.
The fire alarm disconnect feature is individually selectable for any or
all of the eight (8) outputs.
AL400ULACMJ
• Eight (8) independently controlled
fuse protected outputs.
AL400ULACMCBJ
• Eight (8) independently controlled
PTC protected outputs.
R
Specifications
• 12VDC @ 4 amp supply current
or 24VDC @ 3 amp supply current.
• Class 2 Rated power limited outputs.
• Power supply input options:
One (1) common power input for
a)
ACM8CB and lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8/ACM8CB and one (1) for lock
accessory power, (external power supply
is required). (Current is determined by the
power supply connected, not to exceed a
maximum of 10 amp total).
• Eight (8) Access Control System trigger inputs.
Input options:
y open (NO) inputs.
Eight (8) nor
a)
b) Eight (8) open collector inputs.
y combination of the above.
An
c)
Eight (8) independentl
•
Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b) Eight (8) dry form “C” 5 amp rated relay outputs
(AL400ULACMJ only).
c) Any combination of the above
(AL400ULA
• Eight (8) auxiliary power outputs (unswitched)
Output ratings:
•
- Fuses are rated @ 3.5 amp (AL400ULA
- PTCs are rated @ 2.5 amp (AL400ULACMCBJ).
• ACM8 board main fuse is rated at 10 amp.
Input 115V
•
mall
y controlled outputs.
CMJ onl
AC 60Hz rated @ 1.9 amp.
y).
ACM8/
CMJ).
• Filtered and electronically regulated outputs
(built-in power supply).
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is
individually selectable for an
eight (8) outputs.
Fire Alarm disconnect input options:
a) Nor
b)
Alar
•
is triggered (form “C” contact rated @ 1 amp 28VDC
not evaluated by UL).
Green LED indicates when FACP disconnect
•
is triggered.
• Built-in charger for sealed lead acid or gel type batteries.
AL400ULXB (P
•
maximum charge current .7 amp.
Automatic switch over to stand-by battery
•
w
• AC input and DC output LED indicators.
• Zero voltage drop when unit switches over to battery
backup (AC failure condition).
• Short circuit and thermal overload protection.
• AC fail supervision (form "C" contact).
Batter
•
(form "C" contact).
• Enclosure accommodates up to two (2) 12AH batteries.
mally open (NO) or nor
dry contact input.
olarity re
P
signaling circuit.
m output rela
A
hen
y f
versal input from FACP
y indicates that F
w
o
ails.
C f
ail and batter
er Suppl
y presence super
y or all of the
y closed (NC)
mall
CP input
A
y Board)
vision
![](/html/2d/2ded/2ded92ed8f9adf7b809db69270e6ed744797b01996764a0f99df19f40a419ffb/bg2.png)
•
1.50"
1
.25"
2.50"
6.00"
2.50"
1.50"
2.50"
1.50"
1
.00"
1
.50"
1.00"
1.50"
2.75"
4.50" 4.50"
1.00"
1.00"
1.25"
1.50"
8.50"
1.00"
1.00"
2.75"
18.00"
14.50"
18.00"
18.00"
14.50"
Product weight:
- AL400ULACMJ: 15.0 lbs.
- AL400ULACMCBJ: 14.0 lbs.
•
Shipping weight:
- AL400ULACMJ: 16.0 lbs.
- AL400ULACMCBJ: 15.0 lbs.
Agency Approvals
UL Listed for Access Control Systems Units
(UL 294).
CUL Listed - CSA Standard C22.2
No.205-M1983 Signal Equipment.
Enclosure Dimensions
18”H x 14.5”W x 4.625”D
MEA - NYC Department of
Buildings Approved.
CSFM - California State Fire
Marshal Approved.
Altr
onix Cor
- 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
p.