For a red enclosure, add an “R” suffix to the part # e.g. AL1024ULXPD8R
Rev. 111003
Overview:
The AL1024ULX is a power supply that converts a 115VAC / 60Hz input, to a 24VDC regulating output
(see specifications below).
The AL1024ULX is the base power supply unit for the UL Listed multi-output power supply/charger series:
AL1024ULXPD4, AL1024ULXPD4CB, AL1024ULXPD8, AL1024ULXPD8CB, AL1024ULXPD16,
AL1024ULXPD16CB (Refer to AL1024ULX Series Power Supply Configuration Reference Chart below).
AL1024ULX Series Power Supply Configuration Reference Chart:
Distribution
Model Number
Altronix
Accessory Power
Module(s)
Class 2 Rated
Number of Outputs
Power Limited Outputs
Fused Outputs
PTC Outputs
Output Rating (amp)
Agency Lisitings
per Output
UL Listings and
File Numbers
AL1024ULX(R)-1---10
AL1024ULXPD4PD4UL4-x-3.5
AL1024ULXPD4CBPD4ULCB4x-x2.5
AL1024ULXPD8PD8UL8-x-3.5
AL1024ULXPD8CBPD8ULCB8x-x2.5
AL1024ULXPD1616
AL1024ULXPD16CB16
Two (2)
PD8UL
Two (2)
PD8ULCB
-x-3.5
x-x2.5
Do not exceed total output rating of 10 amp per unit.
Specifications:
Maximum char
Input:
• Input 115VAC / 60Hz, 4.4 amp.
Output:
24VDC output.
•
rent in non-alarm condition with
8 amp suppl
•
y cur
10 amp supply current during alarm for Fire Alarm
Applications.
10 amp supply current for Access Control Applications.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Battery Backup:
Built-in char
•
gel type batteries.
• Automatic switch over to stand-by battery when
C fails.
A
ger for sealed lead acid or
•
• Zero voltage drop when switched over to battery backup.
• Power supply, enclosure, cam lock and battery leads
• All models are available in red enclosure
(add an “R” suffix to the part # e.g. AL1024ULXPD8R).
California
State Fire
arshal
M
ge cur
Factory
Mutual
Approved
UL Listed Standard
Protective Signaling
UL Listed for Access
Control System Units.
“Signal Equipment”
CSA Standard C22.2
rent 3.6 amp.
UL File # S4707
UL 1481
for Safety for Fire
Systems.
UL 294
Evaluated to
No.205-M1983
-
2
-
AL1024ULXseries
Stand-by Specifications (total current shown):
-- DC +
B
AT FAIL
NO C NC NO C NC
+
BAT ---
DC
AC FAIL
L
G N
A
C
10A
250V
15A
250V
Green
L
ead
Battery connection (non power limited)
Door
Wire Strap
(from
Enclosure
to Door)
115VAC
power mains
non-power limited
Divider
CAUTION: De-energize unit prior to servicing. For continued protection
against risk of electric shock and fire hazard replace fuses with the same type
and rating: Input fuse 10A, 250V, Battery fuse 15A, 32V.
Replace fuse cover before energizing. Do not expose to rain or moisture.
INPUT
1
2
Power
Distribution
Module(s)
Battery and AC Supervision Circuit
(power limited).
Fuse
Cover
non-power limited
Class 1
Green Lead
Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.
12VDC Rechargeable Battery
(optional)
12VDC Rechargeable Battery
(optional)
O
utput15 Min. of Stand-by &4 hr. of Stand-by &24 hr. of Stand-by &60 hr. of Stand-by &
5 Mins. of Alarm5 Mins. of Alarm5 Mins. of Alarm5 Mins. of Alarm
See battery size calculation worksheet for other batteries (
Pag e 7).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
Fig. 1
AL1024ULXseries- 3 -
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
e
nclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 7,8).
Secure enclosure to earth ground.
2. Secure enclosure to earth ground. Connect AC power (115VAC / 60 Hz to terminals marked [L, G, N]
(Fig. 1, pg. 3).
Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power
limited circuits (AC Fail/Low Battery reporting). Keep power limited wiring separate from non-power limited wiring
(115VAC / 60Hz Input, Battery Wires). Minimum .25” spacing must be provided.
3. Measure output voltage before connecting device. This helps avoid potential damage.
When servicing the unit, AC mains should be removed.
4. Connect devices to be powered:
a. For AL1024ULX Power Supply connect devices to terminals marked [- DC +]
(Fig. 1, pg. 3)
b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 4 marked
5. For Access Control applications, batteries are optional. When batteries are not used a loss of AC will result in
the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
6. Connect appropriate signaling notification devices to terminals marked [AC FAIL & BAT FAIL]
(Fig. 1, pg. 3)
supervisory relay outputs.
Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used to
provide a visual indication of
AC power on.
7. Please insure that the cover is secured with the provided Key Lock.
LED Diagnostics:
AL1024ULXB - Power Supply Board
Red (DC)Green (AC)Power Supply Status
ONON
ON
OFF
Normal operating condition
Loss of AC, Stand-by battery supplying power
OFFONNo DC output
OFFOFFLoss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
AL1024ULXB - Power Supply Board
Terminal LegendFunction/Description
L, G, N
- DC +
AC FAILIndicates loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally
NO, C, NCenergized when AC power is present. Contact rating 1 amp @ 28VDC.
BAT FAILIndicates low battery condition, e.g. connect to alarm panel. Relay normally energized
NO, C, NCwhen DC power is present.
+ BAT -Stand-by battery connections. Maximum charge rate 3.6 amp.
Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground.
24VDC @ 8 amp continuous, 10 amp in alar
m non-power limited output, 10 amp continuous when
batteries are not used.
AC or brownout fail is reported within 0ne (1) minute of event. To delay reporting of up to
6 hrs., cut “AC delay” jumper and reset power to unit.
Contact rating 1 amp @ 28VDC.
A remo
within 1 minute. Lo
ved battery is reported within 1 minute. Battery reconnection is reported
w batter
y threshold: @ appro
ximately 21VDC.
-
4
-
AL1024ULXseries
LED Diagnostics:
L
ED
F1F2F3F4
1P
1N
2P
2N
3P
3N
4P
4N
Non-Power Limited
DC Output to devices
1P-4P Power Outputs,
1N-4N Common Outputs
()
From Power Supply
Board
(Factory Installed)
Replace fuses with the same type and rating 3.5A, 250V.
INPUT
LED
F1F2F3F4
POWER OUTPUTS
1P
1N
2P
2N
3P
3N
4P
4N
Class 2 Rated Power Limited
DC Output to devices
1P-4P Power Outputs,
1N-4N Common Outputs
From Power Supply
Board
(Factory Installed)
()
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
D1
INPUT
R1
LED
From Power Supply
Board
(Factory Installed)
Replace fuses with the same type and rating 3.5A, 250V.
Non- Power Limited
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
()
N
COMMON POWER OUTPUTS
P
FUSED POWER OUTPUTS
1 2 3 4 5 6 7 8
D1
INPUT
R1
LED
From Power Supply
Board
(Factory Installed)
Class 2 Rated Power Limited
DC Output to devices
1P-8P Power Outputs,
1N-8N Common Outputs
()
PD4UL/PD4ULCB/PD8UL/PD8ULCB - Power Distribution Module
G
reenPower Distribution Module Status
ONNormal operating condition.
OFFNo Power Output.
Terminal Identification:
PD4UL/PD4ULCB/PD8UL/PD8ULCB - Power Distribution Module
Terminal LegendFunction/
PD4UL/PD4ULCBPD8UL/PD8ULCBDescription
1P to 4P1P to 8PPositive DC power outputs.
1N to 4N1N to 8NNegative DC power outputs.
Power Distribution Module(s):
Fig. 2A
Fig. 3A
Fig. 2B
Fig. 3B
AL1024ULXseries- 5 -
Wiring:
USE 14 AWG or larger for all power connections.
Note: Take care to keep power limited circuits separate from non-power limited wiring (115VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level.
Battery Test: Under normal load conditions check that the battery is fully charged, check specif ied voltage both at
battery terminal and at the board terminals marked [+ BAT -] to insure there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 3.6 amp.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
-
6
-
AL1024ULXseries
Battery size calculation worksheet.
A
. AL1024ULX series internal cur rent consumption(standby) _ _ _ _ _ _ _ _ _ _ _ _ .05 A
B. Load current consumption(standby) _ _ _ _ _ _ _ _ _ _ _ _ A
C. Standby time required (hours) _ _ _ _ _ _ _ _ _ _ _ _ H
D. Battery capacity required for standby(A+B)*C _ _ _ _ _ _ _ _ _ _ _ _ AH
E. AL1024ULX series internal power consumption(Alarm) _ _ _ _ _ _ _ _ _ _ _ _ .05 A
F.Load cur rent consumption(Alarm) _ _ _ _ _ _ _ _ _ _ _ _ A
G. Alarm duration (Hours, 15 Min=.2 Hour)(Alarm) _ _ _ _ _ _ _ _ _ _ _ _ H
H. Battery capacity required for Alar m(E+F)*G _ _ _ _ _ _ _ _ _ _ _ _ AH
Note: AL1024ULX series power supply is designed to work with batteries up to 65AH. Please note, line [I]
must not exceeds 36AH. You have to reduce either standby current consumption or standby time in order to
comply with requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size
(e.g. 3.5 AH = 4.0 AH).
AL1024ULXseries- 7 -
1.285
1.285
Enclosure Dimensions:
15.5”H x 12”W x 4.5”D