Altronix AL1024ULACMCBJ Installation Manual

ACMCBJ Series
Access Power Controllers with Power Supplies
Installation Guide
Models Include:
AL400ULACMCBJ AL600ULACMCBJ
- 12VDC @ 4 amp - 12VDC or 24VDC @ 6 amp. or 24VDC @ 3 amp - Class 2 Rated PTC Protected
- Class 2 Rated PTC Protected Power-Limited Outputs Power-Limited Outputs
AL1012ULACMCBJ AL1024ULACMCBJ
- 12VDC @ 10 amp. - 24VDC @ 10 amp.
- Class 2 Rated PTC Protected - Class 2 Rated PTC Protected Power-Limited Outputs Power-Limited Outputs
Rev. 102512
Overview:
LISTED
These units distribute and switch power to access control systems and accessories. They convert a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC PTC protected outputs. Outputs are activated by an open col­lector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) outputs.
ACMCBJ Series Configuration Reference Chart:
Altronix Model Number
AL400ULACMCBJ
AL600ULACMCBJ
AL1012ULACMCBJ
AL1024ULACMCBJ
12VDC Total
Output Current
24VDC Total
Output Current
Outputs
Individual Output
Rating
Class 2 Rated
Power Limited
115VAC 60Hz
Input
(current draw)
Power Supply
Board Input Fuse
Rating
Power Supply
BoardOutput Fuse
4A 3A 8 2A Yes 3.5A 5A/250V 15A/32V
6A 6A 8 2A Yes 3.5A 5A/250V ---------
10A --------- 8 2A Yes 2.6A 5A/250V 15A/32V
--------- 10A 8 2A Yes 4.2A 5A/250V 15A/32V
Rating
Agency Listings
Altronix Corp.
140 58th St. Brooklyn, NY
California State Fire
Marshal
UL Listings and File Numbers
NYC
Dept. of
Buildings
UL Listed for Access Control System Units.
“Signal Equipment”
Evaluated to CSA
UL 294
(File # BP6714)
Standard C22.2 No.205-M1983
Specifications:
• Power supply input options: a) One (1) common power input for ACM8CB and lock power (factory installed). b) Two (2) isolated power inputs (external power supply is required). (current is determined by the power supply connected, not to exceed a maximum of 10 amp total).
• Eight (8) Access Control System trigger inputs. Input options: a) Eight (8) normally open (NO) inputs. b) Eight (8) open collector inputs. c) Any combination of the above.
• Eight (8) independently controlled Fail-Safe and/or Fail-Secure power outputs.
• Eight (8) auxiliary power outputs (unswitched) (PTC protected outputs are rated 2.5 amp).
• ACM8CB board main fuse is rated at 10 amp.
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the eight (8) outputs. Fire Alarm disconnect input options: a) Normally open (NO) or normally closed (NC) dry contact input. b) Polarity reversal input from FACP signaling circuit.
• Alarm output relay indicates that FACP input is triggered (form “C” contact rated @ 1 amp 28VDC not evaluated by UL).
• Green LED indicates when FACP disconnect is triggered.
• Filtered and electronically regulated outputs (built-in power supply).
• Built-in charger for sealed lead acid or gel type batteries.
• AL400ULXB2, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge current 0.7 amp. AL1024ULXB2 (Power Supply Board) maximum charge current 3.6 amp.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when unit switches over to battery backup (AC failure condition).
• Thermal and short circuit protection with auto reset.
• AC input and DC output LED indicators.
• AC fail supervision (form “C” contact).
• Battery fail and battery presence supervision (form “C” contact).
• Enclosure accommodates up to two (2) 18AH batteries. Enclosure dimensions (H x W x D): 18” x 14.5” x 4.625” (457.2mm x 368.3mm x 117.48mm).
- 2 - ACMCBJ series
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 10). Secure enclosure to earth ground. It is recommended to first review the following tables to facilitate installation:
Output Voltage and Stand-by Specifications Charts (pg. 3) Typical Application Diagram (pg. 5) LED Diagnostics (pg. 5) Terminal Identification Tables (pg. 7) Hook-up Diagrams (pg. 8)
2. Set output voltage: AL400ULACMCBJ and AL600ULACMCBJ set desired DC output voltage by setting switch SW1 to the appropriate position on the power supply board. AL1012ULACMCBJ is 12VDC and AL1024ULACMCBJ is 24VDC
(Output Voltage and Stand-by Specification Charts below).
Output Voltage and Stand-by Specification Charts:
AL400ULACMCBJ
Voltage Switch Position Stand-by Battery 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
12VDC SW1 - ON 40AH 3.5 amp / 3.5 amp 1 amp / 4 amp 24VDC SW1 - OFF 40AH 2.75 amp / 2.75 amp 1 amp / 3 amp
AL600ULACMCBJ
Voltage Switch Position Stand-by Battery 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
12VDC SW1 - ON 40AH 5.5 amp / 5.5 amp 0.5 amp / 5.5 amp 24VDC SW1 - OFF 40AH 5.75 amp / 5.75 amp 0.75 amp / 5.75 amp
AL1012ULACMCBJ
Voltage Switch Position Stand-by Battery 4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm
12VDC N/A 40AH 9.5 amp / 9.5 amp 0.5 amp / 9.5 amp
AL1024ULACMCBJ (refer to AL1024ULACMCB Battery Size Calculation Worksheet, pg. 9).
Voltage
24VDC 12AH 7.7 amp / 9.7 amp 1.2 amp / 9.7 amp ------------ -----------­24VDC 65AH ------------ 7.7 amp / 9.7 amp 1.2 amp / 9.7 amp 200mA / 9.7 amp
3. Measure voltage before connecting devices. This helps avoiding potential damage.
4. Connect AC (Fig. 2, pg. 6): Connect unswitched AC power (115VAC 60Hz) to terminals marked [L, G, N]. Use 14 AWG or larger for all power connections. Secure green wire lead to earth ground. Keep power-limited wiring separate from non power-limited wiring (115VAC 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
5. Output options (Fig. 1, pg. 5): The unit will provide eight (8) switched power outputs or eight (8) unswitched auxiliary power outputs.
(a) Switched Power outputs:
Connect the negative (-) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal marked [NC]. For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal marked [NO].
(b) Auxiliary Power outputs (unswitched):
Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (-) of the device being powered to the terminal marked [COM]. Output can be used to provide power for card readers, keypads etc.
Stand-by
Battery
15 mins. Stand-by /
5 mins. Alarm
4 hr. Stand-by /
5 mins. Alarm
24 hr. Stand-by /
5 mins. Alarm
60 hr. Stand-by /
5 mins. Alarm
ACMCBJ series - 3 -
6. Input trigger options (Fig. 1, pg. 5): (a) Normally Open [NO] input trigger:
Inputs 1-8 are activated by normally open or open collector sink inputs. Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].
(b) Open Collector Sink inputs:
Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (-) to the terminal marked [GND].
7. Fire Alarm Interface options (Figs. 4 through 8, pg. 8): A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will trigger selected outputs. To enable FACP Disconnect for an output turn the corresponding switch [SW1-SW8] ON. To disable FACP disconnect for an output turn the corresponding switch [SW1-SW8] OFF.
(a) Normally Open [NO] input:
For non-latching hook-up (Fig. 5, pg. 8). For latching hook-up (Fig. 6, pg. 8).
(b) Normally Closed [NC] input:
For non-latching hook-up (Fig. 7, pg. 8). For latching hook-up (Fig. 8, pg. 8).
(c) FACP Signaling Circuit input trigger:
Connect the positive (+) and negative (-) from the FACP signaling circuit output to the terminals marked [+ INP -]. Connect the FACP EOL to the terminals marked [+ RET -] (polarity is referenced in an alarm condition). Jumper J3 must be cut (Fig. 4, pg. 8).
8. FACP Dry form “C” output (Fig. 1a, pg. 5): Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C] FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.
9. Battery Connections (Fig. 2, pg. 6): For Access Control applications batteries are optional. If batteries are not used a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked [- BAT +] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation.
10. Battery and AC Supervision output (Fig. 2, pg. 6): It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] supervisory relay outputs marked [NC, C, NO] to appropriate notification devices. Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting. Cut “AC delay” jumper to delay report 6 hour. Note: A tamper switch must be installed and connected to the appropriate notification device to report a trouble condition when the enclosure door is open.
11. Multiple power supply inputs (Fig. 1, pg. 5): When using two (2) power supplies jumpers J1 and J2 (located to the left of the power/control terminals) must be cut (Fig. 1b, pg. 5 & Fig. 3 pg. 8). Connect power for the ACM8CB to the terminals marked [- Control +] and connect power for the locking devices to the terminals marked [- Power +]. When using DC power supplies polarity must be observed. When using AC power supplies polarity need not be observed. Note: For UL compliance the additional power supply must be power-limited, UL Listed for Access Control Systems and accessories.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Output Voltage and Stand-by Specification Charts, pg. 3).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [- BAT +] to ensure that there is no break in the battery connection wires. Note: AL400ULXB2, AL600ULXB, AL1012ULXB (Power Supply Board) maximum charge current is 0.7 amp. AL1024ULXB2 (Power Supply Board) maximum charge current is 3.6 amp. Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.
- 4 - ACMCBJ series
Loading...
+ 8 hidden pages