Alpha SDACT-2 Specsheet

Product Specification Sheet APS925 - Rev. 08/2016
SDACT-2 Serial Dialer and Digital CommunicatorSDACT-2 Serial Dialer and Digital Communicator
42 Central Drive • Farmingdale • NY • 11735-1202 • Phone: (631) 777-5500 • Fax: (631) 777-559942 Central Drive • Farmingdale • NY • 11735-1202 • Phone: (631) 777-5500 • Fax: (631) 777-5599
TOLL-FREE: (800) 666-4800 • Web: AlphaCommunications.com • Email: info@alphacommunications.comTOLL-FREE: (800) 666-4800 • Web: AlphaCommunications.com • Email: info@alphacommunications.com
Copyright © 1998-2 016 Alpha Communication s® - All Righ ts Reserved.
Due to c ontinuo us product i mprovement, all col ors, sizes, materials, finishes and sp ecifications are subject to change witho ut not ice.
SDACT-2 Serial Dialer and Digital CommunicatorSDACT-2 Serial Dialer and Digital Communicator
The Alpha Communications® / Keltron SDACT-2 is a unique solution that interfac es with emergency-c all, ac cess c ontrol, building management and other systems to enable an appropriate and instantaneous response from personnel at a central or remot e monitoring locat ion. The SDACT-2 provides a bridge to an on- or off- site central stat ion-st yle digital receiver t hrough the dial-up public switc hed telephone network (PSTN).
The SDACT-2 ac c epts pre-defined ASCIII RS232 data strings and converts t o SIA, a standard, digital receiver-compatible, alarm reporting format.
The most c ommon applications for the SDACT- 2 is for use with our
AlphaEntry™ and AlphaEcall™ emergency-c all systems and
devices, although it c an be used with other similar syst ems.
FeaturesFeatures
RS232 Port enables acc urate monitoring of event type and locat ion identification Test c ode call-in c yc les are programmable. A manual test button is also included Transmit s signals in industry standard SIA format Works with a variety of alarm notification equipment Zones 1-4 supervised EOL, suitable for fault- c ontac t monitoring Zones 5-7 are available for loss of AC and batt ery fail indications, which are also reported using standard SIA event codes Local LEDs and audible devic es c learly indicate Serial Dialer stat us
SpecificationsSpecifications
Dimensions (in
SDACTBX-GRAY
Housing):
Height: 14.00" (356mm) Width: 17.00" (432mm) Depth: 4.00" (102mm) from mounting surface
Phone Lines:
2 RJ45 receptac les. Line seizure via RJ31x jack (by others)
Hardwired Zone Inputs:
7 (4-EOL resistor supervised). EOL resistor value 10K Ohms.
Audible Device: rated at 92DB
Ringer Equivalence: .1
FCC Reg.# US: KELAL00BSDACT- 2
User Controls:
Jumper (8 t otal) and Pushbuttons: Reset, Manual Test, Silence, Program.
Power Requirements:
Power Input - regulated or unregulated, filtered 20.4 to 27.5VDC
Power Draw:
75mA Idle, 200mA all alarm or lamp test
Programming and
Monitoring Port:
DB- 9F RS-232
Loading...