alpha Evoke 28 User guide

Installation and Servicing
Instructions
Evoke 28 and 33
Wall Mounted, Fan Assisted, Room Sealed,
Gas Fired, High Efficiency Condensing Combination Boiler
ALPHA HELPLINE Tel: 0844 871 8764
website: www.alpha-innovation.co.uk
Nepicar House, London Road,
Wrotham Heath, Sevenoaks,
Kent TN15 7RS
Set for use with Natural Gas
Leave these instructions with the User
These instructions have been carefully prepared but we reserve the right to alter the specification at any time in the interest of product improvement. © Alpha Therm Limited 2017.
Part No. 1.040251 rev. ST.003028.000
0317/D373
BENCHMARK SCHEME
To comply with Building Regulations Part L1 (Part 6 in Scotland) the boiler should be installed in accordance with the manufacturer’s instructions. Self-certification that the boiler has been installed to comply with Building Regulations can be demonstrated by completing and signing the Benchmark Checklist at the back of these instructions
Code of Practice
For the installation, commissioning and servicing of domestic heating and hot water products.
Benchmark places responsibilities on both manufacturers and installers*. The purpose is to ensure that customers** are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer's instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. Installers are required to carry out work in accordance with the following:
Standards of Work
• Be competent and qualified to undertake the work required.
• Install, commission, service and use products in accordance with the manufacturer's instructions provided.
• Ensure that where there is responsibility for design work, the installation is correctly sized and fit for purpose.
• Meet the requirements of the appropriate Building Regulations. Where this involves notifiable work be a member of a
Competent Persons Scheme or confirm that the customer has notified Local Authority Control (LABC), prior to work commencing.
• Complete all relevant sections of the Benchmark Checklist/Service Record when carrying out commissioning or servicing of a product or system.
• Ensure that the product or system is left in a safe condition and, where possible, in good working order.
• Highlight to the customer any remedial or improvement work identified during the course of commissioning or servicing work.
• Refer to the manufacturer's helpline where assistance is needed.
• Report product faults and concerns to the manufacturer in a timely manner.
Customer Service
• Show the customer any identity card that is relevant to the work being carried out prior to commencement or on request.
• Give a full and clear explanation/demonstration of the product or system and its operation to the customer.
• Hand over the manufacturer's instructions, including the Benchmark Checklist, to the customer on completion of an installation.
• Obtain the customer's signature on the Benchmark Checklist to confirm satisfactory demonstration and receipt of
manufacturer's instructions.
• Advise the customer that regular product servicing is needed, in line with manufacturers' recommendations, to ensure that safety and efficiency is maintained.
• Respond promptly to calls from a customer following completion of their work, providing advice and assistance by phone and, if necessary, visiting the customer.
• Rectify any installation problems at no cost to the customer during the installer's guarantee period.
* The use of the word "installer" is not limited to installation itself and covers those carrying out installation, commissioning and/or servicing of heating and hot water
products, or the use of supporting products (such as water treatment or test equipment).
** Customer includes householders, landlords and tenants.
Benchmark Commissioning and Servicing Section
It is a requirement that the boiler is installed and commissioned to the manufacturers instructions and the data fields on the commissioning checklist completed in full.
To instigate the boiler guarantee the boiler needs to be registered with the manufacturer within one month of the installation.
To maintain the boiler guarantee it is essential that the boiler is serviced annually by a Gas Safe registered engineer who has been trained on the boiler installed. The service details should be recorded on the Benchmark Service Interval Record and left with the householder.
www.centralheating.co.uk
Useful contact details: Gas Safe Register - 0800 408 5577 - www.gassaferegister.co.uk
Alpha Heating Innovation: General Sales Enquiries - 0844 871 8760
Technical Helpline - 0844 871 8764
Alpha Evoke 28 and 33 - Benchmark Scheme
2
CONTENTS
1 Introduction ........................................ 3
2 Technical data ...................................4
3 General boiler information ................. 9
4 Installation .........................................16
5 Commissioning .................................. 25
6 Routine servicing ............................... 34
8 Wiring diagram ..................................45
9 Error codes and fault finding..............46
10 Short parts list ...................................49
11 Energy classification .......................... 50
Benchmark Checklist ......................... 56
Service Record .................................. 57
7 Component replacement ...................40
1 INTRODUCTION
The Evoke 28 and 33 are wall mounted, room sealed, fan assisted, high efficiency, condensing boilers. The burner is lit electronically and the heat output is controlled by a modulating fan and gas valve.
The Evoke 28 and 33 are combination boilers providing both central heating and domestic hot water at mains pressure.
The boiler is supplied with a pump, pressure relief valve, expansion vessel and pressure gauge fully assembled and tested. It is designed for use with a fully pumped, sealed and pressurised central heating system.
IMPORTANT
Failure to install and commission this appliance in compliance with the manufacturer's instructions may invalidate the warranty.
It is the law that all gas appliances are installed by a competent person, ie Gas Safe registered personnel, in accordance with the following recommendations:-
Current Gas Safety (Installation and Use) Regulations All current Building Regulations issued by the Department of the Environment, i.e. Approved Document L26. Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department UK Water Regulations/Byelaws (Scotland) Health & Safety Document No. 635 (The Electricity At Work Regulations 1989) The installation should also be in accordance with the following British Standard Codes of Practice:-
BS 5440-1: 2008 ........................Flueing and Ventilation Requirements
BS 5440-2: 2009 ........................Installation and Maintenance of Flues and Ventilation
BS 5546: 2010 ...........................Specification for Water Heating Appliances
BS 6798: 2009 ...........................Specification for Installation gas fired boilers up to 70 kW
BS 6891: 2005 + A2: 2008 .........Installation of low pressure Gas Pipework
IGEM/UP/2 ...............................Installation of pipework
IGEM/UP/4 ................................Commissioning of gas fired plant
IGE/UP/10 .................................Installation of Flued gas appliances
IGEM/UP/16 ..............................Design for natural gas installations
IGE/UP/1 and 1B .......................Strength Testing and tightness testing Natural Gas Installations
Reference should also be made to any other standards and requirements relating to the installation depending on the location and use. Reference should be made to DEFRA document 'Guide to condensing boiler installation assessment procedures for dwellings'.
If installation is in a timber framed building, refer to the Institute of Gas Engineers document IGE/UP/7. This appliance meets the requirements of IPX5D, ie degree of protection against moisture. This appliance contains no asbestos and no substances have been used in the construction process that contravene the
COSHH Regulations (Control of Substances Hazardous to Health). Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that
the law is complied with. Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations. Notes: 1. Ensure that the Benchmark Checklist has been completed after the boiler has been installed and commissioned.
2. It is the law that all domestic boiler installations are registered by the installer through the Gas Safe Notification Scheme.
3. The boiler must only be used with Alpha CD condensing flue components.
Propane Gas (LPG) - In addition to the regulations and requirements stated, the boiler must be installed in accordance with BS 5482:1 - The Installation of Propane Burning Appliances in Permanent Dwellings.
Alpha Evoke 28 and 33 - Contents/Introduction
3
2 TECHNICAL DATA
2.1 TECHNICAL PERFORMANCE DATA - NATURAL GAS (Cat I2H 2H - G20 20 mbar)
Heat input gross - DHW kW
Heat input gross - CH kW
Heat input net - DHW kW
Heat input net - CH kW
Heat output condensing (50/30°C) - CH kW
Heat output non condensing (80/60°C) CH kW
Heat output min. - CH kW
Heat output nominal - DHW kW
Gas rate at max. output m³/h
Gas supply pressure mbar
Max. CH temperature - Set point °C
Gas burner injector diameter mm
DHW flow rate at 35°C rise l/min
DHW flow rate at 30°C rise - EN13203-1 l/min
Dry NOx weight mg/kWh
Dry NOx ppm
NOx Class
Factory set CO
CO
at maximum CH output %
2
CO
at maximum DHW output %
2
CO
at minimum output %
2
2
CO (max) ppm
Maximum CO/CO
Ratio
2
SAP/SEDBUK seasonality efficiency 2005 %
SAP/SEDBUK seasonality efficiency 2009 %
ErP DHW efficiency %
ErP Seasonal space heating efficiency %
Max. primary system pressure bar
Min. primary system pressure bar
Recommended system pressure - Cold bar
System pressure relief valve setting bar
Expansion vessel size litres
Expansion vessel charge pressure bar
Electrical power consumption - Max. Watts
Electrical power consumption - Standby Watts
Evoke 28
32.0
27.3
28.8
24.6
26.1
24.1
4.3
28.3
3.05
20
85
5.00
12.1
14.1
35
20
6
9.7
9.7 (+0.5/-0.2%)
8.8 (+0.2/-0.3%)
450
0.004
90.1
88.9
87 (XL)
93
2.5
0.5
1.0
3.0
8.0
1.0
80
2
Evoke 33
36.2
31.7
32.6
28.6
29.7
28
4.9
32
3.45
20
85
6.00
14.1
16.5
30
17
6
9.5
9.5 (±0.2%)
8.6 (+0.2/-0.3%)
450
0.004
90.2
89.0
87 (XL)
93
2.5
0.5
1.0
3.0
8.0
1.0
105
2
2.1 TECHNICAL PERFORMANCE DATA - LPG - PROPANE GAS (Cat I3P 3P - G31 37 mbar)
Evoke 28 Evoke 33
Heat input gross - DHW kW
Heat input gross - CH kW
Gas supply pressure mbar
Gas burner injector mm
CO
at maximum CH output
2
CO
at maximum DHW output
2
CO
at minimum output
2
Gas rate at maximum output kg/h
Note: OtherTechnical data is the same as NG data.
Alpha Evoke 28 and 33 - Technical Data
4
31.3
26.7
37
3.80
11.4
11.4 (±0.3)
10.6 (±0.2)
2.24
35.4
31.1
37
4.30
11.2
11.2 (+0.2/-0.4)
10.0 (+0.4/-0.2)
2.53
2.2 PHYSICAL DATA
Boiler flow and return connections mm
DHW inlet (cold) DHW outlet (hot) connections mm
Gas connection diameter mm
Boiler dimensions Height mm
Width mm
Depth mm
Clearances for servicing Bottom mm
Bottom (with jig) mm
Top (horizontal flue) mm
Top (vertical flue) mm
Sides mm
Front mm
Recommended hole size for flue pipe mm
Recommended hole size for instalation from inside the building mm
Boiler dry lift weight Evoke 28 kg
Evoke 33 kg
Boiler operating weight (full of water) approx. Evoke 26 kg
Evoke 33 kg
Max. total flue length Horizontal m
Max. total flue length Vertical m
Flue system diameter mm
22
15
22
712
440
256
150
250
235
150
5
450
110
130
33.6
35.5
35.8
37.9
12
14
60/100
2.3 FLUE LENGTHS
A 500 mm or 1000 mm Easy-Flue terminal kit with 90° bend or horizontal terminal is available.
CD 750 mm and 1000 mm flue extensions are available.
Length of Flue Required:-
Rear Flue = wall thickness + 180 mm (includes terminal).
Side Flue = wall thickness + distance between wall and side of boiler + 265 mm (includes terminal).
Vertical Flue = distance from top of boiler side panel to required roof position minus 1000 mm for vertical terminal assembly.
Maximum horizontal flue length = 12 m.
Maximum vertical flue length including terminal is 14 m.
Each additional CD 90° Bend is equivalent to 1.3 m of flue length.
Each CD 45° Bend is equivalent to 0.9 m of flue length.
The CD Vertical Flue terminal assembly is equivalent to 1 m of flue length.
2.4 PUMP
The boiler is equipped with a variable speed low power consumption pump.
During the DHW mode, the pump always runs at the maximum speed. During the CH mode, three different functioning modes of the pump are available, Proportional, Fixed and Constant )T.
Proportional - The pump speed is controlled automatically in order to give a proportional pump head, the pump speed
varies based on the heat output supplied by the burner - the greater the heat output the higher the pump speed. See parameter A3 in Section 5.13.
It is possible to adjust the pump speed range in the boiler parameter menu.
Fixed - The pump runs at a constant speed by setting the same minimum and maximum speeds. See parameters
A1 and A2 in Section 5.13.
Constant - The pump speed is controlled to give a set )T. See parameter A3 in Section 5.13. The boiler is factory set to Constant - to achieve a )T of 15°C (parameter A3 is set to 15)
By-pass Regulation - The boiler leaves the factory with the by-pass open. If necessary, the by-pass can be adjusted to the system requirements from maximum (by-pass open) to minimum (by-pass
closed). Adjust using a flat head screwdriver, turn anticlockwise to close the by-pass, and clockwise to open. With the by-pass in the closed position the system must have a continuous open circuit.
If zone valves are used in the system an external by-pass must be fitted.
Alpha Evoke 28 and 33 - Technical Data
5
2.4.1 Evoke 28 Available Pump Head and Power Consumption
7
6
Speed 9
5
A
4
3
Head (m water)
2
1
0
200 600 1000 1400800 1200 16004000
A+B = Head available with by-pass closed B = Head available with by-pass open C+D = Power consumed by the pump with by-pass open (dotted area) D = Power consumed by the pump with by-pass closed (dotted area)
C
Speed 9
Speed 6
Flow rate (l/h)
70
60
50
40
D
30
20
B
Pump electrical consumption (W)
10
0
Fig. 2.1
2.4.2 Evoke 33 Available Pump Head and Power Consumption
7
6
5
4
3
Head (m water)
2
1
0
200 600 1000 1400800 1200 16004000
A+B = Head available with by-pass closed B = Head available with by-pass open C+D = Power consumed by the pump with by-pass open (dotted area) D = Power consumed by the pump with by-pass closed (dotted area)
Speed 9
C
Speed 9
D
Speed 5
Flow rate (l/h)
70
60
50
40
30
20
B
Pump electrical consumption (W)
10
0
Alpha Evoke 28 and 33 - Technical Data
6
Fig. 2.2
2.5 ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
Optional integral single channel controls are available if required.
Note: Only use the Alpha single channel controls. Do not fit any two channel controls.
Programmer clock
(optional)
R
3
connect clock
Remove link to
Bl
Br
G/Y
N
L
Br
Bl G/Y
Mains Supply 220 V ~ 50 Hz
Remove link to
connect 220 V
room thermostat
When an Alpha Climatic control is connected to terminals 41 and 44
4
Bk
Bk Bl
A
B
remove the links between terminal blocks 1 and 2
1
Bl
2
R
Br
R
Bl
Y
Br
1
256 39 38 48
Bk
R
For testing
R
only
Room
thermostat
(optional)
Climatic Control
J2 on PCB
Or
R
Bk Or Y
40
41
44
Alpha
(optional)
38
B4
J2 on PCB
Y
J1 on PCB
B9
X4 on PCB
B4 External sensor B9 DHW inlet sensor
Colour Code
Bk Black Bl Blue Br Brown
G Green Gy Grey G/Y Green/Yellow
Or Orange P Purple R Red
W White YYellow
Fig. 2.3
2.6 DATA BADGE ANNOTATION
NOTE: Technical data is provided on the boiler data label and in Section 2.1.
Md
o
Sr N Type Q
nw/Qn min.
PMS NO
x Class
nw/Qn max.
Q PMW
P D
Md.............................Model
Cod. Md ....................Model code
o
Sr N
.........................Serial number
CHK ..........................Check
Cod. PIN ...................PIN code
Type ..........................Type of installation (ref. CEN TR 1749)
Q
nw min. .....................DHW minimum heat input
Q
n min. .......................CH minimum heat input
Q
nw max. ....................DHW maximum heat input
Q
n max. ......................CH maximum heat input
n min.
Cod. Md Cod. PIN
n max.
P TM
n min. .......................Minimum heat output
P P
n max. .......................Maximum heat output
PMS ..........................Maximum system pressure
PMW .........................Maximum DHW pressure
D ...............................Specific flow rate
TM ............................Maximum operating
temperature NO
x Class .................NOx Class
CONDENSING .........Condensing boiler
CONDENSING
Alpha Evoke 28 and 33 - Technical Data
7
2.7 BOILER SCHEMATIC
16
15
14
13
12
11
10
17
18
19
20
21
22
23
9
24
8
7
6
5
25
26
27
4
3
2
1
Domestic
hot water
outlet
Gas
1 Gas isolation valve
2 Cold mains isolation valve
3 Gas valve
4 DHW flow switch
5 Gas injector
6 Flow regulator
7 DHW temperature sensor
8 Condensate trap
9 3 bar safety valve
10 Expansion vessel
11 Venturi positive pressure point (+)
Cold mains
water inlet
Condensate discharge
and expansion relief
12 Venturi
13 Primary flow temperature sensor
14 Ignition/sensing electrode
15 Air supply pipe
16 Flue temperature sensor
17 Flue test point (pressure point +)
18 Air test point (pressure point -)
19 Burner
20 Primary return sensor
21 Fan
22 Automatic air vent
Primary Heating
return
28
29
30
31
Primary
Heating flow
23 Boiler pump
24 Primary pressure switch
25 DHW heat exchanger
26 Diverter valve
27 By-pass
28 Drain point
29 Safety valve indicator
30 Heating return isolation valve
31 Heating flow isolation valve
Alpha Evoke 28 and 33 - Technical Data
8
Fig. 2.4
3 GENERAL BOILER INFORMATION
3.1 GAS SUPPLY
The meter and supply pipes must be capable of delivering the required quantity of gas in addition to the demand from any other appliances connected to the same gas supply.
Refer to Technical performance data in Section 2.1 and 2.2. The complete installation, including the meter, must be tested for gas tightness and purged as described in BS 6891.
3.2 ELECTRICAL SUPPLY
The boiler requires a 230/240 V ~ 50 Hz mains supply, fused at 3 A
The boiler must be earthed.
There must only be one common isolator, providing complete electrical isolation, for the boiler and any external controls.
This boiler has been fitted with a supply cable, however, if it is necessary to fit a cable use PVC insulated cable not less than
0.75 mm² (24 x 0.2 mm) to BS 6500 Table 16. The boiler should be connected to a fused three pin plug and unswitched shuttered socket outlet (both complying with BS 1363), or a fused double pole switch with a contact separation of at least 3 mm in both poles.
Wiring external to the boiler must be in accordance with the current IEE Wiring Regulations (BS 7671).
Note: If a room thermostat is fitted, it must be suitable for 230/240 V switching.
3.3 AIR SUPPLY
The boiler does not require any air vents for cooling in the room in which it is installed or when installed in a cupboard or compartment. The minimum clearances for servicing must always be maintained.
Note: A cupboard or compartment used to enclose the boiler must be designed and constructed specifically for the purpose, i.e. comply with the Building Regulations.
3.4 FLUE SYSTEM - Fig. 3
The flue system must be installed in accordance with BS 5440:1.
When using a horizontal flue kit ensure that the flue outer duct is installed horizontally (please note that the flue inner duct already has a pre-determined slope towards the boiler for condensate to run back towards the boiler).
When additional flue extensions are used, ensure the flue slopes downwards towards the boiler by a minimum of 25 - 30 mm per metre of flue.
Horizontal and vertical flue assemblies should be supported every metre with access provided to the joints.
Additional flue components are available as follows:-
CD EasyFlue 500 mm telescopic terminal - Part No. 6.12000510.
CD EasyFlue 1000 mm telescopic terminal - Part No. 6.12001010.
CD 750 mm flue extension - Part No. 6.2000750.
CD 1000 mm flue extension - Part No. 6.2001050.
CD 100 mm flue support brackets (pack of 5) - Part No. 6.1000355.
CD 90° bend - Part No. 6.2000590.
CD 45° bend - Part No. 6.2000545.
CD Vertical flue terminal kit - Part No. 6.2000520. Refer to the separate installation instructions supplied with the kit.
Flue support brackets - Part No. 6.1000355.
Terminal guard - Part No. 6.2000570.
Additional flue accessories and plume management are also available.
Note: 1. If an extra 90° bend is used, this reduces the maximum flue length by 1.3 m. Each 45° bend used reduces the
maximum flue length by 0.9 m.
2. Under no circumstances must the flue length (including allowances for extra bends) exceed 12 metres horizontally
and only 14 metres vertically.
3. Failure to use Alpha flue components with the boiler will invalidate the boilers CE approval, guarantee and may be
unsafe.
Alpha Evoke 28 and 33 - General Boiler Information
9
12 m
B
A
A
B
A
HORIZONTAL FLUE OPTIONS - Lmax - 12 metres
Not less than
300 mm
H
L = A + B = 12m max.
L = A + B + (90° bend = 1.3 metre)
VERTICAL FLUE OPTIONS
L = A + (2 x 45° bends = 1.8 metre)
Fig. 3.1
Not less than
300 mm
H
Hmax = 14 m Hmax = 12.2 m (14 m - 1.8 m)
Fig. 3.2
Alpha Evoke 28 and 33 - General Boiler Information
10
3.5 FLUE TERMINAL LOCATION - Figs. 3.3 and 3.4
J
D
G
HI
Q
Boundary
O
P
N
A Directly below an opening, air brick, windows, etc.
B Below gutters, soil pipes or drain pipes
C Below eaves
D Below balconies
E From a vertical drain pipe or soil pipe
F From an internal or external corner
G Above ground, roof or balcony level
H From a surface or boundary facing the terminal
I From a terminal facing the terminal
J Above an opening, air brick, window etc.
K Vertically from a terminal on the same wall
L Horizontally from a terminal on the same wall
M Horizontally from an opening, air brick, window etc.
N Minimum protrusion through a roof
O From a vertical obstruction
P From an openable window
Q From an adjacent vertical terminal
Min. distance (mm)Terminal position
(See Note 1)
300
75 (See Note 3)
200 (See Note 3)
200 (See Note 3)
150 (See Note 3)
300 (See Note 2)
300 (See Note 9)
600 (See Note 4)
1200 mm
300
(See Note 1)
1500 mm
300 mm
300 mm
(See Note 1)
300 mm
300 mm
600 mm
600 mm
Fig. 3.3
Notes:
1. In addition, the terminal should not be nearer than 150 mm to the framework of an opening into the building, i.e. a
window surround or door surround.
2. This clearance may be reduced to 25 mm without effecting the performance of the boiler. However, to ensure the
condensate plume does not affect adjacent surfaces a clearance of 300 mm is preferable.
3. These clearances may be reduced to 25 mm without effecting the performance of the boiler. However, to ensure the
condensate plume does not affect adjacent surfaces the terminal can be extended beyond gutters, pipes, eaves, balconies etc. by upto 500 mm. If the flue is extended more than 500 mm outside, it should be boxed and insulated.
4. To reduce the possibility of nuisance to neighbouring buildings etc. it is recommended the terminal should not be less
than 2500 mm from car parking spaces, building boundary walls, fences etc.
5. A terminal must not be sited under a car port roof.
6. In certain weather conditions the terminal will emit a plume of steam. If possible avoid positioning the terminal where
this may cause a nuisance, i.e. positions A, D, G, H, J or M.
7. The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times.
8. The flue terminal must be positioned where products of combustion will freely disperse and not cause a nuisance.
9. Where a terminal is sited below 2 m from the ground or floor level, the terminal must be protected by a terminal guard.
In these situations, consideration should also be given to prevent nuisance plume and fumes in areas such as access routes, passageways, patios, balconies etc.
Alpha Evoke 28 and 33 - General Boiler Information
11
Proximity of flue duct outlets to boundaries
The flue duct shall be sited so that it is at least 600 mm (see Fig. 3.4) from the boundary line when facing it and at least 300 mm from the boundary line when running parallel to it.
Boundary
Building
Terminal facing the boundary
Boundary
Building
Terminal at an angle to the boundary
Terminal
300 mm
600 mm
600 mm
Terminal
Fig. 3.4
Boundary
Building
Terminal parallel to the boundary
Adjacent building
Boundary
Building
Terminal facing an opening in adjacent building
Terminal
300 mm
Terminal
Window
2000 mm
3.6 BOILER LOCATION
The boiler is not suitable for external installation unless it is installed within a purpose designed weatherproof building. The boiler must be installed on a flat vertical wall which is capable of supporting the weight of the boiler. The boiler can be fitted
to or adjacent to a wall comprising of a combustible material without the need for a special thermal insulation barrier. If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with the Institute of Gas Engineers
'Guide for Gas Installations in Timber Frame Housing', reference IGE/UP/7.
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the current IEE Wiring (BS 7671) Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. Where a room­sealed boiler is installed in a room containing a bath or shower, it must not be possible for a person using the bath or shower to touch any electrical switch or boiler control utilising mains electricity.
The boiler may be installed in a cupboard or compartment, provided it is correctly designed for that purpose, i.e. complies with the Building Regulations and the requirements of BS 6798.
Alpha Evoke 28 and 33 - General Boiler Information
12
3.7 CENTRAL HEATING SYSTEM - Fig. 3.5
The boiler is designed for use in a sealed central heating system in accordance with the requirements of BS EN 12828 and BS 6798.
The system should be designed to operate with flow temperatures of up to 90°C. When designing the system, the pump head, expansion vessel size, mean radiator temperature, etc. must all be taken into account. Refer to the pump performance table for guidelines.
System volume - The expansion vessel incorporated into the boiler is suitable for a sealed heating system with a maximum water content of 80 litres (18 gal). Above 80 litres, consideration should be given to fitting an additional expansion vessel fitted in the position shown in Fig. 32.5. To check correct operation of the expansion vessel(s) the system pressure should not be more than 2.5 bar when the system is at maximum operating temperature (for further guidance refer to BS 7074:1).
The boiler is supplied with the following components built in:-
Pressure gauge - To indicate the system pressure to be maintained.
Expansion vessel - Conforming to EN 13831 with a capacity of 8 litres and pre-charged with air to a pressure of 1.0 bar.
By-pass - The boiler incorporates an automatic by-pass, therefore an automatic by-pass is not required for the system.
Static head of system
Note: A drain tap should be installed at the lowest point of the heating circuit and beneath the appliance.
Boiler
casing
Heating
flow
Heating return
System drain tap
Automatic air vent
Note: If the mains is fitted with a water meter, check valves or loose jumper stop cock, then a DHW expansion device must
Additional expansion vessel (if required)
Filling point
DHW outlet
Mains water inlet
be fitted.
Fig. 3.5
3.8 FILLING THE CENTRAL HEATING SYSTEM - Fig. 3.6
The system design pressure (cold) should be set to 1.0 bar. This pressure is equivalent to a static head (see Fig. 3.5) of 10.2 metres of water.
Provision must be made for filling the system. This is done by the use of a filling loop. See Fig. 3.6. A filling loop is not supplied with this boiler.
Filling of the system must be carried out in a manner approved by the local Water Undertaking. Where allowed, the system may be filled via a temporary connection as shown in Fig. 3.6. After filling, always disconnect the flexible hose of the filling loop.
All fittings used in the system must be able to withstand pressures up to 3 bar.
Drain taps (to BS 2879) must be used to allow the system to be completely drained.
Heating circuit
return
Stop valve
temporarily connected
Fig. 3.6
Hose
unions
Filling loop
Double check
valve assembly
Test cock
Stop valve
Mains water supply
Alpha Evoke 28 and 33 - General Boiler Information
13
3.9 FLUSHING THE HEATING SYSTEM
It is essential that the central heating system is thoroughly cleaned and flushed when fitting an Alpha boiler. Failure to do so will invalidate the warranty.
The primary condensing heat exchanger is constructed in stainless steel and therefore is compatible with most materials used in a heating system.
Cleaning agents and inhibitors must be applied in accordance with their manufacturers instructions. Suitably approved products for cleaning and treatment must be used.
The system should be flushed in accordance with BS 7593 and BS EN 14336. The following procedures are recommended:
1. Installing onto a new system:­ a. Fill the system, vent at high points and radiators. b. Check for leaks. c. Drain the system. d. Chemically clean the system as instructed by the recommended cleaner manufacturer. Note: Ensure that the system is flushed to remove any remains of the cleaner. e. If chemical cleaner is not used to clean the system:­ i) Refill the system. ii) Switch on the boiler and allow the system to heat up to the normal operating temperature. iii) Switch off the boiler and drain the system while the water is still hot. iv) Refill the system and check for leaks. f. Add the inhibitor to the system as instructed by the inhibitor manufacturer instructions.
2. Installing onto an existing system, clean the system before fitting the new boiler:­ a. If the old boiler is still working:­ i) Switch on the boiler and allow the system to heat up to the normal operating temperature. ii) Switch off the boiler and drain the system while the water is still hot. iii) Refill and chemically clean the system as instructed by the cleaner manufacturer instructions. iv) Ensure the system is flushed to remove any remains of the cleaner. v) Fit the new boiler. b. If the old boiler is not working:­ i) Drain the system. ii) Remove the old boiler. iii) Flush the system through. iv) Fit the new boiler. v) Refill and chemically clean the system as instructed by the cleaner manufacturer instructions. vi) Ensure the system is flushed to remove any remains of the cleaner and check for leaks. c. Add the inhibitor to the system as instructed by the inhibitor manufacturer instructions.
The system inhibitor level must be maintained at the correct concentration. The PH of the system water must be between 7.5 and 9.5 or the appliance guarantee will be invalidated.
The system must not be filled with softened water.
3.10 DISPOSAL OF CONDENSATE
Provision must be made for the safe disposal of condensate produced by the flue gases of the Alpha boilers and reference should be made to BS 6798 for the requirements on the disposal of condensate.
The boilers incorporate a condensate trap which has a seal of greater than 75 mm, therefore no additional trap is required.
The condensate should ideally be discharged internally into an internal waste pipe (washing machine/sink waste) or soil pipe to avoid the possible risk of freezing. The pipework must be in 22 mm pipe (minimum).
External pipe runs should be avoided, but if it is necessary, the pipework should be protected from the risk of freezing with waterproof insulation and the length should be kept to a maximum of 3 m and the condensate pipework should be increased to a minimum of 32 mm diameter. Termination should be into an external gulley or soakaway as shown in Figs. 3.7 and 3.8.
Note: All pipework must have a continuous fall (see Figs. 3.7 and 3.8) from the boiler and must be of an acid resistant material such as plastic waste pipe. (copper or steel is not suitable).
The condensate pipe is combined with the expansion relief discharge. The flexible condensate hose supplied meets the requirements for use with both condensate and expansion relief. This should be connected to a suitable waste pipe and fittings with approval for hot and cold water, i.e. BS EN1451-1PP Waste piping, BS EN1455-1 ABS piping or BS EN 1566-1 MUPVC piping.
The condensate and discharge should be connected to a drain for sewage and foul waste or a dedicated soak away with neutraliser added.
It should be noted that the connection of a condensate pipe to a drain may be subject to local building control requirements.
Alpha Evoke 28 and 33 - General Boiler Information
14
Plastic pipe (minimum 32 mm)
22mm termination from boiler, increase to 32 mm if external
Minimum gradient 2½°
Fig. 3.7 - External gully
Cement mortar sealing
500 mm min.
Use waterproof pipework insulation in very exposed positions
Ensure pipe is adequately supported
Open end of pipe diverted into gully below grid but above water level
O
2½ fall
Ground level (either/or)
25mm
100mm plastic tube
Bottom of tube sealed
Soakaway depth 400mm filled with limestone chippings
300mm
Two rows of 3 x 12mm holes at 25mm centres, 50mm from the bottom of the tube. Holes to face away from house.
Fig. 3.8 - External soakaway
3.11 DOMESTIC HOT WATER SYSTEM
The minimum flow rate needed for the flow switch and burner to operate is 1.5 litres/min.
If the incoming mains water pressure is above 5 bar a pressure reducing valve must be fitted.
If the mains supply is fitted with a water meter, check valves or loose jumper stop cock, then a DHW expansion device must be fitted.
Following Part L Building Regulations, where the mains water hardness exceeds 200 parts per million, provision should be made to treat the feed water to the hot water circuit of combination boilers to reduce the rate of accumulation of limescale.
To ensure economic use, the pipe runs between the boiler and taps should be in 15 mm copper pipe and be as short as possible. Where possible the pipework should be insulated to reduce heat loss.
All taps and mixing valves used with the hot water system must be suitable for operating at a mains pressure of up to 8 bar.
Showers - A shower may be used with the boiler if required. If a loose or flexible head type shower is used it may require the fitting of a double check valve, to comply with Water Bye Law 17.
Bidets - No anti-syphonage arrangements are necessary, provided the outlets are shrouded and it is not possible to attach a temporary hand held spray. A supply of direct mains fed hot and cold water is permitted provided the appliance is of the over-rim flushing type.
Before the mains water supply pipe is connected to the boiler, it should be thoroughly flushed out to avoid the danger of dirt or foreign matter entering the boiler.
Alpha Evoke 28 and 33 - General Boiler Information
15
4 INSTALLATION
256 mm
5 mm
5 mm
150 mm
235 mm - Can be reduced to 150 mm when using a vertical flue
440 mm
4.1 UNPACKING
1. The boiler carton also contains the following:-
Connection kit (union bends, washers and valves)
Mounting bracket plus screws and wall plugs
Condensate discharge pipe
Literature pack and Wall template
A suitable Alpha flue system must be selected to use with the boiler.
Notes: a. All flues must be suitable for Alpha condensing boilers. b. CD 750 mm and 1000 mm flue extensions are available, if required.
2. Unpack boiler and remove the loose items, packs and mounting bracket.
Note: The boiler can be stood in an upright position (only while the valves and union bends are not fitted).
It is recommended that two persons lift the boiler.
4.2 CLEARANCES REQUIRED - Fig. 4.1
712 mm
Minimum clearance of 450 mm from front of boiler
Minimum clearances
Fig. 4.1
4.3 PREPARE THE WALL - Fig. 4.2
1. Decide upon the position of the boiler taking into account the clearances required for servicing and the flue terminal position.
2. Tape the template to the wall (ensure it is level and the right way up) and mark the position of the holes for the boiler mounting bracket. If rear exit flue is used, mark the position of the hole for the flue.
3. Side exit flue - Continue the horizontal centre line of the flue across the wall to the side wall, then along the side wall 135 mm (ensure the lines are horizontal). This will give the position of the centre of the hole for the flue.
4. Cut the 110 mm diameter hole (or use a 107 mm core drill) in the wall for the flue.
Notes: 1. Ensure the hole is horizontal.
2. For internal fitting of the flue, using the flue sealing
collar supplied, cut a 130 mm dia. flue hole using a 127 mm core drill.
5. Drill the fixing holes (10 mm dia.) to accept the No.10 plugs supplied. Using the screws supplied, fit the mounting bracket.
Rear exit hole 110 mm dia.
=
=
Ensure line is level
143 mm
Fixing holes if mounting bracket used
Fixing holes if wall jig used
Outline of boiler
Template
Fig. 4.2
135 mm
Position of 110 mm hole to be cut for side exit flue
Alpha Evoke 28 and 33 - Installation
16
4.4 FIT THE BOILER - Refer to Figs. 4.2 and 4.3
Lift the boiler and locate it on the mounting bracket - the boiler should be lifted
Pour water into flue duct (to fill condensate trap)
by two persons.
Note: When handling or lifting always use safe techniques - keep your back
straight, bend your knees, don't twist - move your feet, avoid bending forwards and sideways and keep the load as close to your body as possible. Where possible transport the boiler using a sack truck or other suitable trolley. Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary.
Location for wall mounting bracket on rear of boiler
4.5 CONNECT THE PIPEWORK - Fig. 4.4
1. Thoroughly flush out all the water pipework. Refer to Section 3.9.
2. Fit the valves to the boiler connections as shown in Fig. 4.4 - note the colours of the operating levers.
3. Connect the system pipework to the union fittings on the valves just fitted.
Note: When soldering bends, ensure they are not connected to the
valves, otherwise the internal seals may be damaged.
One metre of copper pipe must be fitted to the boiler before connecting to any plastic pipework conforming to
BS 7291.
4. Connect the flexible condensate pipe to the rubber connector as shown in Fig. 4.4. Using the adaptor supplied, connect the flexible pipe to the condensate drain.
Ensure that the condensate discharge pipe is as required in Section 3.10.
5. Ensure that all the valves are closed (operating lever at right angle to valve) and do not turn on the water or gas supplies at this stage.
Fig. 4.3 - rear of boiler
Condensate discharge pipe
Hot water outlet
Gas service cock (yellow)
Electrical connection
30
Cold water inlet, filter and restrictor
65 70 457095 95
AB C
A - Gas inlet - (22 mm)
B - DHW outlet elbow - (15 mm)
C - Cold water mains inlet - (15 mm)
D - Heating return - (22 mm)
E - Heating flow - (22 mm)
Safety valve operation indicator
Heating return valve
Heating flow valve
120
Heating drain point
D
E
Fig. 4.4
Alpha Evoke 28 and 33 - Installation
17
4.6 FIT THE FLUE - Figs. 4.5 and 4.6
The following procedure applies to fitting an Alpha CD Easy-Flue to both rear or side exit flue - horizontally only.
1. The CD Easy-Flues are suitable for use in the flue length ranges shown in the tables below.
Note: Where the length is less than the minimum or more than the maximum, refer to Section 4.7.
(B + C)
B (mm)
Max
530
975
Min
305
765
Side Flue
(B)
Rear Flue
CD Easy-Flue
500 mm
1000 mm
Note: Add 45 mm to dimension B if the wall jig is used.
Fig. 4.5 Fig. 4.6
2. Determine the overall length (L) of flue required, (see Fig. 4.7) as follows:-
Rear flue L = wall thickness (B) + 60 mm (105 mm if the wall jig is used)
Side flue L = wall thickness (B) + distance between boiler and wall (C) + 145 mm
L
Seal Joint with Tape
CD Easy-Flue
500 mm
1000 mm
B + C (mm)
Max
Min
440
215
885
675
Fig. 4.7
3. Adjust the telescopic section of the flue to the distance ‘L’, ensuring that the two labels marked ‘TOP’ are aligned, then seal and secure the joint between the ducts with the sealing tape supplied.
Note: Always ensure that there is a minimum overlap of 25 mm when fully extending the telescopic section.
4. Pass the flue assembly through the wall (from inside or outside).
Note: Internal fitting - If there is no access to make good the outside wall, locate the outside (black) flue sealing collar
onto the outer duct of the flue immediately before the terminal grille onto the location provided. Push the flue assembly through the 130 mm flue hole, so that the collar completely passes through the wall. Then pull the flue assembly back into the correct position. Visually check that the collar is sealing the outside wall and that it is not restricting any of the openings of the flue terminal.
Note: Silicone grease or other lubricants must not be used on the flue joints or seals.
Where a flue terminates less than 150 mm below a gutter, eaves or other obstructions it is possible to extend the flue to
allow the flue termination to clear the obstruction, providing the flue is not extended beyond the first joint. For situations below balconies or large eaves where extensions may be required, the flue must be supported using the correct brackets. Alternatively plume management components can be used with supports where necessary.
Alpha Evoke 28 and 33 - Installation
18
Fig. 4.8 - Fitting the flue from inside
Check collar is sealing the wall and it is not restricting any openings of the flue terminal
130 mm
5. Position the smaller Easy-Flue 40 mm clamp (with seal) supplied, over the bend. Fit the bend to the boiler and rotate to the correct position. Secure in position using the clamp. Ensure the clamp is located centrally over both the bend and boiler adaptor.
6. Fit the inside (white) flue sealing collar over the Easy-Flue. If it was not previously fitted, fit the outside (black) flue sealing collar onto the flue immediately before the terminal grille onto the location provided.
7. Slide the larger Easy-Flue 45 mm clamp over the outer duct and pull the flue assembly towards the bend, locating the inner duct into the seal joint on the bend. Ensure the labels marked 'TOP' are positioned at the top before securing the flue assembly to the bend with the clamp (two screws) located centrally over the joint.
Note: Check the flue terminal protrudes 120 mm out of the wall and the inner duct of the terminal is positioned correctly
(see Fig. 4.9).
8. Make good the inside wall by pushing the inside flue sealing collar up to the wall.
The hole around the flue can be made good using the flue sealing collars supplied or using a suitable sealant/cement if
required.
Ensure the inner duct within the terminal is at the top.
The inner duct must
Note:
be positioned to slope towards the boiler
Flue sealing collar
Inner duct seal
120
20
Terminal
65
Note: Ensure the outer flue duct is horizontal
CD Easy-Flue
40 (85 if wall jig used)
Inner duct
Easy-Flue 45 mm clamp
Elbow seal joint
90° bend
Easy-Flue 40 mm clamp and seal
Side of boiler
135 (180 if wall jig used)
Fig. 4.9 - Rear flue
4.7 REDUCING THE FLUE - Fig. 19
When the flue length required is less than the minimum stated in Section 4.6, paragraph 1, refer to Fig. 4.10.
Discard the first telescopic section (not the section with the terminal) of the Easy-Flue 1000 mm or 500 mm and cut to the required length.
Note: Ensure that all cuts are square and free from burrs. Once assembled with the components pushed home, the flue is fully sealed.
Allow 20 mm 30 mm
Do not cut past this point
Fig. 4.10
Alpha Evoke 28 and 33 - Installation
19
Front of boiler
4.8 EXTENDING THE FLUE - Fig. 4.11
Note: The flue assembly length must not exceed the maximum length stated, including the equivalent lengths of any extensions, bends etc. used for plume management components. Evoke boilers must not exceed the maximum of an
equivalent horizontal flue length of 12 m.
1. When the flue length required is more than the maximum stated in Section 4.6, paragraph 1, refer to the table below and Figs 4.5 and 4.6.
Rear Flue length (B)
Up to maximum:-
11.890 m
(Subtract 45 mm if the wall jig is used)
Side Flue length (B + C)
Up to maximum:-
11.805 m
Comments
Alpha CD 750 mm flue extension (Part No. 6.2000750) or 1000 mm extension (Part No. 6.2001050) is required to extend the range of telescopic flue.
Refer to Section 4.8 for instructions on how to extend the flue. Note: A 130 mm flue hole (127 mm core drill) may be required in the wall.
This is when the extended flue is passed through the wall.
Additional support brackets are required when extending the flue. These are available from Alpha, Part No. 6.1000355.
2. Use the template (supplied with the boiler) to mark the required flue position, ensure the slope towards the boiler is correct.
3. Determine the overall flue length as described in Section 4.6, paragraph 2 to determine the number of Alpha CD 750 or 1000 mm flue extensions required.
4. Assemble the flue extensions together by locating the inner duct into the seal joint and secure each extension together with the extension clamps supplied (three screws). Ensure that the clamps are positioned centrally over the joints.
Note: If it is required to cut an extension, DO NOT cut the end of the inner duct that incorporates the seal joint. Ensure
the inner duct end without the seal joint is cut so that it is 20 mm longer than the outer duct.
Ensure that all cuts are square and free from burrs. Once assembled with the components pushed home, the flue is fully sealed.
5. Adjust the telescopic section of the Easy-Flue to the required length and secure the Easy-Flue with the sealing tape supplied. Fit the Easy-Flue to the extensions by locating the inner duct into the seal joint and secure with the clamp (three screws), ensuring it is located centrally over the joint.
6. Mark the end of the flue assembly 'TOP' where it is connected to the boiler, so that the 'TOP' of the flue terminal is aligned with the 'TOP' at the boiler end of the flue assembly.
7. Pass the complete flue assembly through the wall.
8. Position the smaller Easy-Flue 40 mm clamp (with seal) supplied, over the bend. Fit the bend to the boiler and rotate to the correct position and secure in position. Ensure the seal is located centrally over both the bend and boiler adaptor. If the inside sealing collar (white) is being used to make good the inside wall, then it will need to be fitted before assembling the flue.
9. Slide the larger Easy-Flue 45 mm clamp (two screws) over the outer duct and pull the flue assembly towards the bend, locating the inner duct into the seal joint on the bend.
Ensure the inner duct within the terminal is at the top.
The inner duct must be positioned to slope towards the boilerNote:
Terminal
Flue sealing collar
20
120
20
Alpha Evoke 28 and 33 - Installation
CD Easy-Flue
Ensure outer flue duct of Easy-Flue is horizontal
Inner seal joint
Flue length (L)
Fig. 4.11 - Side flue
Extension clamp
Inner seal joint
CD Flue extension
Ensure the flue extension slopes downwards towards the boiler by a minimum of 25 - 30 mm per metre
Easy-Flue 45 mm clamp
90° bend
Easy-Flue 40 mm clamp and seal
125
220
Seal joint
45
Loading...
+ 44 hidden pages