Alpha DCX3000 Operator's Manual

DCX3000 Portable Generator
Operation Manual
3.0kW, 36/48V, DC Portable Generator
Effective: September 2006
Alpha Technologies
Alpha Technologies
Power
®
AlphaGen DCX3000
3.0kW, 36/48V DC Portable Generator Operation Manual
041-028-B0-003, Rev. C
Effective Date: September 2006
Copyright© 2006
Alpha Technologies, Inc.
NOTE:
Photographs contained in this manual are for illustrative purposes only. These photographs may not match your installation.
NOTE:
Operator is cautioned to review the drawings and illustrations contained in this manual before proceeding. If there are questions regarding the safe operation of this powering system, please contact Alpha Technologies or your nearest Alpha representative.
NOTE:
Alpha shall not be held liable for any damage or injury involving its enclosures, power supplies, generators, batteries, or other hardware if used or operated in any manner or subject to any condition not consistent with its intended purpose, or is installed or operated in an unapproved manner, or improperly maintained.
TM
Contacting Alpha Technologies: www.alpha.com
or
For general product information and customer service (7 AM to 5 PM, Pacifi c Time), call
1-800-863-3930
For complete technical support, call
1-800-863-3364
7 AM to 5 PM, Pacifi c Time or 24/7 emergency support
3
Table of Contents
Safety Notes ..........................................................................................................................6
1.0 Introduction .................................................................................................................8
2.0 Specifi cations.............................................................................................................. 9
3.0 Battery Cable Connections .......................................................................................10
3.1 Enclosures with Generator Access Door ....................................................... 10
3.2 Enclosures without Generator Access Door ...................................................11
3.3 Grounding ...................................................................................................... 16
4.0 Starting the Engine ................................................................................................... 18
5.0 Engine Shut-Down and Cable Removal ................................................................... 20
5.1 Long-term Storage ......................................................................................... 20
5.2 Scheduled Maintenance ................................................................................ 20
5.3 Transporting the Generator ............................................................................ 20
5.4 Fuse Replacement .........................................................................................21
6.0 Maintenance Record................................................................................................. 22
4
041-028-B0-003, Rev. C
List of Figures
Fig. 1-1, DCX3000 Overview ................................................................................................. 8
Fig. 1-2, Basic Block Diagram ............................................................................................... 8
Fig. 3-1, Generator Access Door and Battery Pack Adapter Cable ..................................... 10
Fig. 3-2, Enclosure without Generator Access Door.............................................................11
Fig. 3-3, Alligator Clamp-style Connection .......................................................................... 12
Fig. 3-4, Ring Lug-style Connection .................................................................................... 13
Fig. 3-5, Novus-style Connection ........................................................................................ 14
Fig. 3-6, Y-style Connection................................................................................................15
Fig. 3-7, Generator Grounding ............................................................................................ 16
Fig. 3-8, Overview of PWE Installation ................................................................................ 17
Fig. 4-1, Starting the Engine ................................................................................................18
Table 4-1, Battery Voltage and Output Indications .............................................................. 19
041-028-B0-003, Rev. C 5
Safety Notes
Review the drawings and illustrations contained in this manual before proceeding. If there are any questions regarding the safe installation or operation of this product, contact Alpha Technologies or the nearest Alpha representative. Save this document for future reference.
To reduce the risk of injury or death, and to ensure the continued safe operation of this product, the following symbols have been placed throughout this manual. Where these symbols appear, use extra care and attention.
ATTENTION:
The use of ATTENTION indicates specifi c regulatory/code requirements that may affect the placement of equipment and /or installation procedures.
NOTE:
A NOTE provide additional information to help complete a specifi c task or procedure.
CAUTION!
The use of CAUTION indicates safety information intended to PREVENT DAMAGE to material or equipment.
WARNING!
WARNING presents safety information to PREVENT INJURY OR DEATH to the technician or user.
6
041-028-B0-003, Rev. C
General Safety Information
The manufacturer cannot anticipate every circumstance that may involve a hazard, therefore, these warnings are not all inclusive.
Do not use the generator or any of its parts as a step.
Generator must be properly grounded.
Do not place or operate the generator in standing water, or expose to a forced spray of water.
Do not make or break any connections while generator is running.
Fuel spillage cleanup is the responsibility of the operator and should comply with local codes and regulations.
Do not refuel the generator while engine is running. Allow generator to cool before refueling.
• For fi re safety, the generator must be properly connected, maintained, and in compliance with applicable codes and regulations.
Engine exhaust contains carbon monoxide gas, which can be deadly in closed or poorly ventilated areas.
Prior to each use, inspect the generator for leaks and damage. Immediately repair or replace any damaged parts.
Never operate the generator near combustible materials.
Ensure cables do not cross hot surfaces or sharp edges. Inspect cables before and after each use.
Drain oil and empty the fuel tank before transporting. Fuel can leak from the fi ller cap if the generator is tilted.
Never refuel the generator in the vicinity of open fl ames of heat sources. Do not smoke near the generator.
The generator should be operated on level ground. If necessary, it may be operated on a grade <15°.
Use only vendor-authorized repair parts.
Do not operate generator unattended.
ATTENTION:
Alpha Technologies’ products are subject to change through continual improvement processes. Therefore, specifi cations and design layouts may vary slightly from descriptions included in this manual. Updates to the manual are issued when changes affect form, fi t or function.
This product is manufactured to conform to the Federal Communications Commissions (FCC) Part 15, Class A regulations. It is intended to be used for commercial, industrial or business environments.
This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
041-028-B0-003, Rev. C 7
1.0 Introduction
The Alphagen DCX3000 portable DC generator supplies DC power to a power node battery bus during AC line interruptions. Upon loss of commercial AC power, the existing battery strings supply the power supply inverters. After some interval of battery discharge, the operator deploys the portable generator at the site to supply power to the DC bus. The generator delivers continuous, high-quality power throughout the commercial AC interruption period. After restoration of commercial AC power, the operator disconnects and removes the generator.
Status LEDs
1
Engine Switch
2
Choke
3
Fuel Valve
4
Voltmeter
5
Output Off Button
6
9
1
2
3
5
8
7
4
6
DC Out
7
Pull-start
8 9
Fuel Tank
Fig. 1-1, DCX3000 Overview
Engine Alternator Rectifier
Controller
DC Sense Feedback
Load
(batteries)
Fig. 1-2, Basic Block Diagram
8
041-028-B0-003, Rev. C
2.0 Specifi cations
Engine
Fuel/Fuel Tank Unleaded gasoline/3.5 gallon metal tank with level gauge Rated Power 2800W continuous, 3000W maximum Alternator Permanent magnet, brushless, bearingless Output Voltage
Dual range selector Output Regulation +/-1VDC Control Features Automatic Voltage Regulation
Cable Interface Anderson type SBE-80 connector Runtime @25% load (48V): 15.4 hours
Audible Noise Approximately 65dBA @ 7 meters under full load Frame Fully enclosed Dry Weight 117 lb Dimensions 22" H X 17.6" W X 25.9" D (557mm x 447mm x 657mm) Operating Temp 5°F to 104°F (-15°C to 40°C) Required Accessories Output Interface Cable: Available in 10', 30', or 50' lengths
Agency Compliance CSA 22.2 No. 100-95
Optional Accessories Portable Generator Wheel Kit: P/N 745-793-20
Honda GX 200 6.5 hp, air-cooled, OHV, single cylinder, manual recoil starting, manual choke
36V: 39.5VDC, nominal at generator output connector 48V: 52.5VDC, nominal at generator output connector
Electronic Governor Overcurrent Protection Analog voltmeter with back light
@25% load (36V): 17.5 hours @100% rated load: 6.5 hours
Battery Interface Cable: Choose Ring Lug, Heavy-duty Alligator Clamp, or Y-adapter (Connects the
power supply’s battery input directly to the generator. See Section 3.0 for more information)
FCC part 15B Class A CARB UL 50, Section 30 NFPA 37, 70 EPA
Punch Tool Kit for Enclosures, 2.5" dia: P/N 745-131-20 Enclosure Upgrade Kit: P/N 745-131-21 Cable Bag and Cable Key Lanyard: P/N 745-764-21 Locking Handle: P/N 745-792-20
NOTE:
Please refer to www.alpha.com for available options and data sheets.
041-028-B0-003, Rev. C 9
3.0 Battery Cable Connections
3.1 Enclosures with Generator Access Door
Tools and Materials Needed:
Portable Generator Battery Cable Kit
• DC Multimeter
Procedure:
1. Open the enclosure’s battery compartment and locate the battery pack connections for the positive and negative battery cables leading to the power supply.
2. Observing polarity (red to positive, black to negative), connect the Battery Pack Adapter Cable to the connections located in Step 1. Attach Ring Lug or Alligator Clamp connections directly to the battery post. See Fig. 3-5 and Fig. 3-6 for Novus-style and Y-
style connections. Do not connect the extension cable to the DC OUT jack on the
front panel of the generator at this time.
3. Route the extension cable (10’, 30’, or 50’) into the enclosure’s battery compartment. Protect cable from chafi ng against sharp edges.
4. Connect the Battery Pack Adapter Cable to the extension cable. Extension cables are equipped with in-line fuses. Replace only with 100 Amp 300VAC fuse (Alpha P/N 460­191-10).
CAUTION! Inspect cable sets before each use for damage and wear. Use only cable sets that are designed for
this generator.
10
Fig. 3-1, Generator Access Door and Battery Pack Adapter Cable
041-028-B0-003, Rev. C
3.0 Battery Cable Connections, continued
3.2 Enclosures without Generator Access Door
Tools and Materials Needed:
2.5" Punch Tool Kit for Enclosures (Alpha P/N 745-131-20)
2.5" Enclosure Upgrade Kit (Alpha P/N 745-131-21)
• Electric drill
#7 Drill bit (.2010”) or #9 drill bit (.1960”)
#2 Phillips screwdriver
WARNING!
Disconnect all sources of service power to the enclosure before drilling holes. Ensure the area is clear of wires and electrical boxes. Do not locate the hole above electrical boxes to prevent damage from water intrusion while the plug is removed.
Procedure:
1. If not previously installed, punch or cut a 2.5” hole in the enclosure (shown below) to
route the generator’s battery cable. Ensure area is clear of electrical wires and boxes.
2. Install the grommet into the hole, and install the weatherproof plug into the grommet.
3. Using the #7 or #9 drill bit, drill a hole approximately 2” below and to one side of the
grommet, attach the lanyard on the inside of the enclosure with the #10 bolt and nut provided.
Suggested location of battery
cable hole for PWE enclosures
Hole for lanyard bolt
Fig. 3-2, Enclosure without Generator Access Door
041-028-B0-003, Rev. C 11
3.0 Battery Cable Connections, continued
Extension Cable Set, 50’ P/N 875-324-21 30’ P/N 875-324-20 10’ P/N 875-324-22
Alligator Clamp-style
Battery Pack Adapter Cable,
P/N 874-946-20
3
Red
2
Fuse
1
Black
Ensure clamps lay fl at against
batteries, facing inward
12
Fig. 3-3, Alligator Clamp-style Connection
041-028-B0-003, Rev. C
3.0 Battery Cable Connections, continued
Extension Cable Set, 50’ P/N 875-324-21 30’ P/N 875-324-20 10’ P/N 875-324-22
Ring Lug-style
Battery Pack Adapter Cable,
P/N 874-946-21
3
Red
2
Fuse
1
Black
Cable rings connect directly
to the battery terminals
Fig. 3-4, Ring Lug-style Connection
041-028-B0-003, Rev. C 13
3.0 Battery Cable Connections, continued
Circuit Breaker
mustbe CLOSED
GENERATOR
BREAKER
60A
EXTGENERATOR
REDBLACK
BYPAS
FROMXT1
UPS
S
CONVENI ENCE
HEATING PADS
Novus Power
Panel
Novus-style
Battery Pack Adapter Cable
P/N 875-324-23
OUTPUTS
Plus
LA-P
Extension Cable Set, 50’ P/N 875-324-21 30’ P/N 875-324-20 10’ P/N 875-324-22
Fig. 3-5, Novus-style Connection
14
041-028-B0-003, Rev. C
3.0 Battery Cable Connections, continued
Extension Cable Set, 50’ P/N 875-324-21 30’ P/N 875-324-20 10’ P/N 875-324-22
Y-style
Battery Pack Adapter Cable
P/N 874-946-22
3
2
Fuse
1
Fig. 3-6, Y-style Connection
041-028-B0-003, Rev. C 15
3.0 Battery Cable Connections, continued
3.3 Grounding
Tools and Materials Needed:
#8AWG copper ground wire and clamps
Procedure:
1. Read and thoroughly understand the Engine Owner’s Manual before operating this equipment.
2. Before starting the generator, follow all instructions outlined in the BEFORE OPERATION section of the Engine Owner’s Manual.
3. Attach #8AWG copper grounding wire between the generator grounding lug and the service entrance grounding bar, or directly to the utility grounding rod.
WARNING!
To prevent injury, the generator must share a common ground with the enclosure service entrance.
Fig. 3-7, Generator Grounding
Generator Grounding Lug
16
041-028-B0-003, Rev. C
3.0 Battery Cable Connections, continued
To prevent injury, the generator MUST share a common ground with the enclosure service entrance.
Power Meter
Ground Stake
Ground Wire
Ground Wire
Fig. 3-8, Overview of PWE Installation
041-028-B0-003, Rev. C 17
4.0 Starting the Engine
Prior to starting the generator, review the Safety Information on page 6 of this manual. Set the generator on a fl at, level surface, free of standing or running water, or combustible materials.
Operating the generator at an angle of more than 15 degrees may result in the oil level dropping below a safe level. This may cause the low oil sensor to trip, or failure of the generator to shut down.
This generator runs very quietly. It is not always possible in ambient-noise situations to determine whether it is running simply by sound. Verify that the generator is OFF before proceeding with the following procedure.
Tools and Materials Needed:
#2 Flat-tip screwdriver (to open side panel)
Procedure:
1. Verify fuel is in the fuel tank.
2. Open the maintenance cover on the left side panel of the generator. Set the Voltage Select switch to match the battery pack voltage (36V or 48V). Close cover before starting engine.
3. Verify polarity and battery voltage continuity on extension cables. Connect the extension cable coupler to the DC OUT jack on the generator. Verify the voltmeter indicates the voltage of the battery pack.
Voltage Select Switch
NOTE:
Set correct voltage on Voltage Select Switch. Generator will not engage with incorrect voltage setting.
4. Insert key and turn the ENGINE SW to the ON position.
5. If the engine is cold, pull the CHOKE knob out.
6. Turn the FUEL VALVE to the ON position.
7. Pull the starter handle (right side panel) until the engine starts. Verify the OUTPUT INDICATOR LED is a steady green (not blinking). If the OUTPUT INDICATOR LED is fl ashing red, a voltage mis-match has occurred, or the battery pack is excessively discharged. Refer to the voltage table on page 19 for more information.
8. As the engine warms, push the CHOKE knob in.
OUTPUT INDICATOR LED
(Step 7)
ENGINE SW
(Step 4)
FUEL VALVE (Step 6)
CHOKE
(Steps 5, 8)
DC OUT (Step 3)
18
Fig. 4-1, Starting the Engine
041-028-B0-003, Rev. C
4.0 Starting the Engine, continued
Battery Voltage
0V to 2V
2V to 27V
27V to 42V
42V to 55V
>56V
1 All battery voltage measurements are ± 1V 2 To enable forced output when the Overload Alarm LED is fl ashing, press the output button for at least 5
seconds. The Overload Alarm LED stops fl ashing. Release the output button, and then press it again for at least fi ve seconds. The Output Indicator LED turns on steady, and power output begins. The operator may then release the output button.
3 Engine shuts down after 1 second.
Voltage Select
Switch Position
36V 48V 36V 48V 36V 48V 36V 48V 36V 48V
Output Indicator
(Green LED)
OFF OFF OFF OFF
ON
OFF OFF
ON
OFF OFF
Overload Alarm
(Red LED)
OFF OFF
FLASHING FLASHING
OFF
FLASHING FLASHING
OFF
FLASHING FLASHING
Forced Output
Not Available Not Available
ENABLED ENABLED
Not Available
ENABLED
Not Available Not Available Not Available Not Available
21
3 3
Table 4-1, Battery Voltage and Output Indications
NOTE:
To manually disconnect the Output Voltage, press the OUTPUT SW momentarily to remove voltage from the battery pack. See Step 1 of Section 5.0, Engine Shutdown and Cable Removal.
To re-establish output voltage after manual or automatic disconnection, turn the ENGINE SW counter­clockwise to OFF. After the engine stops, turn the ENGINE SW to ON and follow the procedures in Section
4.0, Starting the Engine.
041-028-B0-003, Rev. C 19
5.0 Engine Shut-Down and Cable Removal
WARNING!
Engine block and muffl er become extremely hot during normal operation.
Procedure:
1. Press the OUTPUT SW to remove voltage from the battery pack.
2. Turn the ENGINE SW OFF.
3. Turn the FUEL VALVE OFF.
4 Disconnect the battery pack adaptor from the extension cable.
5. Remove the extension cable from the front panel of the generator.
6. Remove the battery pack adaptor from the battery pack.
7. Remove #8AWG copper ground wire.
5.1 Long-term Storage
If the generator is not going to be operated for an extended period of time, follow the storage instructions in the TRANSPORTING/STORAGE section of the Engine Owner’s Manual.
CAUTION! Drain fuel system before extended storage. Inspect fuel system and cable sets prior to restarting
generator after extended storage.
5.2 Scheduled Maintenance
Refer to the Honda Engine Owner’s Manual and follow all instructions in the MAINTENANCE section.
5.3 Transporting the Generator
Refer to the Engine Owner’s Manual and follow all instructions in the TRANSPORTING/ STORAGE section.
20
041-028-B0-003, Rev. C
5.0 Engine Shut-Down and Cable Removal, continued
5.4 Fuse Replacement
Tools and Materials Needed:
10mm and 8mm socket
• Ratchet handle
• Torque wrench
Replacement fuse: Alpha P/N 460-273-10, Hinode Electric Co. P/N 350GH-80
Procedure:
1. Set the ENGINE SW to OFF. Disconnect the extension cable from the DC Out jack.
2. Remove the four 10mm nuts from the front plastic housing, and remove the housing.
3. Locate the fuse cover below the OUTPUT SW.
4. Remove the two 8mm bolts on the bottom of the fuse cover. Remove the cover.
5. Remove the two 10mm nuts holding the fuse onto the fuse holder. When reassembling, carefully tighten nuts to the following torque specifi cations:
3.2 to 6.4 N m
2.4 to 4.7 ft-lbs. 28 to 56 in-lbs.
6. Replace fuse, and reassemble the generator in reverse order.
041-028-B0-003, Rev. C 21
6.0 Maintenance Record
Use the following form to log maintenance and repair of your DCX3000.
Maintenance Record
Model Number Serial Number
Date
Hour
Mete
r
Action Initials
(Refer to engine owners manual for service requirements and intervals)
22
041-028-B0-003, Rev. C
Alpha Technologies
Power
Copyright © 2006 Alpha Technologies, Inc. All rights reserved. Alpha is a registered trademark of Alpha Technologies. 041-028-B0-003, Rev. C.
Due to continuing product improvements, Alpha reserves the right to change specifi cations without notice.
®
Alpha Technologies 3767 Alpha Way Bellingham, WA 98226
USA
Tel: +1 360 647 2360 Fax: +1 360 671 4936 Web: www.alpha.com
Alpha Technologies Ltd. 4084 McConnell Court Burnaby, BC, V5A 3N7
CANADA
Tel: +1 604 430 1476 Fax: +1 604 430 8908
Alpha Technologies Europe Ltd. Twyford House Thorley Bishop's Stortford Hertfordshire CM22 7PA
UNITED KINGDOM
Tel: +44 01279 501110 Fax: +44 01279 659870
Alpha Technologies GmbH Hansastrasse 8 D 91126 Schwabach
GERMANY
Tel: +49 9122 79889 0 Fax: +49 9122 79889 21
Alphatec, Ltd P.O. Box 56468 Limassol, Cyprus
CYPRUS
Tel: +357 25 375675 Fax: +357 25 359595
AlphaTEK ooo Khokhlovskiy Pereulok 16 Stroenie 1 109028 Moscow
RUSSIA
Tel: +7 495 916 1854 Fax: +7 495 916 1349
Alphatec Baltics S. Konarskio G. 49 Vilnius 2009
LITHUANIA
Tel: +350 5 210 5291 Fax: +350 5 210 5292
Alpha Technologies 5 Avenue Victor Hugo F 92140 Clamart France
FRANCE
Tel: +33 1 41 90 07 07 Fax: +33 1 41 90 93 12