Alpha CFR 600, CFR 600XT, CFR 1000 User Manual

Operator’s Manual
Alpha CFR 600, CFR 600XT and CFR 1000
U N I N T E R R U P T I B L E P O W E R S U P P L I E S
F R O M A L P H A T E C H N O L O G I E S
ALPHA TECHNOLOGIES
Operator’s Manual
Alpha CFR 600, CFR 600XT and CFR 1000
U N I N T E R R U P T I B L E P O W E R S U P P L I E S
IMPORTANT SAFETY INSTRUCTIONS
CONTAINED IN THIS MANUAL
CAUTION
RISK OF ELECTRICAL SHOCK
CAUTION: TO REDUCE THE RISK OF ELECTRICAL SHOCK, AND TO ENSURE THE SAFE OPERATION OF THIS UNIT, THE FOLLOWING SYMBOLS HAVE BEEN PLACED THROUGHOUT THE MANUAL. WHERE THESE SYMBOLS APPEAR, SERVICING SHOULD BE PER-
FORMED ONLY BY QUALIFIED PERSONNEL.
DANGEROUS VOLTAGE A DANGEROUS VOLTAGE EXISTS IN THIS AREA. USE EXTREME CAUTION
ATTENTION IMPORTANT OPERATING INSTRUCTIONS. FOLLOW THESE INSTRUCTIONS CLOSELY.
WARNING: TO REDUCE THE RISK OF FIRE AND SHOCK HAZARDS, DO NOT EXPOSE THIS UNIT TO RAIN OR MOISTURE.
SAVE THESE INSTRUCTIONS
THIS MANUAL CONTAINS IMPORTANT INSTALLATION AND OPERATING INSTRUCTIONS. KEEP THIS MANUAL IN A SAFE PLACE.
THE ALPHA CFR
CAREFULLY UNPACK THE CFR. REPORT ANY SHIPPING DAMAGE IMMEDI­ATELY.
PLEASE READ THE OPERATORS MANUAL. IF YOU HAVE QUESTIONS REGARD­ING THE SAFE INSTALLATION OF THE CFR, CONTACT ALPHA TECHNOLOGIES.
RETURN THE ENCLOSED WARRANTY CARD. THIS WILL ALLOW US TO SERVE YOU BETTER.
THE UPS SHOULD BE SERVICED ONLY BY QUALIFIED PERSONNEL. WHEN NOT IN SERVICE, THE UPS BATTERIES SHOULD BE CHARGED AT LEAST
ONCE EVERY THREE MONTHS TO ENSURE OPTIMUM PERFORMANCE AND BATTERY LIFE.
THE UPS SHOULD BE INSTALLED UPRIGHT, IN A WELL VENTILATED AREA THAT IS FREE OF DUST AND MOISTURE.
VERIFY THE VOLTAGE REQUIREMENTS OF THE EQUIPMENT TO BE PROTECTED (LOAD), THE AC INPUT TO THE UPS (LINE), AND THE OUTPUT VOLTAGE OF THE UPS PRIOR TO INSTALLATION.
THE UTILITY SERVICE PANEL SHOULD BE EQUIPPED WITH A CIRCUIT BREAKER THAT IS RATED (AMPERAGE) FOR USE WITH THE UPS.
NOTIFY FIRE OR EMERGENCY PERSONNEL THAT AN UPS IS INSTALLED IN THE BUILDING BY PLACING A NOTIFICATION OR WARNING LABEL ON THE ELECTRI­CAL PANEL.
WHEN CONNECTING A LOAD TO THE UPS REAR PANEL, DO NOT EXCEED THE OUTPUT RATING OF THE UPS.
USE PROPER LIFTING TECHNIQUES WHENEVER HANDLING THE UPS OR AN EXTERNAL BATTERY PACK.
THE UPS CONTAINS MORE THAN ONE LIVE CIRCUIT. EVEN THOUGH AC IS NOT PRESENT AT THE INPUT, IT MAY BE PRESENT AT THE OUTPUT.
ALWAYS SWITCH THE UPS BATTERY CIRCUIT BREAKER TO OFF BEFORE CONNECTING OR DISCONNECTING AN EXTERNAL BATTERY PACK. THIS GREATLY REDUCES THE CHANCE OF SPARK.
THE BATTERY COMPARTMENT OF THE UPS CONTAINS DANGEROUS VOLT­AGES. BATTERY INSPECTION AND REPLACEMENT SHOULD BE PERFORMED ONLY BY QUALIFIED PERSONNEL.
WEAR INSULATED GLOVES AND EYE PROTECTION WHENEVER WORKING INSIDE THE BATTERY COMPARTMENT.
DO NOT ALLOW LIVE BATTERY WIRES TO CONTACT THE UPS CHASSIS. SHORTING BATTERY WIRES COULD RESULT IN A FIRE OR POSSIBLE EXPLO­SION.
BATTERIES SHOULD BE INSPECTED EVERY YEAR FOR SIGNS OF CRACKS, LEAKING OR SWELLING.
ALWAYS REPLACE BATTERIES WITH THOSE OF AN IDENTICAL TYPE AND RATING. NEVER INSTALL OLD OR UNTESTED BATTERIES.
AVOID USING UNINSULATED TOOLS OR OTHER CONDUCTIVE MATERIALS WHEN HANDLING BATTERIES OR WORKING INSIDE THE UPS.
REMOVE ALL RINGS, WATCHES AND OTHER JEWELRY BEFORE SERVICING BATTERIES.
SPENT BATTERIES ARE CONSIDERED ENVIRONMENTALLY UNSAFE. ALWAYS RECYCLE BATTERIES.
IMPORTANT SAFETY PRECAUTIONS
Table of Contents
THE ALPHA CFR 600 and CFR 1000
UNINTERRUPTIBLE POWER SUPPLY
The Alpha CFR
1. INTRODUCTION 1
1.1 The Alpha CFR 1
1.2 The CFR Advantage 2
1.3 Unpacking and Inspection 4
2. FEATURES 5
2.1 A Tour of the CFR 5
2.2 CFR Front Panel 5
2.3 CFR Rear Panel 6
2.4 Information Management Options 8
Standard Interface Device Intelligent Interface Device External Modem
2.5 Communication / Interface Options 10
RS-232 Monitoring / Control Applications Rear Panel Connectors RS-232 Connector
Standard CFR-UPS
2
Desktop I LAN Interface Connector External I External Alarms Connector EPO Emergency Power OFF Switch
D
2
D Connector
3. INSTALLATION 16
3.1 Pre-Installation 16
Site Preparation Utility Circuit Breaker Grounding Standby Generators
3.2 Connecting the CFR 17
3.3 External Battery Pack 18
4. OPERATION 19
4.1 Start-up and Test 19
Manual Self-test Audible Alarm OFF Manual Start (No AC Line Power) Switching OFF the UPS
i
950710
The Alpha CFR
Table of Contents,
4. OPERATION,
continued
continued
4.2 Using the Standard Interface Device 22
UPS Powering Up Output Shutdown Pending Output Shutdown in Progress Line Present Operation Line Failure (AC Input Out of Tolerance) Line Failure Operation Line Synchronization Low Battery Warning Low Battery Shutdown Test Service Alarm Off Switch Manual Start / (Hold to Test) Switch Output Load Display
5. RS-232 TERMINAL COMMUNICATIONS 26
5.1 Remote RS-232 Operation 26
5.2 RS-232 Menu Selection Icons 27
5.3 Remote Terminal Quick Reference 28
5.4 Menu Commands Overview 29
5.5 System Parameters 31
5.6 Input Parameters 32
5.7 Output Parameters 33
5.8 Battery Parameters 34
5.9 User Parameters 35
5.10 Maintenance Parameters 40
5.11 Parameter DUMP Command 42
5.12 Event Descriptions 43
5.13 RS-232 Terminal Setup 47
6. MAINTENANCE 48
6.1 CFR Maintenance 48
6.2 Battery Maintenance 48
6.3 Battery Testing 49
6.4 Removing the CFR Front Panel and Cover 50
6.5 Internal Battery Replacement 51
6.6 Troubleshooting Guide 54
6.7 Troubleshooting Using The SID 56
6.8 Repair Instructions 58
6.9 Parts and Ordering Instructions 58
7. SPECIFICATIONS 59
7.1 Specifications 59
8. WARRANTY 61
IMPORTANT:
EMERGENCY SHUTDOWN PROCEDURE ON INSIDE BACK COVER
ii

1. INTRODUCTION

1.1 The Alpha CFR

Congratulations on your purchase of one of the most advanced and intelligent Controlled Ferro Resonant-Uninterruptible Power Supply (CFR­UPS) in the world! The Alpha CFR is designed to keep your equipment operating, regardless of the condition of your utility power. This means that your vital equipment will no longer be affected by spikes, surges, sags, noise, brownouts, blackouts or other forms of electrical disturbances. Operation is as simple as plugging your equipment into the back of the UPS and switching on the power.
The CFR provides you with a wide range of power management options using your choice of interface devices. The Standard Interface Device displays vital UPS operating parameters, including Alarms, and allows you to manually self-test the UPS. The Intelligent Interface Device provides you with precise Voltage, Current and Frequency information, plus maintains an on­going record of all Alarm and Line Failure Events. As an active center of communication, your CFR can also be interfaced directly to your computer system to inform you, and your users, of changes in status as they occur.
With distribution networks and service centers located throughout the world, Alpha Technologies is here to back you up. From your date of purchase, Alpha provides complete technical support and prompt, reliable service to ensure that your CFR-UPS provides you with a lifetime of reliable operation.
The Alpha CFR-UPS
provides regulated, current-limited,
output with excellent isolation and noise attenuation
1
1. INTRODUCTION

1.2 The CFR Advantage

ADVANCED POWER PROTECTION TECHNOLOGY
Power protection devices can be judged by the type and quality of power they provide. Alpha CFR Uninterruptible Power Supplies provide continuous, conditioned “computer-grade” AC power to electronic equipment such as Computer Systems, Point of Sale Terminals, Process Controls, Telecommunications, CATV Headend, Broadband LAN, Manufacturing Control Systems, Critical Care and Hospital Lab Equipment.
Alpha's proven design virtually eliminates surges and spikes. The Alpha CFR UPS provides spike attenuation of 2000 to 1 and meets the requirements of IEEE 587 / ANSI 62.41.
Unlike many standby power systems, which regulate output voltage only when operating from their battery backup, the Alpha CFR UPS constantly maintains power. Even with input voltage fluctuations as great as +10% or -25%, the output remains constant, regardless of load.
Electromagnetic and Radio Frequency Interference (EMI and RFI) can damage semiconductors and have devastating effects on critical data. The CFR UPS input is tection from this type of interference. Measured in decibels (dB) of attenua­tion, Alpha's CFR achieves up to 120 dB common mode, and 60 dB normal mode.
SURGE AND SPIKE REJECTION
REGULATION
+1% output regulation without using precious battery
ISOLATION
totally isolated
from the output to provide maximum pro-
Alpha's EBP Series External Battery Packs allow you to greatly extend your backup capabilities and power through long utility outages. Completely self-contained and pre-wired, simply plug the EBP cabinet into your CFR and forget about it. EBP Series External Battery Packs can also be ordered with an optional, external charger to greatly reduce battery recharge times.
EXTENDED BACKUP CAPABILITY
2
1. INTRODUCTION
1.2 The CFR Advantage,
COMMUNICATIONS AND INTELLIGENCE
Alpha's interchangeable Standard Interface Device and Intelligent Interface Device allows your CFR to become an active part of your communications network providing you with a variety of interface options.
SELF-TEST CAPABILITIES
The CFR has a built-in, self-test function that checks all critical areas of the UPS, including the batteries, to ensure optimum performance. When­ever a problem is detected, the UPS lights a “Service” indicator. Self-test is extremely useful during troubleshooting and maintenance.
PRECISE LOAD & OVERLOAD INFORMATION
The Alpha CFR provides vital load information to eliminate guess work associated with matching the appropriate load to your unit. The Alpha CFR displays the existing load, and whenever the load exceeds the rated output, an "Overload" indicator is illuminated.
GENERATOR READY
The CFR UPS is equipped with a frequency sense circuit, along with a constant slew frequency synchronization circuit, to provide trouble-free operation with most standby generators.
Designed to meet or exceed the safety standards established by UL, CSA and VDE, the Alpha CFR UPS is one of the safest, most reliable and versatile uninterruptible power supplies available. Our commitment to safety and quality engineering has not only established industry-wide safety standards, but has earned Alpha Technologies international recognition as a leader in power protection equipment.
continued
SAFETY
3
1. INTRODUCTION

1.3 Unpacking and Inspection

Carefully remove the UPS from its shipping container. Inspect the contents. If items appear to be damaged or missing, contact Alpha Technolo­gies and the shipping company immediately. Most shipping companies have only a short claim period. Make sure the following items have been included:
1. CFR Series UPS with AC Line Cord
2. Operator's Manual
3. Any other ordered options
SAVE THE ORIGINAL SHIPPING CONTAINER. In the event the UPS
needs to be returned for service, it should be packaged in its original shipping container. If the original container is not available, make sure that the unit is packed with at least three inches of shock-absorbing material to prevent shipping damage. Note: Do not use popcorn-type material. Alpha Technolo­gies is not responsible for damage caused by the improper packaging of returned units.
PLEASE READ THE OPERATOR'S MANUAL.
Become familiar with the UPS front and rear panels. Review the drawings and illustrations before proceeding with the UPS installation. If you have questions regarding the safe installation or operation of the UPS, contact Alpha Technologies.
COMPLETE THE FOLLOWING FOR YOUR RECORDS:
Model # Serial # Options Purchase date
THIS UNIT WAS PURCHASED FROM:
Dealer name City State/Province Zip/Postal Code Country Telephone #
RETURN THE ENCLOSED
WARRANTY CARD
TO ALPHA TECHNOLOGIES
4

2. FEATURES

2.1 A Tour of the CFR

The Alpha CFR is designed to be easy to use and extremely flexible.
The CFR’s interchangeable front panel interface devices provide you with a wide range of information management options. The rear panel accepts a variety of connectors and receptacle plates to facilitate your most demanding communication and powering needs.
2.2 The CFR Front Panel
The CFR front panel comes equipped with a Standard Interface Device
(SID), or an optional Intelligent Interface Device (I operating parameters. The front panel can be easily removed for service or battery access by loosening the two screws located in the lower grill.
Standard Interface Device
2
D), to display vital UPS
Panel Screws
Figure 1

CFR Front Panel

5
2. FEATURES

2.3 CFR Rear Panel

AC INPUT Connector
The UPS is equipped with a standard, grounded AC power cord.
EXTERNAL BATTERY Connector
The connector accepts a standard plug from the EBP Series Battery Pack. Extending backup time is as simple as plugging in the battery pack.
BATTERY Circuit Breaker
The battery breaker protects the DC circuit. When the UPS is not in service, the breaker should be switched OFF to preserve the batteries in the UPS and in the EPS Series Battery Pack, if installed (see section 4.1 “UPS Shutdown”).
External Ground Lug (Single Point Ground)
The external ground lug provides a single point connection for optimum grounding protection. Always refer to your local electrical codes for prescribed grounding practices.
UPS Nameplate Label
The nameplate label contains valuable information relating to the UPS. Always verify input voltage and frequency (i.e., 120 VAC / 60 Hz) before use.
RS-232 Serial Connector (DE-9 Female Connector)*
The standard RS-232 serial interface allows for connection to a host computer /dumb terminal for remote monitoring, control and calibration of the UPS. Use a straight through serial cable to connect the UPS to the computer.
LAN Interface Connector (DE-9 Female Connector)
The LAN Interface connector provides dry contact status monitoring and output shutdown capability on a DE-9 female connector. Used by basic UPS monitoring software for orderly shutdown of computer networks.
External I
This connector is used for the optional desktop Intelligent Interface Device (I NOTE: This port is disabled by the factory unless an internal I
2
D Connector (MMJ Connector)*
2
D) for remote monitoring and control of the UPS (up to 2000 ft.).
2
D is installed.
External Alarms Connector (RJ-45 Connector)
This connector provides dry contact alarm status on a RJ-45 (center keyed) connector. Contact closures indicate LINE FAIL and LOW BATTERY WARNING.
*NOTE: With the SID installed in the UPS, either the External I the RS-232 port can be activated. The factory default is set for RS-232 operation. With the internal I
2
D option installed in the UPS both ports are
2
D port or
active.
6
2. FEATURES
2.3 CFR Rear Panel
Exhaust Fan
The UPS contains a rear panel exhaust fan to ensure maximum cooling
protection during all modes of operation.
OUTPUT Receptacle Plate
The load (equipment to be protected) connects to the rear panel output
receptacles. Styles vary depending upon country, frequency and voltage.
UPS
Nameplate
Label
RS-232
(DE-9)
Connector
LAN
Interface
(DE-9)
Connector
2
External I
(MMJ)
Connector
External Alarm
(RJ-45)
Connector
AC INPUT
Circuit
Breaker
D
Exhaust Fan
External Ground Lug
Warning
Labels
AC Input
(Line Cord)
OUTPUT
Receptacles
BATTERY
Circuit Breaker
EXTERNAL
BATTERY
Connector
Figure 2
CFR 1000 Rear Panel
7
2. FEATURES

2.4 Information Management Options

Standard Interface Device
The Standard Interface Device provides you with vital UPS operating parameters from front panel LED's (see section 4.2). The Standard Interface also has a load indicator to help you determine precise loading on your UPS, plus Manual Start and Alarm Off switches. To ensure optimum backup performance, the Standard Interface comes with a self-test feature which lights the “Service” LED whenever a problem is detected.
Standard Interface Device
CFR Front Panel with Standard Interface Device
Figure 3
8
2. FEATURES
2.4 Information Management Options,
Intelligent Interface Device (optional)
The Intelligent Interface Device (I
2
D) option is available either as a
continued
replacement of the Standard Interface Device (SID) or as a desktop unit for remotely accessing the unit (up to 2000 ft.). The desktop unit comes with an optional modem for accessing the UPS information via a telephone line. The
2
D front panel provides precise UPS information and guides you through
I the various menu options which include Ambient Battery Temperature, Input Voltage and Current, Line Frequency, Output Voltage and Current, Power in Watts, Power Factor, Battery Voltage, Charger Status, and more. The History Log maintains an on-going record of UPS alarms and power anomalies by time, date and type of occurrence. Whenever a UPS alarm condition occurs, such as Line Failure, Low Battery Warning, Low Battery Shutdown or Service, it is displayed by the front panel indicators and recorded in the History Log.
External Modem (optional)
The optional modem that comes with the desktop I
2
D provides access to the unit via a phone line. Service personal can dial up the unit to remotely monitor, control, and calibrate the unit. On specified alarm conditions, the unit can dial an emergency number to notify the system manager via modem of the alarm. The modem option may also be used to page service personnel on critical alarm conditions.
NOTE: The CFR 600 and CFR 1000 do not support the modem option with internal I
2
D.
For further information on operation and installation of the I
2
D, please refer to its operator’s manual “Information Management Using the Intelligent Interface Device.”
Intelligent Interface Device
Figure 4
9
2. FEATURES

2.5 Communication / Interface Options

The CFR is equipped with four rear panel jacks for communication
and remote interfaces: RS-232 Serial data; LAN Interface; External I
2
D and
External Alarms. NOTE: With the SID installed in the UPS, either the External I2D port or
the RS-232 port can be activated. The factory default is set for RS-232 operation. With the internal I
2
D option installed in the UPS both ports are
active.
RS-232 Monitoring / Control Applications
The Alpha CFR-UPS provides a standard RS-232 serial port on a DE­9 female connector. This port may be used to monitor and control the CFR using 1) ASCII terminals, 2) UPS monitoring software and 3) SNMP agent devices.
You may use the serial port to interface with a dumb terminal or a personal computer (running a terminal emulation software) to monitor, control, and calibrate the CFR. All you need is a standard off-the-shelf RS­232 cable (straight through) and a terminal. Refer to section 5 “RS-232 TERMINAL COMMUNICATION” for more information.
You may also use the RS-232 serial port to communicate with the intelligent UPS monitoring software running on a host computer or a SNMP agent device connected to your LAN network. Alpha Technologies provides the “AlphaNet C” family of UPS monitoring software and SNMP agents to manage your network requirements. You can use the “AlphaNet C shutdown software” to monitor the CFR in a network environment and to perform an orderly system shutdown when the battery becomes low (during extended line fail situations). AlphaNet C shutdown software informs all workstations of pending power failures and shutdowns and in multi-server networks, AlphaNet can shutdown other servers in the network as well as the workstations. For a full description of the features and capabilities of AlphaNet C shutdown software, refer to its user’s manual or contact Alpha Technologies. AlphaNet C is available for all major network platforms and operating systems — Novell Netware, SCO Unix, IBM OS/2, IBM AIX, Sun Solaris, Hewlett-Packard HP-UX (DAT), and Digital Equipment (OS/F, VMS, and DECNET).
Alpha Technologies also provides the “AlphaNet CS SNMP Agent Device” to monitor and control the CFR using the SNMP protocol. This provides an interface between the CFR and your network environment and allows you to use your Network Management Station (NMS) to monitor and control the CFR. To obtain detailed information on SNMP manage­ment solutions for your CFR refer to
or contact Alpha Technologies.
Manual
AlphaNet CS SNMP Agent User’s
10
2. FEATURES
2.5 Communication / Interface Options,
continued
Rear Panel Connectors:
Below are the various communication connectors as they appear on
the back of the CFR-UPS. The photographs show the pin numbering for the different connector types.
RS-232 Serial Connector
LAN Interface Connector
2
External I
D Connector
External Alarms Connector
Pin 1Pin 5
Pin 6 Pin 9
DE-9 Connector (RS-232 and LAN)
Pin 1 Pin 1
RJ-45
(External Alarms)
MMJ
(External I
Figure 5
CFR-UPS Connector Identification and Pin-out
11
2
D)
2. FEATURES
2.5 Communication / Interface Options
RS-232 Connector:
The connection/specifications for the RS-232 serial port vary depending on the installed interface device (i.e., SID or I2D option).
RS-232 connections for the standard CFR-UPS (with SID display or internal I
2
D)
The standard CFR-UPS configuration with SID or internal I2D connects to a computer or terminal using a standard straight-through RS­232 cable.
1 2 Tx 3 Rx 4 5 Gnd 6 7 RTS * 8 CTS *
* I2D Only
Not used with SID
Communication Settings with SID:
Baud Rate: 1200 Parity: None Stop Bits: One Data Bits: 8 Handshaking: XON / XOFF
RS-232 Connections with desktop I2D:
With the desktop I
9
2
D the cable connecting the computer or terminal to
1 2 3 4 5 6 7 8 9
RS-232 cable to computer or terminal
Use standard straight through typeInternal CFR connections
Communication Settings
2
D:
with I
Baud Rate: 300 to 9600 Parity: None, Even, or Odd Stop Bits: 1 or 2 Data Bits: 7 or 8 Handshaking: RTS/CTS
1 2 3 4 5 6 7 8 9
the UPS is a non standard type.
1 2 Tx 3 Rx 4 5 Gnd 6 7 RTS 8 CTS 9
Internal CFR connections
Communication Settings with I2D:
Baud Rate: 300 to 9600 Parity: None, Even, or Odd Stop Bits: 1 or 2 Data Bits: 7 or 8 Handshaking: RTS/CTS
1 2 3 4 5 6 7 8 9
RS-232 cable to computer or terminal
For the desktop I
2
D use a nonstandard
cable type
1 2 3 4 5 6 7 8 9
12
2. FEATURES
2.5 Communication / Interface Options,
continued
LAN Interface Connector
The Alpha UPS provides a LAN interface port on a DE-9 female
connector. This port may be used to monitor the status of the UPS and shutdown the output using basic UPS monitoring and shutdown software.
Two dry contacts are provided to indicate LINE FAIL and LOW
BATTERY status information. The port also accepts a dry contact input or an RS-232 level input to shutdown the UPS output. The shutdown delay, duration, and recovery modes can be configured using the RS-232 ASCII terminal commands (see section 5 “RS-232 Terminal Communication”). This port has the following pin out:
Pin out: (DE-9 connector, Female)
1
2 LINE FAIL
3
4 COMMON
5 LOW BATTERY
6 OUTPUT SHUTDOWN
7 GND
8 +12VDC, 5mA max.
9
Using basic UPS monitoring software you can monitor and shutdown
the CFR through this port. In network applications, your UPS monitoring software can perform an orderly shutdown on the network. Basic UPS monitoring software is provided as part of many operating systems and can also be purchased from third party vendors. Alpha Technologies “AlphaNet C shutdown software” can also operate in the basic mode to shutdown the CFR before its battery reserve is exhausted. Refer to
Software User’s Manual
or contact Alpha Technologies for more information.
AlphaNet C Shutdown
13
2. FEATURES
2.5 Communication / Interface Options
External I2D Connector
The external I desktop Intelligent Interface Device (I
2
D connector provides an interface for the optional
2
D). This allows the CFR to be remotely monitored and controlled from up to 2,000 feet away. The port uses a proprietary RS-485 protocol and has the following pin out:
Pin out: (MMJ connector, offset key)
1: +12V DC (unreg) 4: RS-485 Negative 2: +12V DC (unreg) 5: GND 3: RS-485 Positive 6: GND
Pin 1
External Alarms Connector
The external alarms connector provides two contact closures to
indicate LINE FAIL and LOW BATTERY alarms.
EPO (Emergency Power OFF) Switch
(Factory Installed Option on
the CFR 1000 Only)
Pins 7 and 8 of the ALARM INTERFACE connector provide EMERGENCY POWER OFF contacts. A switch contact can be hard-wired to the UPS to completely shut down the system in the event of an emergency, such as a fire.
In an emergency, the switch must be depressed (shorted) for at least
1.5 seconds. The UPS will shut down approximately 2 seconds after the signal is recognized. The switch, connected to pins 7 and 8, must be electrically isolated (up to 1500VAC isolation is recommended).
A system shut down in this manner will open the BATTERY circuit breaker. In the event there is an actual fire in the equipment room, the wire will melt causing as short circuit between pins 7 and 8 and open the BATTERY circuit breaker.
CAUTION: When the EPO switch is activated, the AC LINE connected to the UPS input may still be energized. To completely remove the power from the building, the MAIN AC LINE breaker must be switched OFF. Consult your national and local electrical codes for further information.
14
2. FEATURES
2.5 Communication / Interface Options,
External Alarms Connector,
Pin out: (RJ-45 connector, centered key)
Pin 1
Line Present
Line Failure
Low Battery
Warning
N.C. = Normally Closed N.O. = Normally Open
N.C.
N.C.
Battery OK
continued
EPO Emergency Power OFF
Option
Pin out: (RJ-45 connector, Female)
1. LINE FAIL, COM contact
2. LINE FAIL, N. C. contact
3. LINE FAIL, N. O. contact
4. LOW BATTERY, N. O. contacts
5. LOW BATTERY, COM contacts
6. LOW BATTERY, N. C. contacts
7.
8.
continued
N.O.
Emergency UPS Shutdown Switch (Wall Mounted). NOTE: Cable length must not exceed 100 feet. Use twisted or shielded wire.
External Alarms Connector Pin-out (with EPO Switch Option)
15

3. INSTALLATION

3.1 Pre-Installation

DO NOT CONNECT THE UPS TO A LINE CONDITIONER, ISOLATION TRANSFORMER OR ANY OTHER SIMILAR TYPE OF DEVICE. DAMAGE TO THE UPS AND THE LINE CONDITIONING EQUIPMENT CAN OCCUR.
Site Preparation
The UPS should be installed upright in a well-ventilated, dust free environment. The weight of the UPS, especially if it has an optional battery pack, is quite heavy (see specifications). Do not place the unit on any surface unable to fully support its weight.
Utility Circuit Breaker
The UPS should be installed on a dedicated circuit with a properly sized circuit breaker. Breaker size can be determined by adding 15% to the maximum input current of the unit (see specifications). For example, the CFR 600 draws 4.8 Amps of current. By adding 15%, the number becomes 5.5 Amps. In this case, a standard 15 Amp circuit breaker is suitable for use.
Grounding
Since the CFR UPS bonds output neutral to ground (qualifying it as a "separately-derived power source"), proper grounding is critical. Many older facilities may have an electrical system that is incapable of supporting this type of grounding requirement. To ensure optimum performance from your UPS, always install a hardwired ground. A qualified electrician should also inspect the existing wiring in the building prior to installation to verify proper grounding.
Standby Generators
The CFR is equipped with a frequency sense circuit, along with a constant slew frequency synchronization circuit, to optimize operation with most standby generators. Prior to installation, compare the output voltage of the generator to the voltage requirements of the UPS (see CFR nameplate label). If the UPS requires 240 VAC input and the generator produces only 208 VAC, it will cause the UPS to run continuously off of battery power. This would discharge the UPS batteries and cause the output load to fail.
Alpha Technologies recommends using a generator equipped with an electronic speed and voltage control. If a generator equipped with a mechani­cal governor "speed control" is used, this could also cause the UPS to run continuously in LINE FAILURE mode due to the unstable frequency of the generator.
The generator should also produce less than 10% voltage THD. Generators with a higher THD rating may cause the CFR UPS to switch to LINE FAILURE mode, and switch to battery operation, as the generator output would be sensed as a noisy utility.
16
3. INSTALLATION

3.2 Connecting the CFR

1. Connect the CFR's AC power cord to the wall receptacle.
2. If using an external battery pack, plug its connector into the rear panel of
the UPS (see section 3.3).
3. Start and test the UPS without the load connected (see section 4.1). After testing, switch the unit OFF before connecting the load.
4. Plug the equipment to be protected into the UPS rear panel receptacles. Note: The load should be switched OFF prior to connection.
5. Individually ground each piece of equipment connected to the UPS at the single point ground lug located on the CFR's rear panel. Note: Consult your local electrical code to ensure prescribed grounding practices.
THE UPS UTILIZES A TRANSFORMER TO PROVIDE EXCELLENT ISOLA­TION AND VOLTAGE REGULATION. DURING NORMAL OPERATION, THE UPS WILL BE WARM TO THE TOUCH, BUT NOT HOT ENOUGH TO BURN. THE TRANSFORMERS HAVE BEEN COATED WITH A LACQUER FINISH WHICH MAY PRODUCE A SLIGHT, NONTOXIC ODOR DURING THE FIRST SEVERAL WEEKS OF OPERATION.
THE UPS GENERATES EMR (ELECTROMAGNETIC RADIATION). KEEP
WARNING
ALL SENSITIVE MAGNETIC MEDIA, SUCH AS CREDIT CARDS, FLOPPY DISKS, MAGNETIC KEY CARDS, RECORDING TAPE, ETC., AWAY FROM THIS UNIT.
UPS
Receptacle
BATTERY
Circuit Breaker
AC LINE
Circuit Breaker
AC LINE
Power Cord
GROUND
Lug
Figure 6
CFR 1000 Rear Panel
17
3. INSTALLATION

3.3 External Battery Pack

The CFR is designed so that battery backup time can be greatly extended simply by plugging the EBP 24 External Battery Pack into the back of the UPS. Battery packs are completely self-contained.
Unit Rating Voltage Run Time*
EBP 24A 17 Ah 24 VDC 0.66 hrs 1 hrs 0.5 hrs EBP 24C 66 Ah 24 VDC 3.75 hrs 4.3 hrs 2.1 hrs EBP 24E 176 Ah 24 VDC 8.5 hrs 9.0 hrs 5.0 hrs
*Battery run times are calculated at typical load (80%) and represent the total time of the CFR internal batteries and EBP battery pack.
1. Switch the CFR's BATTERY circuit breaker OFF.
2. Locate the EXTERNAL battery connector on the rear panel of the UPS
and remove the Phillips screw #1 and loosen Phillips screw #2.
3. Slide the cover plate to the left and insert the battery pack’s connector
into the UPS. Secure the connector to the UPS using the Phillips screw #1.
4. Switch the EBP and CFR “BATTERY” breakers ON and test the unit
for proper operation.
CFR 600 CFR 600XT CFR 1000
Requires
BATTERY
Circuit Breaker
Phillips Screwdriver
Note: Battery Pack can be installed along side, or underneath the CFR UPS.
Figure 7
CFR 600 and EBP External Battery Pack
18
Phillips Screw # 2
Phillips Screw #1
External Battery
Connector

4. OPERATION

4.1 Start-up and Test

1. Plug the CFR’s AC line cord into a wall receptacle. The TEST LED and
OUTPUT LOAD display LEDs will flash for a few seconds to indicate the CFR is powering up. The LINE PRESENT LED will then come ON to indicate the AC input line is OK and the CFR is running on AC line power.
2. Switch the rear panel BATTERY circuit breaker ON to activate the battery circuit.
3. Test the UPS by unplugging the AC LINE cord from the wall receptacle. The front panel amber “LINE FAILURE” LED will light as the UPS initiates LINE FAILURE operation.
4. Plug the AC LINE cord back into the wall receptacle. The “LINE PRESENT” LED will come ON to indicate the presence of AC line power. Within 20 seconds, the “LINE FAILURE” LED will shut OFF to indicate that the UPS has resumed LINE PRESENT operation.
5. Once the UPS has been tested, switch the load ON, one unit at a time, and observe the front panel “OUTPUT LOAD” display. As each additional piece of equipment is switched ON, the LED’s will display the increased load up to 100%. If the “OVERLOAD” LED lights, decrease the load by switching equipment OFF, one unit at a time, until the “OVERLOAD” LED goes OFF. WARNING: DO NOT RUN THE UPS IN AN OVERLOADED CONDITION.
Manual Self-test
Press (and hold for several seconds) the “MANUAL START” switch, located on the Standard Interface Panel, when the UPS is running on AC line power (“LINE PRESENT” LED ON). The unit will test the backup capabilities of the UPS for approximately one minute (“TEST” LED ON). Both the “LINE PRESENT” and “LINE FAILURE” LEDs will be ON. If a problem is detected, the UPS will resume LINE PRESENT operation, without interruption to the output, and light the “SERVICE” LED.
Audible Alarm OFF
Press the “ALARM OFF” switch, located on the Standard Interface Panel, to cancel the audible alarm which may activate when first starting the UPS. The alarm, along with the front panel “LOW BATTERY WARNING” LED, indicates that the UPS batteries are low. The batteries will recharge within several hours of operation.
Manual Start (No AC Line Power)
Press the “Manual Start” switch to start the UPS from battery power. The UPS will start even though AC line power is not available (“LINE PRESENT” LED OFF).
19
4. OPERATION
4.1 Start-up and Test,
continued
Switching OFF the UPS:
1. Switch all equipment connected to the UPS OFF.
2. Switch the rear panel “BATTERY” circuit breaker OFF. This will
prevent the UPS from initiating LINE FAILURE operation when AC power is removed.
3. Unplug the CFR's AC power cord from the wall receptacle.
BATTERY
Circuit Breaker
AC LINE
Power Cord
Figure 8
UPS Shutdown
20
4. OPERATION

4.2 Using the Standard Interface Device

The Standard Interface Device displays vital UPS operating parameters and has the ability to self-test the UPS at the touch of a button. When used in conjunction with the CFR's rear-panel “Form-C” contact closures, UPS status information can be sent directly to a Local Area Network (see section 2.5).
Alarm OFF Switch
Manual Start (Hold to Test) Switch
OUTPUT LOAD LEDs
LINE PRESENT LED
LINE FAILURE LED LOW BATTERY SHUTDOWN LED
SERVICE LED
LOW BATTERY WARNING LED
TEST LED
Figure 9
Standard Interface Device
21
4. OPERATION
4.2 Using the Standard Interface Device
UPS Powering Up
Whenever the CFR is powering up, the TEST LED flashes for a few seconds. At the same time the OUTPUT LOAD indicator LEDs flash in a chasing pattern to indicate that there is no output. As soon as the power up sequence is completed, the TEST LED switches OFF and the OUTPUT LOAD display LEDs show the percentage of the load.
Output Shutdown Pending
The TEST LED will flash to indicate that a UPS output shutdown is pending to occur. When the operator gives an output shutdown command (either via the RS-232 serial port or by the LAN Interface port), the UPS delays the shutdown (for a programmable period) before actually switching off the output.
Output Shutdown In Progress
The five OUTPUT LOAD LEDs will flash in a chasing pattern whenever the CFR output is switched off by an output shutdown command (either via the RS-232 serial port or by the LAN Interface port). This will also occur when the unit is first powering up.
Test LED and Output Load LED Indicators
Figure 10
22
4. OPERATION
4.2 Using the Standard Interface Device
Line Present Operation
The green “LINE PRESENT” LED indicates that the UPS is running on
AC line (utility / mains) power.
Line Failure (AC Input Out of Tolerance)
Whenever AC line voltage becomes unacceptably high or low (+10 % /
-25%), or the line frequency exceeds flashes and the "LINE FAILURE" LED lights indicating the UPS is running on backup power. NOTE: High generator THD can also cause this condition.
+ 3%, the "LINE PRESENT" LED
Line Failure Operation
Whenever a utility power outage occurs, the UPS initiates LINE
FAILURE operation without interruption of output power. The amber “LINE FAILURE” LED lights to indicate that the UPS is running on backup power.
Line Synchronization
When both the “LINE POWER” and “LINE FAILURE” LEDs are ON, the
UPS is synchronizing its output frequency to the utility input prior to resuming AC line operation. Synchronization takes approximately 15 seconds. If the line frequency (generator frequency) is out of tolerance, the UPS can not synchronize to it, and stays in the inverter mode.
23
4. OPERATION
4.2 Using the Standard Interface Device,
Low Battery Warning
The red “LOW BATTERY WARNING” LED precedes “LOW BATTERY SHUTDOWN” by 2 to 5 minutes and indicates that the batteries can no longer support the load. Immediate steps should be taken to begin an orderly system shutdown. From LOW BATTERY WARNING, it may take several hours to fully recharge the batteries.
Low Battery Shutdown
The “LOW BATTERY SHUTDOWN” LED indicates that the UPS has shut itself down to prevent over-discharge damage to the batteries. In critical applications, an additional power source (such as a generator) should be used until utility line power returns.
Test
The yellow “TEST” LED indicates that the UPS is simulating a LINE FAILURE to self-test the backup capabilities of the unit. If, during the one minute test, the UPS fails to supply backup power, it resumes LINE PRESENT operation without interruption to the load and lights the “SERVICE” LED.
continued
Service
The “SERVICE” LED indicates that the UPS is no longer able to provide backup power to the load and that service is required. Consult the manual's troubleshooting section or contact your authorized Alpha service center.
24
4. OPERATION
4.2 Using the Standard Interface Device,
continued
Alarm Off Switch
The switch cancels the audible LOW BATTERY WARNING alarm. The
alarm remains disabled until line power is restored and the batteries are recharged.
ALARM OFF
Switch
Manual Start / (Hold to Test) Switch
The switch is used to start the UPS from battery power whenever AC line
power is not available (“LINE PRESENT” LED OFF). The switch can also be used to test the UPS’ backup capabilities (“LINE PRESENT” LED ON) without interruption to the load.
MANUAL START
Switch
Output Load Display
The green “25%, 50%, 75%, and 100%” LED’s indicate the loading on the
UPS. Whenever the output load exceeds the rated output of the UPS, the red “OVERLOAD” LED lights. Note: Each successive LED lights depending upon the load. If the UPS has a 75% load (displayed), then the 25%, 50% and 75% LEDs will light. DO NOT EXCEED THE OUTPUT RATING OF THE UPS.
OUTPUT LOAD
LED’s
25

5. RS-232 TERMINAL COMMUNICATION

5.1 Remote RS-232 Operation

Introduction:
This section of the manual describes how to monitor, control and calibrate the CFR-UPS using RS-232 ASCII commands and how to navigate through the program using the menu structure.
The RS-232 serial interface is designed to work with terminal emulation software in an interactive mode. Various parameters and commands may be accessed either through the menus or by typing the number associated with the desired functions. See section 5.3.
RS-232 menus have a hierarchical format. The top level menu, which is also called the OPENING MENU, can be accessed by pressing the ENTER key (which sends a carriage return character). This menu lists the numbers for accessing other sub-menus plus displays the current LINE status and pending ALARM conditions.
The figure below shows the typical opening menu screen which displays the menu options 1 through 7 followed by status and alarm messages. The INPUT LINE shows the current status of the AC line which may be PRESENT; FAILURE; or TEST MODE. The ALARMS message lists all current alarms. For a complete description of alarms refer to section 5.12.
Alpha Technologies - CFR Micro Serial#00000000
Opening Menu
1 System Parameters 2 Input Parameters 3 Output Parameters 4 Battery Parameters 5 User Parameters 6 -not available­7 Maintenance Parameters
Input Line - Present Alarms -
SERVICE2: SERV CODE 3
CFR-UPS Micro
Serial No.
Available Menu
Items (1-7)
AC Line Status
Alarms
Figure 11
Opening Menu
To display the System Parameters screen, type "1" and press ENTER.
26
5. RS-232 TERMINAL COMMUNICATION
5.2 RS-232 Menu Selection Icons
Icons have been placed throughout this section to easily guide you to
key commands using remote terminal emulation. The icons provide short cuts to desired display screens without having to step through various menus. To use the icons, simply enter the number contained in the icon screen while you are in the terminal emulation mode. A dark screen icon with white numbers accesses one of the 7 main menus. A light screen icon with black numbers directly accesses the chosen sub-menu function.
5
55
The dark screen icon with white lettering accesses one of the main menus. In this example, the #5 (USER PARAMETERS) will appear.
The light screen icon with black lettering directly accesses a sub-menu. In this example, the #55 (SET TEST FREQUENCY) will appear.
This function is not independently selectable as a sub-menu item. It is included as part of the USER PARAMETERS main screen selection.
PC Communication Icons (used in this manual)
27
5. RS-232 TERMINAL COMMUNICATION

5.3 Remote Terminal Quick Reference

The menu items outlined in this manual can be accessed from a remote terminal. The numbers contained in this guide act as a quick reference to accessing menu functions. Single-digit numbers relate to specific main menus. Double-digit numbers relate to specific sub-menus.
0 QUERY ALL PARAMETERS
1 SYSTEM PARAMETERS
2 INPUT PARAMETERS
3 OUTPUT PARAMETERS
4 BATTERY PARAMETERS
5 USER PARAMETERS
6 - not available -
7 MAINTENANCE PARAMETERS
BATTERY TEMPERATURE
11 START TEST Mode 12 STOP TEST Mode
VOLTAGE CURRENT VOLT AMPS POWER IN WATTS POWER FACTOR LINE FREQUENCY
OUTPUT #1
VOLTAGE CURRENT
OUTPUT #2
VOLTAGE
CURRENT VOLT AMPS POWER IN WATTS POWER FACTOR LINE FREQUENCY
VOLTAGE CURRENT CHARGER STATUS TEMPERATURE
SET TEST SCHEDULE
53 SET TEST START 55 SET TEST FREQUENCY 56 TRANSMIT UNSOLICITED ALARMS 58 SET USER SECURITY CODE 59 SET MAINTENANCE SECURITY CODE
CFR SOFTWARE VER.
MICRO BOARD SER. NO.
EEPROM VERSION NO.
POWER BOARD SER. NO.
501 START SHUTDOWN WHEN DELAY IS SET 502 START OUTPUT SHUTDOWN 503 CANCEL OUTPUT SHUTDOWN 504 RECOVER OUTPUT SHUTDOWN ONLY WHEN AC LINE RESTORED 505 SET OUTPUT SHUTDOWN DELAY 506 SET OUTPUT SHUTDOWN DURATION 507 SHUT OFF INVERTER - SAVE BATTERY 508 START UP INVERTER FROM SAVE BATTERY 509 NONE 510 TRANSMIT IPC-XXX TYPE UNSOLICITED ALARMS 511 INVERTER ON ALARM DELAY
70 FAST DETECT LOW REF 71 FAST DETECT HIGH REF 72 MEDIUM DETECT LOW REF 73 MEDIUM DETECT HIGH REF 74 SLOW DETECT LOW REF 75 SLOW DETECT HIGH REF 76 SLOW DETECT HYS. LO REF 77 SLOW DETECT HYS. HI REF 78 MAX. PLL SLEW RATE 79 BATTERY WARNING REF.
28
5. RS-232 TERMINAL COMMUNICATION

5.4 Menu Commands Overview

Overview:
The following section provide a general overview of the menu structure and give some examples of how to perform certain command functions such as testing the UPS.
Querying CFR Status and Measured Parameters
The current status (mode of operation) of the CFR and all active alarms are displayed at the end of the opening menu (see section 5.12 for a list of status messages and alarm events). Press “ENTER” to query CFR status and alarms. Use commands “1” to “4” to query the battery temperature, input (line) parameters, output (load) parameters, and battery parameters. Command “0” is a special command which displays all of the UPS param­eters together. This command is discussed in section 5.11.
Testing the CFR
Use commands “11” and “12” to start and terminate a self-test. During a self-test, the UPS switches to the inverter mode to test the battery and the inverter hardware. The test takes about one minute and, when complete an ASCII message is sent to indicate the result. You may also schedule a self­test using commands “53” to “55”.
Shutting OFF the Inverter to Save Battery
Commands “507” and “508” can be used when the UPS is in the inverter mode to switch the inverter OFF to prevent a deep battery discharge during extended line failures. The UPS-CFR switches to normal operation when input line is restored. Note: This command will drop the connected load.
Scheduling Output Shutdown/Reboot
The output of the UPS can be turned OFF by sending a RS-232 command. Commands “501” to “506” control the output shutdown feature. When the UPS receives a start shutdown command, “502”, it waits for the period specified in output shutdown delay, “505”, and then turns OFF the UPS output. The UPS remains in the shutdown mode for the mandatory down time specified by output shutdown duration, “506”. Depending upon the setting of the output shutdown recovery mode, “504”, the output is switched ON when the shutdown duration expires or when the input is restored. You start a shutdown whenever the shutdown delay is set using command “501” may cancel a pending shutdown by sending command “503”.
29
5. RS-232 TERMINAL COMMUNICATION
5.4 Menu Commands Overview,
Calibrating the CFR
The CFR-UPS may be calibrated using two sets of parameters ­Maintenance Parameters (commands “70” to “79”) and Service Parameters (commands “80” to “89”). Maintenance parameters allow you to customize the CFR detection and warning levels. There should be no need to change these setting unless wider or narrower detection tolerances are required.
T ransmitting Unsolicited Alarms
The UPS can automatically transmit alarm messages (in ASCII format) to notify a status change or a power problem as it occurs. You can enable or disable this option by using commands “510” and “509” respectively.
continued
30
5. RS-232 TERMINAL COMMUNICATION
5.5 System Parameters
The “SYSTEM PARAMETERS” screen provides UPS battery tempera-
ture information and manual initiation and termination of SELF TEST.
Battery Temperature
1
11
12
Displayed in degrees C, Ambient Temperature is measured inside the
UPS in the vicinity of the battery compartment.
Start Test
Self Test can be initiated by selecting this menu. The test duration
default is 60 seconds.
Stop Test
Self Test can be terminated prior to the full duration of the test run time.
31
5. RS-232 TERMINAL COMMUNICATION
5.6 Input Parameters
2
“INPUT PARAMETERS” provides UPS Input Voltage, Current, Volt Amps, Power in Watts, Power Factor, and Line Frequency information.
Voltage
The voltage measured at the input of the UPS (i.e., 120 VAC).
Current
The flow of current measured at the input of the UPS (i.e., 3.1 Amps).
Volt Amps
The apparent input power of the UPS calculated by multiplying input voltage by the input current (i.e., 663 VA).
Power in Watts
The true input power of the UPS calculated in Watts (i.e., 600 Watts).
Power Factor
The ratio of true power (power actually consumed) to apparent power (simple product of voltage and current) at the input of the UPS (i.e., 0.89).
Line Frequency
The frequency of the AC Line measured at the input of the UPS (i.e., 60.0 HZ).
32
5. RS-232 TERMINAL COMMUNICATION
5.7 Output Parameters
3
“OUTPUT PARAMETERS” provides UPS Output Voltage, Current, Volt
Amps, Power in Watts, Power Factor, and Line Frequency information.
OUTPUT #1
Voltage
The RMS voltage measured at the output of the UPS (i.e., 120 VAC).
Current
The flow of current measured at the output of the UPS (i.e., 3.1 Amps).
OUTPUT #2
Voltage
Not available on this unit and should read ‘0’.
Current
Not available on this unit and should read ‘0’.
Volt Amps
The apparent output power of the UPS calculated by multiplying output
voltage by the output current (i.e., 663 VA).
Power in Watts
The true output power of the UPS calculated in Watts (i.e., 600 Watts).
Power Factor
The ratio of true power (power actually consumed) to apparent power
(simple product of voltage and current) at the output of the UPS (i.e., 0.89).
Line Frequency
The frequency of the AC Line measured at the output of the UPS
(i.e., 60.0 HZ).
33
5. RS-232 TERMINAL COMMUNICATION
5.8 Battery Parameters
4
“BATTERY PARAMETERS” provides UPS Battery Voltage, Charger Current, and Charger Status information.
Voltage
Voltage indicates the average DC voltage of UPS batteries. When the UPS is running in “LINE PRESENT” mode and the batteries are charged, the voltage will be approximately 27.6 VDC (equal to the charger’s “FLOAT” charge). When the UPS is running in “LINE FAILURE” mode, the battery voltage will slowly decrease until the Battery Low Voltage Cutout is reached (approximately 21.0 VDC). Once utility power is restored, after a prolonged power outage, the battery voltage will slowly climb until the batteries are recharged. Note: If external batteries are connected, their voltage will be reflected as well.
Battery Current
When the UPS is running in “LINE PRESENT” mode, the average DC charger current is displayed (i.e., 2.1 Amps). When the UPS is running in “INVERTER” mode the battery charge current is zero (0).
Charger Status
When the UPS is in “LINE PRESENT” mode, the charger keeps the batteries charged, indicated by “CHARGER STATUS ON”. When the UPS is in “LINE FAILURE” mode and running on the batteries, the charger immedi­ately switches OFF, indicated by the display “CHARGER STATUS OFF”. Once utility power returns, or an alternative power source (generator) is connected, the charger will switch ON and the DC current will slowly rise after an initial 3 second “soft start” delay.
34
5. RS-232 TERMINAL COMMUNICATION
5.9 User Parameters
“USER PARAMETERS” allows you to set the information for
automatic test, output voltage shutdown, display unit identification, and to
5
change the security codes. Whenever one of the USER PARAMETER items is accessed, you are prompted for a security code. Note: The code (1111) is preset at the factory and can be changed by entering the SET USER SECURITY CODE screen (menu item 58).
Unsolicited Alarm Messages
The CFR can transmit alarm messages (in ASCII format) to notify a
status change or a power problem. Once this feature is enabled, alarm messages are transmitted automatically on the RS-232 port as soon as the status of the CFR changes. You can connect a terminal to the CFR to monitor its status and log all power problems. Refer to menu items 56 and 509-511 for a detailed description.
Automatic Output Shutdown
The output of the CFR can be turned off by sending a command via
the RS-232 port using a computer or terminal. Refer to menu items 501­508 a for detailed description (menu items 501-506 are intended for scheduled shutdown even when the AC line is present; 507 and 508 items can be used to switch the inverter ON and OFF to preserve the battery).
When the CFR receives a
502), it waits for the period that is specified in the (menu item 505) and then shuts down its output. The CFR will remain in the shutdown mode for the time specified in the
Duration” Shutdown Recovery Mode”
power immediately, even if the input AC line is not present, or may wait for the input AC line to be restored.
(menu item 506). Depending upon the setting of the
“Start Shutdown”
(menu item 504) the CFR may restore output
command (menu item
“Output Shutdown Delay”
“Output Shutdown
“Output
35
5. RS-232 TERMINAL COMMUNICATION
5.9 User Parameters,
Set Test Schedule
The UPS can be setup to perform a routine self-test at intervals you specify. This will place the UPS into “LINE FAILURE” mode at a specific time in order to test its functionality and the capacity of the batteries.
Set Test Start (DD:HH:MM = dd:hh:mm)
53
55
dd = Days
hh = Hours
mm = Minutes
(i.e., “05:02:15” represents start test in 5 days, 2 hours, 15 minutes).
the dd, hh and mm are set to 00 then the automatic self-test is inactive. After each self-test the start time is reset to the number of days specified in the “Set Test Frequency” (menu item 55). This feature requires the USER SECURITY CODE for activation.
This menu is utilized to set the self test schedule by setting the count down duration for the start of test. For example, if the user wishes to set the start of test at midnight and the current time is 6:00 PM, the user can enter the start of test frequency to (00:06:00) which represents 6 hours.
absence of an I 2D, the CFR does not have a real time clock on board, and therefore the timing function may drift slightly over a period)
takes 1 minute to complete.
Set Test Frequency (XXX)
xxx = “off” or “dd days” - dd represents days
The user can activate the auto self-test feature by setting the test frequency to every “dd” days. The self-test will start at the value displayed in the “Set Test Start” line in “DD:HH:MM” format.
“OFF” indicates that the automatic self-test function is disabled. It can be set by entering 0 days for Test Frequency. “dd days” indicates that the automatic self-test function is enabled and is set to run the self-test at the interval entered in this field. The maximum value is 30 days; def ault is “OFF”. This feature requires the USER SECURITY CODE for activation.
continued
If
(NOTE: In the
. The self-test
NOTE: If the SID is installed, the TEST LED flashes while the test is in progress.
Transmit Unsolicited Alarms
56
This command displays the current settings of the unsolicited alarms feature. The following text is displayed when this menu is accessed.
56 Transmit Unsolicited Alarms 509 None (xxxx) 510 IPC-XXX (xxxx) 511 Inverter On Alarm Delay (xxxx)
36
5. RS-232 TERMINAL COMMUNICATION
58
59
501
502
5.9 User Parameters,
Set User Security Code
The security code is used to restrict entry into certain areas of the
program. The code (1111) is preset at the factory and allows access to USER PARAMETERS and HISTORY programs. The security code can be changed using the number keys on the keypad. CAUTION: code is changed and no record is kept, especially if the code becomes forgotten or lost, you will not be able to reenter the program.
Display Unit Ident.
This screen is used to display vital information pertaining to the
Intelligent Interface Device, the micro-controller board and the CFR’s power board. This information is extremely useful for troubleshooting and mainte­nance.
Display Micro Ident.
Displays the software version and serial # of the micro-controller board.
Display PwrBd. Ident.
Displays the EE Prom # and serial # of the CFR's power board.
Set Maintenance Security Code
The Maintenance Security Code is a second level of security and is used
to gain access to the maintenance programs. The code can be changed using the number keys on the keypad. CAUTION: and no record is kept, especially if the code becomes forgotten or lost, you will not be able to reenter the program. The factory default setting is 1111.
Start Shutdown When Delay is Set (xxx)
xxx= “Yes” or “No”, (Default value is “No”) This command sets the “Output Shutdown Start Mode”. If this option is
set to “No”, the CFR waits for a shutdown command (menu item 502) to start the shutdown sequence. However, if this option is set to “Yes”, the CFR starts a shutdown sequence when the output shutdown delay is set (menu item 505). Changing this option requires the USER SECURITY CODE.
Start Output Shutdown
This command causes the unit to shutdown after the delay period
specified in menu item 505 mandatory shutdown duration specified in menu item 506
Output Shutdown Duration”.
output shutdown delay and duration, and then send this command to shutdown the unit. During the flashes to indicate that a shutdown is pending. When the unit is in the Output Shutdown mode, the five power LED’s will flash, in sequence, to indicate that the UPS is powered-up with no output voltage present.
Also displayed on line 502 is the current status of the output:
“off” No shutdown is scheduled. “shutting down in hh:mm:ss” Indicates the time remaining until
“shutdown in progress” No output.
continued
If the security
If the code is changed
“Set Output Shutdown Delay”
You can use commands 505 and 506 to set the
“Output Shutdown Delay”
shutdown.
, and for the
“Set Minimum
the TEST LED
Activating this command requires the USER SECURITY CODE.
37
5. RS-232 TERMINAL COMMUNICATION
503
504
505
506
5.9 User Parameters,
Cancel Output Shutdown
This command cancels any pending or current UPS output shutdown. This
command requires the USER SECURITY CODE.
Recover Output Shutdown Only When AC Line Restored (xxx)
xxx=“Yes” or “No”, (Default value is “Yes”)
This command determines when the CFR restores output power after a
output shutdown. If this option is set to “Yes”, the UPS restores output when the input AC line is restored. Note that the output is guaranteed to be off for
“Output Shutdown Duration”
the activate the output, even if AC line is restored. However, if this option is set to “No”, then the CFR activates its output as soon as the
Duration”
inverter mode. Changing this option requires the USER SECURITY CODE.
Set Output Shutdown Delay (HH:MM:SS= hh:mm:ss)
receives an output shutdown command, it will wait for this period before switching off the output.
seconds is optional, (i.e., HH:MM format is also acceptable). The factory default setting for this value is 00:00:00 which causes the CFR to immedi­ately shutdown when a shutdown command is set. If the CFR is set to start shutdown when delay is set (menu item 501 is set to “Yes”), then it also acts as a shutdown command, and the count down for shutting down the unit starts immediately (there is no need to issue a 502 command). This feature requires the USER SECURITY CODE for activation.
Set Output Shutdown Duration (HH:MM:SS= hh:mm:ss)
guaranteed down time after an output shutdown.
has expired. Thus, the CFR may even restore output in the
This command sets the “output shutdown delay” period. After the CFR
hh:mm:ss - hh is hours; mm is minutes; ss is seconds. Entering the
This command sets the
continued
period. During this period, the CFR will not
“Output Shutdown
“Output Shutdown Duration”
which is the
507
508
hh:mm:ss - hh is hours; mm is minutes; ss is seconds. Entering the
seconds is optional, (i.e. HH:MM format is also acceptable). The factory default setting for this value is 00:00:05 which causes the CFR to remain in shutdown for a minimum of 5 seconds. The CFR may restore output immediately when this duration is expired, or may wait for the AC line to be restored (depending on the setting of menu item 504). This feature requires the USER SECURITY CODE for activation.
Shut Off Inverter / Save Battery
This feature requires the USER SECURITY CODE and can only be
activated if unit is in LINE FAILURE mode. The inverter can then be shut off to preserve battery power if its no longer necessary to back up the load. Upon return of the line voltage, the unit will then resume operation as normal.
Start-up Inverter From Save Battery
This feature requires the USER SECURITY CODE and can be
activated only if the inverter was shut off from save battery (507). The inverter then can be restarted to provide power to the load.
38
5. RS-232 TERMINAL COMMUNICATION
509
510
5.9 User Parameters,
Disable Transmission of Unsolicited Alarms
“509 None (xxxx)”; xxxx= “active” or blank; default is “active.” Setting this option to “active” disables the transmission of all unsolicited
alarm messages. USER SECURITY CODE is required to set this option.
Transmit IPC-XXX Type Unsolicited Alarms
“IPC-XXX (xxxx)”; xxxx= “active” or blank; default is blank Setting this option to “active” causes unsolicited alarm messages of type
IPC-XXX to be transmitted whenever the status of the CFR changes. These are ASCII type messages which are sent on the RS-232 port. The USER SECURITY CODE is required to activate this option.
The following is a list of the unsolicited alarm messages. UPS000 - power up
UPS001 - input out of tolerance UPS002 - input blackout UPS003 - inverter on UPS004 - line mode UPS005 - low battery warning UPS006 - low battery shutdown UPS007 - overload UPS008 - load OK UPS009 - temperature high UPS010 - temperature OK UPS011 - service required UPS012 - UPS malfunction UPS013 - self-test (Inv. on) UPS014 - self-test passed (line mode) UPS015 - self-test failed
continued
511
Delay Transmission of Inverter On Unsolicited Alarms
“Inverter on Alarm Delay (xxxxx)”; xxxxx= “off” or “m=min”, where m
specifies 1 to 5 minutes; default setting is “off”.
Transmission of the “inverter on unsolicited message,”
inverter on),
the input AC line from being displayed. Setting this option to “off” causes all AC line interruptions to be displayed. USER SECURITY CODE is required to change this option.
can be delayed for 1 to 5 minutes to prevent short interruptions in
39
(i.e.,UPS003 -
5. RS-232 TERMINAL COMMUNICATION
5.10 Maintenance Parameters
“MAINTENANCE PARAMETERS” allow you to customize UPS detection and warning characteristics. Normally, there should be no need to
7
change these factory settings. CAUTION: If any of these parameters are changed, it is vital to thoroughly test the UPS since an improper adjustment can render the unit useless. Since each parameter is viewed through reference numbers (1 - 16) and translated into a scale of “reasonable” adjustments, an increase or decrease of 2 - 3 reference numbers will have a noticeable affect. If you have questions, contact Alpha prior to making any adjustment.
Fast Detect Lo Ref
70
71
72
73
Increasing this value will make the UPS more sensitive to a fast, low amplitude line disturbance (glitch).
Fast Detect Hi Ref
Increasing this value will make the UPS more sensitive to a fast, high amplitude line disturbance (spike).
Medium Detect Lo Ref
Increasing this value will make the UPS more sensitive to a slow, low amplitude line disturbance (sag).
Medium Detect Hi Ref
Increasing this value will make the UPS more sensitive to a slow, high amplitude line disturbance (surge).
Slow Detect Lo Ref
74
75
76
77
Increasing this value will make the UPS more sensitive to a slow, low amplitude line disturbance (brownout) by raising the brownout detection level. Note: The Slow Detect Hys Lo Ref should also be adjusted by the same amount.
Slow Detect Hi Ref
Increasing this value will make the UPS more sensitive to a slow, high amplitude line disturbance (sustained overvoltage) by lowering the overvolt­age detection level. Note: The Slow Detect Hys Hi Ref should also be adjusted by the same amount.
Slow Detect Hys Lo Ref
Increasing this value will raise the voltage level at which the UPS will resume LINE POWER operation after a line disturbance has been corrected. This setting should normally be 1 - 3 settings above the Slow Detect Lo Ref setting.
Slow Detect Hys Hi Ref
Increasing this value will lower the voltage level at which the UPS will resume LINE POWER operation after an overvoltage condition has been corrected. This setting should normally be the same, or 1 - 3 settings above, the Slow Detect Hi Ref setting.
40
5. RS-232 TERMINAL COMMUNICATION
5.10 Maintenance Parameters
Max. PLL Slew Rate
78
79
Increasing this value will reduce the speed at which the Phase Locked
Loop (PLL) will change the output frequency while the UPS resumes LINE PRESENT operation after a line fault has been corrected. It will also increase the time required to resume LINE PRESENT operation.
Battery Warning Ref
Increasing this value will increase the time before a LOW BATTERY
WARNING occurs, thus allowing the batteries to drain more of their charge before a warning is given. Decreasing this value will allow more run time between LOW BATTERY WARNING and SHUTDOWN.
41
5. RS-232 TERMINAL COMMUNICATION
5.11 Parameter Dump Command (Function 0)
Parameter Dump Command (Function 0)
0
Function ‘0’ displays all UPS parameters in the following format:
#####,###.#,#####,#####,##.##,###.#,#####,###.#,#####,###.#,#####,#####,##.##, ###.#,###.#,###.#,xxxxx,#####,#####,#####,#,##,##,##,##,##,##,##,##,
###############,############ <CR> <LF>
Where ‘#’ indicates a digit or a blank character and ‘x’ represents a letter. The string is terminated by a Carriage Return and a Line Feed. Parameters are separated by a comma (‘,’). Above is the exact format for the SID option; IID option has slightly different format (less blank charac­ters). This command lists the CFR parameters in the following order:
1. Input Voltage 17. Charger Status
2. Input Current 18. Battery Temperature
3. Input VA 19. Efficiency
4. Input Watts 20. Capacity
5. Input Power Factor 21. Run Time Remaining
6. Input Frequency 22. Mode Data
7. Output Voltage #1 23. Input Alarms #1
8. Output Current #1 24. Input Alarms #2
9. Output Voltage #2 25. Battery Alarms
10. Output Current #2 26. Output Alarms
11. Output Watts 27. Environmental Alarms
12. Output VA 28. Inverter Alarms
13. Output Power Factor 29. System Alarms
14. Output Frequency 30. IID/Micro Board Serial #
15. Battery Voltage 31. Unit model - config. version
16. Battery Current
Example: 114, 1.22, 133, 38, 0.29, 59.9, 127, 0.31, 222, 0.49, 95, 0, 0.00,
59.9, 55.2, 2.8,ON , 24, 0, 0, 0,00,00,00,00,00,00,00,00, 88430A000000CA,001060001000<CR><LF>
In the above example, 114 represents the Input Voltage, 1.22 repre­sents the Input Current, 133 represents the Input VA, etc.
42
5. RS-232 TERMINAL COMMUNICATION
5.12 Event Descriptions (Alarms)
There are 6 alarm groups which upon activation will be displayed at the end of the opening menu. These are:
INPUT: BATTERY: OUTPUT: ENVIRONMENTAL: SERVICE1: SERVICE2:
The following lists the mnemonics and description for each alarm group:
INPUT:
FREQ_LO - input line frequency low FREQ_HI - input line frequency high GLITCH - input line glitch has been detected SPIKE - input line spike has been detected SAG - input line sag has been detected SURGE - input line surge has been detected BROWNOUT - input line brownout has been detected SLOW_SURGE - input line slow surge has been detected BLACKOUT - input line blackout has been detected
BATTERY:
LO_BAT_SHTDWN - battery voltage shutdown level detected LO_BAT_WARN - battery voltage low warning level detected BAT_VOLT_HI - battery over voltage level detected * FAIL_SELF_TEST - failed self test * BATT_FLT - battery fault has been detected *
OUTPUT:
VOLT_LO - output voltage low has been detected VOLT_HI - output voltage high has been detected PWR_OVLD - output power overload has been detected V A_OVLD - output VA overload has been detected OVER_V_FLT - output over voltage fault has been detected * SHORT_CCT - output short circuit has been detected *
ENVIRONMENTAL:
AMB_TEMP_HI - high internal ambient temperature detected *
SERVICE 1:
SERV CODE 1 - phase lock loop failure has been detected *
SERVICE 2:
SERV CODE 2 - micro software reset has been activated SERV CODE 3 - micro hardware reset has been activated
SERV CODE 4 - power board EEPROM fault has been detected * SERV CODE 5 - power board hardware fault has been detected * SERV CODE 6 - neg DC supply rail has been detected * EMGNCY POFF - emergency power off has been activated OUTV SHTDWN - remote shutdown feature is currently active
*(service light alarm)
43
5. RS-232 TERMINAL COMMUNICATION
5.12 Event Descriptions (Alarms),
Several alarms can be triggered during the same event. If there is a loss of AC line voltage, for example, the UPS may detect a glitch, low frequency and blackout.
Low Battery Warning (LO_BAT_WARN) - The batteries are near the end of their useful charge. If AC line power is not restored within a short period of time, output power will be lost. All systems should be shutdown immediately to prevent loss of data.
Low Battery Shutdown (LO_BAT_SHTDWN) - To prevent an over­discharge condition of the batteries, the unit has shutdown. Output power is terminated in this condition.
Battery Voltage High (BAT_VOLT_HI) - The charging voltage is higher than the threshold setting for the batteries. This could be the result of a defective charger, improper external battery connections, or defective batteries. Service the unit or batteries to correct condition. Note: This condition activates the SERVICE alarm, along with an audible alarm which can be cleared by pressing the ALARM OFF or MUTE key.
Failed Self-Test (FAIL_SELF_TEST) - The unit could not maintain output power while in the self-test mode. Check the batteries and circuit breakers. Note: This condition activates the SERVICE alarm, along with an audible alarm which can be cleared by pressing the ALARM OFF or MUTE key.
Battery Fault (BATT_FLT) - The battery charger is not able to supply the proper amount of current or voltage to the batteries. This condition usually indicates that the batteries are not connected or the BATTERY circuit breaker is switched OFF.
continued
Glitch (GLITCH) - A glitch is a fast, low amplitude line disturbance where
the input voltage drops momentarily (less than 8 ms). * *
Spike (SPIKE) - A spike is a fast, high amplitude line disturbance where the input voltage rises momentarily (less than 8 ms). * *
Sag (SAG) - A sag is a slow, low amplitude line disturbance where the input voltage decreases for 8 - 40 ms. * *
Surge (SURGE) - A surge is a slow, high amplitude line disturbance where the input voltage increases for 8 - 40 ms. * *
Brownout (BROWNOUT) - A brownout is a slow, low amplitude line disturbance where the input voltage decreases for a long period of time (greater than 16 ms). * *
Slow Surge (SLOW_SURGE) - A brownout high (high overvoltage) is a slow, high amplitude line disturbance where the input voltage increases for a long period of time (greater than 16 ms). * *
* * Indicates events that cause the UPS to operate in “LINE FAILURE” mode.
44
5. RS-232 TERMINAL COMMUNICATION
5.12 Event Descriptions,
Blackout (BLACKOUT) - The blackout alarm is triggered when the input
voltage is lost for 12 ms, or when the RMS input voltage is less than 1/2 the nominal voltage for 100 ms or longer. * *
Frequency High (FREQ_HI) - A frequency high alarm is triggered when
there is a power line problem where the input frequency increases beyond the preset limit. * *
Frequency Low (FREQ_LO) - A frequency low alarm is triggered when
there is a power line problem where the input frequency decreases beyond the preset limit. * *
Output Voltage Low (VOLT_LO) - The output voltage low alarm
indicates that the output of the UPS is too heavily loaded, or there is a fault within the UPS. Reduce the load connected to the UPS.
Output Voltage High (VOLT_HI) - The output voltage high alarm can be
caused by some equipment which draws power at irregular intervals. Disconnect all equipment from the UPS and determine whether the fault will repeat. If it does, the unit may be out of calibration, or there is an internal fault causing the overvoltage condition. Have the unit serviced by an authorized Alpha Repair Depot.
Output Power Overload (PWR_OVLD) - The output power overload
alarm indicates a condition where the output of the UPS is too heavily loaded. If this is not corrected, the unit may go into a shutdown condition to protect the UPS's internal circuitry.
Output VA Overload (VA_OVLD) - The output VA overload alarm is
triggered when the RMS current exceeds the rating of the UPS. Reduce the load on the output of the UPS to prevent overheating.
continued
Output Over Voltage Fault (OVER_V_FLT) - The output overvoltage
fault alarm indicates a malfunction has been detected in the control circuit. The output voltage has been shut off to protect the load from an overvoltage condition.
Output Short Circuit (SHORT_CCT) - The output short circuit alarm
indicates a load was connected to the UPS that was shorted. This could be caused by a miswired AC power cord or equipment connected to the UPS that is in need of repair. Note: This condition activates the SERVICE alarm, along with an audible alarm which can be cleared by pressing the MUTE key.
Internal Temperature High (AMB_TEMP_HI) - The internal tempera-
ture high alarm indicates that the temperature of the UPS, measured by internal circuitry, was found to be too high. This could be caused by a sustained overload on the output of the UPS, a blocked fan (if equipped), or operating the unit in an excessively high ambient temperature. To prolong the life of the batteries and UPS components, determine and correct the cause of the over-temperature condition.
* * Indicates events that cause the UPS to operate in “LINE FAILURE” mode.
45
5. RS-232 TERMINAL COMMUNICATION
5.12 Event Descriptions,
Input Line Fail - Indicates that the UPS switched to backup power to
protect the equipment for one (or more) of the above conditions. * *
Normal Line Mode - Indicates that the UPS is drawing power from the AC line and charging the batteries.
Test Mode - Indicates the UPS was put into a test mode condition either by the TEST SCHEDULE routine or by pressing the TEST button on the Intelligent Interface Device's panel. The unit will switch to backup power while in the test mode. * *
Float Charge Mode - This is the normal operating mode of the battery charger. During LINE PRESENT operation, the batteries constantly receive a "Float" charge voltage to ensure that backup power is available when required.
Service Codes (1-6) - These codes indicate a potential fault within the UPS. Call Alpha Customer Support and report any displayed Service Codes. Also refer to the Troubleshooting section (6.7) of the manual.
Serv Code 1 - Phase Lock Loop Failure. The phase lock loop circuitry has failed to lock onto the AC input LINE due to instability of the frequency. If the UPS is operating from a generator, check the frequency and adjust it if necessary.
Serv Code 2 - Micro software reset. The internal “watch dog” circuit has detected a fault and reset the software. Contact Alpha to help determine the cause of the fault.
Serv Code 3 - Micro hardware reset. A micro hardware reset is activated as part of the power on condition. If this alarm occurs during normal operation, it may indicate a malfunction in the hardware circuitry. Contact Alpha to help determine the cause of the fault.
Serv Code 4 - Power board EEPROM fault. The EEPROM on the power board contains the unit configuration information. If this fault occurs, it signifies either the configuration information has been corrupted, the EEPROM has malfunctioned, or there is a loose connection inside the UPS.
continued
Serv Code 5 - Power board hardware fault. The control circuitry on the
power board has detected a hardware fault condition which impedes correct operation of the UPS.
Serv Code 6 - Neg DC supply rail fail. The negative voltage power supply to the microcontroller has malfunctioned.
EMGNCY POFF - Emergency power shutdown.
OUTV SHTDWN - See menu 505 & 506 (see section 5.9).
* * Indicates events that cause the UPS to operate in “LINE FAILURE” mode.
46
5. RS-232 TERMINAL COMMUNICATION
5.13 RS-232 Terminal Setup
Terminal Emulation Setup
If you are using a terminal emulation software (such as PROCOMM) to
communicate with the CFR, use the following setup:
Emulation Type: VT100 or compatible Duplex Mode: Half Duplex Xon/Xoff Flow Control: SID: ON, IID: OFF RTS/CTS Flow Control: SID: OFF, IID: ON Line Wrap: ON Screen Scroll: ON CR Translation: CR Back-Space: N/A (See NOTE 1) Break Length: N/A Inquiry: N/A
NOTE 1: Back-Space and Delete characters are ignored by the CFR. To correct a miss-typed command, you should press Enter and type the command again.
RS-232 Cable Diagrams
The RS-232 port on the CFR follows the Data Communication
Equipment (DCE) pinout. To connect this port to a terminal or a host computer (which uses a DTE pinout) you need a standard off-the-shelf (straight through) RS-232 cable. Depending on your computer, you need a
9 to 9 serial cable
“ make you own cable, see Figure 12. This Figure shows the cable that works with both SID and IID. If your CFR has a SID interface, then you do not have to wire up the RTS and CTS signals.
” or a “
9 to 25 serial cable
”. However, if you decide to
DE-9 Male
1
2 - RxD 3 - TxD 4 5 - GND 6 7 - CTS 8 - RTS 9
To CFR RS-232
Port
1
2 - TxD 3 - RxD 4 5 - GND 6 7 - CTS 8 - RTS 9
Port
DE-9 Male to DE-9 FemaleDE-9 Male to DE-25 Female
DE-9 Male
DE-25
Female
(DTE)
1
2 - TxD 3 - RxD 4 - RTS 5 - CTS 6 7 - GND 8 9
24 25
To IBM-PC Serial Port
To CFR RS-232
Figure 12
RS-232 Connector Cable Wiring
47
DE-9
Female
(DTE)
1
2 - RxD 3 - TxD 4 5 - GND 6 7 - RTS 8 - CTS 9
To IBM-PC Serial Port

6. MAINTENANCE

6.1 CFR Maintenance

The electronic components used in the UPS require no maintenance. If
the unit fails to perform a specific function, refer to the troubleshooting guide. The guide lists typical symptoms, causes and solutions that apply to the UPS, starting with the most obvious and working systematically through the unit.
By establishing a routine maintenance program and following the
guidelines contained in this manual, your Alpha CFR will continue to provide years of trouble-free service.

6.2 Battery Maintenance

The maintenance free batteries used in the UPS will be affected by many
variables including operating temperatures, number of discharges over the life of the battery, charging characteristics, and low voltage cell cutoff. The Alpha CFR complies with all factory recommendations for charging and discharging batteries to ensure optimum performance and the longest possible battery life.
During normal operation, the UPS batteries will tend to increase in
capacity over the first three to twelve months of service. There can be as much as a 20% increase in available backup power after the first ten to fifteen battery discharges. Once the batteries reach this peak, they will slowly begin to lose capacity until, eventually, they will be unable to provide the required backup power.
Note: Battery terminals vary in size and shape.
Figure 13
Typical UPS Battery
48
6. MAINTENANCE

6.3 Battery Testing

To determine the maximum amount of battery run time available, run this
test at least once a year. The length of the test can vary from several minutes to many hours and should not be done during critical applications. Since the test discharges the batteries, backup power may not be readily available (for several hours) in the event of a utility power failure.
1. Unplug the AC Line cord from the wall receptacle. The front panel “LINE FAILURE” LED will come ON. Make a note of the START time.
2. When the CFR reaches LOW BATTERY WARNING, record the time. Subtract the START time to determine the actual safe run time. To cancel the test, plug the AC Line cord back into the wall receptacle.
3. To determine the reserve time available, allow the UPS to continue until it reaches LOW BATTERY SHUTDOWN. Warning: This will cause the load to go down. Make a note of the time. Subtract the LOW BATTERY WARNING time to determine your available reserve time.
4. Switch the load OFF. Plug the AC Line cord back into the wall receptacle. The “LOW BATTERY WARNING” LED will remain ON until the batteries are partially recharged. Switch the load ON, one device at a time. To determine recharge time, subtract the time you resumed LINE PRESENT operation from when the “LOW BATTERY WARNING” LED goes OFF.
Figure 14 - Standard Interface Device
ALPHA TECHNOLOGIES
05-07-92 08:02:10
LINE PRESENT
LOW BATTERY
Figure 15 -Intelligent Interface Device
49
LINE FAILURE
WARNING
SHUTDOWN
SERVICE
6. MAINTENANCE

6.4 Removing the CFR Front Panel and Cover

CAUTION: INTERNAL MAINTENANCE SHOULD BE SERVICED ONLY BY QUALIFIED PERSONNEL.
1. Disconnect all loads from the OUTPUT receptacles on the UPS.
2. Switch the rear panel BATTERY circuit breaker OFF.
3. Disconnect the UPS from the AC wall receptacle.
4. If an external battery pack is connected to the UPS, remove the connector
from the UPS rear panel.
5. Loosen the two (2) Phillips screws from the UPS front panel (located in the lower grill). Carefully pull the lower part of the front panel away from the UPS and lift the panel straight up.
6. Remove the eight (8) Phillips screws from the sides of the UPS.
7. Carefully lift the cover upward until it clears the chassis.
Cover Screws
(on rear panel)
Phillips Screwdriver
(behind front panel)
Requires
Cover Screw
Front Sub-Panel Screws
Figure 16
Front Panel Removal
50

6.5 Internal Battery Replacement

6. MAINTENANCE
Internal Battery Replacement (For CFR 600
)
IMPORTANT: READ THE SAFETY PRECAUTIONS LOCATED AT THE FRONT OF THE MANUAL BEFORE PROCEEDING. WARNING: DO NOT SHORT OUT BATTERY TERMINALS.
(Note: All references to left and right are made facing the front of the CFR)
1. Switch OFF all power to the UPS and turn the battery breaker to the OFF position.
2. Remove the CFR front panel and cover. (Refer to section 6.4).
3. Make a note of battery orientation and cable connections. Carefully remove the BLACK (negative) wire from the battery’s quick-connect tab.
4. Remove the RED (positive) wire from the battery’s quick-connect tab.
5. Remove the battery fuse assembly from the center two battery quick­connect tabs (see Fig. 17).
6. Slip the two front ends of the plastic battery straps towards the buckles (Fig. 19).
7. Loosen straps and remove foam cushion in front of the batteries.
8. Carefully remove both batteries through the left side of the CFR chassis. WARNING: Do not let the battery terminals contact the chassis.
9. Place new batteries into the CFR chassis according to figure 17.
10. Attach the wires to the batteries in reverse order of steps 1 - 7. Test the UPS for proper operation before connecting the load.
BATTERIES SHOULD BE INSPECTED EVERY YEAR FOR SIGNS OF CRACKS, LEAKING OR SWELLING.
ALWAYS REPLACE BATTERIES WITH THOSE OF AN IDENTICAL TYPE AND RATING. NEVER INSTALL OLD OR UNTESTED BATTERIES.
CONTACT ALPHA TECHNOLOGIES TO ORDER AND RECYCLE BATTERIES.
Internal Battery Replacement CFR 600
Figure 17
(top view)
51
6. MAINTENANCE
6.5 Internal Battery Replacement,
continued
Internal Battery Replacement (For CFR 600XT and CFR 1000)
IMPORTANT: READ THE SAFETY PRECAUTIONS LOCATED AT THE FRONT OF THE MANUAL BEFORE PROCEEDING. GENERAL WARNING: DO NOT SHORT OUT BATTERY TERMINALS.
(Note: All references to left and right are made facing the front of the CFR)
1. Switch OFF all power to the UPS and turn the battery breaker to the
OFF position.
2. Remove the CFR front panel and cover. (Refer to section 6.4).
3. Make a note of battery orientation and cable connections. Carefully
loosen the battery’s “-” terminal screw and remove the BLACK (negative) wire from the right front battery terminal.
4. Loosen the battery’s “+” terminal screw and remove the RED (positive)
wire from the right rear battery fasten terminal.
5. Loosen the screws on the battery terminals on the left side and remove
the battery fuse assembly CFR 600XT) or wire assembly (CFR 1000).
6. Slip the two front ends of the plastic battery straps towards the buckles
(Fig. 19).
7. Loosen straps and remove foam cushion in front of the batteries.
8. Carefully remove both batteries through the left side of the CFR
chassis. WARNING: Do not let the battery terminals contact the chassis.
9. Place the new batteries into the CFR chassis according to figure 18.
10. Restore the UPS in reverse order of steps 1 - 7. Test the UPS for
proper operation before connecting the load.
BATTERIES SHOULD BE INSPECTED EVERY YEAR FOR SIGNS OF CRACKS, LEAKING OR SWELLING.
ALWAYS REPLACE BATTERIES WITH THOSE OF AN IDENTICAL TYPE AND RATING. NEVER INSTALL OLD OR UNTESTED BATTERIES.
CONTACT ALPHA TECHNOLOGIES TO ORDER AND RECYCLE BATTERIES.
CFR 600XT
only
Figure 18
Internal Battery Replacement CFR 600XT and CFR 1000
(top view)
52
6. MAINTENANCE
6.5 Internal Battery Replacement,
Figure 19
Battery Tie-down Strap Loop
(side view)
continued
53
6. MAINTENANCE

6.6 Troubleshooting Guide

SYMPTOM CAUSE REMEDY
No Output Power: "LINE PRESENT" OFF "LINE FAILURE" OFF
Unit does not resume LINE PRESENT operation when power returns: "LINE PRESENT" ON (or flashing) "LINE FAILURE" ON
"SERVICE" LED ON
Utility power outage;
or
AC power cord unplugged;
or
AC input circuit breaker OFF.
and
BATTERY circuit breaker OFF.
AC line voltage too high or low;
or
UPS is in its synchronization mode.
BATTERY breaker tripped.
or
Internal charger fuse open.
or
Loose or corroded battery cables.
or
Bad batteries.
Plug in AC power cord.
Reset breaker.
Reset breaker.
Wait for voltage to stabilize.
Wait approximately one minute for synchronization.
Reset breaker.
*Replace fuse.
*Clean and tighten
battery cables.
*Replace batteries.
Incorrect output voltage: "LINE PRESENT" ON "LINE FAILURE" OFF "OVERLOAD" ON
Overloaded output;
or
Shorted output.
54
Reduce load.
Check load for short.
6. MAINTENANCE
6.6 Troubleshooting Guide,
SYMPTOM CAUSE REMEDY
No output voltage during utility outage: "LINE PRESENT" OFF "LINE FAILURE" OFF "LOW BATTERY SHUTDOWN" ON
Batteries do not charge: "LOW BATTERY SHUTDOWN" ON
Battery voltage below low voltage cutout (after long outage).
Battery voltage below low voltage cutout (after several short outages).
BATTERY breaker tripped.
Loose battery cable or connection.
continued
Wait for line power to return and recharge batteries.
or
Wait for batteries to recharge.
*Check batteries and replace if necessary.
Reset breaker.
or
*Clean and tighten connections.
or
Faulty batteries.
*Check batteries and replace if necessary.
or
Open charger fuse.
*Check internal fuse on main circuit board and replace if necessary.
* ITEMS TO BE PERFORMED ONLY BY A QUALIFIED TECHNICIAN
Notice
This equipment generates, uses, and can radiate radio frequency energy if not installed and used in accordance with the instructions contained in the manual. It has been tested and found to comply with the limits established for a Class A computing device pursuant to Part 15 of FCC rules and the radio interfer­ence regulations of DOC which are designed to provide reasonable protection against such interference when this type of equipment is operated in a commercial environment. If the UPS appears to cause interference to radio or television reception, which can be determined by switching the unit OFF and ON, relocate the equipment and/or use an electrical circuit other than that used by the UPS.
55
6. MAINTENANCE

6.7 Troubleshooting Using the SID

The OUTPUT LOAD LED’s, located on the front panel of the Standard Interface Device, are designed to display UPS fault conditions once the unit has detected an internal problem, indicated by the SERVICE LED. This information provided by the LED’s is extremely useful during troubleshooting and maintenance. If the UPS is equipped with an I manual for further troubleshooting information.
If your UPS SERVICE LED is ON, press and hold the ALARM OFF switch for approximately 3 seconds. The OUTPUT LOAD LED's indicate:
LED Status Condition
OVERLOAD Flashing Not Applicable OVERLOAD ON Fast Detector / Low Sensitivity Fault
100% Flashing PLL Fault 100% ON High Ambient Temperature
75% Flashing Output Voltage High 75% ON Output Voltage Short Circuit
50% Flashing PWR BRD Fault / -5 VDC Failure 50% ON PWR BRD EPROM Failure
2
D, refer to its operator’s
25% Flashing Self-Test Failure 25% ON Battery Over-Voltage / Charger Fault
SERVICE LED
OUTPUT LOAD LED's
Standard Interface Device - Fault Indicators
Standard Interface Device (Troubleshooting)
ALARM OFF Switch
Figure 20
56
6. MAINTENANCE
6.7 Troubleshooting Using the SID,
SYMPTOM CAUSE REMEDY
OVERLOAD LED (ON) SERVICE LED (ON) ALARM OFF switch pressed and held:
100% LED (Flashing) SERVICE LED (ON) ALARM OFF switch pressed and held:
100% LED (ON) SERVICE LED (ON) ALARM OFF switch pressed and held:
75% LED (Flashing) SERVICE LED (ON) ALARM OFF Switch pressed and held:
75% LED (ON) SERVICE LED (ON) ALARM OFF Switch pressed and held:
Fast Detector / Low Sensitivity Fault.
PLL Fault. Instability in line freq from generator; or out of phase wiring.
High Ambient Temp. Caused by excessive load or heat source.
Output Voltage High. Calibration problem or incorrect jumper setting on power board.
Output Voltage Short Circuit.
Call Alpha.
Wait for line power to return.
Check wiring.
Reduce ambient temperature. Alarm will reset when temp returns to safe level.
Contact Alpha.
Contact Alpha.
continued
50% LED (Flashing) SERVICE LED (ON) ALARM OFF Switch pressed and held:
50% LED (ON) SERVICE LED (ON) ALARM OFF Switch pressed and held:
25% LED (Flashing) SERVICE LED (ON) ALARM OFF Switch pressed and held:
25% LED (ON) SERVICE LED (ON) ALARM OFF Switch pressed and held:
PWR BRD Fault or
-5 VDC Failure.
PWR BRD EPROM Failure.
Self-Test Failure.
Battery Over-Voltage or Charger Fault.
57
Contact Alpha.
Contact Alpha.
Check batteries and retest unit. Contact Alpha if unit continues to fail.
Contact Alpha.
6. MAINTENANCE

6.8 Repair Instructions

Before returning a unit to Alpha Technologies for repair, a Return
Material Authorization (RMA) should first be obtained from Alpha's Customer Service Department. The RMA number should be clearly marked on the unit’s original shipping container. If the original container is no longer available, the UPS should be packed with at least 3 inches of shock-absorbent material. Note: Do not use popcorn-type packing material. Returns should be prepaid and insured (COD and freight collect can not be accepted).
ALPHA TECHNOLOGIES DOES NOT ASSUME RESPONSIBILITY FOR DAMAGE CAUSED BY THE IMPROPER PACKAGING OF RETURNED UNITS.

6.9 Parts and Ordering Instructions

To order parts, contact the Alpha Technologies Customer Service
Department directly at:
United States (360) 647-2360 Canada (604) 430-1476 United Kingdom +44-1279-422110 Germany +49-9122- 997303 Middle East +357-5-375675
TO OBTAIN COMPLETE TECHNICAL SUPPORT
(7 DAYS / WEEK, 24 HOURS / DAY)
CALL
1 - 8 0 0 - 3 2 2 - 5 7 4 2
(USA)
1 - 8 0 0 - 6 6 7 - 8 7 4 3
(Canada)
58

7.1 Specifications

7. SPECIFICATIONS

84 63
28
CFR 1000
1000
750 230
4.3
120
8.3
230
4.3
120
8.3 92
90
3.5 12
5.0
<40
CFR
600
Output Power (VA) Active Power (WATTS) Input Voltages @ 50 Hz (VAC) Input Current Max. (A) Input Voltages @ 60 Hz (VAC) Input Current Max. (A)
Output Voltages @ 50 Hz (VAC) Output Current Max. (A) Output Voltages @ 60 Hz (VAC) Output Current Max. (A)
Efficiency @ Full Load (%) Efficiency @ .25 Load (%) Max Charger Current (A) Batt Run Time* - internal (min) Battery Recharge Time (hrs)
* Battery run times are calculated
at typical load (80%)
Audible Noise @ 1M (dBA)
Note: Specifications are based upon use with computer-type loads with a crest factor of 3:1 max., and a typical power factor of 0.75 for CFR 1000 and 0.67 for CFR 600.
600 400 230
2.5
120
4.8
230
2.6
120
5.0 84
63
3.5
8
2.0
<40
CFR
600XT
600 400 230
2.5
120
4.8
230
2.6
120
5.0
3.5
5.0
<40
Dimensions
CFR 600 8.5"W x 10"H x 20.5"D (205mm x 140mm x 194mm) CFR 1000 8.5"W x 10"H x 20.5"D (216mm x 254mm x 521mm)
EBP 24A 8.5"W x 5.5"H x 15.5"D (216mm x 140mm x 194mm) EBP 24C 8.5"W x 9.75"H x 24"D (216mm x 248mm x 610mm) EBP 24E 8.5"W x 21.5"H x 31"D (216mm x 546mm x 787mm)
Weights 60 Hz Units 50 Hz Units
CFR 600 52 lbs. (39.5 kg) 56 lbs. (26 kg) CFR 600XT 69.5 lbs. (24 kg) 74 lbs. (33.6 kg) CFR 1000 93.5 lbs. (42.4 kg) 94 lbs. (42.5 kg)
EBP 24A 35 lbs. (16 kg) 35 lbs. (16 kg) EBP 24C 125 lbs. (57 kg) 125 lbs. (57 kg) EBP 24E 314 lbs. (142 kg) 314 lbs. (142 kg)
The EBP 24A is an external 24 volt battery pack, pre-wired, with two, 17
Ah maintenance free batteries.
Specifications subject to change without notice.
59
7. SPECIFICATIONS
7.1 Specifications,
continued
Common Specifications 600, [1000 ]
Input Frequency 60 Hz or 50 Hz (± 3% Hz) Input Voltage Variation - 25% to + 10% Output Frequency ± 0.1 Hz Output Regulation ± 1% (from 10 - 100% load) Total Harmonic Distortion < 5% Output Waveform Sine Step Load Response < 10% @ 100% load Noise Attenuation
Common Mode Normal Mode
Low Voltage Trigger 80% nominal voltage (adjustable) High Voltage Trigger 110% nominal voltage (adjustable) Batteries Valve regulated, maintenance-free Battery Voltage 24 VDC Batt. Low Volt. Cutout 19.5 VDC (>25% load), [21 VDC (<25% load)] Charger Linear(3.5 A max.) Charger Voltage 27.6 VDC at 25 Operating Temp 32 Heat Output 260 BTU, [404 BTU] Indicators Line Present, Line Failure,
Controls Manual Start / Test, Alarm OFF Connectors AC Input, AC Output, External Alarm;
Output Alarms Rear panel RJ-45 connector (Form C
-120dB (100K - 1 MHz)
-60dB (100K - 1 MHz)
0
0
-1040 F / 00 - 400C
C (adjustable)
Low Battery Shutdown, Low Battery Warning (LED / audible alarm), Test, Service and Output Load
Intelligent Interface Device and External Battery
contact closures rated 1A, 30 V) for Line Present / Line Failure, and Battery OK / Low Battery Warning
Specifications subject to change without notice.
60

8. WARRANTY

WARRANTY
ALPHA TECHNOLOGIES
Alpha Technologies warrants its equipment to be free of manufacturing defects in material and workmanship for a period of 24 months from the date of manufacture. The liability of Alpha Technologies under this warranty is solely limited to repairing, replacing, or issuing credit (at the discretion of Alpha Technologies) provided that:
1. Alpha Technologies is promptly notified in writing, or by telephone, that a failure
or defect has occurred;
UNITED STATES
Alpha Technologies
Bellingham, WA 98226
Tel: (360) 647-2360
Fax: (360) 671-4936
UNITED KINGDOM
Alpha Technologies
Cartel Business Estate
Edinburgh Way
Harlow, Essex CM20 2DU
Tel: +44-1279-422110
Fax: +44-21279-423355
3767 Alpha Way
GERMANY
Alpha Technologies
Hansastrasse 8
D-91126 Schwabach Tel: +49-9122-997303 Fax: +49-9122-997321
CANADA
Alpha Technologies
5700 Sidley Street
Burnaby, B.C. V5J 5E5
Tel: (604) 430-1476
Fax: (604) 430-8908
3307 Limassol, Cyprus
Tel: +357-5-375675 Fax: +357-5-359595
MIDDLE EAST
Alphatec
P.O. Box 6468
2. A Return Authorization number is obtained and clearly marked on the outside of the shipping container;
3. Customer is responsible for all shipping and handling charges (COD and freight collect will not be accepted without prior approval from Alpha Technologies);
4. The service engineer’s examination of the returned unit shall disclose, to his satisfaction, that such defects have not been caused by misuse, neglect, improper installation, repair, alteration, or accident. If Alpha Technologies does determine that the unit has been damaged due to one of these causes, or if the unit is free of defects, a handling or repair fee will be necessary prior to returning the unit.
THIS 24 MONTH WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES,
EXPRESSED OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
IN NO CASE SHALL ALPHA TECHNOLOGIES BE LIABLE FOR ANY
CONSEQUENTIAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESSED OR IMPLIED, WHATSOEVER.
ANY ACTION FOR BREACH OF THIS LIMITED 24 MONTH WARRANTY
MUST BE BROUGHT WITHIN A PERIOD OF 24 MONTHS FROM DATE OF PURCHASE.
Alpha Technologies reserves the right to discontinue particular models and to
make modifications in design and/or function at any time, without notice and without incurring obligations to modify previously purchased units.
048-133-00 3/93
61
62

EMERGENCY SHUTDOWN

EMERGENCY SHUTDOWN
IMPORTANT
THE UPS CONTAINS MORE THAN ONE LIVE CIRCUIT. DURING AN EMERGENCY, UTILITY POWER MAY BE DISCONNECTED AT THE SERVICE ENTRANCE OR MAIN ELECTRICAL PANEL TO PROTECT EMERGENCY PERSONNEL; HOWEVER, POWER WILL STILL BE PRESENT AT THE UPS OUTPUT.
TO PREVENT THE POSSIBILITY OF INJURY TO SERVICE OR EMERGENCY PERSONNEL, ALWAYS SWITCH THE UPS REAR PANEL BATTERY CIRCUIT BREAKER(S) OFF TO DE­ENERGIZE THE CIRCUIT.
EMERGENCY SHUTDOWN PROCEDURE:
1. Switch the rear panel BATTERY circuit breaker OFF.
2. Unplug the AC power cord from the wall receptacle or the back of the unit. If hardwired, switch the main panel AC breaker to the UPS OFF
NOTE: Press the wall mounted EPO switch to switch OFF the Battery Circuit Breaker (only on CFR 1000 units equipped with this option).
1
BATTERY
Breaker OFF
EPO Switch
N.O.
7 8
Factory Installed Option on
CFR 1000 Only
REMOVE
AC LINE
Power Cord
2
CFR 1000
Bellingham, WA 98226
FAX: (360) 671-4936
FAX: (604) 430-8908
Alpha Technologies
Tel: (360) 647-2360
Tel: (604) 430-1476
UNITED STATES
3767 Alpha Way
Burnaby, B.C. V5J 5E5
Alpha Technologies
5700 Sidley Street
CANADA
Harlow, Essex CM20 2DU
FAX: +44-21279-423355
Cartel Business Estate
Tel: +44-1279-422110
UNITED KINGDOM
Alpha Technologies
Edinburgh Way
ALPHA TECHNOLOGIES
FAX: 49-9122-997321
D-91126 Schwabach
Tel: 49-9122-997303
3307 Limassol, Cyprus
FAX: +357-5-359595
Tel: +357-5-375675
017-100-B0-001 7/95
Alpha Technologies
Hansastrasse 8
GERMANY
MIDDLE EAST
P.O. Box 6468
Alphatec
Loading...