Supplementary LPG Boiler
Instructions
Alpha CD50
Wall Mounted, Fan Assisted, Room Sealed, Gas Fired,
High Efficiency, Condensing Combination Boiler with
Unvented Hot Water Storage
For Technical help or for Service call ...
ALPHA HELPLINE Tel: 0870 3001964
website:www.alpha-innovation.co.uk
Nepicar House, London Road,
Wrotham Heath, Sevenoaks,
Kent TN15 7RS
British Gas
Service Listed
Alpha CD50 G.C. No. 47 532 24
For use with LPG (Propane) only
Leave these instructions with the User
1 INTRODUCTION
This supplement is for the LPG model of the boiler; it must be read in conjunction with the 'Installation and Servicing
Instructions' supplied with the boiler and provides the extra information which is particular to LPG.
The Alpha CD50 is a wall mounted, high efficiency, fan assisted, room-sealed, condensing combination boiler - incorporating a
52 litre unvented hot water storage cylinder. The burner is lit electronically and heat output is controlled by a modulating gas
valve and fan.
The boiler, providing both central heating and domestic hot water at mains pressure, is designed for use with a fully pumped,
sealed and pressurised heating system using only PROPANE gas.
2 TECHNICAL DA T A
2.1 PERFORMANCE - PROPANE GAS (CAT 3P-G31-37 mbar)
Central Heating
Heat Input (H
)kW
s
(Gross) Btu/h
Heat Input (Hi)kW
(Net) Btu/h
Heat Output (Hs condensing) kW
(50°C/30°C) Btu/h
Heat Output (Hi non-condensing) kW
(80°C/60°C) Btu/h
Differential Burner mbar
Pressure in wg
Room sealed
chamber panel
fitted
MAX.
31.0
105 770
28.0
95 230
29.7
101 430
27.6
94 130
4.16
1.66
Gas Supply Pressure (LPG) mbar
in wg
Gas Rate (LPG) m³/h
ft³/h
1.08
38.6
CH Water Temp. (Approx. max.) °C
°F
Domestic Hot Water
Heat Input (H
)kW
s
(Gross) Btu/h
Heat Input (Hi)kW
(Net) Btu/h
Output to Water (Hs)kW
(modulating) Btu/h
Differential Burner mbar
Pressure in wg
Room sealed
chamber panel
fitted
MAX.
36.1
123 190
32.6
110 910
32.0
109 200
5.9
2.36
Gas Supply Pressure (LPG) mbar
in wg
Gas Rate (LPG) m³/h
ft³/h
Flow Rate L/min
G.P.M.
Outlet Water Temp. (Approx.) °C
°F
1.25
44.6
18.0
4.0
65
149
Time to raise water store by 50°C
Reheat time for 70% of store
(boiler ON)
(boiler OFF)
MIN.
25 360
22 830
23 980
21 500
0.24
0.10
37.0
14.8
0.26
82
180
MIN.
25 360
22 830
21 500
0.24
37.0
14.8
0.26
0.22
7 minutes
3 minutes
5 minutes
7.4
6.6
7.0
6.5
9.3
7.4
6.6
6.3
0.1
9.3
1.0
5
41
CD50 LPG Supplement
2