13 Service record ................................... 34
1INTRODUCTION
The Alpha CD Regular range of high efficiency condensing boilers are wall mounted, fan assisted room-sealed boilers. The
burner is lit electronically and the heat output is controlled by a modulating fan and gas valve.
The boilers provide heating only for open vented systems and with the addition of a sealed system kit for sealed central
heating systems.
The boilers are designed for use with a fully pumped open vented or sealed and pressurised central heating system using only
Natural gas.
The boiler CD13R is suitable for central heating loads of between 5.4 and 13.1 kW (18 400 and 44 700 Btu/h).
The boiler CD18R is suitable for central heating loads of between 5.4 and 19.6 kW (18 400 and 66 800 Btu/h).
The boiler CD24R is suitable for central heating loads of between 6.5 and 25.6 kW (22 200 and 87 300 Btu/h).
The boilers are rated to the SEDBUK efficiency band A and have a NOx class 5 rating.
IMPORTANT
It is the law that all gas appliances are installed by a competent person, ie CORGI registered personnel, in accordance with
the following recommendations:-
Current Gas Safety (Installation and Use) Regulations
All current Building Regulations issued by the Department of the Environment, i.e. Approved Document L1.
Building Standards (Scotland) (Consolidation) Regulations issued by the Scottish Development Department
Health & Safety Document No. 635 (The Electricity At Work Regulations 1989)
The installation should also be in accordance with the following British Standard Codes of Practice:BS 5440:1:2008Flues
BS 5449:1990Forced circulation hot water systems
BS 5546:2000Installation of hot water supplies for domestic purposes
BS 6700:1997Design, installation, testing and maintenance of services supplying water
BS 6798:2000Installation of gas fired boilers
BS 6891:1998Gas installation
BS 7593:2006Code of Practice for treatment of water in heating systems
BS 7671:2001Requirements for electrical installations, IEE Wiring Regulations
Reference should also be made to the DEFRA document 'Guide to condensing boiler installation assessment procedure for
dwellings'
If installation is in a timber framed building, refer to the Institute of Gas Engineers document IGE/UP/7.
This appliance meets the requirements of IPX4D, ie degree of protection against moisture.
Failure to install this appliance correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the
law is complied with.
Manufacturer's instructions must NOT be taken in anyway as over-riding statutory obligations.
Notes: 1. Ensure that the Benchmark Checklist has been completed after the boiler has been installed and commissioned.
2. Ensure the appliance has been supplied with an Alpha CD flue system.
Note: When installed using a sealed heating system, a sealed system kit must be fitted.
Central Heating (Sealed System)
Max. Working System Pressure
Min. System Pressure
Max. System temperature
Pressure Relief Valve Setting
Expansion Vessel Size (pre-charge press.)
Flow Connection
Return Connection
Relief Valve Connection
Recommended System Pressure (cold)
CH Water Temp. (Approx. max.)
2.3COMPONENTS
Burner
Main Heat exchanger
Main Burner InjectorCD13R/18R
CD24R
Flue - Outer Duct
Flue - Inner Duct
2.5 bar
0.5 bar
82°C
3 bar (44 PSI)
8 L at 1.0 bar
22 mm
22 mm
15 mm
1.0 bar
80°C (176°F)
Stainless steel
Stainless steel
5.1 mm
5.25 mm
White
Plastic
Note: Refer to Fig. 5 when using with a fully
pumped open vented system.
2.4ELECTRICAL
Supply
External Fuse
Power Consumption
Internal Fuse
Electrode Spark Gap
230/240 V ~ 50 Hz
3 A
55 W
F2 A
3 - 4 mm
Alpha CD13R, 18R, 24R - Technical Data
3
2.5INSTALLATION
2.6GENERAL
Min. Clearances for ServicingTop
(from casing)Bottom
Sides
Front
Flue Terminal Size
Flue Terminal Protruding
Hole Size Required For Flue Assy.
Lift WeightCD13R/18R
CD24R
235 mm
100 mm
5 mm
450 mm
100 mm Dia.
100 mm
110 mm Dia.
27 kg
28 kg
Case DimensionsHeight
Width
Depth
Gas ConnectionCD13R/18R
CD24R
Primary Water Content
Air Duct Diameter
Flue Duct Diameter
600 mm
390 mm
305 mm
15 mm
22 mm
1.6 L
100 mm
60 mm
2.7FLUE LENGTHS
CD Easy-Flue 500 mm with terminal and 90° bend. A CD Easy-Flue 1000 mm with terminal and 90° bend is also available.
CD 750 mm and CD 1000 mm flue extensions are available.
Length of Flue Required:-
Rear Flue (includes terminal) = wall thickness + 170 mm (or 140 mm for CD24R)
Side Flue (includes terminal) = wall thickness + distance between wall and side of boiler + 200 mm
Vertical Flue = distance from top of boiler side panel to required roof position minus 1 m for vertical terminal assembly
Maximum horizontal flue length = 12 m.
Maximum vertical flue length including terminal is 15 m.
Each additional CD 90° Bend is equivalent to 1.3 m of flue length.
Each CD 45° Bend is equivalent to 0.9 m of flue length.
The CD Vertical Flue terminal assembly is equivalent to 1 m of flue length.
2.8PRESSURE LOSS ACROSS BOILER
2.5
2.0
Pressure loss
(metres head of water)
1.5
1.0
0.5
0
02003001004005006007008009001000
Flow rate (litres/hr)
2.9ELECTRICAL CONNECTIONS
Note: This Appliance Must Be Earthed
An optional integral two channel Clock kit (Part No. 6.1000220) is available if required.
Note: Only use the Alpha two channel clock. Do not fit any single channel clocks.
Fuse - Always fit fast blow 2 A
Live (Brown wire)
Neutral (Blue wire)
Earth (Green/Yellow wire)
Switched Live
230/240 V (Ch1 ON)
Ch1 OFF
Ch2 ON
Live (Brown wire)
Neutral (Blue wire)
Earth (Green/Yellow wire)
Fig. 1
Use only when internal
clock is fitted
Boiler terminal block
White
Grey
Black
Blue
wire
wire
wire
Internal 2 Channel Clock Terminals
wire
Brown
wire
12345
WARNING
1. Ensure wires are connected
correctly
2. Only fit the Alpha recommended
2 channel clock. Other clocks
could cause damage.
Clock connections
F2A
L
N
1
2
3
4
L
N
230/240 V ~ 50 Hz
Fuse supply 3 A
Note: To connect external
control, remove link from
terminals 1 and 2 and
connect a 230/240 V
switched live to terminal 1
External Pump
20°C System design
temperature difference
Note: The pump must
always be connected
to this terminal block
Alpha CD13R, 18R, 24R - Technical Data
4
2.10 BOILER SCHEMATIC
12
10
Primary
Heating
return
2
8
Primary
Heating
flow
5
15
1
+
-
11
13
14
16
9
7
-
17
18
6
+
3
19
4
20
GasCondensate
discharge
1- Flue sampling point
2- Flue thermostat
3- Injector
4- Gas valve
5- Primary return temperature sensor
6- Venturi
7- Main burner
8- Primary/condensing heat exchanger
9- Room sealed chamber
10 - Fan
11 - Pressure differential test points
21
12 - Flue hood
13 - Overheat thermostat
14 - Primary flow temperature sensor
15 - Drain point
16 - Ignition electrodes
17 - Flame sensing electrode
18 - Venturi negative point
19 - Venturi positive point
20 - Gas service cock
21 - Condensate trap
Fig. 2
Alpha CD13R, 18R, 24R - Technical Data
5
3GENERAL BOILER INFORMATION
3.1GAS SUPPLY
The CD13R boiler requires a gas rate of 1.31 m³/h (46.2 ft³/h).
The CD18R boiler requires a gas rate of 1.94 m³/h (68.5 ft³/h).
The CD24R boiler requires a gas rate of 2.54 m³/h (89.7 ft³/h).
The meter and supply pipes must be capable of delivering this quantity of gas in addition to the demand from any other
appliances in the house. The CD13R and CD18R require at least a 15 mm gas supply pipe and the CD24R requires a 22 mm
gas supply pipe.
The complete installation, including the meter, must be tested for gas soundness and purged as described in BS 6891.
3.2ELECTRICAL SUPPLY
The boiler requires a 230/240 V ~ 50 Hz mains supply, fused at 3 A
The boiler must be earthed.
There must only be one common isolator, providing complete electrical isolation, for the boiler and any external controls.
This boiler has been fitted with a supply cable, however, if it is necessary to fit a cable use PVC insulated cable not less than
0.75 mm² (24 x 0.2 mm) to BS 6500 Table 16. The boiler should be connected to a fused three pin plug and unswitched
shuttered socket outlet (both complying with BS 1363), or a fused double pole switch with a contact separation of at least 3 mm
in both poles.
Wiring external to the boiler must be in accordance with the current IEE Wiring Regulations (BS 7671).
Note: If a room thermostat is fitted, it must be suitable for 230/240 V switching.
3.3AIR SUPPLY
The boiler does not require any air vents for cooling in the room in which it is installed or when installed in a cupboard or
compartment. The minimum clearances for servicing must always be maintained.
Note: A cupboard or compartment used to enclose the boiler must be designed and constructed specifically for the purpose,
i.e. comply with the Building Regulations.
3.4FLUE SYSTEM - Fig. 3
The flue system must be installed in accordance with BS 5440:1.
For horizontal flues ensure the flue assembly is horizontal and the inner duct is sloping downwards towards the boiler.
Flue components are available as follows:CD Easy-Flue 500 mm (includes 90° bend and terminal) - Part No. 6.2000510.
CD Easy-Flue 1000 mm (includes 90° bend and terminal) - Part No. 6.2001010.
CD 750 mm flue extension - Part No. 6.2000750.
CD 1000 mm flue extension - Part No. 6.2001050.
CD 90° bend - Part No. 6.2000590.
CD 45° bend - Part No. 6.2000545.
CD Vertical flue terminal assembly. Refer to the separate installation instructions supplied with the assembly.
The following methods determine the correct length of flue required.
For rear exit flue (including terminal)L = B + 170 mm (or 140 mm for CD24R)
For side exit flue (including terminal) L = B + C + 200 mm (min. side clearance required is 5 mm)
For vertical flue L = H minus 1000 mm for vertical terminal assembly
WhereL = Required flue length
B = Finished wall thickness
C = Distance from the inside wall to the side of the boiler
H = Distance from top of boiler side panel to roof position
Note: 1. If an extra 90° bend is used, this reduces the maximum flue length by 1.3 m. Each 45° bend used reduces the maximum
flue length by 0.9 m.
2. Under no circumstances must the flue length (including allowances for extra bends) exceed 12 metres horizontally and
only 15 metres vertically.
3. Failure to use Alpha CD flue components with the boiler will invalidate the boilers CE approval, guarantee and may be
unsafe.
4. Further Plume management flue accessories are available - Refer to the Easy-Flue installation instructions.
Alpha CD13R, 18R, 24R - General Boiler Information
6
HORIZONTAL FLUE OPTIONS - Lmax = 12 metres
L = B + C + 200 mm
C
B
B
F
E
L = B + E + F + 200 mm + (90° bend = 1.3 metre)
L = B + C + E + 200 mm
C
B
E
C
B
VERTICAL FLUE OPTIONS
Not less than
300 mm
H
L = B + C + 200 mm + (2 x 45° bends = 1.8 metre)
Not less than
300 mm
Not less than
300 mm
Not less than
300 mm
H
Hmax=15m
Hmax = 13.2 m
Fig. 3
Alpha CD13R, 18R, 24R - General Boiler Information
7
3.5FLUE TERMINAL LOCATION - Fig. 4
Fig. 4
Notes: 1.In addition, the terminal should not be nearer
Min. distance (mm)Terminal position
A Directly below an opening, air brick, windows, etc.
B Below gutters, soil pipes or drain pipes
C Below eaves
D Below balconies
E From a vertical drain pipe or soil pipe
F From an internal or external corner
G Above ground, roof or balcony level
H From a surface facing the terminal
IFrom a terminal facing the terminal
JAbove an opening, air brick, window etc.
K Vertically from a terminal on the same wall
L Horizontally from a terminal on the same wall
M Horizontally from an opening, air brick, window etc.
300 (See Note 1)
75 (See Note 3)
200 (See Note 3)
200 (See Note 3)
150 (See Note 3)
300 (See Note 2)
300
600 (See Note 4 & 5)
1200 mm
300 (See Note 1)
1500 mm
300 mm
300 mm (See Note 1)
Note: A terminal must not be sited under a car port roof
Note: In certain weather conditions the terminal will emit a plume of steam. If possible avoid positioning the terminal where this may cause
a nuisance, i.e. positions A, D, G, H, J or M.
The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times.
If the terminal is fitted within 850 mm of a plastic or painted gutter or 450 mm of painted eaves, an aluminium shield at least 1 m
long should be fitted to the underside of the gutter or painted surface. A terminal must not be sited below 2 m where people
have access to, such as public footpaths, access routes, patios etc. However, If the terminal is fitted less than 2 m above a
surface where there is no public access, the terminal must be protected by a terminal guard.
A suitable guard is available from Alpha Therm Ltd.
For further information refer to BS 5440 Pt1:2008.
than 150 mm to the framework of an
opening into the buiding, i.e. a window
surround or door surround.
2.This clearance may be reduced to 25 mm
without effecting the performance of the
boiler. However, to ensure the condensate
plume does not affect adjacent surfaces a
clearance of 300 mm is preferable.
3.These clearances may be reduced to 25 mm
without effecting the performance of the
boiler. However, to ensure the condensate
plume does not affect adjacent surfaces the
terminal should be extended beyond gutters,
pipes, eaves, balconies etc.
4.It is recommended the terminal should not
be less than 2000 mm from boundary walls,
fences etc. if the plume is likely to cause a
nuisance.
5.This distance may be reduced to 300 mm if
terminal is not facing the boundary.
3.6BOILER LOCATION
The boiler is not suitable for external installation, unless it is installed within a purpose designed weatherproof building.
The boiler must be installed on a flat vertical wall which is capable of supporting the weight of the boiler. The boiler can be fitted
to or adjacent to a wall comprising of a combustible material without the need for a special thermal insulation barrier.
If the boiler is to be fitted in a timber framed building, it should be fitted in accordance with the Institute of Gas Engineers 'Guide
for Gas Installations in Timber Frame Housing', reference IGE/UP/7.
The boiler may be installed in any room or internal space, although particular attention is drawn to the requirements of the
current IEE Wiring (BS7671) Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in
Scotland, with respect to the installation of the boiler in a room or internal space containing a bath or shower. Where a roomsealed boiler is installed in a room containing a bath or shower, it must not be possible for a person using the bath or shower
to touch any electrical switch or boiler control utilising mains electricity.
The boiler may be installed in a cupboard or compartment, provided it is correctly designed for that purpose, i.e. complies with
the Building Regulations and the requirements of BS 6798.
Alpha CD13R, 18R, 24R - General Boiler Information
8
3.7CENTRAL HEATING SYSTEM - Fig. 5 and 5a
The boiler is designed for use in an open or (if the alpha sealed system kit is used) sealed central heating system in accordance
with the requirements of BS 5449 and BS 6798.
Vent (22mmmin)
Cold feed
(15mmmin)
150mmmax
Pump
Boiler
Mid position3-port valve
Automatic
by-pass valve
Fig. 5 - Open system with Y-Plan
Make-up
vessel
Manual air vents
450mmminheight
Feed and
expansiontank
1000mmminheight
DHW storage
cylinder
Balancing
valve
Above highest
pointof system
Double
Pump
Boiler
Mid position3-port valve
Automatic
by-pass valve
check valve
Pressure
gauge
Expansion
vessel
Balancing
valve
Filling point
Discharge
pipe
DHW storage
cylinder
Fig. 5a - Sealed system with Y-Plan
3.8FILLING THE OPEN VENTED CENTRAL HEATING SYSTEM
A minimum head of 1 m is required between the boiler/pump and the feed and expansion tank.
The boiler must be supplied from an unrestricted water supply taken from a feed and expansion cistern situated at a maximum
height of 27 m above the boiler.
The cold feed must be 15 mm minimum size. The vent should be 22 mm in size, rise continuously and be unrestricted.
It is important that the relative positions of the pump, cold feed and open vents are as shown in Fig. 5.
The domestict hot water cylinder must be of the fully indirect coil type.
Alpha CD13R, 18R, 24R - General Boiler Information
9
3.9FILLING THE SEALED CENTRAL HEATING SYSTEM - Figs. 6, 7
The system design pressure (cold) should be set to 1.0 bar. This pressure is equivalent to a static head (see Fig. 5) of 10.2 metres of water.
Provision should be made to replace water lost from the system. This can be by manual or automatic means, as shown in Figs.
6 and 7. The position for connecting an automatic make-up vessel is indicated in Fig. 5a. A double check valve assembly must
be used, as shown in Fig. 7.
Filling of the system must be carried out in a manner approved by the local Water Undertaking. Where allowed, the system
may be filled via a temporary connection as shown in Fig. 6. After filling, always disconnect the flexible hose of the filling loop.
All fittings used in the system must be able to withstand pressures up to 3 bar.
Drain taps (to BS 2879) must be used to allow the system to be completely drained.
Mains
water
supply
Feed cistern to be
located above highest
point in the system
Heating circuit
return
Stop
valve
temporarily connected
Hose
unions
Filling loop
Double check
valve assembly
Test cock
Stop
valve
Mains
water
supply
Heating circuit
return
Double check
valve assembly
Test cock
Overflow
Stop
valve
Fig. 6Fig. 7
3.10 FLUSHING THE HEATING SYSTEM
It is essential that the central heating system is thoroughly cleaned and flushed when fitting an Alpha CD boiler. Failure to do so
will invalidate the warranty.
The primary and condensing heat exchanger is constructed in stainless steel and therefore is compatible with most materials
used in a heating system.
If a cleaning agent and inhibitor are used, they must be applied in accordance with their manufacturers instructions. Only
products from Fernox and Sentinel are acceptable for use with the Alpha CD boilers. Further information can be obtained from
Fernox (Tel: 0179 9521133) or Sentinel (Tel: 0151 4209563).
The system should be flushed in accordance with BS 7593 and BS 5449. The following procedures are recommended:
1.Installing onto a new system:a.Fill the system, vent at high points, at pump and radiators.
b.Check for leaks.
c.Rapidly drain the system.
d.If required, chemically clean the system as instructed by the recommended cleaner manufacturer.
Note: Ensure that the system is flushed to remove any remains of the cleaner.
e.If chemical cleaner is not used to clean the system:-
i)Refill the system.
ii)Switch on the boiler and allow the system to heat up to the normal operating temperature.
iii)Rapidly drain the system while the water is still hot.
iv)Refill the system.
f. As required, add the recommended inhibitor to the system as instructed by the inhibitor manufacturer.
g.Recheck for leaks.
2.Installing onto an existing system, clean the system before fitting the new boiler:a.If the old boiler is still working:-
i)Switch on the boiler and allow the system to heat up to the normal operating temperature.
ii)Rapidly drain the system while the water is still hot.
iii)Refill and chemically clean the system as instructed by the recommended cleaner manufacturer.
iv)Ensure the system is flushed to remove any remains of the cleaner.
v)Fit the new boiler.
b.If the old boiler is not working:-
i)Rapidly drain the system.
ii)Remove the old boiler.
iii)Flush the system through.
iv)Fit the new boiler.
v)Refill and chemically clean the system as instructed by the recommended cleaner manufacturer.
vi)Ensure the system is flushed to remove any remains of the cleaner.
c.As required, add the recommended inhibitor to the system as instructed by the inhibitor manufacturer.
d.Check for leaks.
Alpha CD13R, 18R, 24R - General Boiler Information
10
3.11 DISPOSAL OF CONDENSATE
Provision must be made for the safe disposal of condensate produced by the flue gases of the Alpha CD boilers and reference
should be made to BS 6798: 2000 for the requirements on the disposal of condensate.
The boilers incorporate a condensate trap which has a seal of 75 mm, therefore no additional trap is required.
The condensate should ideally be discharged internally into an internal waste pipe (washing machine/sink waste) or soil pipe to
avoid the possible risk of freezing. The pipework must be in 22 mm pipe.
External pipe runs should be avoided, but if it is necessary, the pipework should be protected from the risk of freezing with
waterproof insulation and the length should be kept to a maximum of 3 m. Alternatively the condensate pipework could be
increased to a minimum of 32 mm diameter without the requirement to insulate the pipework. Termination should be into an
external gulley or soakaway as shown in Figs. 8 and 9.
Note: All pipework must have a continuous fall (see Figs. 8 and 9) from the boiler and must be of an acid resistant material
such as plastic waste pipe. (copper or steel is not suitable).
It should be noted that the connection of a condensate pipe to a drain may be subject to local building control requirements.
Use waterproof
pipework insulation
Plastic pipe
in very exposed
positions
Ensure pipe isadequately supported
Minimum gradient 2½°
Fig. 8 - External gully
Open end of pipe
divertedinto gully
below grid butabovewater level
Fig. 9 - External soakaway
Alpha CD13R, 18R, 24R - General Boiler Information
11
4INST ALLATION
Bottom
fixing holes
Template
Outline of
boiler
Ensure line is levelRear exit hole
110 mm dia.
Position of
110 mm hole
to be cut for
side exit flue
160 mm CD13R/CD18R
130 mm CD24R
=
=
Wall
mounting
bracket
fixing holes
135 mm
4.1UNPACKING
1.The boxes required when the boiler is installed with a horizontal flue are as follows:Box 1Cased boiler fitted with gas isolation valve, gas union and washers
Mounting bracket plus screws and wall plugs, 15 mm gas union bend
Literature pack and Wall template
Box 2CD Easy-Flue 500 mm or CD Easy-Flue 1000 mm. Both include 90° bend and horizontal flue terminal
Note: NOT required for vertical flue
Notes: a. All flues must be suitable for CD condensing boilers.
b. CD 750 mm and 1000 mm flue extensions are available, if required.
2.Unpack boiler and remove the loose items packs and mounting bracket.
Note: To prevent any damage being caused, ensure the gas union bend is removed before standing the boiler in an
upright position.
4.2CLEARANCES REQUIRED - Fig. 10
Fig. 10
4.3PREPARE THE WALL - Figs. 11, 12
1.Decide upon the position of the boiler taking
into account the clearances required for
servicing and the flue terminal position.
2.Tape the template to the wall (ensure it is
level and the right way up) and mark the
position of the holes for the boiler mounting
bracket and bottom fixings. If rear exit flue is
used, mark the position of the hole for the
flue.
3.Side exit flue - Continue the horizontal centre
line of the flue across the wall to the side wall,
then along the side wall 160 mm for the CD13R
and CD18R or 130 mm for the CD24R (ensure
the lines are horizontal). This will give the position
of the centre of the hole for the flue.
4.Cut the 110 mm diameter hole (or use a 107
mm core drill) in the wall for the flue.
Notes: a. Ensure the hole is horizontal.
5.Drill the fixing holes (10 mm dia.) to accept the No.10 plugs supplied. Using the screws supplied, fit the mounting bracket.
b. For internal fitting of the flue, using
the flue sealing collar supplied, cut a
130 mm dia. flue hole using a 127 mm core drill.
Fig. 11
Alpha CD13R, 18R, 24R - Installation
12
4.4FIT THE BOILER - Refer to Fig. 11
1.Lift the boiler and locate it on the mounting bracket. Fit the bottom screws to secure the boiler in position.
CH flow
CH return
Boiler locating
bracket
Pour water into flue duct
Rear view of boiler
Fig. 12
4.5CONNECT THE PIPEWORK - Fig. 13
1.Thoroughly flush out all the water pipework. Refer to Section 3.9.
2.The gas isolation valve has been factory fitted, however, check that the connections underneath the boiler have been
tightened.
Note: When soldering to the boiler union bend, ensure the bend is not connected to the valve, otherwise the internal seals
may be damaged.
3.Connect the system pipework to the boiler.
Note: Ensure the flow and return pipes are correctly connected to the boiler. Refer to Fig. 12.
4.Connect the 22 mm condensate trap drain pipe to the condensate discharge pipe.
Ensure that the condensate discharge pipe is as required in Section 3.11.
Pour at least 0.5 litre of water into the flue duct, as shown in Fig. 12, and check the condensate discharge pipe for soundness.
5.Ensure that the gas isolation valve is closed (spindle flats at right angles to valve) and do not turn on the gas supply at this stage.
A - Gas valve
B - Gas isolating valve
C - Condensate trap
B
A
C
85
20
235
10550
Fig. 13
Alpha CD13R, 18R, 24R - Installation
13
4.6FIT THE FLUE - Figs. 14, 15
The following procedure applies to fitting an Alpha CD Easy-Flue to both rear or side exit flue - horizontally only.
1.The CD Easy-Flues are suitable for use in the flue length ranges shown in the tables below.
Note: Where the length is less than the minimum or more than the maximum, refer to Section 4.7.
(B+C)
(B)
Rear Flue
SideFlue
Fig. 14
B (mm)
MaxMin
13R/18R
13R/18R
500 mm
1000 mm
2.Determine the overall length (L) of flue required, (see Fig. 16) as follows:-
Rear flueL = wall thickness (B) + 90 mm for CD13/18R or 60 mm for CD24R
Side flueL = wall thickness (B) + distance between boiler and wall (C) + 120 mm
515
960
24R
545
990
325
750
24R
355
780
CD Easy-Flue
Fig. 15
500 mm
1000 mm
B + C (mm)CD Easy-Flue
Max
475
920
Min
285
710
Fig. 16
3.Adjust the telescopic section of the flue to the distance 'L', ensuring that the two labels marked 'TOP' are aligned, then seal
and secure the joint between the ducts with the sealing tape supplied.
4.Pass the flue assembly through the wall (from inside or outside).
Note: Internal fitting - If there is no access to make good the outside wall, locate the flue sealing collar onto the outer duct
of the flue immediately before the terminal grille onto the location provided. Push the flue assembly through the 130 mm flue
hole, so that the collar completely passes through the wall. Then pull the flue assembly back into the correct position. Visually
check that the collar is sealing the outside wall and that it is not restricting any of the openings of the flue terminal.
Fig. 17 - Fitting the flue from inside
5.Position the seal and clamp (two screws) supplied, over the bend. Fit the bend to the boiler and rotate to the correct position.
Secure in position using the seal and clamp, ensuring the seal is located centrally over both the bend and boiler adaptor.
6.Fit the inside flue sealing collar over the Easy-Flue. Fit the outside flue sealing collar onto the flue immediately before the
terminal grille onto the location provided.
Alpha CD13R, 18R, 24R - Installation
14
f.Slide the clamp (three screws) over the outer duct and pull the flue assembly towards the bend, locating the inner duct into
the seal joint on the bend. Ensure the labels marked 'TOP' are positioned at the top before securing the flue assembly to
the bend with the clamp (three screws) located centrally over the joint.
Note: Check the flue terminal protrudes 90 mm out of the wall and the inner duct of the terminal is positioned correctly
(see Fig. 18).
g.Make good the inside wall by pushing the inside flue sealing collar up to the wall.
Ensure the inner duct within
the terminal is at the top.
Note:
The inner ductmust
be positioned toslopetowardsthe boiler
Inner ductseal joint
90
Terminal
Fluesealing collar
Note: Ensuretheouter flue duct ishorizontal
CD Easy-Flue
CD13R/18R
CD24R
CD13R/18R
CD24R
65 mm
35 mm
Outer duct clamp
Inner ductseal joint
90° bend
Boiler side
160mm
130mm
Fig. 18 - Rear flue
4.7EXTENDING THE FLUE - Fig. 19
Note: The maximum horizontal flue assembly length must not exceed a length of 12 metres.
1.When the flue length required is more than the maximum or less than the minimum stated in Section 4.6, paragraph 1,
refer to the table below.
Flue Length
CD13R/18R Up to:-
CD24RUp to:-
CD13R/18R Between:CD24RBetween:-
CD13R/18R Between:CD24RBetween:-
Rear Flue (B)
11.93 m max
11.96 m max
740 mm and 945 mm
770 mm and 975 mm
95 mm and 685 mm
125 mm and 715 mm
Side Flue (B + C)
11.89 m max
11.89 m max
700 mm and 905 mm
700 mm and 905 mm
55 mm and 645 mm
55 mm and 645 mm
Comments
Alpha CD 750 mm or 1000 mm flue extension
(Part No. 6.2000750 or 6.2001050) is required to
extend the range of telescopic flue.
Refer to Section 4.7 paragraph 2 for instructions
on how to extend the flue.
Note: A 130 mm flue hole (127 mm core drill) is
required in the wall.
Within the standard Easy-Flue 1000 mm
(Part No. 6.2001010) telescopic range.
Discard the first telescopic section of the Easy-Flue
1000 mm (i.e. not with terminal) and cut to the required
length
CD13R/18R Between:CD24RBetween:-
CD13R/18R Between:CD24RBetween:-
Less than above
300 mm and 505 mm
330 mm and 535 mm
95 mm and 245 mm
125 mm and 275 mm
260 mm and 465 mm
260 mm and 465 mm
55 mm and 205 mm
55 mm and 205 mm
Within standard Easy-Flue 500 mm
(Part No. 6.2000510) telescopic range.
Discard the first telescopic section of the Easy-Flue 500
mm (i.e. not with terminal) and cut to the required length.
Terminal may protrude somewhat from the outside wall.
2.Use the template (supplied with the boiler) to mark the required flue position and cut a 130 mm diameter hole for the flue
(use a 127 mm core drill). The size of the hole provides sufficient clearance for the clamps on the flue extension to pass
through the hole.
Alpha CD13R, 18R, 24R - Installation
15
3.Determine the overall flue length as described in Section 4.6, paragraph 2 to determine the number of Alpha CD 750/1000
mm flue extensions required.
4.Assemble the flue extensions together by locating the inner duct into the seal joint and secure each extension together
with the clamps supplied (three screws). Ensure that the clamps are positioned centrally over the joints.
Note: If it is required to cut an extension, DO NOT cut the end of the inner duct that incorporates the seal joint. Ensure the
inner duct end without the seal joint is cut so that it is 15 mm longer than the outer duct.
5.Adjust the telescopic section of the Easy-Flue to the required length and secure the Easy-Flue with the sealing tape
supplied. Fit the Easy-Flue to the extensions by locating the inner duct into the seal joint and secure with the clamp (three
screws), ensuring it is located centrally over the joint.
6.Mark the end of the flue assembly 'TOP' where it is connected to the boiler,so that the 'TOP' of the flue terminal is aligned
with the 'TOP' at the boiler end of the flue assembly.
7.Pass the complete flue assembly through the wall.
8.Position the seal and clamp (two screws) supplied, over the bend. Fit the bend to the boiler and rotate to the correct position
and secure in position using the seal and clamp, ensuring that the seal is positioned centrally over both the bend and adaptor.
9.Slide the clamp (three screws) over the outer duct and pull the flue assembly towards the bend, locating the inner duct into
the seal joint on the bend.
10. Secure the flue assembly to the bend with the clamp (three screws) ensuring it is positioned centrally over the joint,
ensuring the 'TOP' marked on the outer duct is positioned at the top.
Note: Check the flue terminal protrudes 100 mm out of the wall and that the inner duct of the terminal is positioned
correctly, i.e. the inner duct within the terminal is at the top. See Fig. 19.
11. Make good the outside wall by fitting a flue sealing collar onto the location provided immediately behind the flue terminal
grille. Make good the inside wall as required.
Note: If flue sealing collars are being used to make good the inside wall, then they will need to be fitted before assembling
the flue.
Ensure the inner duct within
the terminal is at the top.
Note:
The inner ductmust
be positioned toslopetowardsthe boiler
90
Flueterminal
Fluesealing
collar
CD Easy-Flue
Inner seal joint
Note: Ensurethe flueextensionslopes
downwardstowardsthe boiler by aminimumof 25 - 30mm per metre
Flue length (L)
Fig. 19 - Side flue
Outer duct clamp
Inner seal joint
CD Flueextension
100mm
90° bend
Clamp
and seal
Seal joint
45
Boiler front
195 mm
Alpha CD13R, 18R, 24R - Installation
16
4.8CONNECT THE MAINS SUPPLY - Fig. 20
1.Gain access to the boiler terminal block by removing one
screw at the top centre of the front panel, then lift up and
Terminal block cover
remove panel. Release the two fixing screws (one each
side) securing the control panel. Lower the control panel.
Refer to Technical Data, Section 2.9 for connection details.
Fuse
2.Note: This boiler has been fitted with a mains supply cable.
However, if it is necessary to fit an alternative supply cable,
ensure the cable clamp that has been fitted is removed and
connect as follows:Remove the two screws securing the terminal block cover
from the back of the control box (see Fig. 20). Pass the
mains supply cable through the grommet and cable clamp
and connect as follows:- Brown to L, Blue to N and Green/
Yellow to
. Ensure correct polarity.
Note: Ensure that the length of the earth wire is such
that if the supply cable is pulled out of its clamp the live
and neutral wires become taut before the earth wire.
The main terminal block can be removed by pulling it off
the pins to give easy access to the terminals.
Do not switch on the electrical supply at this stage.
Remove link to
connect external
controls. See
Wiring diagram
Fig. 20
3.If an external control, i.e. room thermostat or external clock is to be fitted, remove the terminal block cover and remove the
link between terminals 1 and 2. Pass the cable through the cable clamp and connect it to terminals 1 and 2. Connect the
external pump cable to the boiler terminal block by passing the cable through the cable clamp and connecting it to L, N
and
terminals for the external pump. Replace the terminal block cover. (Refer to Section 2.9).
Note: Ensure the pump is always connected to the boiler terminal block.
4.Replace the terminal block, ensuring it is located correctly on the plastic pins and replace the cover.
5.Ensure that there is sufficient free cable to allow the control panel to be raised and lowered then tighten the cable clamp screws.
6.Leave the control panel open until commissioning procedures have been completed.
7.Carry out electrical system checks - Short circuit, Polarity, Earth continuity and Resistance to earth with a suitable multimeter.
Grommets
Cable clamps
Connect external
pump. See wiring
diagram.
Note: The pump
must always be
connected to this
terminal block.
4.9FIT THE CLOCK KIT - Fig. 21
Ensure the electrical supply to the boiler is isolated.
Note: Only use an Alpha two channel clock. Do not fit a single channel clock.
1.Remove the two screws securing the clock cover at the rear of the control panel.
2.Remove and discard the clock blanking panel.
3.Insert the clock into the opening and secure in place with the screws supplied - do not overtighten the screws..
4.Disconnect the clock wiring from the terminal block and connect it to the clock as follows:Brown wire to terminal 1, Blue wire to terminal 2, Black wire to terminal 3, Grey wire to terminal 4 and White wire to terminal
5, (or as per the instructions supplied with the clock). Ensure wiring is correct.
Note: Before the clock is fitted, remove the link between terminals 1 and 3 on the clock wiring harness fitted to the boiler.
5.Replace the clock cover. Do not overtighten the fixing screws.
6.Leave the control panel open until commissioning procedures have been completed.
Rear of control panel
Clock cover
Fig. 21
Alpha CD13R, 18R, 24R - Installation
17
5COMMISSIONING
When commissioning the boiler, ensure the Benchmark Checklist is completed.
5.1FILL THE SYSTEM
1.To remove the air - Vent each radiator in turn, starting with the lowest in the system.
2.It is important that the external pump is properly vented to avoid it running dry and damaging its bearings. Unscrew and remove
the cap from the centre of the pump. Using a suitable screwdriver rotate the exposed spindle about half a turn, then replace
the cap.
3.Refer to Sections 3.8, 3.9 and 3.10 for filling and flushing the system.
4.Ensure that the condensate trap has been filled with water. Refer to Section 4.5, paragraph 4.
5.2BOILER CONTROLS - Fig. 22
Selector Switch
Indicator
Neons
Frost
Thermostat position
OFF
FROST
0
A
B
C
D
1
ON
2
RESET
3
SELECTORTHERMOSTAT
9
8
7
Central
HeatingThermostat
1
2
3
4
5
6
CD18R
Fig. 22
5.3TEST FOR GAS SOUNDNESS AND PURGE THE SUPPLY
1.With the boiler gas service cock closed (slot at right angles to valve). Pressure test the gas supply and inlet pipework
connection to the boiler gas service cock for soundness in accordance with BS 6891.
2.Loosen the gas inlet pressure test point screw on the gas valve (see Fig. 24). Ensure the gas supply is on and open the
boiler service cock to purge in accordance with BS 6891.
3.Retighten the test point screw and test for gas soundness. Close the boiler gas service cock.
5.4INITIAL LIGHTING - Refer to Fig. 22
1.Ensure that the gas and electrical supplies to the boiler are off.
2.Turn on the gas and electrical supplies to the boiler.
3.Ensure all external controls are calling for heat.
If the optional Clock is fitted, set the time and ensure the Clock is in an 'on' mode.
4.Set the central heating thermostat to maximum.
5.Set the selector switch to 'ON'. The boiler will now run. The external pump will start, the fan will start and the main gas
valve solenoid will open allowing the main burner to light.
5.5CHECK THE BURNER PRESSURES - Figs. 23, 24
Turn the boiler off. Remove the two pressure test point screws at the top of the boiler and connect a differential pressure gauge
to P1 and P2 as shown in Fig 23. Allow the boiler to run for 10 minutes and check the differential burner pressures.
1.Set the selector switch to 'ON'.
2.The burner will light at the ignition rate and will increase to the factory pre-set maximum output after approximately 4 minutes.
Alpha CD13R, 18R, 24R - Commissioning
18
3.Turn off the boiler. Disconnect the pressure gauge and tighten the test point screws. Test for gas soundness using
suitable leak detection fluid.
Note: The burner pressure settings have been factory set and do not require adjusting. If incorrect, check that the
inlet gas pressure is 20 mbar.
If the inlet gas pressure is not 20 mbar, either the pipework is too small or the gas supply to the house is insufficient, in
which case contact your gas supplier. If the differential burner pressures are still incorrect contact Alpha.
Note: Refer to Technical Data, Section 2.1 for the required differential burner pressures.
Differential
Burner
pressure
Fig. 24Fig. 23
5.6FINAL COMMISSIONING
1.Allow the heating system to heat up, then balance the system to achieve the necessary temperature difference across the
heating flow and return pipes at the boiler.
2.Turn off the boiler.
5.7FINAL ASSEMBLY
1.Raise the control panel and secure in position with the screws provided, locate the front casing panel in position and
secure with the screw at the top of the panel.
2.If the boiler is to be left in service with the User, set the controls, clock (if fitted, see Clock User's Operating manual) and
room thermostat (if fitted) to the User's requirements.
3.If the boiler is not to be handed over immediately, close the boiler gas service cock and switch off the electrical supply.
4.If there is any possibility of the boiler being left during frost conditions, then the boiler and system should be drained (refer to Section
8.2). It is recommended that a label is attached to the boiler drawing attention to the fact that the system has been drained.
5.Complete the details of the installation in the Benchmark Checklist on page 33.
5.8USER INFORMATION
The User must be advised (and demonstrated if necessary) of the following important points:-
1.How to light and turn off the boiler and how to operate the system controls.
2.The importance of annual servicing of the boiler to ensure safe and efficient operation.
3.That any servicing or replacement of parts must only be carried out by CORGI registered personnel.
4.Ensure that the boiler controls and room thermostat (if fitted) are set to the User's requirements.
5.Tell the User that if the electrical supply is on and the boiler has not operated for 24 hours for heating, the pump will
automatically operate for 5 minutes.
6.Explain to the User that an internal frost thermostat is fitted in the boiler, and that the electrical supply to the boiler must be
left on for the thermostat to operate.
7.Explain to the User that in certain weather conditions the terminal will emit a plume of steam, i.e. water vapour. This is safe
and quite normal.
8.Show the User the position of the condensate discharge pipe.
9.Hand the User's instructions to the User.
10. Ensure the Benchmark Checklist in Section 12, page 34, has been completed after the boiler has been installed and
commissioned.
11. Leave these Installation and Servicing instructions with the User for use on future calls.
Alpha CD13R, 18R, 24R - Commissioning
19
6BOILER OPERATION
6.1CENTRAL HEATING MODE
The operating sequence of the boiler is controlled by the selector switch on the control panel.
Setting the selector switch to position (2) the boiler will operate to provide central heating.
When the selector is set to central heating, it will respond to a demand for heat in the following sequence:a. The external pump will start, the fan will operate and the main burner will light.
b. The output of the burner is automatically controlled to suit the system demand.
c. When the temperature of the system water in the boiler reaches that set by the thermostat or the room thermostat is
satisfied, the main burner is turned off and the fan stops after 50 seconds. The pump will continue to run to remove any
residual heat from the boiler.
6.3FROST THERMOSTAT
The boiler incorporates a built in frost thermostat which automatically turns on the boiler and pump if the water in the boiler falls
below 8°C, providing the electrical supply is on and the selector switch is set to position (1) or position (2). The boiler will
operate until the water temperature in the system reaches approximately 40°C.
6.4PUMP
If the electrical supply is on and the boiler has not operated for 24 hours for heating or hot water, the external pump will operate
automatically for five minutes every 24 hours.
6.5INDICATOR NEONS
When neons A (red), B (red), C (yellow), D (green) are illuminated, the following conditions apply:-
Neon
DIlluminated continuously - Electricity supply to the boiler is on.
CIlluminated continuously - Burner is alight.
AFlashing on and off - Temperature sensor fault.
BFlashing on and off - Overheat thermostat has operated. Rotate selector switch to the reset position (3) to reset.
BIlluminated continuously - Burner has failed to light. Rotate selector switch to the reset position (3) and the ignition
sequence will restart after a delay of about 30 seconds.
A and B Flashing on and off at the same time - Blocked flue or fan fault.
A Flashing and B Illuminated continuously - Pump fault or restricted flow.
A Illuminated continuously and B flashing - PCB or flame sensor fault.
A and B illuminated continuously - No flow or air present
A, B and C flashing on and off at the same time - Temperature sensor wiring or flow and return connections incorrect.
Note: Do not hold the selector switch in the reset position (3) for more than 2 to 3 seconds.
Alpha CD13R, 18R, 24R - Boiler Operation
20
7ROUTINE SERVICING
To ensure efficient operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals.
The frequency of servicing will depend upon the particular installation conditions and usage, but in general once per year
should be adequate.
It is the law that any service work must be carried out by a competent person, i.e. CORGI registered personnel.
Warning: Before servicing the boiler, isolate the electrical supply and close the boiler gas service cock. Allow the boiler to cool.
The data label is positioned on the underneath of the bottom casing.
Always test for gas soundness after servicing any gas carrying components.
Always carry out electrical system checks i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable
meter after servicing.
7.1IMPORTANT NOTES PRIOR TO SERVICING
1.Check the flue terminal outside and ensure it is not blocked.
2.Run the boiler and check the operation of its controls.
3.Refer to Fig. 2 for location of flue sampling point.
4.Ensure that all system connections and fittings are sound. Remake any joints and check the tightness of any fittings that
may be leaking.
5.Check that the condensate trap drain pipe is connected and all joints are sound.
6.Record details of the service in the Service Record Section on back page of this manual and in the Benchmark Log Book.
7.2PREPARE FOR SERVICING - Fig. 25
1.Ensure the electrical supply is isolated and the gas supply is off.
2.Remove the screw at the top centre of the front panel, then lift it up and remove the panel. Release the two screws
securing the control panel and lower the panel.
3.Remove the six screws securing the room sealed chamber panel and remove the panel, taking care not to damage the seal.
4.Disconnect the gas supply pipe union.
5.Remove the two screws securing the fan assembly to the combustion chamber front.
6.Remove the two pressure tubes, noting their positions.
7.Disconnect the electrode lead from the ignition generator and the in-line connector to the flame sensing electrode.
8.Remove the six nuts and washers securing the combustion chamber front assembly and remove the assembly.
Room sealed panel
fixing screws
Combustion
chamber front
assembly
Gas pipe
union
Viewing
window
Fan
assembly
Fan assembly
fixing screws
Fig. 25
Drain valve
Six nuts and washers
securing combustion
chamber front
assembly
Ignition generator
Pressure tube
connections
Condensate trap
Alpha CD13R, 18R, 24R - Routine Servicing
21
7.3CLEANING THE BOILER
1.Remove any deposits from heat exchanger using a
suitable soft brush. Do not use a brush with metallic
bristles.
2.Check the condition of the combustion chamber
Gap3-4mm
insulation panels. Any damaged panels must be
replaced. (Refer to Component Replacement,
Section 8.17).
Combustion chamber
front assembly
3.Check the condition of the burner injector on the
combustion chamber front assembly, carefully clean
it with a soft brush if necessary.
Do not use a brush with metallic bristles as this might
damage the injector.
4.Remove any deposits from the heat exchanger coils.
Ignition electrodes
This can be done by suction or water sprayed onto
the coils. Ensure all electrical components are
protected from water. Any water used to clean the
heat exchanger will drain to the condensate trap.
5.Unscrew and replace the injector if it appears
damaged.
6.Remove the four screws securing the burner (see
Fig. 26) and remove the burner. Clean the burner with a soft brush and check that the flame ports are clear. Blockages
may be removed with a stiffer brush. Tap the burner, open end down, to remove any deposits from inside.
7.Check the condition of the electrodes.
9.Check the spark gap, positioning and height of the electrodes. See Fig. 26.
10. Unscrew the condensate trap drain cap, clean and remove any deposits from the trap.
Note: Before removing the cap, ensure that the water released from the trap can be contained to avoid spillage.
The trap will contain no more than 200 cc of condensate water. Replace the drain cap.
Burner
Gap 11 mm
Front insulation
panel
Fig. 26
Flame sensing
electrode
7.4RE-ASSEMBLE THE BOILER
1.Replace the burner, ensuring it is located correctly and secure it in position using the four screws previously removed.
Important: Before replacing the combustion chamber front assembly, pour at least 200 cc of water into the coils of the
heat exchanger. This is to ensure the condensate trap is full of water before operating the boiler.
2.Replace the combustion chamber front assembly, ensuring it is correctly located.
3.Ensure the electrode lead is connected and the seal is in position in the bottom of the room sealed chamber.
4.Test the connections for gas soundness and re-commission, Sections 5.4 and 5.5.
5.Ensure that the room sealed chamber panel seal is intact and in position, replace the panel ensuring it has been located
correctly and secure it in position with the screws previously removed.
6.Raise the control panel and secure in position with the two screws provided.
7.Replace the front case panel and secure in position.
8.Check the operation of the boiler. (Refer to Boiler Operation, Section 6).
9.Return all controls to their original settings.
Alpha CD13R, 18R, 24R - Routine Servicing
22
8COMPONENT REPLACEMENT
It is the law that any service work must be carried out by a competent person, i.e. CORGI registered personnel.
Warning: Before replacing any boiler components, isolate the electrical supply and close the boiler gas service cock. Allow the
boiler to cool.
Always test for gas soundness after replacing any gas carrying components or disturbing any gas connections.
Always carry out electrical system checks i.e. Eart Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable
meter after servicing.
Check the operation of the boiler. (Refer to Boiler Operation, Section 6).
Ensure that all the controls are returned to their original settings.
The replacement of components in Sections 8.3 to 8.15 does not require draining of the boiler.
8.1GENERAL ACCESS - Fig. 25
Isolate the electrical supply and close the boiler gas cock (see Fig. 13).
1.If access is required behind the control panel - Release the fixing screw located at the top of the case front panel and lift
the panel upwards from its locating pins and then forwards from the boiler. Remove the two fixing screws that secure the control
panel and lower the panel.
2.To gain access to the control panel components - Remove the five screws securing the rear cover and carefully raise
the cover from the control panel. When replacing the cover, ensure no wires are trapped and all wiring is secured. Secure
with screws previously removed - do not overtighten.
3.To gain access behind the room sealed chamber panel - Remove the six screws securing the room sealed chamber
panel and remove the panel, taking care not to damage the seal.
Note: When replacing the panel, ensure the seal is intact and that the panel has been located correctly.
8.2DRAINING THE BOILER - Refer to Figs. 2 or 25
1.Isolate the electricity supply and close the boiler gas service cock (see Fig. 13). Allow the boiler to cool.
2.Gain access as described in Section 8.1. Connect a hose to the drain valve located in the flow pipe just above the heat
exchanger (see Fig. 25) and route it to a suitable container. Open the drain valve.
Note: Water will remain in the heat exchanger and care must be taken when removing it to prevent any electrical
components from becoming wet.
8.3ELECTRODES - See Fig. 26
Gain access behind the room sealed chamber panel as in Section 8.1.
1.Ignition electrode and lead
Disconnect the lead from the ignition generator, noting its position.
Remove the two screws securing the electrode to the front of the combustion chamber and carefully withdraw the electrode.
2.Flame sensing electrode and lead
Remove the grommet in the bottom of the chamber, disconnect the flame sensing electrode in-line connector and
withdraw the lead.
Remove the two screws securing the electrode to the front of the combustion chamber and carefully withdraw the electrode.
3.Ignition electrode
Remove the two screws securing the electrode to the front of the combustion chamber and carefully withdraw the electrode.
Re-assemble in reverse order
8.4MAIN BURNER - Fig. 26
1.Remove the burner assembly as described in Routine Servicing, Section 7.2.
2.Remove the four screws securing the burner to the combustion chamber front assembly.
3.Re-assemble with a new burner as described in Routine Servicing, Section 7.4.
8.5BURNER INJECTOR - Fig. 25
1.Gain access behind the room sealed chamber panel as described in Section 8.1.
2.Undo the gas inlet pipe union to the combustion chamber front to gain access.
3.Unscrew the damaged injector and screw in a replacement.
4.Re-assemble in reverse order.
8.6FAN - Fig. 27
Alpha CD13R, 18R, 24R - Component Replacement
23
1.Gain access behind the room sealed chamber panel as described in Section 8.1 and remove the combustion chamber
front assembly as described in Section 7.2.
2.Remove the screw securing the air inlet tube and remove.
3.Disconnect the fan wiring and remove the fan.
4.Remove the inlet and outlet flanges from the fan, fit them to the new fan and re-assemble in reverse order.
Ensure that the pressure tubes are connected correctly.
5.Re-assemble and test the boiler as described in Routine Servicing, Section 7.4 paragraphs 5 to 9.
8.7IGNITION GENERATOR - Fig. 27
1.Gain access behind the room sealed chamber panel
as described in Section 8.1.
2.Disconnect all the wiring from the ignition generator.
3.Remove the two screws securing the generator and
remove.
4.Secure the new generator in position and reconnect the wiring.
5.Re-assemble in reverse order.
8.8TRANSFORMER - Fig. 27
1.Gain access behind the room sealed chamber
panel as described in Section 8.1.
2.Remove the screw securing the air inlet tube and
remove.
3.Remove the two screws securing the transformer
and remove the transformer.
4.Disconnect all of the wiring from the transformer
noting their position.
5.Fit the new transformer and re-assemble in
reverse order.
Fig. 27
Overheat thermostat
Flue thermostat
Primary flow and return
temperature sensors
Ignition electrode
Air inlet tube
Flame sensing electrode
Transformer
Fan assembly
Ignition generator
8.9OVERHEAT THERMOSTAT - Fig. 27
1.Gain access behind the room sealed chamber panel as described in Section 8.1.
2.Disconnect the wiring from the overheat thermostat.
3.Unscrew and remove the overheat thermostat from the heat exchanger.
4.Fit the new overheat thermostat taking care not to cross thread it and re-assemble in reverse order.
8.10 FLUE THERMOSTAT - Fig. 27
1.Gain access behind the room sealed chamber panel as described in Section 8.1.
2.Remove the two screws securing the thermostat retaining bracket and remove the thermostat from the top rear of the heat
exchanger.
3.Disconnect the wiring.
4.Fit the new thermostat and re-assemble in reverse order.
8.11 GAS VALVE
1.The gas valve is located at the bottom of the boiler (see Fig. 13).
2.Disconnect the pressure tube from the gas valve.
3.Loosen the screw securing the electrical plug and remove the plug.
4.Disconnect the burner manifold union and the gas pipe union.
5.Remove the support bracket screws from beneath the boiler.
6.Lower the valve downwards and out of its location.
7.Unscrew the support bracket from the faulty valve and fit it to the new valve.
8.Fit the new assembly and re-assemble in reverse order.
9.Carry out a soundness test. Light the boiler and set the gas valve to the settings stated on the instruction sheet provided
with the new valve.
Alpha CD13R, 18R, 24R - Component Replacement
24
8.12 VIEWING WINDOW - Fig. 25
1.Gain access behind the casing as in Section 8.1.
2.Remove the rubber window frame and remove the damaged glass.
3.Re-assemble in reverse order with a new glass. Ensure the rubber frame is located correctly in the front panel.
8.13 TERMINAL BLOCK FUSE - Refer to Fig. 20
The fuse is located in the boiler terminal block.
1.Gain access as described in Installation, Section 4.8.
2.Lift out the fuse holder and remove the fuse. Fit a fast blow 2 A fuse as a replacement, ensuring that the holder snaps into position.
3.Re-assemble in reverse order, ensuring the terminal block is located correctly on the plastic pins.
8.14 PCB - Fig. 28
1.Gain access behind the control panel as described in Section 8.1.
2.Disconnect all the wiring connectors from the PCB.
3.Remove the four fixing screws and carefully withdraw the board from the switch spindles.
4.Re-assemble in reverse order. Refer to the wiring diagram in Section 9.1 for connections.
5.Light the boiler and adjust the PCB as described in the instructions supplied with the replacement PCB.
PCB
PCB Fuse
Fig. 28
8.15 CLOCK (if fitted) - Refer to Fig. 21
Note: For replacement only use an Alpha two channel clock. Do not fit a single channel clock.
1.Gain access behind the control panel as described in Section 8.1.
2.Remove the two screws securing the clock cover at the rear of the control panel.
3.Disconnect the wiring from the clock.
4.Remove the clock retaining screws and withdraw the clock from the control panel.
5.Fit the new clock, and connect the wires as follows:Brown wire to terminal 1, Blue wire to terminal 2, Black wire to terminal 3, Grey wire to terminal 4 and White wire to
terminal 5, (or as per the instructions supplied with the clock).
6.Re-assemble in reverse order. Refer to the User's instructions and the boiler's control cover to set the clock.
8.16 PRIMARY HEAT EXCHANGER - See Fig. 29
1.Gain access behind the room sealed chamber panel as described in Section 8.1 and drain the boiler as described in
Section 8.2.
2.Disconnect the gas inlet union from the combustion chamber manifold.
3.Remove the two screws and six nuts and washers securing the combustion chamber front burner assembly and remove.
4.Remove the overheat thermostat (Section 8.9), flue thermostat (Section 8.10) and unplug the primary temperature sensors
(Section 8.18).
5.Disconnect the condensate drain union.
6.Undo the ¾ " flow and return unions.
7.Remove the four screws securing the heat exchanger retaining brackets and remove the brackets.
8.Slide the heat exchanger forwards from its mounting, being cafeul not to spill any water onto any electrical components
9.Empty the water from the heat exchanger, remove the two temperature sensors and transfer them to the new heat exchanger.
9.Fit the new heat exchanger to the boiler and re-assemble in reverse order,
Refill the system. (Refer to Commissioning, Section 5.1).
Alpha CD13R, 18R, 24R - Component Replacement
25
Back insulation panel
Four screws securing
heat exchanger
Fig. 29
8.17 COMBUSTION CHAMBER INSULATION
Gain access to the combustion chamber as described in Section 8.1.
Front insulation - see Fig. 26
1.Remove the electrodes from the combustion chamber front as described in Section 8.3.
2.Remove the four screws securing the burner.
3.Carefully remove the insulation.
Back insulation - see Fig. 29
1.Remove the combustion chamber front/burner assembly.
2.Remove the centre screw retaining the insulation.
3.Carefully remove the insulation, suction applied to the centre of the insulation will aid this.
Fit a new panel and re-assemble in reverse order.
Refill the system. (Refer to Commissioning, Section 5.1).
8.18 TEMPERATURE SENSORS - Refer to Fig. 27
Note that both sensors are the same.
1.Gain access as described in Section 8.1 and drain as described in Section 8.2.
2.Remove the screw securing the air inlet tube and remove.
3.The primary sensors are positioned on the right hand side of the heat exchanger (see Fig. 27), flow at the front and return
at the rear. Disconnect the wiring and unscrew the sensor using a 13 mm A/F socket spanner, (access to the return
sensor will be improved by removing the right side panel).
4.Re-assemble in reverse order with a new sensor and sealing washer.
Refill the system. (Refer to Commissioning, Section 5.1).
8.19 CONDENSATE TRAP - Fig. 13
1.Gain access behind the room sealed chamber as described in Section 8.1.
2.Disconnect the inlet and drain connection of the condensate trap.
3.Remove the fixing screw and lift the trap from its location.
4.Fill the new trap with water and fit it to the boiler and re-assemble in reverse order.
Alpha CD13R, 18R, 24R - Component Replacement
26
9WIRING DIAGRAMS
9.1ILLUSTRATED WIRING DIAGRAM
(Optional) 2 Channel Clock
5
4
3
2
1
Bl
230/240V-50Hz Fused at 3A
Fuse
F2A
Br
Bl
Bk
Fan
W
Gy
Bk
Br
Supply
Gy
W
External Pump
Link
1 234LNNL
R
Flue Limit
Thermostat
Bl
Br
G/Y
Bl
Overheat
Thermostat
Spark
Generator
Bk
R
W
Or
Bk
Gy
21
Flame
Sensing
Electrode
Br
W
Gy
R
Or
Bk
G/Y
Ignition
Electrodes
W
Br
Bl
Green LED
Yellow LED
Red LED
Red LED
Or
X12
35
H1
40
H4
H3
H2
Pk
PkP
PkGy
24 Vac
Transformer
22
CH SET
X9
X7
45
Or
S10 S3 S2 S1
48
46
47
GG
X16
55
34333
W
Bl
Bk
36
38
37
43
42
41
R
R
Pk
Br
39
X11
315mAT
11
P
FUSE
12
Gy
13
X1
14
X4
Br
Bl
184419
2
29 30 31 32
LN
Main
X6
DHW SET
++
PCB
CH CAP
X10
MAX CAP
+
+
2721
25
Gas Valve
S1 CH set jumper
S2CH timer jumper
S3 DHW temp off
S10 Range fan speed
51
50
X8
49
G
G
26
23
24
Primary Return
Temperature
Sensor
RR
240 Vac
Primary Flow
Temperature
Sensor
Br - Brown
Bk - Black
Bl- Blue
R- Red
Or- Orange
G- Green
G/Y - Green/Yellow
W- White
Gy - Grey
Pk - Pink
P- Purple
NOTE:TO CONNECT EXTERNAL CONTROL
REMOVE LINK FROMTERMINALS 1 & 2
AND CONNECT 230/240 V SWITCHED LIVE TO
TERMINAL1.
AFROST THERMOSTAT I S INCORPORATED
WITHIN THE MAIN PCB
Alpha CD13R, 18R, 24R - Wiring Diagrams
27
9.2FUNCTIONAL FLOW WIRING DIAGRAM
230/240V ~ 50Hz
Fuse 3A
Remove link to connect
external control
External
pump
Fan
LL
1
2
3
4
L
N
FUSE 315 mAT
Fuse
F2A
34333
X1
55
LN
2
X16
29 30 31 32
Optional
2Channel Clock
1
2
3
4
5
Spark
Generator
X7
N
N
N
N
Overheat
Thermostat
Flue Limit
Thermostat
Gas Valve
26
23
24
22
2721
25
Green LED
Yellow LED
Red LED
Red LED
X12
H1
H4
H3
H2
24 Vac
Transformer
11
14
12
13
X4
184419
X6
35
40
39
36
37
38
43
42
41
X11
DHW SET
++
X10
Main
PCB
CH CAP
+
+
MAX CAP
CH SET
X9
S10 S3 S2 S1
45
46
S1 CH set jumper
S2CH timer jumper
S3 DHW temp off
S10 Range fan speed
51
50
48
47
X8
49
Primary Flow
Temperature
Sensor
Primary Return
Temperature
240 Vac
Sensor
Note:
Main Terminal Block
TO CONNECT EXTERNAL CONTROL REMOVE LINK
FROM TERMINALS 1 AND 2 AND CONNECT 230/240 V
SWITCHED LIVE TO TERMINAL 1.
Alpha CD13R, 18R, 24R - Wiring Diagrams
28
10 F AULT FINDING
10.1 CARRY OUT INITIAL FAULT FINDING CHECKS
1.Check that gas, water and electrical supplies are available at the boiler.
i.e. Inlet gas pressure = 20 mbar
Electrical supply = 230/240 V ~ 50 Hz
CH water system pressurised to between 0.75 and 1.25 bar, if installed in a sealed central heating system.
2.Carry out electrical system checks, i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable meter.
Note: These checks must be repeated after any servicing or fault finding.
3.Ensure all external controls are calling for heat and check all external and internal fuses.
4.Check that the gas and water pipework has been connected to the correct connections on the boiler and all valves are open.
However, before any servicing or replacement of parts ensure the gas and electrical supplies are isolated.
10.2 CENTRAL HEATING - Follow operational sequence
Alpha CD13R, 18R, 24R - Fault Finding
29
10.2 FAULT FINDING SOLUTIONS A to E
240 V ac at:-
A
B
Main terminals L and N
1.
Main terminal fuse
2.
PCB - X1 connector, terminals 55, N
3.
PCB fuse
4.
240 V ac at:-
Pump
1.
PCB - X6 connector, terminals 18, 19
2.
NO
YES
NO
NO
NO
Replace fuse
Is 240 V ac across
PCB X4 connector terminals 11,12
Is 26 V ac across
PCB X11 connector terminals 40,41
NO
Check electrical supply
Replace fuse
Check wiring
Neon D illuminated contiuously
NO
YES
NO
If pump jammed, release
Replace PCB
Neon D
illuminated continuously
NO
NO
YES
Replace pump
Replace PCB
Replace PCB
Replace transformer
NO
Replace PCB
C
D
1.
Check and correct connections/wiring at
temperature sensors and PCB
2.
Primary temp. sensor faulty. Cold resistance approx.
12-14 k ohms (resistance reduces with increase in temp.
i.e. when hot, resistance is approximately 3 k ohms)
1.
Check and correct:-
1. Electrical connections
2. Restriction in flue
Neon A and B flashing
at the same time
YES
2.
Fan connections correct at fan and PCB connector X12
PCB connector, is 36 V dc across terminals 39 and 37 or 38
NO
3.
Fan runs at maximum speed
YES
(BUT)
Primary return temperature sensor faulty
i.e. no heating
Check resistance throughout
the range from cold to hot
Primary flow temperature sensor faulty
i.e. no heating
YES
Is dc volts at PCB, X12 connector:across terminals 35 and 37-3to9Vdc
across terminals 36 and 37-3to9Vdc
Ensure the following is completed after the boiler has been installed and commissioned:-
BOILER SERIAL No. ......................................................... NOTIFICATION No. ..........................................................
CONTROLS
Time & temperature control to heating
Time & temperature control to hot water
Heating zone valves
Hot water zone valves
Thermostatic radiator valves
Automatic by-pass to system
FOR ALL BOILERS CONFIRM THE FOLLOWING:
The system has been flushed in accordance with the boiler manufacturer's instructions?YesNo
The system cleaner used ........................................................................................................ ............
The inhibitor used................................................................................................................................
FOR CENTRAL HEATING MODE, MEASURE AND RECORD THE FOLLOWING:
Gas ratem³/hrft³/hr
Burner operating pressure (if applicable)N/Ambar
Central heating flow temperature°C
Central heating return temperature°C
FOR COMBINATION BOILERS ONLY
Has a water scale reducer been fitted?YesNo
What type of scale reducer has been fitted?......................................................................................
To comply with the Building Regulations, each section must have a tick in one or other of the boxes
room t/stat & programmer/timer
cylinder t/stat & programmer/timer
Fitted
Fitted
Fitted
Fitted
Programmable roomstat
Combi boiler
Not required
Not required
Not required
FOR DOMESTIC HOT WATER MODE, MEASURE AND RECORD THE FOLLOWING:
Gas ratem³/hrft³/hr
Maximum burner operating pressure (if applicable)N/Ambar
Cold water inlet temperature°C
Hot water outlet temperature°C
Water flow ratelts/min
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING:
The condensate drain has been installed in accordance with the manufacturer's instructions?Yes
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING:
The heating and hot water system complies with current Building RegulationsYes
The appliance and associated equipment has been installed and commissioned
in accordance with the manufacturer's instructionsYes
If required by the manufacturer, have you recorded a CO/CO
The operation of the appliance and system controls have been demonstrated to the customerYes
The manufacturer's literature has been left with the customerYes
COMMISSIONING ENG'S NAME:
Print...................................................................... CORGI ID No...................................................
ratio readingN/AYesCO/CO2 ratio
2
Sign ...................................................................... Date .................................................................
Alpha CD13R, 18R, 24R - Benchmark Checklist
33
13 SERVICE RECORD
It is recommended that your heating system is serviced regularly and that you complete the appropriate Service Interval Record
below.
Service Provider: Before cpmpleting the appropriate Service Interval Record below, please ensure you have carried out the
service as described in this instruction manual. Always use the manufacturer's specified spare parts when replacing all controls.
SERVICE 1: Date .......................................................................
Engineers Name .........................................................................
Company Name ..........................................................................