Alpha B-5248A Specsheet

Product Specification Sheet A PS963 - Rev. 11/2015
B-5248A Power Supply for Area of Rescue Assistance Systems
42 Central Drive • Farmingdale • NY • 11735-1202 • Phone: (631) 777-5500 • Fax: (631) 777-5599
TOLL-FREE: (800) 666-4800 • Web: AlphaCommunications.com • Email: info@alphacommunications.com
Copyright© 1998-201 5 Alpha Communications® - All Rights Reserved.
Due to co ntinuous pro duct improvement, all colo rs, sizes, materials, finishes and specification s are subject to ch ange without n otice.
B-5248A Power Supply for Area of Rescue Assistance
Systems
The B-5248A Power Supply with Battery Back-Up converts a 115VAC/60 Hz. input t o a 24VDC output, and is UL 1481 Listed for fire alarm, burglar alarm and acc ess control applicat ions. The B-
5248A Power Supply with Battery Back-Up is designed t o be used
with our 4800 series Area of Rescue Assistanc e Systems, to provide system power and emergency back-up power when required.
The B-5248A Power Supply comes complete with power supply, enclosure, c am loc k (and keys), battery leads and two (2) 12VDC batt eries.
Features
UL 1481 Listed, FCC Approved Short Circuit and T hermal Overload Protection Housed in a Locked Steel Housing Provides 24VDC Output - 8 Amps (2) 12VDC Batt eries Included
Specifications
Dimensions:
15.75" H x 11.25" W x 4.50" D (401mm x 286mm x 115mm)
Housing: Baked Enamel finish over Steel
Outputs:
24VDC at 8 amps, continuous supply current (with LED Indicator Diagnostics)
Power:
115VAC/60 Hz. with maximum c harge current of 5.0 amps
Batteries:
Unit is supplied with 2- (12VDC) 7.5 Amp/Hour batteries. T his allows the master stat ion to operate on battery power (in Standby Mode Only) for minimum 24 hours as required in most stat e's c odes.
Connectors: Positive Sc rew Terminals
Mounting: Surface Mount
Temperature Range: 50°F - 120°F (10°C - 49°C) Indoor
Loading...