Alpha 6K, 10K User Manual

Alpha Continuity: 6K / 10K
Indoor Double Conversion Online UPS
User Manual
Effective: 03/2011
member of The Group
Your Power Solutions Partner
Alpha Continuity: 6K / 10K
Indoor Double Conversion Online UPS
NOTE:
Photographs contained in this manual are for illustrative purposes only. These photo­graphs may not match your installation.
NOTE:
Operator is cautioned to review the drawings and illustrations contained in this manual before proceeding. If there are questions regarding the safe operation of this powering system, contact Alpha Technologies or your nearest Alpha representative.
NOTE:
Alpha shall not be held liable for any damage or injury involving its enclosures, power supplies, generators, batteries, or other hardware if used or operated in any manner or subject to any condition inconsistent with its intended purpose, or if installed or oper­ated in an unapproved manner, or improperly maintained.
Copyright
Copyright © 2011 Alpha Technologies Ltd. All rights reserved. Alpha is a registered trademark of Alpha Technologies.
No part of this documentation shall be reproduced, stored in a retrieval system, translated, transcribed, or transmitted in any form or by any means manual, electric, electronic, electromechanical, chemical, opti­cal, or otherwise without prior explicit written permission from Alpha Technologies.
This document, the software it describes, and the information and know-how they contain constitute the proprietary, confidential and valuable trade secret information of Alpha Technologies, and may not be used for any unauthorized purpose, or disclosed to others without the prior written permission of Alpha Technologies.
The material contained in this document is for information only and is subject to change without notice. While reasonable efforts have been made in the preparation of this document to assure its accuracy, Alpha Technologies assumes no liability resulting from errors or omissions in this document, or from the use of the information contained herein. Alpha Technologies reserves the right to make changes in the product design without reservation and without notification to its users.
Canada and USA: 1-888-462-7487
International: +1-604-436-5547
Email: support@alpha.ca
Table of Contents
1. Important Safety Instructions ................................................................................................3
1.1 Important Information ........................................................................................................... 3
1.2 Storage Instruction ............................................................................................................... 4
2. Introduction ...........................................................................................................................5
2.1 General Characteristics ........................................................................................................ 5
2.2 Optional Congurations ........................................................................................................ 6
2.3 System Block Diagram ......................................................................................................... 6
2.4 Symbols on the LCD Display Panel .................................................................................... 7
2.5 Front and Rear Panels ......................................................................................................... 9
2.6 Communication Ports ..........................................................................................................11
3. Installation and Operation ...................................................................................................12
3.1 Unpacking .......................................................................................................................... 12
3.2 Selecting Installation Position ........................................................................................... 13
3.3 Installation of the Accessory kits ........................................................................................ 14
3.4 Terminal Block Wiring ......................................................................................................... 15
3.5 Operation Test and Installation Instruction ......................................................................... 17
4. Troubleshooting Guide ........................................................................................................27
5. Bundled Software Installation Guide ...................................................................................28
5.1 Hardware Installation ......................................................................................................... 28
5.2 Software Installation ........................................................................................................... 28
6. Optional Communication Cards ..........................................................................................29
6.1 R2E (2nd RS-232 ) Card .................................................................................................... 29
6.3 RSE (RS-485) Card ........................................................................................................... 29
6.2 USE (USB) Card ................................................................................................................ 29
6.4 DCE (Dry Contact) -B Card ................................................................................................ 30
6.5 SNMP Cards ...................................................................................................................... 30
6.6 Interface Card Installation .................................................................................................. 31
7. Specications ......................................................................................................................32
8. Warranty and Service Information ......................................................................................34
Appendix A - Transformer Installation ........................................................................................35
Appendix B - Parallel Installation ...............................................................................................41
2
0170012-J0 Rev A

1.  Important Safety Instructions

1.1  Important Information

SAVE THESE INSTRUCTIONS – This manual contains important instructions that must be followed during the installation and maintenance of the UPS and batteries.
The UPS has its own external energy source (battery). A voltage may be present at the output terminals even when no AC input power is available.
This UPS is equipped with an EMI filter. To prevent potential leakage current hazard, ensure that the AC main supply is securely grounded.
Make sure that the AC utility outlet is correctly grounded.
Make sure that the input voltage to the UPS matches the rating on its name plate. Use a certified input power cable with the correct plugs and sockets for the appropriate voltage system.
Install the UPS indoors only as it is not designed for outdoor use. Install in a temperature-controlled indoor area free of conductive contaminants
To prevent the UPS from overheating, keep all ventilation openings unobstructed. Do not place anything on top of the UPS. Keep the UPS rear panel at least 20 cm away from the wall or other objects.
Units are considered acceptable for use in a maximum ambient of 40°C. Make sure the UPS is in­stalled in an appropriate environment—0 to 40ºC (32 to 104ºF) ambient temperature, and 30 to 90% relative humidity (non-condensing).
Do not install the UPS in direct sunlight. Failure of the batteries under these conditions may void the warranty.
Do not install in a inflammable or hazardous environment.
Dusty, corrosive, or salty environments can damage the UPS.
Install the UPS away from objects that give off excessive heat and areas that are excessively wet.
Do not install the UPS in an environment with sparks, smoke or gas. Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data processing Equipment, ANSI/NFPA 75.
The entrance of liquids or foreign objects into the UPS will void the warranty.
The external battery will gradually discharge if the system is unused for extended periods.
If unused, recharge the external battery pack every 2 to 3 months. Neglecting to do so will void the warranty. The batteries charge automatically and are kept in good condition if the UPS is installed and used.
A battery can present a risk of electrical shock and high short circuit current. Observe the following precautions when working on batteries:
a. Remove watches, rings, or other metal objects.
b. Use tools with insulated handles.
c. Wear rubber gloves and boots.
d. Do not lay tools or metal parts on top of batteries.
e. Disconnect charging source prior to connecting or disconnecting battery terminals.
f. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit).
0170012-J0 Rev A
3
There is a risk of explosion if a battery is replaced by an incorrect type.
Do not dispose of batteries in a fire—the batteries may explode. Dispose of used batteries accord­ing to the battery manufacturer's instructions.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
This UPS supports electronic equipment in offices, telecommunications, process control, medical and security applications. Only authorized personnel must install the UPS in the following locations:
a. Medical applications directly related to human life
b. Elevators, metro (subway) system or any other equipment related to human safety
c. Public security system or critical computer systems
Always switch off the UPS and disconnect the batteries before relocating the UPS. It may cause electrical shocks if the output is not completely switched off.
Do not open the UPS—there are no serviceable parts inside. Opening the UPS will void the warranty.
Do not repair the UPS yourself Contact your local supplier. Opening the UPS will void the warranty.
The UPS can be equipped with an optional Maintenance Bypass Switch. Follow the procedures strictly to switch on/off the Maintenance Bypass Switch.
The UPS offers CVCF (Constant Voltage Constant Frequency) setting function.
a. For correct setting and wiring, contact the Alpha technical service team (see chapter 8).
b. Do not do it yourself; otherwise, your warranty will be void.
This UPS has been designed and constructed to protect your assets from the wide range of power aberrations experienced on Utility power lines today. It is your insurance for reliable, clean and stable voltage supply. It is worth taking care to install the system correctly and to have it maintained correctly by your regional Alpha service center (see chapter 8).
CAUTION!
Disconnection Device - The customer must provide a disconnect switch for the AC output circuit. To reduce the risk of re, connect only to a circuit provided with branch circuit over-current protection of 30 amperes for 6KVA and 40 amperes for 10KVA rating in accordance with the National Electric Code, ANSI/NFPA 70. (See details in the follow­ing table.)
CAUTION!
To reduce the risk of re, connect the unit input only to a circuit provided with branch circuit over-current protection of 40A for 6KVA and 65A for 10KVA amperes rating in ac­cordance with the National Electric Code, ANSI/NFPA 70.

1.2  Storage Instruction

Store the UPS in a location where the temperature ranges between -15ºC (+5ºF) to 40ºC (104ºF).
For extended storage in moderate climates, charge the external battery pack for 12 hours every 3 months. Repeat every 2 months if the ambient storage temperature is above 30ºC (86ºF).
4
0170012-J0 Rev A

2.  Introduction

2.1  General Characteristics

The UPS continuously supplies your critical device with stable, regulated, transient-free pure sine wave AC power.
High-efficiency 20 kHz pulse-width modulation (PWM) sine-wave topology yields an excellent overall performance. The output is capable of handling high crest factor and high inrush current loads.
A multi-functional LCD/LED panel displays the status of the UPS. The LED display shows the UPS working status, utility power status, and abnormal UPS status. The LCD display shows the input/out­put voltage, frequency, load status, inner cabinet temperature, and abnormal conditions.
Automatic overload protection switches the output from inverter mode to bypass mode if the load increases to between 105 and 120% of full load for 30 seconds and automatically enables inverter mode when the overload condition is removed. If the load reaches 150% of the rated capacity, the UPS switches to the bypass mode immediately.
If the output is short-circuited, the UPS locks automatically, provides visual & audible alarms and cuts the output supply until the short circuit situation is resolved.
If the unit overheats, the internal thermal switch detects the temperature and switches to bypass mode. It switches back to the inverter mode once the temperature drops to a predetermined value.
This UPS is equipped with fully digitized control logic for greater functionality and an enhanced high level of power protection. Digital signal processing (DSP) enhances the UPS communication capa­bility by providing the flexibility for easy remote control and monitoring.
A maintenance-free, sealed-type battery minimizes after-sales service.
An optional maintenance bypass switch provides easy and safe troubleshooting or maintenance when the utility power is normal.
Four different working modes are provided that can be used for a variety of applications:
a. Normal (On-line mode)
b. ECO (Economic mode)
c. CF50 (50Hz Frequency Converter mode)
d. CF60 (60Hz Frequency Converter mode)
When the UPS is operated in the CF50 or CF60 mode, the recommended load must be 75% of the rated capacity if the input voltage is 176 to 280 VAC, and 50% of the rated capacity if the input volt­age is 160 to 280 VAC.
A DC-start function ensures that the UPS starts up during power outages.
Revolutionary battery management circuit analyzes battery discharging status to adjust the battery cut-off point and extend the batteries’ life span.
An intelligent temperature-controlled fan extends the life of the fan, and also reduces annoying noise caused by the sudden acceleration of the fan.
If the UPS is out of order, a fault message will be displayed on the LCD screen.
0170012-J0 Rev A
5
2.2  Optional Configurations
The Continuity 6K / 10K UPS can be installed with a transformer—see Appendix A.
It can also be installed in the parallel configuration—see Appendix B.

2.3  System Block Diagram

6
0170012-J0 Rev A

2.4  Symbols on the LCD Display Panel 

Symbols Description
LINE
Utility or bypass source
OFF
FAIL
Battery low
Battery abnormal
UPS overload
UPS working in specied mode*
A blackout transfer occurred in UPS output
Bypass input abnormal. UPS fails to transfer to bypass. Bypass abnormal at ECO mode
Utility input abnormal
UPS shutoff
UPS abnormal lock
UPS ow chart
4 digit display
Indicates the desired item to be measured
UPS ON switch or alarm silence
UPS OFF switch
Previous page or setting change
Next page
Special function log in /out
Enter or reconrm
0170012-J0 Rev A
7
Symbols Description
Utility input normal LED
Bypass input normal LED
UPS under redundancy mode
UPS under ECO mode
UPS fault or abnormal warning LED
EPO Er05 Er06 Er10 Er11 Er12 Er14 Er15 Er16 Er17
Er21
Er24 Er27 Er28 Er31
Emergency power off
Battery weak or dead
Output short circuit
Inverter over-current
UPS overheating
UPS output overload
Fan error
Wrong procedure to enter maintenance mode
Output parameters set error in parallel system
ID numbers in conict in parallel system or ID number error in single unit
Parallel communication error. Communication wire disconnected or failure to nd ID1 UPS) in parallel system.
CVCF mode with bypass input.
The UPS must be operated in normal mode in parallel system.
Bypass overload time out and cut off output
The settings of the control board and driver board do not match.
Er33
Er**
*The specified modes include Normal mode, ECO mode, CVCF mode, etc.
8
Isolated transformer overheat
Other error code
0170012-J0 Rev A

2.5  Front and Rear Panels

1
3 4 2 11 12
5
9
1078
6
2.5.1  Front Panel Functions
1. LCD display
2. Green LED illuminates to indicate that the UPS has the capability to run under the redundancy mode.
3. Green LED illuminates to indicate that the utility input voltage is within the acceptable range.
4. Green LED illuminates to indicate the bypass input is normal.
5. UPS ON/Alarm Silence
6. Go to previous page or change the settings of the UPS
7. Re-confirm the change of UPS Setting
8. Go to the next page
9. UPS OFF switch
10. Special functions log in/out
11. UPS is working in the ECO (economic) mode
12. UPS fault or abnormal condition
0170012-J0 Rev A
9
2.5.2  Rear Panel Functions
Continuity 6K
Continuity 10K
Item
A RS232 port
B Terminal resistor for parallel function
C CAN bus connection port for parallel system
D Customer options – Slot 1
E Customer options – Slot 2
F Cooling fan
G External battery connector
I Utility input breaker CB1
J Bypass input breaker CB2 for dual input model only
L Input/output terminal block
N EPO emergency power off short to enable the function
O Thermal breaker for the protection of load during abnormal
conditions: CB3
Figure 1 — Rear Panel Components
Description
10
0170012-J0 Rev A

2.6  Communication Ports

The UPS is equipped with a remote emergency power off (REPO) dry contact input, true RS232 and USB communication ports to provide communication with bundled UPS monitoring software for remote monitoring of UPS status via a PC.
Four optional interface cards are available to meet various communication needs (refer to Section 6):
DCE (dry contact relay card)
RS232
USB
SNMP/WEB card
The bundled software of the UPS is compatible with many operating systems such as Windows 98, 2000, ME, NT and XP.
All communication ports (including optional cards) can be active simultaneously to monitor the UPS sta­tus. However only 1 communication interface can be active at any one time. The interface with the high­est priority controls the UPS. The priority of these communication interfaces are as follows from highest to lowest priority:
REPO input port
Optional Interface card
USB
RS232
The communication port on the UPS provides true RS232 type communication with the UPS software. This is used for remote monitoring the power and UPS status.
Optional interfaces cards include R2E (2nd RS232), RSE (RS485), USE (USB), DCE (dry contact), and SNMP/. These can be combined according to your requirements. However, the R2E, RSE, and USE card cannot be used simultaneously.
The bundled software of the UPS is compatible with many operating systems such as Windows 98, & 2000, ME, NT and XP. For other applications like Novell, NetWare, Unix, Linux, contact your local distribu­tor for advice.
When optional interface cards are used together with the onboard RS232 port for communications. The REPO signals have the highest control command priority followed by the SNMP/WEB card, the shutdown command at the DCE card and the R2E, RSE and USE cards. The onboard RS232 port has the lowest priority.
2.6.1  True RS232 Port Settings
The RS232 interface should be set as follows:
Baud Rate: 2400 bps
Data Length: 8 bits
Stop Bit: 1 bit
Parity: None
2.6.2  USB Port Settings
The USB communication protocol definition complies with:
USB version 1.0, 1.5 Mbps
USB HID Version 1.0
0170012-J0 Rev A
11

3.  Installation and Operation

Read Section 1 (Important Safety Instructions) before installing the UPS

3.1  Unpacking

Inspect the UPS upon receipt. The manufacturer has designed robust packaging for your product, but accidents and damage can occur during shipment. Notify the shipper and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Remove the UPS from the cardboard box. Check that the following standard contents are included:
One (1) user manual
UPS communication software CD with RS232 cable
Accessories shown below for Continuity 6K or Continuity 10K model
Additional 1 piece of wire for a UPS with dual input but no isolation transformer (#8 for 6kVA and #6 for 10kVA).
(Note: Wire is used at the input/output terminal block of the UPS.
All Continuity models
Continuity 10K only
X1A1
X1A2
X2A3
12
(10K x 5)
0170012-J0 Rev A

3.2  Selecting Installation Position 

WARNING!
The UPS is heavy. Select a location that is structurally strong enough to withstand the UPS weight.
To ensure proper operation and a long operating life, position the UPS according to the following requirements:
1. Ensure that there is a minimum of 30 cm (12 inches) of clearance behind the rear panel of the UPS.
2. Do not block the air-flow to the ventilation louvers of the unit.
3. Ensure that the installation site is free from excessive dust and that the ambient temperature and humidity are within the specified limits.
4. Do not place the UPS in a dusty or corrosive environment or near flammable objects.
5. This UPS is not designed for outdoor use.
0170012-J0 Rev A
13

3.3  Installation of the Accessory kits

B1 B2 S3 B1 B2 S3
B2
S2
S2
14
0170012-J0 Rev A

3.4  Terminal Block Wiring

Continuity 6K model
Continuity 10K model
TB1
TB2
Figure 2 — 1-phase terminal block wiring
L11-N1:
L12-N1 
G1: 
L21 ~ N22:
G2:
Terminals for bypass input that provides power to the loads when the UPS is working in the bypass mode.
Terminals for the utility input that provides power to the loads when the UPS is in the Utility mode.
Terminal for the UPS input ground.
Terminals for the UPS output.
Terminal for the UPS output ground.
Remarks:
The maximum output current for each terminal is 30 Amps for the 6 kVA model and 50 Amps for the
10 kVA model.
If the UPS is a DIM (dual input mode) type whose utility and bypass sources are the same, L11 and
L12 must to be shorted for 1-phase input models.
If the UPS is a SIM (single input mode) type, only the AC source can be hooked up to the UPS via
the L12-N1 terminal for a 1-phase input model.
Use cable ties to secure the cables.
0170012-J0 Rev A
15
Continuity 6K model
Continuity 10K model
16
Refer to the table below for input current, output current, and recommended conductors specifications:
AC input and output (75°C minimum copper wire)
Model Maximum current Conductor section Torque
6 kVA 33 A AWG #8
10 kVA 54.3 A AWG #6 23 in-lb
Battery input
Model Maximum current Conductor section
6 kVA 25 A AWG #8
10 kVA 41 A AWG #6
0170012-J0 Rev A

3.5  Operation Test and Installation Instruction

3.5.1  Start Up in Normal Mode 
1. Open the terminal block cover on the rear panel (refer to Section 3.4). Make sure the grounding is properly connected.
2. Make sure the utility breaker, UPS utility breaker, and Bypass breaker are in the Off position.
3. Make sure the utility voltage is within the allowable input voltage range of the UPS.
4. Connect the utility power separately to the terminal blocks of the UPS utility input and the bypass input.
5. Switch on the distribution panel breaker and the UPS utility and bypass input breakers.
6. The UPS starts up.
The green LCD display, with parallel function, scrolls from Screen A1 to Screen B. Otherwise the LCD display scrolls from Screen A2 to Screen B.
7. The UPS is in the bypass mode and automatically runs a self-test. If no fault messages appear, the pre­startup of the UPS has been successful and the charger starts charging the batteries.
Screen A1
and LEDs illuminate indicating that the utility and bypass inputs are normal. The
Screen A2
Screen B
0170012-J0 Rev A
17
8. Press and hold the UPS On button for approximately 3 seconds. The buzzer sounds twice and the LCD display scrolls from Screen B to Screen C.
Screen C
9. The UPS is in self-test mode again. The LCD display scrolls from Screen C to Screen D and remains in the battery mode for approximately 4 seconds. The display scrolls from Screen E1 to Screen F if the self­test is successful.
Screen D
Test
Screen E1
Screen E2
Screen F
OK in self test
If the self-test fails, the LCD display scrolls from Screen D to Screen E2. An error code or sta­tus is shown on the screen
220 VAC in utility input
18
10. The UPS start-up operation is now complete. Charge the batteries for at least 8 hours to ensure they are fully charged.
0170012-J0 Rev A
3.5.2  Start-up in Battery Mode (Cold Start)
1. Make sure the UPS has at least 1 set (20 pcs) of 12 V / 7 Ah batteries installed.
2. Press and hold the UPS On display scrolls from Screen A to Screen G.
3. Press and hold the UPS On Screen G to Screen H. The UPS is in the self-test mode and can supply power to the output after about a minute. The LCD display will scroll to Screen I.
If a failure occurs within 15 seconds of pushing the UPS On button, the UPS will automatically switch off.
Screen G
Screen H1
button for approximately 5 seconds. The buzzer sounds twice. The LCD
button again for about 3 seconds until the LCD display scrolls from
Off means the UPS pre-start has been successful.
Utility input is 0 and abnormal.
Screen H2
0170012-J0 Rev A
19
3.5.3  Check Measured Values & Figures detected by UPS
Use the and keys to check the measured values and figures detected by the UPS. The LCD display will scroll through the following screens: Screen C (Voltage from Utility Input) Screen I (Volt­age from Bypass Input) Screen J (Frequency from Utility Input) Screen K (Frequency from Bypass Input) Screen L (UPS Output Voltage) Screen M(UPS Output Frequency) Screen N (UPS Output Load %) Screen O (UPS Battery Voltage) Screen P (UPS Inner Temperature).
Screen I
Voltage from bypass input
Screen J
Frequency from utility input.
Screen K
Screen L
Screen M
Frequency from bypass input.
UPS output voltage.
UPS output frequency.
20
0170012-J0 Rev A
Screen N
Screen O
Screen P
Output load level (%).
Battery voltage.
UPS inner temperature.
3.5.4  UPS Default Data and Special Function Execution
1. To run a self test or check default data, press the Special function key to scroll to Screen Q1.
Screen Q1
Buzzer on.
Screen Q2
0170012-J0 Rev A
Buzzer off.
21
2. Press the key to scroll through the UPS settings. The LCD display will sequentially show Screen Q1 (buzzer) Screen R1 (self-test) Screen S1 (bypass voltage ranges) Screen T (output frequency synchronization range) Screen U (Inverter output voltage) Screen V1 (UPS operation mode) Screen W (output voltage micro tune value) Screen X (UPS Id) Screen Y (parallel function status).
Screen R1
Self-test is NOT on.
Screen R2
Self-test is on.
Screen S1
Screen S2
Bypass voltage is adjusted to a narrow range.
Bypass voltage is adjusted to a wider range.
22
0170012-J0 Rev A
Screen T
Screen U
Screen V1
Frequency range is +/-3 Hz.
Inverter output voltage.
UPS is in normal mode.
Screen V2
Screen V3
Screen V4
UPS is operated in Eco mode.
UPS is operated in CVCF 50 Hz mode.
0170012-J0 Rev A
UPS is operated in CVCF 60 Hz mode.
23
Screen W
Screen X
Screen Y
Output voltage adjustment % from 0% to 3% or -0% to -3%.
Identification number.
UPS is in the Number 1 parallel system.
3. Press the key to execute special functions. The functions include Screen Q1 (buzzer ON), Screen Q2, alarm silence for UPS warning (buzzer OFF), Screen R1 (self-test OFF), Screen R2 (self-test ON). The UPS will execute a battery test for 10 seconds. Screen E1 will be displayed if the self-test is successful. If the self-test fails, Screen E2 and an error message will be displayed.
24
0170012-J0 Rev A
3.5.5  UPS Default Settings and Alternatives
1. Press and hold the OFF button for 5 seconds. The inverter output switches off and the output load is then supplied by the bypass loop. The LCD displays Screen B.
2. Simultaneously press and hold the ON seconds. The buzzer sounds twice and the LCD display shows Screen Q1.
The UPS is now in setup mode. Except for the buzzer (screens Q1 and Q2) and self-test (screens R1 and R2)
settings, all default settings can be changed by pressing the Scroll Up
3. Screens S1 and S2 show the acceptable range for the input bypass voltage. Acceptable values are 184 to 260 VAC or 195 to 260 VAC.
4. Screen T shows the bypass frequency range of the inverter output. Acceptable values are ±3 Hz or ±1 Hz.
5. Screen U shows acceptable inverter output voltages. The voltage can be set to 200, 208, 220, 230, or 240 VAC.
6. Screen V1, V2, V3 and V4 show the operation modes of the UPS. The available modes are: (1) Online, (2) Eco (Economic), (3) Fixed 50Hz Output, and (4) Fixed 60Hz Output.
7. Screen W shows the inverter output settings, which can be set to 0%, +1%, -1%, +2%, -2%, +3%, or
-3%.
8. Screen X shows the address and position of the UPS when the UPS is in the parallel mode. The values can be set from 1st to 4th. The value must be set to 1st if the UPS is not in parallel.
9. Screen Y shows the parallel function status. P 01 means the parallel function disabled and P 02 means the parallel function is enabled.
button and the Scroll Down key for approximately 3
key.
10. When all the changes have been completed, scroll to Screen Z and press Enter changes. The LCD display will scroll to Screen AA, which means that the setting changes have been
completed. To cancel all the changes, press OFF Screen AA, indicating that all the changes are invalid.
Screen Z
Screen AA
11. Switch the UPS OFF and ON (with utility input breaker CB1—Figure 1) to exit Configuration mode after all settings are complete.
for 5 seconds. The LCD display will scroll directly to
Press Enter to save data.
UPS is locked.
to save all the
12. Your setting changes are now complete.
0170012-J0 Rev A
25
3.5.6  Troubleshooting a UPS that is Off for an Unknown Reasons
1. If a serious abnormal condition has occurred, the UPS will lock into the OFF position. The LCD displays Screen AA and an error message.
2. After 3 seconds, all messages are blocked except the bypass indicators: LED utility voltage is outside the normal range after the UPS is locked, the LED
LCD
3. Unlock the UPS as follows:
will be shown on the LCD.
a. Check all the recorded error messages.
b. Check the table in Section 2.2 to troubleshoot the problem. If this is unsuccessful, consult your
local distributor for service.
c. Press and hold the OFF
d. Switch off the utility input power breaker.
e. The UPS is now unlocked, but you may want to contact your local distributor to make sure the
underlying fault has been solved.
button for 5 seconds. The buzzer sounds twice.
and LCD
will extinguish and the
3.5.7  Shutting Off the UPS
1. Press and hold the OFF button for 5 seconds. The inverter output switches off. The output load is then supplied via the bypass loop. The LCD displays Screen B.
2. Switch off the utility input power breaker and the bypass input power breaker.
3. The UPS is now completely shut off.
. If the
3.5.8  Maintenance Bypass Mode - for Optional Maintenance Bypass Switch
The maintenance bypass mode is for UPS maintenance only. Only authorized technicians should imple­ment this procedure. Your warranty will be void if the UPS is damaged by unauthorized repairs.
CAUTION!
Complete Step 1 before proceeding to Step 2. Otherwise the UPS will go through a 10 second warning procedure to alert you that the procedure is not being followed, which can damage the UPS because of the uncertain utility status. The UPS will switch back to inverter mode immediately if the CAM switch is turned back to the UPS position.
1. Press and hold the OFF the bypass mode.
2. Remove the cover of the maintenance bypass switch (CAM switch). Turn the CAM switch to the Bypass mode. The upper right-hand corner of the LCD display screen shows .
3. Switch off the utility input power breaker and the bypass input power breaker (see Figure 1). The UPS can now be serviced or repaired.
4. When the repair is complete, switch on the utility input power breaker and the bypass input power breaker.
5. The UPS starts up in the bypass mode and automatically runs a self-test. If no fault messages appear, the pre-startup of the UPS has been successful and the charger starts charging the batteries.
button for 5 seconds. The LCD displays Screen B and the UPS output is in
6. Turn the CAM switch back to the INV/UPS position and replace the maintenance bypass switch cover.
7. Complete Steps 8 and 9 of section 3.5.1. The UPS start-up operation is now complete.
26
0170012-J0 Rev A

4.  Troubleshooting Guide

Check the following if the UPS malfunctions during operation:
Are the input and output cables correctly connected?
Is the utility input voltage within the allowable limits?
If the problems or symptoms persist, follow the instructions in the table below. If necessary, contact your local distributor for help.
Problem
UPS Red Fault LED illuminates.
UPS fails to provide battery backup or the back up time is shorter than its design performance.
UPS locks itself and cannot be turned off.
Check Items Solution
Check that the batteries are properly connected, re-charge
Er05,
Er06, Er10, Er12, Er28,
EPO Remove the short circuit that occurred at the EPO terminal.
Er11, Er33 Remove objects that block the ventilation holes.
Er14
Er15
Er16, Er27
Er21 Reconnect the RJ-45 wire or set the UPS to ID=1.
Er24
Other error codes Consult your local dealer for assistance.
and
the batteries for 8 hours, and then check if the UPS backs up normally. If necessary, contact your local dealer for assistance.
If the CB3 is tripped, switch off the UPS completely. Keep the CAM switch at the INV position and then press CB3. Remove one non-critical UPS output load. If the coating of the AC power cord is damaged, replace it with a new one.
Check that the cooling fans on the rear panel are working normally.
Make sure the UPS is in the normal mode. If it is running in the CVCF mode, switch the UPS off and then on again.
All of the settings except the ID Number must be the same in the parallel UPS. Refer to chapter 3.5.5 to reset the values.
When the UPS is on the CVCF mode, do not activate the bypass input. Switch off the UPS, bypass the input, and re­start the UPS.
If the backup time remains non-satisfactory after 4 hours of charging, contact your local dealer for battery replacements.
Refer to chapter 3.5.6 to troubleshoot the problem. If necessary, contact your local dealer for assistance.
0170012-J0 Rev A
27

5.  Bundled Software Installation Guide

5.1  Hardware Installation

1. Connect the male connector of RS232 cable to the UPS communication port.
2. Connect the female connector of the RS232 cable to a dedicated RS232 port on the computer.
3. For optional interface card installation, refer to Chapter 6.

5.2  Software Installation

Refer to the software user’s manual on the CD for installation.
28
0170012-J0 Rev A

6.  Optional Communication Cards

CN2
CN3

6.1  R2E (2nd RS-232 ) Card

CN1 is for RS232 DB9.
For the communication protocol,
refer to section 2.6.1 on page 11.
Installation position Slot 1 (CHA -
CN4) or Slot 2 (CHB - CN5).

6.3  RSE (RS-485) Card

CN1 is for the function of the terminal resistor. Short Pin 1-2 to enable the function and short Pin 2-3
to disable it.
CN2 for RS485 and CN3 for remote power
Specification:
1 Ground
2 A/Data+
1 2
3
3 B/Data-
1 2
Installation position Slot 1

6.2  USE (USB) Card

CN1 for USB.
Specification:
a. Comply with USB version 1.0, 1.5
Mbps
b. Comply with USB HID Version 1.0.
c. The pin assignments of the USE
card:
1 AC+
2 AC-
1 VCC (+5 V)
2 D-
3 D+
4 Ground
Installation position Slot 1 (CHA - CN3) or Slot 2 (CHB - CN4)
0170012-J0 Rev A
29

6.4  DCE (Dry Contact) -B Card

6.4.1  The pin assignments of 10-pin terminal
1 2 3 4 4 5 6 7 8 9 10
1. UPS in bypass mode (bypass).
2. Utility normal (normally closed contact).
3. Utility normal (normally open contact).
4. Inverter on.
5. Battery low.
6. Battery bad or abnormal.
7. UPS alarm.
8. Common.
9. Shutdown UPS positive(+) signal.
10. Shutdown UPS negative(-) signal.
The shutdown function is activated when +6 to +25 Vdc is applied between Pin 9 and Pin 10 for 5
seconds.
The capacity of each relay contact is 40 Vdc / 25 mA.
Installation position optional slot.
Flexible signal output for NC (normally closed) or NO (normally open) contact is provided by short-
ing Pin 1-2 or Pin 2-3 from JP 1-5.
The shutdown function is activated 1 minute after a power outage occurs if Pin 1-2 of both CN1 and
CN6 are shorted by a cap. The shutdown function can also be activated by Pin 9-10 of CN3 if Pin 2-3 of both CN1 and CN6 are shorted by a cap.

6.5  SNMP Cards

For installation, refer to the
user manual attached to the card.
Installation position Slot 2
(CHB).
Insert to UPS
30
0170012-J0 Rev A

6.6  Interface Card Installation

Step 1
Step 2
Step 3
0170012-J0 Rev A
31

7.  Specifications

Model 6000 VA 10000 VA
Input
Voltage range 160 to 280 VAC (1Φ)
Frequency 45 to 65 Hz
Phase/wire Single, Line + Neutral + Ground
Power factor Up to 0.99 at 100% linear load
Current THD (100% linear load) < 6%
Output
Voltage window 208/220/230/240 VAC Selectable
Voltage adjustment ±0%; ±1%; ±2%; ±3%
Voltage regulation ±2%
Capacity 6000 VA** 10000 VA**
Rated power factor 0.9 lagging
Wave form Sine Wave, THD <3% (no load to full load)
Frequency stability ±0.2% (free running)
Frequency regulation ±1Hz; ±3Hz
Transfer time 0 ms
Crest factor 3:1 acceptable
Efciency (AC to AC, normal) Up to 91%
Efciency (AC to AC, ECO) Up to 97% Up to 93%
Autonomy ≥ 6 min. ≥ 4 min.
DC start Yes
Battery
Type
Quantity 20 pcs
Voltage 240 VDC
Recharge Time 4 hours to 90%
Sealed lead acid
maintenance free
12V / 7Ah
Sealed lead acid
maintenance free
12V / 9Ah
Display
Status on LED + LCD
Readings on LCD
Self-diagnostics Upon power-up, front panel setting and software control, 24-hour routine checking
Line Mode, Backup Mode, ECO Mode, Bypass Supply, Battery Low, Battery Bad/
Disconnect, Overload, Transferring with interruption, and UPS Fault
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage,
Battery Voltage, and Inner Temperature.
Alarms
Audible and visual Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions
32
0170012-J0 Rev A
Model 6000 VA 10000 VA
Physical
Dimensions (W x D x H) mm
Input/Output Connection Hardwire
External battery connection Plug-in & Play
Net weight (kg), without isolation transformer*
Without
Heat dissipation
Leakage current < 3 mA at full load
Marks** CE, cUL, UL
* Isolation transformer: net 53kgs for 6000VA, 10000VA
** This unit has been certied for a maximum load of 8.5 kW / 9.5KVA by CSA and 9 kW / 10KVA by UL
isolated transformer at full linear load
440 x 680 x 88 440 x 680 x 132
24 kg 26 kg
< 450W < 600 W
0170012-J0 Rev A
33

8.  Warranty and Service Information

Technical Support
Free Technical Support 24/7/365 is part of the Alpha customer satisfaction commitment. The phone num­bers below can also be used to access a wide range of service solutions both at your premise and at the Alpha facility nearest you.
In Canada and the USA, call toll free 1-888-462-7487 24 hours a day, seven days a week.  Customers outside Canada and the USA, call +1- 604-436-5 547.
Warranty 
Alpha Technologies Ltd. warrants its equipment to be free of manufacturing defects in material and work­manship, for a period of 36 months from the date of shipment from the factory. The warranty provides for repairing, replacing or issuing credit (at Alpha’s discretion) for equipment shipped by it and returned by the customer to the factory or other authorized location during the warranty period.
There are limitations to this warranty coverage. The warranty does not provide to the customer or other parties any remedies other than the above. It does not provide coverage for any loss of profits, loss of use, costs for removal or installation of defective equipment, damages or consequential damages based upon equipment failure during or after the warranty period. No other obligations are expressed or implied. Warranty also does not cover damage or equipment failure due to cause(s) external to the unit including, but not limited to, environmental conditions, water damage, power surges or any other external influence.
The customer is responsible for all shipping and handling charges. Where products are covered under warranty Alpha will pay the cost of shipping the repaired or replacement unit back to the customer.
Battery Warranty 
Battery warranty provided by Alpha is a three year full replacement warranty with a pro-rated warranty for the following two years. Pro rated warranty provides a credit applicable toward the purchase of new batteries from Alpha. The credit is calculated as the purchase price multiplied by the percentage of the battery life that was not available (in months). Battery warranty coverage is lost where the battery charge is not maintained for 6 months. Contact your Alpha sales representative or the Technical Support team at the above number to understand your entitlements under Battery Warranty.
Extended Warranty
The terms of warranty can be extended in time by purchase of an Extended Warranty. Warranty exten­sions are available on a per year basis and can be purchased during the initial warranty period.
Return of Material 
Please contact Technical Support at the number above to obtain a Service Repair Order (or Return Mate­rial Authorization) number BEFORE sending material back. This will ensure that your service needs are handled promptly and efficiently.
On Site Services and Service Plans
A wide range of services are available at your location including installation, commissioning, preventa­tive maintenance, remedial maintenance, battery replacement, battery delivery, etc. Preventative mainte­nance is recommended for Alpha products at least once per year. Customers can arrange to have these services provided automatically with one annual payment.
Service Centers
For a list of service centers, please visit:
http://www.alpha.ca/web2/about-alpha/service-centers.html
34
0170012-J0 Rev A
A
RJ-45 Communication port
F
Thermal breaker for the protection of the load in an abnormal condition: CB3
B
Input & Output Terminal Block
G
Cooling Fan
C
For UPS Input
D
Maintenance Bypass Switch (optional)
E Air Ventilation Openings
TB1
TB2
Not Intended to
TNV Communication
Network
BYPASS
INV
TB1
TB2
Not Intended to
TNV Communication
Network
Appendix A Transformer Installation
A.1. Important Safety Instructions
There is a tiny leakage current from the Transformer Module, so make sure to it is correctly grounded before connecting to the UPS, Utility or Output Device.
To eliminate any overheating of the unit, keep all ventilation openings free from obstruction, and do not store anything on top of the unit. Keep the unit 30 cm away from the wall.
Install in an environment with 5m3 (176.6 ft3) airflow per hour.
A.2. Rear Panel Description
6K
10K
A
E
B C
D
D
0170012-J0 Rev A Page 35
F
A
G
B
A1
A2
A3
S1
S2
S3
S4
B1
B2
F1 C1
B3
x8 x6x4x2
x2
x2
x2
x2x1
x1x4x4
fo r 2U
fo r 3U
A.3. Unpacking
Check for the following parts:
Accessory kit parts:
(C1 & F1 are for a unit with a Maintenance Bypass Switch)
Cables for a unit with a Maintenance Bypass switch: 12" NEMA L6-30P cable x 2 pcs 12" NEMA L6-30R cable x 1 pc
Cables for a unit without a Maintenance Bypass switch: 10 AWG, 105cable x 3pcs
0170012-J0 Rev A Page 36
S3
UPS
GTM
BATTERY
TRANSFORMER
A.4. Installation
A.4.1. Installation as a Tower Unit
0170012-J0 Rev A Page 37
S3
UPS
GTM
BATTERY
B1 B2
S4
B1 B3
S4
A.4.2. Installation as a Rack Unit
0170012-J0 Rev A Page 38
Utility Input
G1:
Connect to UPS Output Terminal
Connect to UPS Output Ground Terminal
Output Terminals of the Unit Output Ground Terminals of the Unit
L11L12N11
L1N1G1G2
TB1
TB2
L22
L2
N22
N2
G3
TR OUTPUT
TO UPS OUTPUT UTILITY INPUT
L11L12N11
G2
TB1
TB2
L22
L2
N22
N2
G3
TR OUTPUT
TO UPS OUTPUT
N/AN/AN/A
A.5. Terminal Block Description for Input, Output
A.5.1. 6K
A.5.2. 10K
L1-N1
Input Ground L2N2 G2 L11L12N11,
L22N22: G3
0170012-J0 Rev A Page 39
110Vac
A.5.3. Output Wiring Description
The maximum output current for each terminal is 30A (6K) or 50A (10K).
When the wiring of the TR OUTPUT block corresponds to drawing (a) and the input of L2-N2 from the UPS OUTPUT block is 200Vac, 220Vac, 230Vac or 240Vac, the output voltage is 100Vac, 110Vac, 115Vac or 240Vac. If the input of L2-N2 from UPS OUTPUT block is 208Vac, the output is 120Vac.
When the wiring of the TR OUTPUT block corresponds to drawing (b) and the input of L2-N2 from the UPS OUTPUT block is 200Vac, 220Vac, 230Vac or 240Vac, the output voltage is 200/100Vac, 220/110Vac, 230/115Vac or 240/120Vac. If the input of L2-N2 from UPS OUTPUT block is 208Vac, the output voltage is 240Vac/208Vac/120Vac.
N22
L22 N11
6KVA (Max)
(a)
L12
L11
N22
208Vac
L22 N11
120Vac
6KVA (Max)
240Vac
6KVA (Max)
L12
120Vac
3KVA (Max)
L11
(b)
0170012-J0 Rev A Page 40
T3
X 1 X 1C1 X 1C2
X 1F1
T2
X 4
T1
X 6
Appendix B Parallel System Installation
The Continuity 6K and 10K can be connected in parallel to provide N+1 redundancy with up to 3 units in parallel plus one redundant.
B.1. Important Safety Instructions
Parallel function of the UPS can only be enabled in the Normal mode operation.
Prior to a parallel installation, ensure the tolerance of the output voltage of each UPS at zero-load condition is
less than 0.5Vac. Consult your authorized dealer if any of the UPS output voltage has a tolerance over 0.5Vac.
Ensure the RJ45 communicating wire is connected securely during parallel mode to avoid damage to both the UPS and the output devices.
Ensure the terminal resistors on the rear panel of the 2 units of UPS in parallel are set to the ON position. With 3 UPS units in parallel, only UPS 1 and 3 terminal resistors are set to ON. With 4 UPS units in parallel, only UPS 1 and 4 terminal resistors are set to ON.
Note that only a UPS with the same rating and type can be installed in parallel. For instance, a UPS without a galvanic transformer cannot be connected in parallel with a UPS with a galvanic transformer. While installing these UPS, add a 40A/250VAC and 30A/250VAC NFB (Non-fuse Breaker) at the input and output of each UPS. The NFB prevents any potential hazard when the UPS is in the maintenance mode.
B.2. Preparation for Installation
B.2.1. Unpacking
Check for the following accessories:
1 set of RJ-45 communication cables for parallel system (C1, C2)  1 set of metal brackets (F1)  1 set of cable ties (T1 or T2 and T3)
0170012-J0 Rev A Page 41
B.2.2. Selecting an Installation Position
Air flow within the unit is from the front to back. Select an installation position that has good ventilation with at least 30 cm clearance around the equipment.
Figure 1 Installation position
B.2.3. Wiring
Refer to the following table for cable and breaker sizes:
Model Maximum
Current
AC input and Output 6KVA 33A 10KVA 54.3
Battery input 6KVA 25A 10KVA 41
Circuit Breaker
40A 63A
30A 63A
Wire Size
AWG #8 AWG #6
AWG 10 AWG 10
0170012-J0 Rev A Page 42
INPUT
I
O
Incorrect
Correct
A  Communication or Control signal wires
B.3. Installation
Take the following steps to minimize EMI when wiring:
1. Make sure the input and output cables and the battery cables are kept separate from each other to avoid unnecessary noise interference.
2. Keep the path of the communication cables (RJ45, RS232, RS485, USB, EPO and Shutdown) separate from the I/O and battery cables. If unavoidable, place them at 90 degrees to each other and at least 20cm apart.
20cm
A
B
A
B
A
90°
B
B  Power wires & cables
Figure 2 Cabling
3. The UPS is equipped with an EMI filter. To prevent potential current leakage hazard, ensure that the AC main supply is securely grounded.
B.4. Start-up Procedure
1. Position the units as shown in Figure 1.
2. Use communication cables that are less than 7M long, connected as a “Ring” loop.
CONTROL CONTROL CONTROL
CONTROL
I O
0170012-J0 Rev A Page 43
I O I O
OUTPUT
1050mm RJ-45 communication connecting wire 1900mm RJ-45 communication connecting wire
Max. 25M; all Input Power cables should be the same length.
Max. 25M, all Output Power cables should be the same
Figure 3
3. Arrange the power cables and the control signal cables as indicated in Figure 1 and Figure 2 depending on the UPS type. Ensure all the circuit breakers at input and output ends are set to OFF position.
4. A maintenance bypass box (MTBS) is recommended for use during maintenance.
5. Only two terminal resistors of the UPS in parallel are to be set to the ON position as indicated in Figure 4. For 3 units in parallel only UPS 1 and 3 terminal resistors are ON; for 4 units in parallel, only UPS 1 and 4 terminal resistors are ON.
6. Turn on the input breaker (CB1 and CBi) of the Utility (see Figure 4). Configure each UPS for parallel operating mode and set the IDs (eg. UPS 1, ID=1) of the respective UPS. Ensure all parameters of each UPS are the same.
7. If you are using the front panel for UPS parameter entry and setting, switch the UPS OFF and ON to exit Configuration mode after all settings are complete.
8. If an external MTBS box is installed, ensure the switch is in Bypass position. Check to see if the UPS is in Bypass mode with output voltage available.
9. Turn on the output breaker (CB2) and ensure the connected loads are supplied with power via the MTBS Box.
10. Turn on the output breaker of the UPS (CBo) and turn the switch of the MTBS Box to INV/UPS position. Now the connected loads should be supplied with power via the UPS Bypass loop.
11. Turn on each UPS individually and make sure the UPS are in Inverter supply mode.
The installation procedures are now complete.
0170012-J0 Rev A Page 44
CB 1 Utility Input Breaker
L12N1G1L21N22G2
OUTPUT INPUT
ON
OFF
S1
Ext. Battery
+
-
G
Parallel Work Comm.
TNV Communication Network
Bus Not Intended to
EPO
RS232
To UPS Battery
To Extended Battery
-
G
+
-
G
+
DC Breaker 30A 250Vdc
BYPASS
INV
UPS INPUT
L1N1G1
INPUT
UTILITY
L2N2G
OUTPUT
UPS
L11N11G
OUTPUT
TR
L22N22
Sensor for MTBS
T2
T2
T2
T2
UPS
BYPASS
L1N1G1
INPUT
L2N2G2
OUTPUT
CAUTION:
BEFORE SWITCHING TO MAINTENANCE MODE,
1. MAKE SURE UTILITY INDICATOR LIGHTS UP.
PROCESS THE FOLLOWING STEPS FIRST:
2. PUSH TEST BUTTON, AND MAKE SURE UPS SWITCHES TO BYPASS MODE.
3. TURN THE SWITCH FROM UPS TO UTILITY.
TEST
UTILITY
T2
T2
T2
T3
CBi
CBi
CB1
CB2
CBo
CBo
UTILITYLOAD
MTBS BOX
T3
To UPS Battery
To Extended Battery
-
G
+
-
G
+
DC Breaker 30A 250Vdc
BYPASS
INV
UPS INPUT
L1N1G1
INPUT
UTILITY
L2N2G
OUTPUT
UPS
L11N11G
OUTPUT
TR
L22N22
Sensor for MTBS
L12N1G1L21N22G2
OUTPUT
INPUT
ON
OFF
S1
Ext. Battery
+
-
G
Parallel Work Comm.
TNV Communication Network
Bus Not Intended to
EPO
RS232
RS232
Parallel Work Comm. Bus
ON OFF
S1
Set the two terminal resistors of two(2) or four(4) UPS to at "On" positions.
CB 1 Utility Input Breaker
Figure 4 Parallel UPS with Maintenance Bypass Box
0170012-J0 Rev A Page 45
Be careful not
securing Clip
F1
to break this
0170012-J0 Rev A Page 46
B.5. Maintenance Operation Procedure
1. Refer to the operations chapter to switch all UPS to Bypass supply mode.
2. Switch MTBS box to BYPASS position first. And then switch off all output breakers (CBo). Now the load is supplied through MTBS box from Bypass.
3. Make sure the UPS that needs maintenance is completely shutdown first. Then switch off the output breakers (CBo) and input breakers(CBi).
4. Proceed with maintenance.
5. Repeat the steps in section B.4 after you have completed repairing/maintaining, to ensure the load is supplied from the UPS.
The maintenance work is complete.
0170012-J0 Rev A Page 47
Alpha Technologies Ltd.
7700 Riverfront Gate Burnaby, BC V5J 5M4 Canada Tel: +1 604 436 5900 Fax: +1 604 436 1233 Toll Free: +1 800 667 8743
Alpha Technologies Inc.
3767 Alpha Way Bellingham, WA 98226 United States Tel: +1 360 647 2360 Fax: +1 360 671 4936
Alpha Industrial Power Inc.
1075 Satellite Blvd NW, Suite 400 Suwanee, GA 30024 United States Tel: +1 678 475 3995 Fax: +1 678 584 9259
Alpha Energy
1628 W Williams Drive Phoenix, AZ 85027 United States Tel: +1 602 997 1007 Fax: +1 623 249 7833
Alpha Technologies Europe Ltd.
Twyford House Thorley Bishop’s Stortford Hertfordshire, CM22 7PA United Kingdom Tel: +44 1279 501110 Fax: +44 1279 659870
Alpha Technologies
Unit 504, 5/F, Fourseas Building No 208-212 Nathan Road Kowloon, Hong Kong Tel: +852 2736 8663 Fax: +852 2199 7988
Alpha Technologies GmbH
Hansastrasse 8 D-91126 Schwabach, Germany Tel: +49 9122 79889 0 Fax: +49 9122 79889 21
Alphatec Ltd.
339 St. Andrews St. Suite 101 Andrea Chambers P.O. Box 56468 3307 Limassol, Cyprus Tel: +357 25 375 675 Fax: +357 25 359 595
Alpha Brasil Serviços e Comércio Ltda.
Rua Manuel Augusto de Alvarenga, 155 São Paulo, SP - Brasil Tel: +55 11 2476 0150 Fax: +55 11 2476 0150
Technologies Argus First de Mexico
Anatole France Num. 17 Colonia Polanco 11560, México D.F. Tel: +52 55 5280 6990
Alpha TEK ooo
Khokhlovskiy Pereulok 16 Stroenie 1, Office 403 Moscow, 109028 Russia Tel: +7 495 916 1854 Fax: +7 495 916 1349
Alphatec Baltic
S. Konarskio Street 49-201 Vilnius, LT-03123 Lithuania Tel: +370 5 210 5291 Fax: +370 5 210 5292
Visit us at www.alpha.ca
Due to continuing product development, Alpha Technologies reserves the right to change specifications without notice. Copyright © 2011 Alpha Technologies. All Rights Reserved. Alpha® is a registered trademark of Alpha Technologies.
Loading...