Allstar Products Group MH5011S, MJ5011S User Manual

Page 1
INSTALLATION AND
OWNER’S MANUAL
MJ5011S & MH5011S
MS SERIES JACKSHAFT COMMERCIAL VEHICULAR
DOOR OPERATORS
As of date of manufacture, meets all ANSI/UL 325 Safety Requirements for Vehicular door operators
Serial #:
Date Installed:
Your Dealer:
100771
READ THIS MANUAL
CAREFULLY BEFORE
INSTALLATION OR USE.
Page 2
TABLE OF CONTENTS
Product Features ...........................................................................................................3
Jackshaft Operator Applications..................................................................................3
Preparation ....................................................................................................................4
Figure 1 - Component Identification Pictorial..............................................................4
Important Installation Warnings (Things To Do Before & During Installation) .........5
Table 1 - Component Identification Listing..................................................................5
Installation Instructions ...........................................................................................6-12
Figure 2 - Operator Footprint........................................................................................6
Figure 3 - Release/Hand Chain Wall Bracket Installation ...........................................7
Figure 4 - Mounting Positions ......................................................................................7
Figure 5 - Operator Dimensions - Model M50JF..........................................................8
Figure 5A - Operator Dimensions - Model M50JH.......................................................8
Setting The Limits .........................................................................................................9
Figure 6 - Limit Adjustment ..........................................................................................9
Electrical Wiring Instructions .....................................................................................10
Figure 7 - Power Connections ....................................................................................10
Figure 8 - Pneumatic Door Edge Installation.............................................................11
Figure 9 - Pneumatic / Foam Door Edge & Photoelectric Wiring ............................. 11
Figure 11 - 3 Button Station Wiring............................................................................12
Figure 12 - Single Button / External Interlock Wiring................................................12
Turning On Power to the Operator.............................................................................12
Operation and Adjustment Instructions ...............................................................13-18
Important Safety Instructions for Owner ...................................................................13
Clutch Adjustment.......................................................................................................14
Brake Adjustment........................................................................................................15
Setting the Switch Selectable Operation Modes .......................................................15
Setup Modes ................................................................................................................17
Testing .........................................................................................................................18
Maintenance ................................................................................................................18
Wiring Diagram............................................................................................................19
Warranty.......................................................................................................................20
2
READ THESE STATEMENTS CAREFULLY AND FOLLOW THE
The Warning and Caution boxes throughout this manual are there to protect you and
your equipment. Pay close attention to these boxes as you follow the manual.
WARNING
Indicates a MECHANICAL
hazard of INJURY OR
DEATH. Gives instructions
to avoid the hazard.
INSTRUCTIONS CLOSELY.
CAUTION
Indicates a MECHANICAL hazard
of DAMAGE to your operator or
equipment. Gives instructions to
avoid the hazard.
WARNING
Indicates an ELECTRICAL
hazard of INJURY OR
DEATH. Gives instructions
to avoid the hazard.
CAUTION
Indicates an ELECTRICAL hazard
of DAMAGE to your operator or equipment. Gives instructions to
avoid the hazard.
Page 3
3
PRODUCT FEATURES
The purpose of this booklet is to provide assembly,
installation and operation information concerning Allstar
Model MJ5011S & MH5011S (MS Series) Commercial
Vehicular Garage Door Operators and related Accessory
Products.
NOTICE
IT IS IMPORTANT THAT THIS INSTRUCTION
MANUAL BE READ AND UNDERSTOOD
COMPLETELY BEFORE INSTALLATION OR
OPERATION IS ATTEMPTED. IT IS INTENDED
THAT THE INSTALLATION OF THIS UNIT WILL BE
DONE ONLY BY PERSONS TRAINED AND
QUALIFIED IN THE INSTALLATION, ADJUSTMENT
AND SERVICE OF COMMERCIAL OVERHEAD
DOORS AND DOOR OPERATORS AND BY
QUALIFIED ELECTRICIANS.
NOTICE
THE IMPORTANT SAFEGUARDS AND
INSTRUCTIONS IN THIS MANUAL CANNOT
COVER ALL POSSIBLE CONDITIONS AND
SITUATIONS WHICH MAY OCCUR DURING ITS
USE. IT MUST BE UNDERSTOOD THAT COMMON
SENSE AND CAUTION MUST BE EXERCISED BY
THE PERSON(S) INSTAL- LING, MAINTAINING
AND OPERATING THE EQUIPMENT DESCRIBED
HEREIN. DO NOT USE THIS EQUIPMENT FOR
ANY OTHER THAN ITS INTENDED
PURPOSE - OPERATING OVERHEAD
COMMERCIAL VEHICULAR GARAGE DOORS.
STANDARD FEATURES
Solid State Controls: The Allstar MJ5011S & MH5011S
operators employ solid state technology with advanced standard features to provide for a complete commercial door operating system.
MS SERIES DOOR OPERATOR APPLICATIONS:
Jackshaft operators are intended for commercial and industrial use to raise or lower sectional overhead doors by chain coupling or direct coupling to the door shaft. Jackshaft operators are suitable where all or part of the door remains in a vertical position when fully open such as doors with at least 18 inches of lift clearance or full vertical lift doors. MS Series Jackshaft operators may also be used with certain roll up service doors and grills when appropriately sprocketed (consult factory).
A jackhaft operator DOES NOT LOCK THE DOOR IN ITS CLOSED POSITION. However, because the cross-header shaft is prevented by the operator from turning, the torsion springs provide no assistance in lifting the door should an attempt be made to raise it manually.
The MS Series jackshaft operators are used in the following applications:
- Intermittent Duty, Limited Cycle Commercial
installations only
- Rate of operation shall not exceed 10 cycles of
opening and closing per hour, maximum 60 cycles per day.
- Indoor Use Only
- Up to 14 foot high doors with a maximum area of
196 square feet, maximum area slightly higher for lighter doors - consult factory
- Use with foam/pneumatic reversing door edge or
photoelectric device - REQUIRED where the 3­button station is out of sight of the door, or any other automatic, remote or manual control is used to activate the door
Limit Switches: Driven limit switches, easily adjusted
over a wide range. The motor may be removed without affecting the limit switch adjustments.
Manual Release: Permits manual operation of the door
in the event of a power failure. The Model MH511S is equipped with a chain hoist to aid in manual operation.
Control Circuit: Connection terminals for a standard
three button Open, Close and Stop control station at 5 Volts DC. The motor control board features a built-in 3 button station for test purposes.
Connections For Auxiliary Entrapment Protection Devices:
provided to connect an Allstar Safe-Finish™ or Access Alliance Safe-Finish II™ monitored photo-beam system. Additional connection terminals for a Normally Open and Normally Closed reversing devices such as foam or pneumatic reversing door edge components or a three wire photo-beam are provided.
For the ultimate in protection, terminals are
Constant Contact To Close: Standard operating mode
(C2), programmable to Momentary Contact To Close (B2) and four additional operational modes.
OPTIONAL FEATURES:
Digital Radio Controls: Open, Close and Stop
operation. Radio units are available to control up to 27 doors from one transmitter.
Timer to Close Operation: Two of the
programmable operation modes (T & TS), closing delay is adjustable from 5 seconds (factory set at 30 seconds) to 5 minutes in five second intervals.
Delay on Reverse: Factory set to 0.6 seconds,
adjustable to 2 seconds.
Keyless Entry System: Connection terminals
provided for hard wired or wireless keyless entry systems.
Page 4
PREPARATION
WARNING
ELECTRIC DOOR OPENERS ARE DESIGNED
FOR DOORS IN GOOD WORKING CONDITION,
PROPERLY COUNTERBALANCED AND
PROPERLY ADJUSTED IN ACCORDANCE
WITH THE DOOR MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
Before starting the installation of the operator, the door must be in good working condition and properly counterbalanced. Inspect the door and track for loose or missing hardware. Test the door manually for balance and ease of operation. Lubricate door hinges and rollers. If necessary, employ a qualified technician to adjust the springs for proper counterbalance of the door.
Stops should be installed at the top end of each track to prevent the possibility of the door rollers moving beyond the ends of the track.
If the cross header shaft is made from hollow tubing rather than solid rod, it is recommended that it be plugged with a short length of solid bar for a more secure installation of the shaft sprocket or flange coupler.
Before removing the operator powerhead from the shipping
4
carton, inspect the nameplate on the cover of the operator control box to verify that it is the correct model for the intended application and that the voltage and phase are in accordance with electrical power provided at the job site. If the operator was ordered with the optional chain hoist, Model MH5011S, see that it is so equipped. A chain hoist CANNOT be added in the field.
Warning: Rope off the area to keep personnel and vehicles clear of the door and floor space in the vicinity of the operator during the installation.
WARNING
SPRINGS ARE SUBJECT TO VERY HIGH FORCES AT ALL TIMES AND
ADJUSTMENTS MUST BE MADE
ONLY BY A QUALIFIED
PROFESSIONAL DOOR INSTALLER.
WARNING
REMOVE OR DISABLE ANY LOCKING
DEVICES FROM DOOR AND REMOVE
ALL ROPES
COMPONENT IDENTIFICATION
107170-2
Page 5
5
WARNING
IMPORTANT INSTALLATION NOTES
TO REDUCE THE RISK OF SEVERE INJURY OR DEATH: READ AND FOLLOW ALL
INSTALLATION INSTRUCTIONS!
Install only on a properly balanced garage
door. An improperly balanced door could cause severe injury. Have a qualified service person make repairs to cables, spring assemblies and other hardware before installing the opener.
Remove all ropes and remove or make
inoperative all locks (unless mechanically and/or electrically interlocked to the power unit) that are connected to the garage door before installing the opener.
Lightweight doors (fiberglass, aluminum
etc.) must be reinforced to avoid door damage. Check the door manufacturer’s instruction manual for a bracing procedure or the availability or a Reinforcement Kit.
Allstar Model MJ5011S and MH5011S are
Commercial Vehicular Door Operators and as such are NOT recommended for pedestrian traffic. In installations where it is known that pedestrians will be nearby ensure a pedestrian door is available for entrance and exit to the building. In addition YOU MUST install an auxiliary entrapment protection device (reversing door edge or photoelectric beam device) as part of the compete operator system.
Connect an auxiliary entrapment protection
device (reversing edge or photoelectric device across the door opening). A device of this type is STRONGLY ADVISED FOR ALL commercial operator installations. An auxiliary entrapment protection device is REQUIRED when the three button control station is out of sight of the door or any other automatic or manual control is used.
Install the opener at least 8 feet or more
above the floor.
Do not connect the opener to the source of
power until instructed to do so.
Locate the control station:
a) within sight of the door and;
b) at a minimum height of five feet above
the floor and;
c) away from all moving parts of the
door.
Do not overtighten the clutch adjustment to
compensate for a poorly working door.
Securely attach any WARNING signs or
placards to either the door or above the control station as directed.
After installing the opener, all safety
features must be tested for proper operation (see page 18).
COMPONENT IDENTIFICATION LISTING
ITEM # PART# DESCRIPTION QUAN.
1 Operator Power Head 1 2 005031 3 Button Station 1 3 009062 30 Tooth Sprocket, 1” Bore, 1/4 Key 1 4 009061 20 Tooth Sprocket, 1” Bore, 1/4 key 1 5 105193 Release/Hand Chain Wall Bracket 1
—— AR - As Required
ITEM # PART# DESCRIPTION QUAN
6 100413 1/4” Square Key 2 7 006119 5/16-18 x 1 Square Head Set Screw 4 8 009249 Release Chain AR 9 100315 #3 Hand Chain - Precut to 26 Ft. 1 10 009239 Drive Chain to Door Shaft, 4 Ft. 1
Page 6
INSTALLATION INSTRUCTIONS
SPRINGS, PULLEYS, CABLES AND MOUNTING HARDWARE USED TO
BALANCE YOUR GARAGE DOOR ARE UNDER EXTREME TENSION AT ALL
TIMES AND CAN CAUSE SEVERE INJURY OR DEATH IF DISTURBED.
WARNING
6
DO NOT ATTEMPT ADJUSTMENT.
Figure 4, page 7 illustrates several positions suitable for
mounting the operator; right hand or left hand, either wall mount or ceiling mount.
CHAIN COUPLING MOUNTING
Refer to Figure 2 (below), Figure 1, page 4 and Figures 5 and 5A, page 8 for component identification and the operator mounting slot locations. Place the sprockets [ 3 ] and [ 4 ] on the chosen side of the torsion shaft of the door and on the corresponding end of the output shaft of the operator. The sprockets should be kept as close as possible to the bearings. Fasten the connecting link to each end of the door chain and loop the chain over the sprocket [ 3 ] on the torsion shaft. Temporarily suspend the operator in its mounting position using the chain over the sprocket [ 4 ] at one end of the jackshaft and a rope or chain at the mid point (to support the operator weight). With the chain tight and straight and the jackshaft parallel with the torsion shaft, trace the mounting slot on the mounting surface then lower the operator to the floor.
IT IS ESSENTIAL THAT THE SURFACE SUPPORTING THE OPERATOR BE RIGID AND SECURE. FAILURE TO PROVIDE A FIRM MOUNTING SURFACE WILL RESULT IN DAMAGE TO THE DOOR TORSION SHAFT AND THE PREMATURE FAILURE OF THE OPERATOR.
through the wall, then use lag bolts to fasten the operator to the mounting surface. Locate the four holes within the tracings of the slots made in the previous step at the positions which will allow for adjust-ment of the chain tension. After drilling the mounting holes and installing lag shields, if necessary, bolt the operator to the mounting surface but do not completely tighten the bolts at this time. Check the alignment of the sprockets, adjust their positions on the shafts if necessary and tighten the set screws securely on both sprockets. pulling downward on the operator to remove slack from the chain, tighten the four mounting bolts.
Inspect the installation. There should be no slack in the chain but neither should it be under severe tension which might shorten the life of the bearings. If there is any flexibility in the system due to construction of the surface supporting the operator or noticeable deflection of the door shaft, it is advisable to install a shaft support between the operator jackshaft and the door shaft to prevent the loss of limit settings due to the possibility of the chain jumping over the sprocket teeth. Shaft supports are available from the factory.
BEFORE PROCEEDING WITH THE OPERATOR INSTALLATION AND SETTINGS, MAKE A FINAL CHECK FOR TIGHTNESS OF ALL MOUNTING HARDWARE AND SET SCREWS.
If the construction permits, the operator should be mounted with 3/8 inch diameter bolts through the wall. If it is not feasible to go
Proceed to “Chain Hoist and Floor Disconnect Installation”.
107864
Figure 2
Page 7
7
INSTALLATION INSTRUCTIONS
CHAIN HOIST AND FLOOR DISCONNECT INSTALLATION
If the operator is furnished with a chain hoist (Model MH5011S),
pass the hand chain over the chain wheel and through the chain guides on the operator clutch shaft (opposite end from the large pulley). Fasten the ends of the chain together by opening and re­closing one link using two pairs of pliers. If the chain is too long (standard length for 16 foot high doors and below is 26 feet total length of chain), shorten it to the desired length using the method described above and discard the unused portion. Fasten the chain hoist holding bracket furnished with the operator to the wall approximately four feet from the floor. This bracket is also used to hold in place the release chain for both the chain hoist equipped units (MH5011S) and floor disconnect models (MJ5011S).
Figure 3
107174
Figure 4
Page 8
FIGURE 5 - OPERATOR DIMENSIONS - MODEL MJ5011S
100769
8
FIGURE 5A - OPERATOR DIMENSIONS - MODEL MH5011S
100771
Page 9
9
INSTALLATION INSTRUCTIONS
WARNING
TO AVOID RISK OF ENTRAPMENT AND
POSSIBLE DAMAGE TO THE DOOR AND
OPERATOR THE LIMITS MUST BE ADJUSTED
BEFORE APPLYING POWER TO THE
OPERATOR.
SETTING THE LIMIT SWITCHES
1) With the cover open on the electrical enclosure, reference Figure 6 below. There are two (2) switches (A and B) mounted to the ‘V’ bracket (F). The switches are activated by the two limit nuts (C and E) on the threaded shaft which move laterally along the shaft as the operator opens and closes the door. When a limit nut nears the end of the shaft it activates a switch, that send a message back to the motor control board to stop the door.
2) Depress the Limit Nut Retention Plate (D) so it disengages from the slots in the limit nuts and move the Limit nuts to the center of the threaded shaft.
3) Manually raise the door to a nearly open position.
4) Depress the limit nut retaining plate (D) so it disengages from the slots in the limit nuts. Turn the OPEN limit nut (C) on
the shaft until it engages the Open Limit Switch (B). You will need to listen for an audible click. Release the retaining bracket and be sure that it engages in slots of both limit nuts.
5) Manually lower the door to the fully closed position and repeat Step #3 with the Reverse Cutout Limit nut (E) and the Reverse Cutout Limit switch (A). The actual Close Limit position is a timed function whereas the door continues to run for a certain period of time after the Reverse Cutout Limit switch is activated. This amount of time (Close Limit Delay) is factory set to 0.32 seconds and will provide reversing cutout of approximately 4 inches from the floor for a door traveling at 12 inches per seconds. If the door fails to reverse when an object at least four inches high is placed in its path (see Testing, page
18) it may be necessary to adjust the Close Limit Delay time, see procedure on page 16 and 17.
6) Manually move the door to a half open position. With the door in a mid position there will be time to stop the door if something or someone were in the door path when initially starting the door.
7) A final limit adjustment will be necessary after the connection of the power supply in order to ensure the door stops at the proper Open and Close positions. If desired, a fine adjustment can be done as part of the final adjustment by loosening the screws holding the Limit Switches to the V bracket and moving the switch within the slots on the bracket.
D
C
A - REVERSE CUTOUT LIMIT SWITCH B - OPEN LIMIT SWITCH C - OPEN LIMIT NUT
E
F
A
B
D - LIMIT NUT RETAINING BRACKET E - REVERSE CUTOUT LIMIT NUT F - “V” BRACKET
Figure 6 - Limit Assembly
Page 10
INSTALLATION INSTRUCTIONS - ELECTRICAL WIRING
10
WARNING
TO PREVENT THE RISK OF PERSONAL INJURY OR DEATH :
• DISCONNECT POWER AT THE FUSE BOX BEFORE PROCEEDING.
• ELECTRICAL CONNECTIONS MUST BE MADE BY A QUALIFIED INDIVIDUAL.
• OBSERVE LOCAL ELECTRICAL CODES WHEN WIRING THE OPERATOR.
WARNING: Allstar's MS Series operators have been designed and constructed for use with 115 Volts AC single phase, see Figure 7 below. Check the operator nameplate label on the control box cover for the proper voltage and phase. The application of an improper input voltage or phase will result in catastrophic failure to the internal electrical components.
Observe local electrical codes when wiring the operator.
When hard wiring, observe state and local electrical codes. A wiring diagram is attached to the inside of the control box cover. Connect the appropriate voltage and phase power leads to the appropriate terminals as per the wiring diagram and connect a ground wire to the grounding screw.
The wiring diagram attached inside the cover of the control box details all of the field wiring terminal connections for the operator. Always connect the wires to the push-button controls and auxiliary devices exactly as shown. Warning: Control voltage of the operator is 5 volts DC, Class 2.
115 VAC
L1
Single Phase
L2
Ground
Figure 7 - Power Connections
WARNING
WARNING
RISK OF ENTRAPMENT THAT MAY
RESULT IN SERIOUS PERSONAL INJURY OR
DEATH. DISCONNECT POWER TO THE
OPENER BEFORE AND DURING
INSTALLATION OF AN ACCESSORY
REVERSING DOOR EDGE OR
PHOTOELECTRIC DEVICE. DO NOT
RECONNECT POWER TO OPENER UNTIL
INSTRUCTED TO DO SO. ENSURE DOORWAY
IS CLEAR BEFORE STARTING TESTING OF
UNIT.
Do not run the power leads and control circuit wiring in the same electrical conduit.
Note: MS Series model operators are pre-wired for door reversing edge components. To comply with code requirements, the door reversing edge components must be installed and wired to the operator. Refer to Figure 8 Door Edge component installation and Figure 9 for Door Edge and photoelectric device wiring.
If an Allstar Safe-Finish™ or Access Alliance Safe-Finish II™ photo-beam is connected and the photo-beam detects an obstruction or becomes inactive, an opening door continues to open and a closing door stops, pauses and starts open. While in this mode, if a problem is detected while the operator is stopped, a close will require constant activation. If the photo-beam is attached and is properly working for 1 second, it will be auto detected and the monitored function will be turned on. Once the monitoring function is active, it will remain active even if the power is removed and the photo-beam is disconnected and power is restored. While in this mode, if a problem is detected while the operator is stopped, a close will require constant activation.
Operators which are equipped with a reversing edge circuit may have one or more additional means of control which should be wired in accordance with the diagram supplied in the operator and also illustrated in Figures 10 & 12. To add a second three button station, refer to Figure 11.
Number 22 gauge wire or heavier must be used for wiring the control stations and auxiliary control devices to the operator. Smaller gauge wire may cause operational problems, especially when multiple push-button stations are used or during summer months.
TO PREVENT THE RISK OF PERSONAL INJURY
AND/OR DAMAGE TO DOOR OR PROPERTY,
ONLY OPERATE DOOR CONTROL WHEN
DOOR IS IN CLEAR VIEW. IF CONTROL
STATION CANNOT BE LOCATED WHERE THE
DOOR IS VISIBLE OR IF ANY OTHER DEVICE IS
USED TO CONTROL THE DOOR AN AUXILIARY
ENTRAPMENT DEVICE (DOOR EDGE OR
PHOTOELECTRIC) MUST BE CONNECTED.
CAUTION
TO AVOID DAMAGE TO DOOR AND
OPERATOR ENSURE ALL DOOR LOCKS ARE
DISABLED.
USE AN INTERLOCK SWITCH IF A LOCK IS
REQUIRED TO RETAIN FUNCTIONALTY.
Page 11
11
DOOR EDGE INSTALLATION & WIRING
MOTOR
CONTROL
Figure 9
BOARD
COM
Door Edge and Photoelectric Wiring
See text on page 10 for operation when Safe-Finish™ or Access Alliance Safe-Finish II™ photo-beams are connected.
Figure 8
NO REV
STOPCLOSEOPEN
COM
STOP
OPEN
CLOSE
TB1
SINGLE
COM
PHOTO
NC REV
ILOCK
24 VAC
SAFE FINISH PHOTOBEAM
3-WIRE PHOTOBEAM
Note: When adding a
photocell device with a
Normally Closed output remove the factory installed jumper from the connection
terminals.
Page 12
INSTALLATION INSTRUCTIONS
P
12
R84
U5
PB1 PB2 PB3
PHOTO
NC REV
MOTOR
R2
R3
C25
CONTROL
BOARD
STOPCLOSEOPEN
COM
NO REV
STOP
C1
D12
PCB 112695 REV B TSLK
OPEN
CLOSE
Single 3 Button Station
Figure 10
D3
R65
C10
D2
U1
MOTOR
CONTROL
R38
R87
BOARD
R94
R95
R2
R3
C25
PB1 PB2 PB3
STOPCLOSEOPEN
NC REV
NO REV
U4
COM
R5
C3
C11
C9
R26
R29
STOP
R57
R25
RADIO
C24
24V
D8
COM
RM3
RM2
RM1
VCC
P7
R54
R55
R30
R56
C1 C8
D12
PCB 112695 REV B TSLK
OPEN
CLOSE
Multiple 3 Button Station
MOTOR
CONTROL
BOARD
TURNING ON THE POWER TO THE OPERATOR
CDOMCB 2005
c.p. ALLSTAR COR
TB1
COM
24 VAC
EXTERNAL INTERLOCK
Figure 11
D1
R93
R4
R8
C21
R24
P5
U5
Figure 12
Single Button and External Interlock Wiring
ILOCK
COM
SINGLE
PHOTO
Note: When adding an External Interlock remove the factory installed jumper from the connection terminals.
NOTE: It is now necessary to turn on the power in order to to change the Operating Mode (if applicable), program any changes desired to the operator’s other settings, check for proper operation, and finalize any adjustments to include the limit settings. Before
doing so, ensure that all mounting hardware are installed and properly tightened, that all electrical connections are per local code requirements, and that proper wiring practices have been followed. Also, double-check that all ropes have been removed from the door and
that the doorway is clear.
Page 13
13
OPERATION & ADJUSTMENT INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS FOR OWNER
TO REDUCE THE RISK OF SEVERE INJURY OR
WARNING
Understand all of the operating features of your door control system at the time of its installation. Your installing dealer will demonstrate them for you.
NEVER let children operate or play with door controls. Keep the Remote Control away from children.
ALWAYS keep a moving door in sight and keep people and objects away from the door area until the door is completely closed. NO ONE SHOULD CROSS THE PATH OF A MOVING DOOR.
TEST THE DOOR OPENER’S REVERSING FEATURE (where applicable) MONTHLY. The door MUST reverse upon contact with a 4” high object on the floor. After adjusting the force setting (clutch) or the limit of travel, ALWAYS RETEST the Opener. Failure to ADJUST THE OPENER PROPERLY may result in SERIOUS INJURY OR DEATH.
To protect the motor protector from tripping - Do not exceed 10 door cycles per hour.
DEATH: READ AND FOLLOW ALL INSTRUCTIONS!
IMPORTANT: The hardware box contains a caution label which states: “This door is operated by a light duty operator. To prevent the motor protector from tripping - Do not exceed 10 door cycles per hour.” Permanently install this label adjacent to the door, near the push button station, at the eye height of the average adult, approximately six feet above the above the floor.
DO NOT over adjust the force setting (clutch) to compensate for a poorly working door. See page 18 for procedure to check the door operation and page 14 for proper clutch adjustment.
If possible, USE THE MANUAL RELEASE only when the door is closed. Use caution when using the Release with the door open. WEAK OR BROKEN SPRINGS MAY ALLOW THE DOOR TO CLOSE RAPIDLY, CAUSING SEVERE INJURY OR DEATH.
KEEP THE GARAGE DOOR PROPERLY BALANCED. See the door owner's manual. An improperly balanced door MAY CAUSE SEVERE INJURY OR DEATH. Have a QUALIFIED SERVICE PERSON MAKE REPAIRS TO CABLES, SPRING ASSEMBLIES AND OTHER HARDWARE.
SAVE THIS INSTRUCTION MANUAL FOR END USER.
Inspect and maintain your door system as described in this manual.
WARNING
WARNING
AVOID ELECTROCUTION:
DO NOT ROUTE LOW VOLTAGE WIRES IN
SAME CONDUIT AS HIGH VOLTAGE
WIRES. FOLLOW ALL LOCAL
ELECTRICAL CODES OR THE NATIONAL
ELECTRICAL CODE (NEC).
FAILURE TO TEST REVERSING SYSTEM COULD RESULT IN DEATH OR SERIOUS
INJURY. TEST THIS SYSTEM ONCE A MONTH
.
Page 14
OPERATION & ADJUSTMENT INSTRUCTIONS
CLUTCH ADJUSTMENT
14
WARNING
RISK OF ENTRAPMENT THAT MAY RESULT
IN SERIOUS PERSONAL INJURY OR DEATH.
DISCONNECT POWER TO THE OPENER
BEFORE SERVICING OR MAKING
ADJUSTMENTS. ENSURE DOORWAY IS
CLEAR BEFORE STARTING TESTING OF UNIT.
ALWAYS DISCONNECT POWER TO
OPERATOR BEFORE SERVICING OR MAKING
ADJUSTMENTS.
The clutch serves to protect the door, the electric operator and other equipment from undue stress or damage caused by starting forces and/or an obstruction to the door. It should be set no tighter than is necessary to smoothly and consistently move the door throughout its full range of travel. When properly set, it will slip freely if the door should encounter an obstruction, and it should be possible to stop the travel of the door by hand.
WARNING: Before adjustment remove power to the
operator.
To adjust the clutch, loosen the jamb nut, , and turn the adjusting nut, as shown at right Make adjustments in 1/4 turn increments. Always re-tighten the jamb nut before running the operator to prevent clutch from changing its setting.
NEVER COMPRESS CLUTCH SPRING BEYOND
POINT LIMITED BY THE DESIGN OF THE
OPERATOR OR REPLACE IT WITH A
HEAVIER SPRING
Due to changing conditions of the door and normal wear, it may be necessary to occasionally readjust the clutch to obtain dependable operation.
WARNING: BEFORE DOING SO BE CERTAIN THAT THE DOOR IS IN GOOD WORKING CONDITION, PROPERLY COUNTERBALANCED AND THAT THE CLUTCH IS NOT SLIPPING BECAUSE OF LOOSE OR MISSING HARDWARE, BINDING IN THE TRACK, RUBBING AGAINST THE DOOR STOPS OR DEFECTIVE OR MISADJUSTED SPRINGS. ANY SERVICE
CAUTION
CAUTION
REQUIRED TO THE DOOR, DOOR SPRINGS OR DOOR OPERATOR MUST BE PREFORMED BY A QUALIFIED PROFESSIONAL DOOR INSTALLER.
The clutch pad will wear during normal operation and should be replaced when it becomes difficult or impossible to sufficiently tighten the clutch to obtain smooth operation of the door when it is in good working condition. To replace the clutch pad, first loosen the motor mounting bolts and remove the V-belt then the clutch adjusting nuts, spring and clutch pulley. Check condition of V-belt before reassembly and replace if required. After reassembly, adjust clutch as described above.
107101
Figure 13
WARNING
IMPROPER ADJUSTMENT OF CLUTCH
SETTING COULD CAUSE ENTRAPMENT,
INJURY OR DEATH.
SET CLUTCH ADJUSTMENT FOR JUST
ENOUGH FORCE TO OPERATE THE DOOR RELIABLY, BUT NO STRONGER. Contact a service professional to correct any binding,
sticking or other door problems. DO NOT
OVER-ADJUST CLUTCH SETTING TO
COMPENSATE FOR A POORLY WORKING
DOOR.
Page 15
15
US
LD4
OFF
S4
S3
S2
S1
R61
R60
R5
SW1
R83
R28
R27
Brake Adjustment
The brake is adjusted at the factory and may need periodic adjustment for wear. When adjustment becomes necessary see Figure 14 at right for the adjustment procedure.
OPERATION & ADJUSTMENT INSTRUCTIONS
BRAKE ADJUSTMENT
Figure 14
SETTING THE SWITCH SELECTABLE OPERATING MODES
Changing the Switch Selectable Operation Modes
The following modes are selected by setting the on-board dip switches, Figure 15 at right shows where the switches are located on the operator control board. For each Operational Mode, the switches are set to either ON or OFF according to the table below (the table is reproduced on page 16 also). For all the modes, if a reversing device is attached, it will function as noted. If a monitored reversing device has been recognized and becomes inactive then the mode will default to constant pressure activation for close regardless of the dip switch setting. The switches must be set to one of the six Operational Mode combinations for the operator to function.
C2 Operation (Factory default)
Open Button: Momentary activation; open override of closing door. Close Button: Constant activation, door will stop when button is released. Stop Button: Momentary activation; stops open, close or reverse action. Single Button: Momentary activation to open; open override of closing door. Reverse: Momentary activation will reverse a closing door, reverse to full open (ignores mid-stop) unless stopped by stop pushbutton input. Mid-Stop: Activation stops an opening door; momentary contact of open button at mid stop will restart door to full open position; if door is moving open, constant pressure on open button will bypass mid-stop. Auto Close Timer: N/A.
Settable
P4
Switches
Location
Figure 15
Operating
Mode
C2 Operation OFF OFF OFF OFF
B2 Operation ON OFF OFF OFF
D1 Operation OFF ON OFF OFF
E2 Operation ON ON OFF OFF
TS Operation OFF OFF ON OFF
T Operation ON OFF ON OFF
Switch 1 Switch 2 Switch 3 Switch 4
HIGH VOLTAGE
K6
P1
TR3
MO4
MO3
MO2
MO1
R89
TR1
ILK
24V
COM
R48
C13
TR2
R52
C14
TR4
R31
EDGE
FRA
VCC
C30
COM
S1
24V
R58
P6
C12
Q1
C7
D1
R8
R24
CDOMCB 2005
c.p. ALLSTAR CORP.
P5
TB1
COM
ILOCK
24 VAC
SINGLE
P2 P3
R49
R62
R47
R51
R19
R17
R13
R1
RO1
R85
R11 R12
R90
R93
R4
C21
COM
OLS
CLS
COM
R10
R22
C16
C6
R20
R18
R14
R21
C2
R16R15
R7R6
R84
U5
PHOTO
COM
POWER
PB1 PB2 PB3
NC REV
MOTOR CONTROL BOARD
K2K4K3K5
STATUS
LD2
R34
R33
R23
R9
R82
D3
R65
C10
D2
U1
R38
R87
R94
R95
R2
R3
C25
NO REV
SW1
S4
S3
LD3
LD4
S2
OFF
S1
R27
R28
C3
C11
C9
U4
STOPCLOSEOPEN
COM
R53
R83
R61
R46
R60
R45
R5
R57
R25
RADIO
C24
24V
D8
COM
RM3
RM2
RM1
VCC
P7
R54
R55
R30
R26
R29
R56
C1 C8
D12
PCB 112695 REV B TSLK
STOP
OPEN
CLOSE
Page 16
OPERATION AND ADJUSTMENT INSTRUCTIONS
16
B2 Operation
Open Button: Momentary activation; open override of closing door.
Close Button: Momentary activation. Stop Button: Momentary activation; stops open, close or reverse
action. Single Button: Momentary activation to open; open override of closing door, closes door from mid-stop or open limit. Reverse: Momentary activation will reverse a closing door, reverse to full open (ignores mid-stop) unless stopped by stop pushbutton input. Mid-Stop: Activation stops an opening door; momentary contact of open button at mid stop will restart door to full open position; if door is moving open, constant pressure on open button will bypass mid-stop. Auto Close Timer: N/A
.
D1 Operation
Open Button: Constant activation; open override of closing door. Close Button: Constant activation, door will stop when button is released. Stop Button: Momentary activation; stops open, close or reverse action (not required).
Single Button: N/A. Reverse: Momentary activation will stop a closing door. Mid-Stop: Activation stops an opening door; after the door stops
at the mid stop, constant contact of open button at mid stop will restart door to full open position. Auto Close Timer: N/A.
E2 Operation (roll-back)
Open Button: Momentary activation; open override of closing door. Close Button: Constant activation, door will reverse to full open (ignores mid-stop) when button is released. Stop Button: Momentary activation; stops open, close or reverse action.
Single Button: N/A. Reverse: Momentary activation to reverse a closing door,
reverse to full open (ignores mid-stop) unless stopped by stop pushbutton input. Mid-Stop: Activation stops an opening door; momentary contact of open button at mid stop will restart door to full open position; if door is moving open, constant pressure on open button will bypass mid-stop. Auto Close Timer: N/A
TS Operation
Open Button: Momentary activation; open override of closing door.
Close Button: Momentary activation. Stop Button: Momentary activation; stops open, close or reverse
action. Single Button: Momentary activation to open; open override of closing door, closes door from mid-stop or open limit. Reverse: Momentary activation will reverse a closing door, reverse to full open (ignores mid-stop) unless stopped by stop pushbutton input. Mid-Stop: Activation stops an opening door; momentary contact
Operating
Switch 1 Switch 2 Switch 3 Switch 4
Mode
C2 Operation OFF OFF OFF OFF
B2 Operation ON OFF OFF OFF
D1 Operation OFF ON OFF OFF
E2 Operation ON ON OFF OFF
TS Operation OFF OFF ON OFF
T Operation ON OFF ON OFF
of open button at mid stop will restart door to full open position; if door is moving open, constant pressure on open button will bypass mid-stop. Auto Close Timer: Closes door from mid-stop or open limit after pre-set time. Stop will deactivate the auto close timer. Open will reactivate the auto close timer or reset the auto close timer when the door is at the mid-stop or open limit. Single button will reset the auto close timer from the mid-stop or open limit. Reverse will reactivate the auto close timer or reset the auto close timer when the door is at the mid-stop or open limit.
T Operation, Dip-Switch Setting
Open Button: Momentary activation; open override of closing door.
Close Button: Momentary activation. Stop Button: Momentary activation; stops open, close or reverse
action. Single Button: Momentary activation to open; open override of closing door, closes door from mid-stop or open limit. Reverse: Momentary activation will reverse a closing door, reverse to full open (ignores mid-stop) unless stopped by stop pushbutton input. Mid-Stop: Activation stops an opening door; momentary contact of open button at mid stop will restart door to full open position; if door is moving open, constant pressure on open button will bypass mid-stop. Auto Close Timer: Closes door from mid-stop or open limit after pre-set time. Stop will deactivate the auto close timer. Open will reactivate the auto close timer or reset the auto close timer when the door is at the open limit. Single button will reset the auto close timer from the mid-stop or open limit. Reverse deactivates the auto close timer if the door is closing. Reverse will reset the auto close timer at the mid-stop or open limit if the auto close timer has not been previously deactivated.
Page 17
17
OPERATION & ADJUSTMENT INSTRUCTIONS
SETUP MODES
Setup Modes
Various operating characteristics can be modified via the setup modes. The operator is moved to the close limit position and the on-board dip switches (see Figure 15) are set according to the table at right to enter a Setup Mode. The on board OPEN and STOP buttons are used to modify the characteristic. Once set, the values are stored in non-volatile memory. These values are set to factory defaults that should be satisfactory for many applications. All values as described here can be reset to the factory defaults as follows:
Remove 24 VAC power from the control board. Press and hold the on-board stop button. Re-apply 24 VAC while holding the on-board stop button.
After completing the procedure to modify the operating characteristic the switches must be returned to the originally set Operating Mode setting (see section previous).
TEMPORARILY
Delay on Reverse Setup
To help prevent stress on the door components, this feature allows for a delay time between the door stopping and reversing when a command to reverse is received as the door is closing. The factory default time is 0.75 seconds; the minimum time is
0.4 seconds; the maximum time is 2 seconds.
After moving the door to the close position and temporarily setting the switches to the appropriate settings in the table, pressing STOP will reset the time to the minimum setting.
Every time OPEN is pressed, 200 mS is added to the time (up to the maximum).
Changing the dip-switch setting to any other setting will save the new time. Return the dip switches to the originally set Operating Mode setting (see section previous).
Close Limit Delay Setup
To provide for irregularities in the floor, this feature allows for the door to continue to travel down after the Reverse Cutout Limit is activated. The factory default time is 0.32 seconds; the minimum time is 0.12 seconds; the maximum time is 0.66 seconds.
After moving the door to the close position and temporarily setting the switches to the appropriate settings in the table, pressing STOP will reset the time to the minimum setting.
Every time OPEN is pressed, 0.02 seconds are added to the time (up to the maximum).
Changing the dip-switch setting to any other setting will save the new time. Return the dip switches to the originally set Operating Mode setting (see section previous).
Mid-Stop Limit Setup
This features provides a timing function to stop a door as it is traveling open at a Mid Stop position instead of the full open position. The door can then be moved to the full open position if desired by pressing the Open button. A single button input when the door is at the mid stop position will cause the door to begin moving in the close direction. The factory default is not set; the minimum run time to mid-stop limit is 6 seconds.
Setup Mode Switch 1 Switch 2 Switch 3 Switch 4
Delay on Reverse ON ON ON ON
Close Limit Delay OFF ON ON ON
Mid-Stop Limit ON OFF ON ON
Auto Close Timer OFF OFF ON ON
Maximum Run Time OFF ON OFF ON
After moving the door to the close position and temporarily setting the switches to the appropriate settings in the table, pressing STOP will remove the mid-stop limit setting.
Pressing OPEN will start the door open. When the door reaches the desired mid-stop position, press STOP.
Changing the dip-switch setting to any other setting will save the mid-stop limit position. Return the dip switches to the originally set Operating Mode setting (see section previous).
Note: The door must move a sufficient distance to fully disengage the Reverse Cutout Limit nut from the Reverse Cutout Limit switch to set the mid-stop limit.
Auto Close Timer Setup
This feature allows for a modification of the amount of time between the door reaching either the Mid Stop or the Full Open position and automatically starting in the close direction. The Auto Close feature is only active when the operator is set to the T or TS Operating Mode (see section previous). The factory default is 30 seconds; the minimum time is 5 seconds; the maximum time is 5 minutes.
After moving the door to the close position and temporarily setting the switches to the appropriate settings in the table, pressing STOP will clear and turn off the auto close timer.
Every time OPEN is pressed, 5 seconds is added to the time.
Changing the dip-switch settings to any other settings will save the new time. Return the dip switches to the originally set Operating Mode setting (see section previous).
Maximum Run Time Setup
This feature provides for a maximum amount of time the motor will be energized after an input is recognized. The factory default time is 30 seconds; the maximum time is 60 seconds.
After moving the door to the close position and temporarily setting the switches to the appropriate settings in the table, pressing STOP will reset the time to the factory default setting.
Pressing OPEN will start the door open. The run time will be recorded when the door reaches the open limit. To prevent nuisance problems, 0.75 seconds are added to this time. Pressing stop before the door reaches the open limit will stop the door and reset the time to the factory default.
Changing the dip-switch setting to any other setting will save the new time Operating Mode setting (see section previous).
. Return the dip switches to the originally set
Page 18
OPERATION AND ADJUSTMENT INSTRUCTIONS
TESTING
18
Following installation, the operator MUST be tested and respond correctly to all controls as specified on the wiring diagram. KEEP personnel and equipment clear of the area beneath the door when performing the tests. When testing the 3-button wall station, first observe that each button operates the door in the direction indicated and that the STOP button performs that function. With the door stopped at its full open position, the OPEN button should be inoperative. This should be verified and, likewise, the CLOSE button should be inoperative with the door fully closed.
Certain operator control circuits use only a single button or a two button control station and may be designed to function differently than the more common three-button circuit described above. Test the controls in accordance with the description of operation as indicated on the wiring diagram.
Observe the door when traveling in each direction for smoothness of operation. Test the setting of the clutch by restraining the door by hand. The clutch should slip. Re-check the limit settings. The door should close tightly at the floor without excessive impact. Likewise, it should fully clear the door opening without the carrier striking the stops on the rail.
The MS Series operators are equipped with a reversing edge circuit and to conform with code need to be connected to a pneumatic edge or foam edge door components. To test it for proper reversal, place an object beneath the leading edge of the
door. The door should stop, pause and reverse when it comes into contact with the object provided the height of the object exceeds the cut out point set for the Reversing Cutout Limit switch (approximately four inches).
CAUTION
DO NOT STAND UNDER DOOR
TO TEST REVERSING EDGE.
USE A STURDY CORRUGATED BOX
OR OTHER SIMILAR OBJECT.
If the operator is equipped with other means of control, such as additional 3 button stations or radio controls, each of these should be tested separately for proper operation.
To test the manual disconnect first move the door to the fully closed position. Then disconnect the power to the operator. Manual door operation mode should engage when the release chain is pulled. The door can then be manually opened or closed by physically moving the door (Model MJ5011S) or using the hoist chain (Model MH5011S). If it is difficult to engage and/or the jackshaft to doorshaft chain appears to be under compression, reset the CLOSE limit slightly to reduce the door travel in the close direction.
WARNING
FAILURE TO TEST REVERSING SYSTEM COULD RESULT IN DEATH OR SERIOUS
INJURY. TEST THIS SYSTEM ONCE A MONTH.
MAINTENANCE
Normally, very little maintenance is required. A monthly visual inspection must be made for loose or missing hardware and for excessive slack in the V-Belt and jackshaft chain. The clutch must be tested periodically and adjustments made if necessary (see Figure 13, page 14). The brake is adjusted at the factory and may need periodic adjustment for wear. When adjustment becomes necessary see Figure 14 on page 15 for the adjustment procedure.
Test the reversing edge circuit at least once a month by permitting the door to contact an obstruction while closing.
WARNING
ALWAYS DISCONNECT POWER TO
THE OPERATOR BEFORE SERVICING,
CONNECTING ACCESSORY DEVICES
OR MAKING ADJUSTMENTS.
CAUTION
DO NOT STAND UNDER DOOR TO TEST REVERSING
EDGE - USE A CORRUGATED BOX
OR OTHER SIMILAR OBJECT
Lubrication of the operator is not required. It is important, for trouble free service from the operator, that the door be kept free from binding, properly counter balanced and periodically lubricated. An annual inspection of the door by a qualified
overhead door professional is recommended.
Warning: Repairs and adjustments to the door and operator should be performed only by someone qualified to service commercial overhead doors and operators.
Page 19
19
WIRING DIAGRAM
BRAKE
L1
N
GROUND
LINE
24 VAC
TRANSFORMER
BROWN
BLACK
WHITE
YELLOW
P4
HIGH VOLTAGE
P1
EDGE
P6
CDOMCB 2005
c.p. ALLSTAR CORP.
TB1
WHITE
RED
BLUE
GREY
GREY
ORANGE ORANGE
CLOSE LIMIT
COM
NO
COM
NO
OPEN LIMIT
K6
TR3
MO4
MO3
MO2
MO1
R89
ILK
TR1
24V
COM
R48
C13
TR2
R52
C14
TR4
R31
FRA
VCC
C30
COM
24V
R49
R62
R47
R51
R19
R17
R13
R1
RO1
R85
S1
R11 R12
R58
C12
Q1
R90
C7
R93
D1
R4
R8
C21
R24
P5
P2 P3
COM
OLS
CLS
COM
R10
R22
C16
C6
R20
R18
R14
R21
C2
R16R15
R7R6
R84
U5
PB1 PB2 PB3
POWER
STATUS
LD2
R34
R33
R23
R9
R82
D3
R65
C10
D2
U1
R38
R87
R94
R95
R2
R3
C25
K2K4K3K5
S4
S3
LD4
LD3
S2
S1
R27
R28
C3
C11
C9
U4
STOPCLOSEOPEN
SW1
OFF
R83
R61
R60
R5
R25
C24
24V
D8
COM
RM3
RM2
RM1
VCC
R30
R26
R29
C1 C8
D12
OPERATING MODES SWITCH SETTING
C2: OFF OFF OFF OFF
R53
B2: ON OFF OFF OFF
R46
R45
D1: OFF ON OFF OFF
R57
E2: ON ON OFF OFF
RADIO
TS: OFF OFF ON OFF T: ON OFF ON OFF
P7
R54
R55
R56
PCB 112695 REV B TSLK
COM
YELLOW
24 VAC
YELLOW
INTERLOCK
SAFE FINISH PHOTOBEAM
3-WIRE PHOTOBEAM
ILOCK
SINGLE
COM
NC REV
PHOTO
NO REV
STOP
COM
OPEN
CLOSE
*
REMOVE FACTORY JUMPER IF USING NC REV INPUT
*
Page 20
NOTES
20
Manufacturer’s Limited Warranty
Linear LLC warrants its Allstar brand commercial door operators to be free from defect in material and workmanship for a period of two (2) years from the date of purchase. To obtain service contact your dealer.
To obtain service under this warranty the buyer must obtain authorization instructions for the return of any goods from Linear before returning the goods. The goods must be returned with complete identification, with copy of proof-of-purchase, freight prepaid and in accordance with Linear’s instructions or they will not be accepted. In no event will Linear be responsible for goods returned without proper authorization or identification.
Goods returned to Linear for warranty repair within the warranty period, which upon receipt by Linear are confirmed to be defective and covered by this limited warranty, will be repaired or replaced at Linear’s sole option, at no cost and returned pre-paid. Defective parts will be repaired or replaced with new or factory rebuilt parts at Linear’s sole option.
This limited warranty does not cover non-defect damage, damage caused by unreasonable use, damage caused by improper installation or care, vandalism or lightning, fire or excessive heat, flood or other acts of God (including, but not limited to misuse, abuse or alterations, failure to provide reasonable and necessary maintenance), labor charges for dismantling or reinstalling a repaired or replaced unit, or replacement batteries.
These warranties are in lieu of all other warranties, either expressed or implied. All implied warranties of merchantability and/or fitness for a particular purpose are hereby disclaimed and excluded. Under no circumstances shall Linear be liable for consequential, incidental or special damages arising in connection with the use or inability to use this product. In no event shall Linear’s liability for breach of warranty, breach of contract, negligence or strict liability exceed the cost of the product covered hereby. No person is authorized to assume for Linear any other liability in connection with the sale of this product.
This warranty gives you specific legal rights. You may also have other rights which vary from state to state. Warranty effective after October 1st, 2007.
For Information:
877-441-9300 800-421-1587 www.allstarcorp.com
This Door Operator is built in the USA and
P/N 190-112914 Rev. B August 2007 Copyright © 2007 Linear LLC
complies with all requirements of
ANSI/UL Standard 325.
Loading...