Allen-Bradley E200 User Manual

Page 1
User Manual
Original Instructions

E200 Electronic Overload Relay/Parameter Configuration Module

Bulletin Numbers 193, 592
Page 2

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Page 3

Table of Contents

Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Preface
Access Relay Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1
Overview Module Descriptions and Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Single-/Three-Phase Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Thermal Overload Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Current Monitoring Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Ground (Earth) Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Control Module Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Sensing Module Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Communication Module Features . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Expansion Digital I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Expansion Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Expansion Power Supply Features. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Expansion Operator Station Features . . . . . . . . . . . . . . . . . . . . . . . 15
External Current Transformer Options . . . . . . . . . . . . . . . . . . . . . 15
Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Test/Reset Button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Single/Three-Phase Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Modular Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Diagnostic Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Simplified Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Sensing Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Communication Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Optional Add-On Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Optional Expansion I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Optional Operator Station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Optional Expansion Bus Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . 20
Protection Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Standard Current-based Protection . . . . . . . . . . . . . . . . . . . . . . . . . 21
Ground Fault Current-based Protection. . . . . . . . . . . . . . . . . . . . . 21
Voltage- and Power-based Protection. . . . . . . . . . . . . . . . . . . . . . . . 21
Thermal-based Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Chapter 2
Diagnostic Station Navigation Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Displaying a Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Parameter Group Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 3
Page 4
Table of Contents
System Operation and Configuration
Linear List Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
System Info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Editing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Editing a Configuration Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . 26
Editing a Numeric Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Editing a Bit Enumerated Parameter . . . . . . . . . . . . . . . . . . . . . . . . 27
Programmable Display Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Display Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Stopping the Display Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Automatic Trip and Warning Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Chapter 3
Device Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Option Match. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Digital I/O Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Analog I/O Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Option Match Action (Parameter 233). . . . . . . . . . . . . . . . . . . . . . 33
Security Policy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
I/O Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Input Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Output Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Output Relay Configuration States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Output Relay Protection Fault Modes. . . . . . . . . . . . . . . . . . . . . . . 34
Output Relay Communication Fault Modes . . . . . . . . . . . . . . . . . 35
Output Relay Communication Idle Modes . . . . . . . . . . . . . . . . . . 36
Expansion Bus Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Emergency Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Diagnostic Station User-defined Screens . . . . . . . . . . . . . . . . . . . . . . . . 39
Display Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Analog I/O Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Analog Input Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Analog Output Channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Analog Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Introduction to Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Chapter 4
Operating Modes Overload Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Overload (Network) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Overload (Operator Station) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Overload (Local I/O) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Overload (Custom). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Non-reversing Starter Operating Modes. . . . . . . . . . . . . . . . . . . . . . . . . 53
Non-reversing Starter (Network) . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Non-reversing Starter (Network) with Feedback . . . . . . . . . . . . . 54
Non-reversing Starter (Operator Station). . . . . . . . . . . . . . . . . . . . 56
4 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 5
Table of Contents
Non-reversing Starter (Operator Station) with Feedback . . . . . 58
Non-reversing Starter (Local I/O) – Two-wire Control. . . . . . . 59
Non-reversing Starter (Local I/O) –
Two-wire Control with Feedback. . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Non-reversing Starter (Local I/O) – Three-wire Control . . . . . 62
Non-reversing Starter (Local I/O) –
Three-wire Control with Feedback. . . . . . . . . . . . . . . . . . . . . . . . . . 64
Non-reversing Starter (Network & Operator Station) . . . . . . . . 65
Non-reversing Starter (Network & Operator Station)
with Feedback. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Non-reversing Starter (Network & Local I/O) –
Two-wire Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Non-reversing Starter (Network & Local I/O) with Feedback –
Two-wire Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Non-reversing Starter (Network & Local I/O) –
Three-wire Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Non-reversing Starter (Network & Local I/O) with Feedback –
Three-wire Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Non-reversing Starter (Custom) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Reversing Starter Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Reversing Starter (Network). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Reversing Starter (Network) with Feedback. . . . . . . . . . . . . . . . . . 76
Reversing Starter (Operator Station) . . . . . . . . . . . . . . . . . . . . . . . . 77
Reversing Starter (Operator Station) with Feedback . . . . . . . . . . 79
Reversing Starter (Local I/O) – Two-wire Control . . . . . . . . . . . 82
Reversing Starter (Local I/O) –
Two-wire Control with Feedback. . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Reversing Starter (Local I/O) – Three-wire Control. . . . . . . . . . 85
Reversing Starter (Network & Operator Station). . . . . . . . . . . . . 86
Reversing Starter (Network & Local I/O) –
Two-wire Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Reversing Starter (Network & Local I/O) –
Three-wire Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Reversing Starter (Custom) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Two-speed Starter Operating Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Two-speed Starter (Network) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Two-speed Starter (Network) with Feedback . . . . . . . . . . . . . . . . 93
Two-speed Starter (Operator Station). . . . . . . . . . . . . . . . . . . . . . . 94
Two-speed Starter (Operator Station) with Feedback. . . . . . . . . 96
Two-speed Starter (Local I/O) – Two-wire Control. . . . . . . . . . 99
Two-speed Starter (Local I/O) –
Two-wire Control with Feedback. . . . . . . . . . . . . . . . . . . . . . . . . . 100
Two-speed Starter (Local I/O) – Three-wire Control . . . . . . . 102
Two-speed Starter (Network & Operator Station) . . . . . . . . . . 103
Two-speed Starter (Network & Local I/O) –
Two-wire Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 5
Page 6
Table of Contents
Protective Trip and Warning Functions
Two-speed Starter (Network & Local I/O) –
Three-wire Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Monitor Operating Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Monitor (Custom) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Chapter 5
Current Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Current Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Current Warning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Phase Loss Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Ground Fault Current Protection. . . . . . . . . . . . . . . . . . . . . . . . . . 116
Stall Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Jam Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Underload Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Current Imbalance Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Line Undercurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Line Overcurrent Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Line Loss Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Voltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Voltage Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Voltage Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Undervoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Overvoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Voltage Imbalance Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Phase Rotation Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Frequency Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Power Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Power Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Power Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Real Power (kW) Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Reactive Power (kVAR) Protection . . . . . . . . . . . . . . . . . . . . . . . . 129
Apparent Power (kVA) Protection. . . . . . . . . . . . . . . . . . . . . . . . . 130
Power Factor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Control Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Control Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Control Warning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Test Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Thermistor (PTC) Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
DeviceLogix Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Operator Station Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Remote Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Start Inhibit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Hardware Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Contactor Feedback Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Nonvolatile Storage Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
6 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 7
Table of Contents
Test Mode Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Analog Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Analog Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Analog Warning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Analog Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Chapter 6
Commands Trip Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Configuration Preset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Factory Defaults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Clear Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Chapter 7
Metering and Diagnostics Device Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Current Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Voltage Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Power Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Energy Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Analog Monitor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Trip / Warning History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Trip History Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Trip History Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Warning History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Warning History Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Trip Snapshot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Chapter 8
DeviceLogix Functionality Output Relay Overrides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
DeviceLogix Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Chapter 9
Connected Components Workbench Software Configuration
Device Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Establish the Connection to
Connected Components Workbench Software . . . . . . . . . . . . . . . . . 162
DeviceLogix Interface in
Connected Components Workbench Software . . . . . . . . . . . . . . . . . 165
Commissioning the Protection Functions . . . . . . . . . . . . . . . . . . . . . . 166
Chapter 10
Firmware and EDS Files Firmware Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Updating Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Electronic Data Sheet (EDS) File Installation. . . . . . . . . . . . . . . . . . . 169
Download the EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Install the EDS File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 7
Page 8
Table of Contents
Chapter 11
Troubleshooting Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Trip/Warn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Reset a Trip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Trip/Warn LED Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Appendix A
Wiring Diagrams E200 Wiring Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Index
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
8 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 9
Preface
This manual describes how to install, configure, operate, and troubleshoot the E200™ Electronic Overload Relay.

Access Relay Parameters

Additional Resources

The Microsoft Excel spreadsheet that is attached to this PDF file details the E200 parameters. To use a spreadsheet file, click the Attachments link
and right-click and save the desired file.
If the PDF file opens in a browser and you don't see the Attachments link , download the PDF file and then reopen the file with the Adobe Acrobat
Reader application. For full functionality (filter and search), use the Microsoft Excel application.
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
E200 Electronic Overload Relay Installation Instructions, publication 193-IN080 Provides complete user information for the E200 Electronic Overload Relay.
E300/E200 Electronic Overload Relay Specifications, publication 193-TD006 Provides complete specifications for the E200 Electronic Overload Relay.
E300/E200 Operator Station, Installation Instructions, publication 193-IN061
Connected Components Workbench Software Quick Tips, publication 9328-SP002 Provides general overview of the Connected Components Workbench Software.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwel l Automation industrial sys tem.
Product Certifications website, https://rok.auto/certifications
Provides complete user information for the E300/E200 Operator Station.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at
http://www.rockwellautomation.com/global/literature-library/overview.page
To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 9
Page 10
Preface
Notes:
10 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 11
Chapter 1
Overview
The E200™ Electronic Overload Relay is the newest part of the E300™ product portfolio. This device is a Parameter Configuration module communication option that is targeted for non-networked (remote) electronic motor overload protection applications. The E200 overload relay is configurable using the Connected Components Workbench™ software. The E200 relay features a single Type B USB interface port, three rotary dials to set the full-load current (FLA) for the application, and an 8-position DIP switch to select trip class and features.
Like the other products in the portfolio, the E200 relay modular design, diagnostic information, simplified wiring, and integration with Connected Components Workbench software make it the ideal overload for motor control applications in an automation system.
E200 Electronic Overload Relays provide the following benefits:
• Intelligent motor control
• Scalable solution
• Diagnostic Information
• Integrated I/O
• Adjustable trip class 5…30
• Wide current range
• Test/Reset button
• Programmable trip and warning settings
• True RMS current/voltage sensing (50/60 Hz)
• Protection for single- and three-phase motors

Module Descriptions and Features

The E200 relay consists of three modules: sensing, control and communications. You have choices in each of the three with additional accessories to tailor the electronic overload for your application’s exact needs.
The E200 overload relay is an overload system configured with the 193-ECM-PCM Parameter Configuration Module communication option. The communication module determines whether the complete assembled device is an E300 or an E200 overload relay.
Single-/Three-Phase Operation
You can apply the E200 Electronic Overload Relay to three-phase and single-phase applications. Straight-through wiring is available in both cases.
The E200 overload relay has 54 operating modes that provide motor control functionality for the following motor starter types:
•Overload
•Non-reversing starter
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 11
Page 12
Chapter 1 Overview
•Reversing starter
• Wye/Delta (Star/Delta) starter
•Two-speed starter
•Monitoring device
Thermal Overload Features
Feature Description
Thermal Utilization
Adjustable Settings
Therma l Memory
Reset Modes You can select between manual and automatic reset for an overload trip. The point of reset is adjustable from 1…100% TCU.
Time to Trip During an overload condition, an estimated time to trip is calculated.
Time to R eset
Therma l Warning
Two-Speed Protection
Based RMS current measurement, the overload relay calculates a thermal model that simulates the actual heating of the motor. Percent of thermal capacity utilization (%TCU) reports this calculated value. An overload trip occurs when the value reaches 100%.
Configure thermal overload protection by programming the motor’s full load current (FLC) rating and the desired trip class (5…30). Programming the actual values via software ensures the accuracy of the protection.
A thermal memory circuit approximates the thermal decay for a Trip Class 20 setting. This means that the thermal model of the connected motor is maintained at all times, even if the supply power is removed.
Following an overload trip, a reset does not occur until the calculated percentage of thermal capacity utilization falls below the reset level. As this value decays, the time to reset adjusts accordingly.
A thermal warning bit is set when the calculated percentage of thermal capacity utilization exceeds the programmed thermal warning level, which has a setting range of 0…100% TCU.
There is a second FLA setting for 2-speed motor protection. What used to require two separate overload relays - one for each set of motor windings - is now accomplished with one device.
Feature Description
Jam (Overcurrent)
Underload (Undercurrent)
Current Imbalance (Asymmetry)
Stall
Phase Loss
The overload relay can take a motor off-line in the event of a mechanical jam. Trip adjustments include a trip setting adjustable from 50…600% FLA and a trip delay time with a range of 0.1…25.0 seconds. A separate warning setting is adjustable from 50…600% FLA.
A sudden drop in motor current can signal conditions such as:
• Pump cavitation
• Tool breakage
• Belt breakage Monitoring for an underload event can provide enhanced protection for motors. The underload trip and warning settings are adjustable from 10…100% FLA. The
trip function also includes a trip delay time with a range of 0.1…25.0 seconds.
Current imbalance trip and warning settings are adjustable from 10…100%. The trip function also includes a trip delay time with a range of 0.1…25.0 seconds.
Stall is a condition where the motor is not able to reach full-speed operation in the appropriate amount of time required by the application. This can result in motor overheating, as current draw is in excess of the motor’s full load current rating. The adjustable stall protection has a trip setting with a range of 100…600% FLA, and the enable time is adjustable up to 250 seconds.
Configurable phase loss protection lets you enable or disable the function plus set a time delay setting, adjustable from 0.1…25.0 seconds. The trip level is factory set at a current imbalance measurement of 100%.
Current Monitoring Functions
The E200 Electronic Overload Relay lets you monitor the following operational data over a communications network:
• Individual phase currents — in amperes
• Individual phase currents — as a percentage of motor FLA
• Average current — in amperes
• Average current — as a percentage of motor FLA
• Percentage of thermal capacity utilized
• Current imbalance p ercentage
•Ground fault current
12 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 13
Overview Chapter 1
Ground (Earth) Fault
The E200 Electronic Overload Relay incorporates zero sequence (core balance) sensing into its design for low level (arcing) ground fault detection. Trip and warning settings are adjustable from 20 mA…5.0 A. For devices rated greater than 200 A and for ground fault detection less than 0.5 A, the external core balance current transformer accessory is required. This particular detection has been evaluated for compliance with Ground-Fault Sensing calibration and operating times from the Standard for Ground-Fault Sensing and Relaying Equipment per UL 1053.. The E200 Electronic Overload Relay provides a max. trip-inhibit setting, offering flexibility to help prevent tripping when the ground fault current magnitude exceeds 6.5 A. This can be useful to guard against the opening of the controller when the fault current could potentially exceed the controller's interrupting capacity rating.
Note: The E200 Electronic Overload Relay is not a Ground Fault Circuit Interrupter for personnel protection (or Class I) as defined in article 100 of the U.S. National Electric Code.
IMPORTANT For applications that require ground fault detection and use the pass-
through sensing module, this feature is only active when native motor current is present in the pass-through apertures; that is, no external step­down current transformers (CTs). You must use an external ground fault sensor for any applications that require external step-down CTs.
Control Module Features
The control module inputs support the connection of devices such as contactors, disconnect auxiliary contacts, pilot devices, limit switches, and float switches. Inputs are rated 24V DC, 120V AC, or 240V AC and are current sinking. Power for the inputs is sourced separately with customer sources. Relay contact outputs can be controlled via the network or DeviceLogix™ function blocks for performing such tasks as contactor operation.
The DeviceLogix engine lets you program custom motor control algorithms. You can write programs for distributed control applications or to turn off a motor smoothly when the network or programmable logic controller is unexpectedly lost.
Control Voltage
110…120V AC, 50/60 Hz
220…240V AC, 50/60 Hz
24V DC
(1) Includes PTC thermistor and external ground fault.
Inputs Relay Outputs Inputs Relay Outputs
I/O I/O and Protection
43
22
43
22
63
22
22
22
42
The control module also monitors positive temperature coefficient (PTC) thermistors.
(1)
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 13
Page 14
Chapter 1 Overview
Sensing Module Features
The E200 sensing module with voltage, current, and ground fault current provides the following:
Feature Description
Voltage Protection Protect against voltage issues (such as undervoltage, voltage imbalance, phase loss, frequency, and phase rotation).
Power Protection
Voltage, Power, and Energy Monitoring
Monitor and protect for both excessive and low real power (kW), reactive power (kVAR), apparent power (kVA), and power factor for a specific application (such as pump applications).
Monitor voltage, current, power (kW, kVAR, and kVA), energy (kWh, kVARh, kVAh, kW Demand, kVAR Demand, and kVA Demand), and power quality (power factor, frequency, and phase rotation) down at the motor level.
The sensing module supports:
• Voltage/current/ground fault
• Current/ground fault
• Current
• Current Range [A]
•0.5…30
•6…60
• 10…100
• 20…200
Communication Module Features
The following communication module is available:
Communication Module Description
The Parameter Configuration Module (PCM) has one Type B USB interface port and supports the following:
Parameter Configuration Module (E200)
• Stand-alone non-networked applications
• Configurable with Connected Components Workbench software
• Three rotary dials to set Full Load Amps (FLA)
• 8-position DIP switch for trip class and feature selection
Expansion Digital I/O
You can add up to four additional expansion digital modules to the E200 relay expansion bus.
• 4 inputs/2 relay outputs
• 24V DC
• 120V AC
• 240V AC
The remote trip function lets an external device (such as a vibration sensor) induce am trip.
External device relay contacts are wire d to the discrete inputs. These discrete inputs
are configurable with an option for assigning the remote trip function.
Expansion Analog I/O
The E200 analog expansion module lets you protect against over-analog readings from analog-based sensors, such as overtemperature, overflow, or overpressure. The analog expansion module monitors resistance temperature detectors.
14 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 15
Overview Chapter 1
You can add up to four additional expansion analog modules to the E200 relay expansion bus.
• 3 universal analog inputs/1 analog output
•0…10V
•0…5V
•1…5V
•0…20 mA
•4…20 mA
•RTD (2-wire or 3-wire)
• 0…150
• 0…750
• 0…3000
• 0…6000 (PTC/NTC)
Expansion Power Supply Features
When more than one expansion digital module and one operator station are added to the E200 relay expansion bus, you need an expansion power supply to supplement power for the additional modules. One expansion power supply powers a fully loaded E200 relay expansion bus.
• 120/240V AC
• 24V DC
Expansion Operator Station Features
You can add one operator station to the E200 relay expansion bus to be used as a user interface device. The operator stations provide status indicators and function keys for motor control. The operator stations also support CopyCat™, which lets you upload and download configuration parameters. Using a Series B Control Module and Series B Control/Diagnostic station offers added functionality for the CopyCat feature by also allowing upload and download of any custom DeviceLogix programming. See publication 193-IN061D
• Control station
•Diagnostic station
for more information about using the CopyCat feature.
External Current Transformer Options
For motor overload protection applications greater than 200 A, external current transformers (CTs) can be used to step down the main operating current. This also provides isolation for high current conductors and the E200 Overload Relay. There are different current ranges to select from and also different certification standards (for example, UL or CE) to which the respective CT kits conform.
• UL compliant CT types: 300 A and 600 A
• CE compliant CT types: 300 A and 400 A
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 15
Page 16
Chapter 1 Overview
Status Indicators
The E200 Electronic Overload Relay provides the following LED indicators:
• Power — This green/red LED indicates the status of the overload relay.
• TRIP/WARN — This LED flashes a yellow code under a warning condition and a red code when tripped.
Inputs/Outputs
Inputs allow the connection of such devices as contactor and disconnect auxiliary contacts, pilot devices, limit switches, and float switches. Input status can be monitored via the network and mapped to a controller’s input image table. Inputs are rated 24V DC, 120V AC, or 240V AC and are current sinking. Power for the inputs is sourced separately with convenient customer sources at terminal A1. Relay contact outputs can be controlled via the network or DeviceLogix function blocks for performing such tasks as contactor operation.
Test/Reset Button

Modular Design

The Test/Reset button, which is located on the front of the E200 Electronic Overload Relay, lets you perform the following:
• Test — The trip relay contact opens if the E200 Electronic Overload Relay is in an untripped condition and the Test/Reset button is pressed for 2 seconds or longer.
• Reset — The trip relay contact closes if the E200 Electronic Overload Relay is in a tripped condition, supply voltage is present, and the Test/Reset button is pressed.
Single/Three-Phase Operation
You can apply the E200 Electronic Overload Relay to three-phase and single-phase applications. A programming parameter is provided for selection between single- and three-phase operation. Straight-through wiring is available in both cases.
You can select the specific options that you need for your motor starter application. The E200 relay consists of three modules: sensing, control, and communication. You can customize each of the three with accessories to tailor the electronic motor overload for your application’s exact needs.
• Wide current range
• Sensing capabilities (Current, Ground Fault Current, and/or Voltage)
•Expansion I/O
• Operator interfaces

Communication Options

16 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
The E200 relay communicates via a USB connection to Connected Components Workbench software.
Page 17
Overview Chapter 1

Diagnostic Information

Simplified Wiring

Sensing Module

The E200 relay provides a wide variety of diagnostic information to monitor motor performance, proactively alert you to possible motor issues, or identify the reason for an unplanned shutdown. Information includes:
• Voltage, Current, and Energy
• Trip / Warning Histories
• % Thermal Capacity Utilization
• Time to Trip
•Time to Reset
•Operational Hours
•Number of Starts
•Trip Snapshot
The E200 relay provides an easy means to mount to both IEC and NEMA Allen-Bradley® contactors. A contactor coil adapter is available for the 100-C contactor, which lets you create a functional motor starter with only two control wires.
Figure 1 - Sensing Module
The sensing module electronically samples data about the current, voltage, power, and energy that are consumed by the electric motor internal to the module. You can choose from one of three varieties of the sensing modules depending on the motor diagnostic information that is needed for the motor protection application:
• Current Sensing
• Current and Ground Fault Current Sensing
• Current, Ground Fault Current, Voltage, and Power Sensing
The current ranges for each of three varieties of sensing module are as follows:
• 0.5…30 A
•6…60 A
• 10…100 A
• 20…200 A
You can choose how the sensing module mechanically mounts inside the electrical enclosure. The following mounting mechanisms are available for the sensing module.
• Mount to the load side of an Allen-Bradley Bulletin 100 IEC Contactor
• Mount to the load side of an Allen-Bradley Bulletin 300 NEMA Contactor
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 17
Page 18
Chapter 1 Overview
• Mount to the load side of an Allen-Bradley Bulletin 500 NEMA Contactor
• DIN Rail / Panel Mount with power terminals
• Replacement DIN Rail / Panel Mount with power terminals for an Allen-Bradley E3 Plus panel mount adapter
• DIN Rail / Panel Mount with pass-thru power conductors
Use the E200 relay sensing module with external current transformers. The following application guidelines should be adhered to when using an external CT configuration:
• You must mount the E200 Overload Relay a distance equal to or greater than six times the cable diameter (including insulation) from the nearest current­carrying conductor.
• For applications that use multiple conductors per phase, the diameter of each cable should be added and multiplied by six to determine the proper placement distance for the E200 Overload Relay.

Control Module

Figure 2 - Control Module
The control module is the base of the E200 relay and can attach to any sensing module. The control module performs all protection and motor control algorithms and contains the native I/O for the system. The control module has two varieties:
•I/O only
• I/O and protection (PTC and External Ground Fault Current Sensing)
The control module is offered in three control voltages:
• 110…120V AC, 50/60Hz
• 220…240V AC, 50/60Hz
• 24V DC
The E200 relay requires external control voltage to power and activate the digital inputs.

Communication Module

18 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
The parameter configuration module lets the E200 relay integrate into an automation system, and it can attach to any control module. Set the full-load current with rotary turn dials; the module uses diagnostic status indicators to provide system status at the panel.
Page 19
Figure 3 - Parameter Configuration Module
Power LED
Trip/Warn LED
Tes t / Re s e t
FLA
(XX.X / XXX)
USB communication port
FLA adjustment dials
Parameter-setting switches
Overview Chapter 1

Optional Add-On Modules

Optional Expansion I/O
If the native I/O count of the base relay is not sufficient for your application, you can add more digital and analog I/O to the system via the E200 relay Expansion Bus. You can add any combination of up to four Digital I/O Expansion Modules that each have four inputs (120V AC, 240V AC, or 24V DC) and two relay outputs.
You can also add up to four Analog I/O Expansion Modules, which have three independent universal analog inputs and one isolated analog output per module. The Analog I/O Expansion Modules require Control Module firmware v3.000 or higher. The independent universal analog inputs accept the following signals:
•4…20 mA
•0…20 mA
•0…10V DC
•1…5V DC
•0…5V DC
• RTD Sensors (Pt 385, Pt 3916, Cu 426, Ni 618, Ni 672, and NiFe 518)
• Resistance (150 , 750 , 3000 , and 6000 )
Program the isolated analog output to reference a traditional analog signal (4…20 mA, 0…20 mA, 0…10V DC, 1…5V, or 0…10V) to represent the following diagnostic values:
•Average %FLA
•%TCU
• Ground Fault Current
• Current Imbalance
•Average L-L Voltage
•Voltage Imbalance
•Total kW
•Total kVAR
•Total kVA
• Total Power Factor
• User-defined Value
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 19
Page 20
Chapter 1 Overview
Control Station
Diagnostic Station
Power LED
Trip/Warn LED
Start Forward/Speed 1
Start Reverse/Speed 2
Local/ Remote
Stop
Reset
Power LED
Trip/Warn LED
Start Forward/Speed 1
Start Reverse/Speed 2
Local /Remote
Stop
Reset
Escape
Up
Select
Enter
Down
Optional Operator Station
Figure 4 - Operator Stations

Optional Expansion Bus Power Supply

LOCAL
REMOTE
0
RESET
LOCAL
REMOTE
ESC
SELECT
0
RESET
The E200 relay lets you add one operator interface to the Expansion Bus. There are two types of operator stations: Control Station or a Diagnostic Station. Both types of operator stations mount into a standard 22 mm push button knockout, and they provide diagnostic status indicators that let you view the status of the E200 relay from the outside of an electrical enclosure. Both operator stations provide push buttons that can be used for motor control logic, and they both can be used to upload and download parameter configuration data from the base relay.
The Diagnostic Station contains a display and navigation buttons that lets you view and edit parameters in the base relay. The Diagnostic Station requires Control Module firmware v3.000 or higher.
The E200 relay expansion bus provides enough current to operate a system that has (1) Digital Expansion Module and (1) Operator Station. An E200 relay system that contains more expansion modules needs supplemental current for the Expansion Bus. the E200 relay offers you two types of Expansion Bus Power Supplies: AC (110…240V AC, 50/60 Hz) and DC (24V DC). One Expansion Bus Power Supply supplies enough current for a fully loaded E200 relay Expansion Bus (four Digital Expansion Modules, four Analog Expansion Modules, and one Operator Station). Both Expansion Bus Power Supplies work with any combination of Digital and Analog Expansion Modules.
20 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Figure 5 - Expansion Bus Power Supply
Page 21
Overview Chapter 1

Protection Features

The numbers in parentheses in this section represent specific device functions as they relate to the respective protection measures provided. These protection functions correlate to ANSI standard device numbers as defined by ANSI/IEEE C37.2 Standard—Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations.
Standard Current-based Protection
All versions of the E200 relay provide the following motor protection functions.
•Thermal Overload (51)
• Phase Loss
• Current Imbalance (46)
• Undercurrent – load loss (37)
•Overcurrent – load jam (48)
•Overcurrent – load stall
•Start Inhibit (66)
Ground Fault Current-based Protection
The E200 relay sensing modules and control modules with a ground fault current option provides the following motor protection function:
• Ground Fault – zero sequence method (50 N)
Voltage- and Power-based Protection
The E200 relay sensing modules with voltage sensing provides the following motor protection functions:
• Undervoltage (27)
• Overvoltage (59)
• Phase Reversal (47) – voltage-based
• Over and Under Frequency (81) – voltage-based
•Voltage Imbalance (46)
• Over and Under Power (37)
• Over and Under Leading/Lagging Power Factor (55)
• Over and Under Reactive Power Generated
• Over and Under Reactive Power Consumed
• Over and Under Apparent Power
Thermal-based Protection
The E200 relay provides the following thermal-based motor protection functions:
•Thermistor – PTC (49)
• Stator Protection – RTD (49)
• Bearing Protection – RTD (38)
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 21
Page 22
Chapter 1 Overview

Applications

Use the E200 relay with the following across-the-line starter applications:
•Non-reversing starter
•Reversing starter
• Wye (Star)/Delta starter
•Two-speed motors
• Low and medium voltage with two or three potential transformers
•With or without Phase current transformers
• With or without zero-sequence core balanced current transformer
22 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 23
Chapter 2
Diagnostic Station
The E200 Electronic Overload Relay supports a Diagnostic Station on the E200 Expansion Bus (requires Control Module firmware v3.000 and higher). The Diagnostic Station lets you view any E200 relay parameter and edit any configuration parameter. This chapter explains the navigation keys on the Diagnostic Station, how to view a parameter, how to edit a configuration parameter, and the Diagnostic Station programmable display sequence.

Navigation Keys

Key Name Description

Displaying a Parameter

The E200 Diagnostic Station has five navigation keys that are used to navigate through the display menu system and edit configuration parameters.
Up Arrow Down Arrow
Escape
Select
Enter
The E200 Diagnostic Station lets you view parameters by using a group menu system or by a linear list. To start the navigation menu, press the key. The menu prompts
you to view parameters by groups, parameters in a linear list, or E200 relay system information.
• Scroll through the display parameters or groups.
• Increment or decrement values.
• Back one step in the navigation menu.
• Cancel a change to a configuration parameter value
• Select the next bit When you view a bit-enumerated parameter.
• Select the next digit when you edit a configuration value.
• Select the next bit when you edit a bit-enumerated parameter.
• Start the navigation menu.
• Advance one step in the navigation menu.
• Display the description for a bit enumerated parameter.
• Edit a configuration parameter value.
• Save the change to the configuration parameter value.
Parameter Group Navigation
To start the navigation menu, press the key. Use the or keys to select the Groups navigation method and press .
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 23
Page 24
Chapter 2 Diagnostic Station
Use the or keys to select the parameter group to display and press .
Use the or keys to view the parameters that are associated with that group.
When you view a bit-enumerated parameter, press to view the description of
each bit. Press to view the next bit. Press to return to the parameter.
Press to return to the parameter group navigation system.
If you do not press any navigation keys for a period that Display Timeout (Parameter 436) defines, the Diagnostic Station automatically returns to the programmable display sequence.
Linear List Navigation
To start the navigation menu, press the key. Use the or keys to select the Linear List navigation method and press .
24 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 25
Diagnostic Station Chapter 2
Use the or and keys to select the parameter number to display and press .
Use the or keys to view the next sequential parameter.
When you view a bit-enumerated parameter, press to view the description of
each bit. Press to view the next bit. Press to return to the parameter.
Press to return to the linear list navigation system.
If you do not press any navigation keys for a period that Display Timeout (Parameter
436) defines, the E200 Diagnostic Station automatically returns to the programmable display sequence.
System Info
The E200 Diagnostic Station can display firmware revision information, view the time and date of the E200 relay virtual clock, and edit the time and date of the E200 relay virtual clock. To view E200 relay system information, start the navigation menu by
pressing key. Use the or keys to select System Info and press .
Use the or keys to view the E200 relay system information.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 25
Page 26
Chapter 2 Diagnostic Station
To edit the system date or time, press to modify the value. Use the or
keys to select the new value. Press to select the next system value. Press
to save the new system values or press to cancel the modification and
restore the previous system values.

Editing Parameters

Press to return to the navigation menu.
If you do not press any navigation keys for a period that Display Timeout (Parameter
436) defines, the E200 Diagnostic Station automatically cancels the modification, restores the previous value, and returns to its programmable display sequence.
This section explains how to edit the parameters of the E200 relay.
Editing a Configuration Parameter
The E200 Diagnostic Station lets you edit configuration parameters by using a group menu system or by a linear list. To start the navigation menu, press the key. You
are prompted to view parameters by groups, parameters in a linear list, or E200 relay system information. Choose the appropriate method and navigate to the parameter to be modified.
Editing a Numeric Parameter
To edit a configuration parameter, press the key to modify the value. Use the
or keys to select the new value. Press to save the new system values
or press to cancel the modification and restore the previous value.
26 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 27
Diagnostic Station Chapter 2
Press to return to the navigation menu.
If you do not press any navigation keys for a period that Display Timeout (Parameter
436) defines, the E200 Diagnostic Station automatically cancels the modification, restores the previous value, and returns to its programmable display sequence.
Editing a Bit Enumerated Parameter
When you edit a bit-enumerated parameter, press the key to view the description
of each bit. Use the or keys to select the new bit value. Press to edit
the next bit. Press to save the new value or press to cancel the modification and restore the previous value.

Programmable Display Sequence

Press to return to the navigation menu.
If you do not press any navigation keys for a period that Display Timeout (Parameter
436) defines, the Diagnostic Station automatically cancels the modification, restores the previous value, and returns to its programmable display sequence.
This section explains the programmable display sequence of the E200 relay.
Display Sequence
The Diagnostic Station of the E200 relay sequentially displays up to seven screens every 5 seconds.
• Three-phase current
•Three-phase voltage
•Total power
• User-defined screen 1
• User-defined screen 2
• User-defined screen 3
• User-defined screen 4
The three-phase voltage and total power screens are only included in the sequence when the E200 relay has a voltage, current, and ground fault current (VIG)-based Sensing Module.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 27
Page 28
Chapter 2 Diagnostic Station
The user-defined screens let you select up to two parameters per screen. See Diagnostic
Station User-defined Screens on page 39 to configure the Screen# and Parameter#
(Parameters 428…435).
If you do not press any navigation keys for a period that Display Timeout (Parameter
436) defines, the Diagnostic Station automatically cancels any editing modifications, restores the previous value, and returns to its programmable display sequence.

Automatic Trip and Warning Screens

Stopping the Display Sequence
To stop the display sequence, press . Use the or keys to manually
sequence through the displays. Press to return to the automatic display sequence.
If you do not press any navigation keys for a period that Display Timeout (Parameter
436) defines, the Diagnostic Station automatically returns to the programmable display sequence.
When the E200 relay is in a trip or warning state, the E200 Diagnostic Station automatically displays the trip or warning event.
Press any of the navigation keys ( , , , , or ) to return to the automatic display sequence.
When the trip or warning event clears, the E200 Diagnostic Station automatically returns to the programmable display sequence.
If another parameter is displayed and you do not press any navigation keys for a period that Display Timeout (Parameter 436) defines, the Diagnostic Station automatically returns to the trip or warning screen if the trip or warning event is not cleared.
28 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 29
Chapter 3
System Operation and Configuration
This chapter provides instructions about how to operate and configure an E200 Electronic Overload Relay system. This chapter includes settings for Device Modes, Option Match, Security Policy, I/O Assignments, Expansion Bus Fault, Emergency Start, and an introduction to Operating Modes.
This chapter shows you the parameters required to program the device; see page 9 information about the complete parameter spreadsheet that is attached to this PDF.
for

Device Modes

The E200 relay has five device modes to validate configuration of the device and limit when you can configure the E200 relay, perform a firmware update, and issue commands.
• Administration Mode
• Ready Mode
•Run Mode
•Test Mode
• Invalid Configuration Mode
Administration Mode
Administration Mode is a maintenance mode for the E200 relay that lets you configure parameters, modify security policies, perform firmware updates, and issue commands.
Follow these steps to enter Administration Mode:
1. Set the rotary dials on the E200 Communication Module to 7-7-7.
2. Cycle power on the E200 relay
After you complete commissioning activities and maintenance tasks, return the E200 relay back to Ready or Run Mode by setting the rotary dials of the E200 communication module back to their previous positions and then cycle power.
Ready Mode
Ready Mode is a standby mode for the E200 relay in which the relay is ready to help protect an electric motor and no electrical current has been detected. You can modify configuration parameters, update firmware, and issue commands if the appropriate security policies are enabled. The Power LED on the Communication Module and Operator Stations flash green and bit 14 in Device Status 0 (Parameter 20) is set to 1 when the device is in Ready Mode.
Run Mode
Run Mode is an active mode for the E200 relay in which the relay is sensing electrical current and is actively protecting an electric motor. Only non-motor protection configuration parameters can be modified if the appropriate security policies are enabled. The Power LED on the Communication Module and Operator Stations is
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 29
Page 30
Chapter 3 System Operation and Configuration
solid green and bits 3, 4, and/or 5 in Device Status 0 (Parameter 20) are set to 1 when the device is in Run Mode.
Test Mode
Test Mode is used by installers of motor control centers who are testing and commissioning motor starters with an automation system. A digital input of the E200 relay is assigned to monitor the Test position of the motor control center enclosure. The Input Assignments (Parameters 196…201) are described later in this chapter.
Anyone who commissions motor starters in an automation system can put their motor control center enclosure into the Test position to activate Test Mode and verif y that the digital inputs and relay outputs of the E200 relay are operating properly with the motor starter without energizing power to the motor. If the E200 relay senses current or voltage in Test Mode, it generates a Test Mode Trip.
Invalid Configuration Mode
Invalid Configuration Mode is an active mode for the E200 relay in which the relay is in a tripped state due to invalid configuration data. Invalid Configuration Parameter (Parameter 38) indicates the parameter number that is causing the fault. Invalid Configuration Cause (Parameter 39) identifies the reason for Invalid Configuration Mode.
The Trip/Warn LED on the Communication Module and Operator Stations flashes a pattern of red, 3 long and 8 short blinks, and bits 0 and 2 in Device Status 0 (Parameter
20) are set to 1 when the device is in Invalid Configuration Mode. To return to Ready/Run Mode, place a valid configuration value in the parameter that
is identified by Invalid Configuration Parameter (Parameter 38) and Invalid Configuration Cause (Parameter 39). Reset the trip state of the E200 relay by pressing the blue reset button on the Communication Module, via Connected Components Workbench software, or by an assigned digital input.
Option Match
Due to the modular nature of the E200 relay, you can enable the Option Match feature to verify that the options that you expect for the motor protection application are the ones that are present on the E200 relay system. You can configure an option mismatch to cause a protection trip or provide a warning within the E200 relay.
Enable Option Match Protection Trip (Parameter 186)
To enable the Option Match feature to cause a protection trip in the event of an option mismatch, place a (1) in bit position 8 of Parameter 186 (Control Trip Enable). You can select the specific option match features to cause a protection trip in Parameter 233 (Option Match Action).
Enable Option Match Protection Warning (Parameter 192)
To enable the Option Match feature to cause a warning in the event of an option mismatch, place a (1) in bit position 8 of Parameter 192 (Control Warning Enable). You can select the specific option match features to cause a warning in Parameter 233 (Option Match Action).
30 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 31
System Operation and Configuration Chapter 3
Control Module Type (Parameter 221)
The E200 relay offers six different control modules. Place the value of the expected control module into Parameter 221. A value of (0) disables the Option Match feature for the control module.
Sensing Module Type (Parameter 222)
The E200 relay offers 12 different sensing modules. Place the value of the expected sensing module into Parameter 222. A value of (0) disables the Option Match feature for the sensing module.
Communication Module Type (Parameter 223)
The E200 relay offers two different communication modules. Place the value of the expected communication module into Parameter 223. A value of (0) disables the Option Match feature for the communication module.
Operator Station Type (Parameter 224)
The E200 relay offers two different types of operator stations. Place the value of the expected operator station into Parameter 224. A value of (0) disables the Option Match feature for the operator station. A value of (1), “No Operator Station”, makes the operator station not allowed on the Expansion Bus and prevents you from connecting an operator station to the E200 relay system.
Digital I/O Expansion Modules
Module 1 Type (Parameter 225)
The E200 relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 1. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 1 into Parameter 225. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1), “No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 1 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 1 to the E200 relay system.
Module 2 Type (Parameter 226)
The E200 relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 2. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 2 into Parameter 226. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1),“No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 2 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 2 to the E200 relay system.
Module 3 Type (Parameter 227)
The E200 relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 3. There are three different types of Digital I/O expansion
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 31
Page 32
Chapter 3 System Operation and Configuration
modules. Place the value of the expected Digital I/O expansion module set to Digital Module 3 into Parameter 227. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1),“No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 3 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 3 to the E200 relay system.
Module 4 Type (Parameter 228)
The E200 relay supports up to four additional Digital I/O expansion modules. This parameter configures the Option Match feature for the Digital I/O expansion module set to Digital Module 4. There are three different types of Digital I/O expansion modules. Place the value of the expected Digital I/O expansion module set to Digital Module 4 into Parameter 228. A value of (0) disables the Option Match feature for this Digital I/O expansion module. A value of (1), “No Digital I/O Expansion Module”, makes the Digital I/O expansion module set to Digital Module 4 not allowed on the Expansion Bus and prevents you from connecting a Digital I/O expansion module set to Digital Module 4 to the E200 relay system.
Analog I/O Expansion Modules
Module 1 Type (Parameter 229)
The E200 relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 1. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 1 into Parameter 229. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 1 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 1 to the E200 relay system.
Module 2 Type (Parameter 230)
The E200 relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 2. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 2 into Parameter 230. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 2 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 2 to the E200 relay system.
Module 3 Type (Parameter 231)
The E200 relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 3. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 3 into Parameter 231. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 3 not allowed on the Expansion
32 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 33
System Operation and Configuration Chapter 3
Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 3 to the E200 relay system.
Module 4 Type (Parameter 232)
The E200 relay supports up to four additional Analog I/O expansion modules. This parameter configures the Option Match feature for the Analog I/O expansion module set to Analog Module 4. There is one type of Analog I/O expansion module. Place the value of the expected Analog I/O expansion module set to Analog Module 4 into Parameter 232. A value of (0) disables the Option Match feature for this Analog I/O expansion module. A value of (1), “No Analog I/O Expansion Module”, makes the Analog I/O expansion module set to Analog Module 4 not allowed on the Expansion Bus and prevents you from connecting an Analog I/O expansion module set to Analog Module 4 to the E200 relay system.
Option Match Action (Parameter 233)
The Option Match feature for the E200 relay lets you specify an action when there is an option mismatch—Protection Trip or Warning. Place a (0) in the appropriate bit position for a warning, and place a (1) in the appropriate bit position to cause a protection trip if there is an option mismatch.

Security Policy

Policy Type Description
Device Configuration
Device Reset
Firmware Upd ate
Security Configuration
• lets you send external message instructions via a communication network to write values to configuration parameters
• when this policy is disabled, all ex ternal message instructions with configuration data return a communication error when the E200 relay is in Ready Mode or Run Mode
• lets you send external message instruction via a communication network to perform a soft device reset when the E200 relay is in Ready Mode
• when this policy is disabled, all external reset message instructions return a communication error when the E200 relay is in Ready Mode or Run Mode
• lets you update the internal firmware of the communication module and control module via ControlFlash when the E200 relay is in Ready Mode
• when this policy is disabled, firmware updates return a communication error when the E200 relay is in Ready Mode or Run Mode
• lets you modify the Security Policy of the E200 relay in Ready Mode
• when this policy is disabled, it can only be modified when the E200 relay is in Administration Mode

I/O Assignments

The E200 relay has a security policy that can be used to prevent anyone with malicious intent to potentially damage a motor or piece of equipment. By default, you can only modify the security policy when the E200 relay is in Administration Mode (see
to learn how to enable Administration Mode).
page 29
Table 1 - Security Policy Types
The E200 relay has native digital inputs and relay outputs in the Control Module. This I/O can be assign to dedicated functions. The following sections list the function assignments for the available Control Module I/O.
Input Assignments
You can assign digital inputs via the following parameters:
• Input Pt00 Assignment (Parameter 196)
• Input Pt01 Assignment (Parameter 197)
• Input Pt02 Assignment (Parameter 198)
• Input Pt03 Assignment (Parameter 199)
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 33
Page 34
Chapter 3 System Operation and Configuration
• Input Pt04 Assignment (Parameter 200)
• Input Pt05 Assignment (Parameter 201)
Output Assignments
You can assign relay outputs via the following parameters:
• Output Pt00 Assignment (Parameter 202)
• Output Pt01 Assignment (Parameter 203)
• Output Pt02 Assignment (Parameter 204)

Output Relay Configuration States

When assigned as a Normal/General Purpose Relay or Control/Control & Trip Relay, you can configure the E200 relay's output relays to go to a specific safe state when one of following events occur:
• Protection Fault Mode - when a trip event occurs
• Communication Fault Mode - when network communication is lost or an error occurs
• Communication Idle Mode - when a network scanner changes to Idle mode or a PLC changes to Program mode
IMPORTANT It is important that you fully understand the use of these parameters and
the order of their priority under the conditions of a protection trip, communication fault, and communication idle event.
The default setting for these three modes is to Open/de-energize all E200 output relays that are assigned as a Normal/General Purpose Relay or Control/Control & Trip Relay.
The E200 output relay states when assigned as a Normal/General Purpose Relay or Control/Control & Trip Relay follow this priority order:
Table 2 - Output Relay Priority
Priority Normal/General Purpose Relay Control/Control & Trip Relay
1 Output Protection Fault State Output Communication Fault State
2 Output Communication Fault State Output Final Fault State
3 O utput Final Fault State Output Communication Idle State
4 Output Communication Idle State
The optional eight output relays on the digital expansion I/O modules operate as a Normal/General Purpose relay with the same E200 relay safe state settings. There are two relays per module with maximum of four modules.
Output Relay Protection Fault Modes
When the E200 relay has a trip event, you can configure the E200 output relays to go to a specific state (Open or Closed) or ignore the trip event and continue to operate as normal. The parameters that are listed in Ta b l e 3 for each E200 output relay.
34 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
configure the Protection Fault Mode
Page 35
Table 3 - Protection Fault Mode Parameters
System Operation and Configuration Chapter 3
Fault Nam e
Output Relay 0 Protection Fault Action 304
Output Relay 0 Protection Fault Value 305 • defines which state Output Relay 0 should go to when a trip event occurs
Output Relay 1 Protection Fault Action 310
Output Relay 1 Protection Fault Value 311 • defines which state Output Relay 1 should go to when a trip event occurs
Output Relay 2 Protection Fault Action 316
Output Relay 2 Protection Fault Value 317 • defines which state Output Relay 2 should go to when a trip event occurs
Digital Expansion Module 1 Output Relay Protection Fault Action 322
Digital Expansion Module 1 Output Relay Protection Fault Value 323 • defines which state both output relays should go to when a trip event occurs
Digital Expansion Module 2 Output Relay Protection Fault Action 328
Digital Expansion Module 2 Output Relay Protection Fault Value 329 • defines which state both output relays should go to when a trip event occurs
Digital Expansion Module 3 Output Relay Protection Fault Action 334
Digital Expansion Module 3 Output Relay Protection Fault Value 335 • defines which state both output relays should go to when a trip event occurs
Digital Expansion Module 4 Output Relay Protection Fault Action 340
Digital Expansion Module 4 Output Relay Protection Fault Value 341 • defines which state both output relays should go to when a trip event occurs
Parameter
No.
Description
• defines how Output Relay 0 when assigned as a Normal/General Purpose Relay responds when a trip event occurs
• defines how Output Relay 1 responds when a trip event occurs when this parameter is assigned as a Normal/General Purpose Relay
• defines how Output Relay 2 responds when a trip event occurs when this parameter is assigned as a Normal/General Purpose Relay.
• defines how both output relays on Digital Expansion Module 1 responds when a trip event occurs
• defines how both output relays on Digital Expansion Module 2 responds when a trip event occurs
• defines how both output relays on Digital Expansion Module 3 responds when a trip event occurs
• defines how both output relays on Digital Expansion Module 4 responds when a trip event occurs
Output Relay Communication Fault Modes
When the E200 relay loses communication, experiences a communication bus fault, or has a duplicate node address, you can configure the E200 output relays with the Communication Fault Mode parameters to go to a specific state (Open or Closed) or hold the last state.
An E200 relay with firmware revision v5.000 or higher supports the Fault Mode Output State Duration feature, which can be used with redundant network scanners or control systems. The Fault Mode Output State Duration is the time that the E200 output relays can go to a temporary state (Open, Closed, or Hold Last State) when a communication fault occurs. Configure this temporary state by using the Communication Fault Mode parameters.
If communication between the E200 relay and a network scanner or control system is not restored within the Fault Mode Output State Duration time (Parameter 561), the E200 output relays go to a final fault state (Open or Closed), which you configure by using the Final Fault Mode parameters.
If communication between the E200 relay and a network scanner or control system is restored within the Fault Mode Output State Duration time (Parameter 561), the E200 output relays resume with the state commanded by the network scanner or control system.
The parameters that are listed in Ta b l e 4 each E200 output relay.
configure the Configuration Fault Mode for
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 35
Page 36
Chapter 3 System Operation and Configuration
Table 4 - Configuration Fault Mode Parameters
Fault Na me
Parameter
No.
Description
• defines the amount of time (s) that the E200 relay remains in the Communication Fault
Fault Mode Output State Duration
(1)
561
Mode state when a communication fault occurs. 0 = forever
• If communication between the E200 relay and a network scanner or control system is not restored within the Fault Mode Output State Duration time the E200 output relays go to the final fault state (configured by using Final Fault Mode Parameters
Output Relay 0 Communication Fault Action 306
• defines how Output Relay 0 responds when a communication fault occurs when this parameter is assigned as a Normal/General Purpose Relay or Control/Control & Trip Relay
Output Relay 0 Communication Fault Value 307 • defines which state Output Relay 0 should go to when a communication fault occurs
Output Relay 0 Final Fault Value
(1)
Output Relay 1 Communication Fault Action 312
• defines which state Output Relay 0 should go to when communication is not restored with
562
the time defined in Fault Mode Output State Duration (Parameter 561)
• defines how Output Relay 1 responds when a communication fault occurs when this parameter is assigned as a Normal/General Purpose Relay or Control/Control & Trip Relay
Output Relay 1 Communication Fault Value 313 • defines which state Output Relay 1 should go to when a communication fault occurs
Output Relay 1 Final Fault Value
(1)
Output Relay 2 Communication Fault Action 317
• defines which state Output Relay 1 should go to when communication is not restored with
563
the time defined in Fault Mode Output State Duration (Parameter 561)
• defines how Output Relay 2 responds when a communication fault occurs when this parameter is assigned as a Normal/General Purpose Relay or Control/Control & Trip Relay
Output Relay 2 Communication Fault Value 319 • defines which state Output Relay 2 should go to when a communication fault occurs
Output Relay 2 Final Fault Value
(1)
Digital Expansion Module 1 Output Relay Communication Fault Action 324
• defines which state Output Relay 2 should go to when communication is not restored with
564
the time defined in Fault Mode Output State Duration (Parameter 561)
• defines how both output relays on Digital Expansion Module 1 responds when a communication fault occurs
Digital Expansion Module 1 Output Relay Communication Fault Value 325 • defines which state both output relays should go to when a communication fault occurs
Digital Expansion Module 1 Output Relay Final Fault Value
(1)
Digital Expansion Module 2 Output Relay Communication Fault Action 330
• defines which state both output relays should go to when communication is not restored
565
with the time defined in Fault Mode Output State Duration (Parameter 561)
• defines how both output relays on Digital Expansion Module 2 responds when a communication fault occurs
Digital Expansion Module 2 Output Relay Communication Fault Value 331 • defines which state both output relays should go to when a communication fault occurs
Digital Expansion Module 2 Output Relay Final Fault Value
(1)
Digital Expansion Module 3 Output Relay Communication Fault Action 336
• defines which state both output relays should go to when communication is not restored
566
with the time defined in Fault Mode Output State Duration (Parameter 561)
• defines how both output relays on Digital Expansion Module 3 responds when a communication fault occurs
Digital Expansion Module 3 Output Relay Communication Fault Value 337 • defines which state both output relays should go to when a communication fault occurs
Digital Expansion Module 3 Output Relay Final Fault Value
(1)
Digital Expansion Module 4 Output Relay Communication Fault Action 342
• defines which state both output relays should go to when communication is not restored
567
with the time defined in Fault Mode Output State Duration (Parameter 561)
• defines how both output relays on Digital Expansion Module 4 responds when a communication fault occurs
Digital Expansion Module 4 Output Relay Communication Fault Value 343 • defines which state both output relays should go to when a communication fault occurs
Digital Expansion Module 4 Output Relay Final Fault Value
(1) Available in E200 relay firmware v5.000 and higher.
(1)
• defines which state both output relays should go to when communication is not restored
568
with the time defined in Fault Mode Output State Duration (Parameter 561)
Output Relay Communication Idle Modes
When a network scanner goes into Idle mode or a PLC goes into Program mode while communicating with an E200 relay, you can configure the E200 output relays to go to a specific state (Open or Close) or hold the last state. The parameters that are listed in
configure the Communication Idle Mode for each E200 output relay.
Ta b l e 5
36 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 37
Table 5 - Communication Idle Mode Parameters
System Operation and Configuration Chapter 3
Fault Na me
Output Relay 0 Communication Idle Action 308
Output Relay 0 Communication Idle Value 309
Output Relay 1 Communication Idle Action 314
Output Relay 1 Communication Idle Value 315
Output Relay 2 Communication Idle Action 320
Output Relay 2 Communication Idle Value 321
Digital Expansion Module 1 Output Relay Communication Idle Action 326
Digital Expansion Module 1 Output Relay Communication Idle Value 327
Digital Expansion Module 2 Output Relay Communication Idle Action 332
Digital Expansion Module 2 Output Relay Communication Idle Value 333
Digital Expansion Module 3 Output Relay Communication Idle Action 338
Digital Expansion Module 3 Output Relay Communication Idle Value 339
Digital Expansion Module 4 Output Relay Communication Idle Action 344
Digital Expansion Module 4 Output Relay Communication Idle Value 345
Parameter
No.
Description
• defines how Output Relay 0 when assigned as a Normal/General Purpose Relay or Control/ Control & Trip Relay responds when a network scanner goes into Idle Mode or a programmable logic controller (PLC) goes into Program Mode
• defines which state Output Relay 0 should go to when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines how Output Relay 1 when assigned as a Normal/General Purpose Relay or Control/ Control & Trip Relay responds when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines which state Output Relay 1 should go to when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines how Output Relay 2 when assigned as a Normal/General Purpose Relay or Control/ Control & Trip Relay responds when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines which state Output Relay 2 should go to when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines how both output relays on Digital Expansion Module 1 responds when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines which state both output relays should go to when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines how both output relays on Digital Expansion Module 2 responds when network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines which state both output relays should go to when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines how both output relays on Digital Expansion Module 3 responds when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines which state both output relays should go to when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines how both output relays on Digital Expansion Module 4 responds when a network scanner goes into Idle Mode or a PLC goes into Program Mode
• defines which state both output relays should go to when a network scanner goes into Idle Mode or a PLC goes into Program Mode

Expansion Bus Fault

The expansion bus of the E200 relay can be used to expand the I/O capabilities of the device with the addition of digital and analog expansion I/O modules. The Expansion Bus Fault lets you have the E200 relay go into a Trip or Warning state when established Expansion Bus communication is disrupted between the Control Module and any digital and analog expansion I/O modules.
The Expansion Bus Fault is used when the Option Match feature is not enabled for the digital and/or analog expansion I/O modules. The Expansion Bus Fault only monitors for communication disruptions between the Control Module and digital and/or analog expansion I/O modules. Expansion bus communication disruptions between the Control Module and Operator Station do not affect the Expansion Bus fault.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 37
Page 38
Chapter 3 System Operation and Configuration
Table 6 - Expansion Bus Fault Functions
Function
Name
Expansion Bus Tri p
Expansion Bus Warn ing
How to Enable
Set Control Trip Enable bit 10 to 1
Set Control
War nin g
Enable bit
10 to 1

Emergency Start

Setting
Parameter No.
186
192
Description
• When communication is disrupted between the Control Module and digital and/or analog expansion I/O modules, the E200 relay goes into a tripped state
• When communication is disrupted between the Control Module and digital and/or analog expansion I/O modules, the E200 relay goes into a warning state
In an emergency, it may be necessary to start a motor even if a protection fault or a communication fault exists. The trip condition may be the result of a thermal overload condition or the number of starts exceeded its configuration. These conditions can be overridden using the Emergency Start feature of the E200 relay.
IMPORTANT Activating Emergency Start inhibits overload and blocked start protection.
Trip/Warn Module
Blink Pattern
• Red 3 long and 11 short
•Yellow 3 long and 11 short
• Verify that the expansion bus cables are properly plugged
• When all expansion I/O modules’ status LEDs are solid
• Verify that the expansion bus cables are properly plugged
• When all expansion I/O modules’ status LEDs are solid
To Return to Ready/Run Mode:
into the Bus In and Bus Out por ts of all expansion modules
green, reset the trip state of the E200 relay by pressing the blue reset button on the Communication Module, via Connected Components Workbench software, or by an assigned digital input.
into the Bus In and Bus Out por ts of all expansion modules
green, the warning state of the E200 relay automatically clears
Running in this mode can cause equipment overheating and fire.
To enable the Emergency Start feature in the E200 relay, set the Emergency Start Enable (Parameter 216) to Enable.
Table 7 - Emergency Start (Parameter 216)
Value Description
0 Disable
1Enable
Configure one of the Ptxx Input Assignments (Parameters 196…201) to Emergency Start and activate the corresponding digital input.
Table 8 - Emergency Start Input PTXX Assignment (Parameters 196…201)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E200 relay when it is in a tripped state
2 Remote Trip Force the E200 relay to go into a tripped state
3Activate FLA2
4 Force Snapshot Force the E200 relay to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
Use the value in FLA2 Setting (Parameter 177) for the current-based protection algorithms
When the Emergency Start feature is active, the following actions occur in the E200 relay:
• Protection trips are ignored
• Output relays configured as Trip Relays are put into closed state
38 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 39
System Operation and Configuration Chapter 3
• Normal operation resumes with any Normal or Control Relay assigned output relay
• The Emergency Start Active bit is set to 1 in Device Status 0 (Parameter 20) bit 6

Language

Diagnostic Station User­defined Screens
User-defined Screen 1 – Parameter 1 428 • the E200 parameter number to display for the first parameter in user-defined screen 1
User-defined Screen 1 – Parameter 2 429 • the E200 parameter number to display for the second parameter in user-defined screen 1
User-defined Screen 2 – Parameter 1 430 • he E200 parameter number to display for the first parameter in user-defined screen 2
User-defined Screen 2 – Parameter 2 431 • the E200 parameter number to display for the second parameter in user-defined screen 2
User-defined Screen 3 – Parameter 1 432 • the E200 parameter number to display for the first parameter in user-defined screen 3
User-defined Screen 3 – Parameter 2 433 • the E200 parameter number to display for the second parameter in user-defined screen 3
User-defined Screen 4 – Parameter 1 434 • the E200 parameter number to display for the first parameter in user-defined screen 4
User-defined Screen 4 – Parameter 2 435 • the E200 parameter number to display for the second parameter in user-defined screen 4
(1) You can select one of the 560 available E200 relay parameters.
Name
The E200 relay supports multiple languages when you usethe optional expansion Operator Diagnostic Station. Parameter text is displayed in the selected language. The language parameter (212) displays the E200 relay parameter text displayed in the selected language.
The Diagnostic Station has four user-defined screens that are part of the its display sequence, in which you can define up to two parameters per screen.
Table 9 - User-defined Screen Parameters
Parame ter
No.
Description
(1)

Analog I/O Expansion Modules

Display Timeout
Display Timeout (Parameter 436) defines the time duration in which there is no display navigation activity, and the E200 Diagnostic Station returns to its normal display sequence. Any configuration parameters that were left in an edit state are canceled. A value of zero disables the display timeout function.
The E200 relay supports up to four Analog I/O Expansion Modules on the E200 Expansion Bus. The E200 Analog Expansion Module has three independent universal inputs and one analog output.
Analog Input Channels
Ta b l e 1 0 shows the analog signals that the universal analog inputs can accept.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 39
Page 40
Chapter 3 System Operation and Configuration
Signal Type Possible Values
Current 0…20 mA 4…20 mA
Voltage 0…10V DC 1…5V DC 0…5V DC
2-Wire RTD Sensors
3-Wire RTD Sensor
Resistance 0…150 Ω 0…750 Ω 0…3000 Ω 0…6000 Ω (PTC and NTC Sensors)
Table 10 - Universal Analog Input Signals
100 Ω, 200 Ω, 500 Ω, 1000 Ω
Pt 385
100 Ω, 200 Ω, 500 Ω, 1000 Ω
Pt 3916
10 Ω Cu 426 100 Ω Ni 618 120 Ω Ni 672 604 Ω NiFe 518
The analog inputs can report data in four different formats. Tab l e 11
through Ta b l e 1 4 display the data ranges for all available analog input types for the four available data formats.
Table 11 - Analog Input Data Format for Current Input Type
Input
Range
4…20 mA
0…20 mA
Input Value Condition
21.00 mA High Limit 21000 2100 32767 17407
20.00 mA High Range 20000 2000 32767 16383
4.00 mA Low Range 4000 400 -32768 0
3.00 mA Low Limit 3000 300 -32768 -1024
21.00 mA High Limit 21000 2100 32767 17202
20.00 mA High Range 20000 2000 32767 16383
0.00 mA Low Range 0 0 -32768 0
0.00 mA Low Limit 0 0 -32768 0
Engineering
Units
Engineering
Units x 10
Raw /
Proportional
PID
Table 12 - Analog Input Data Format for Voltage Input Type
Input
Range
0…10 V DC
1…5 V DC
0…5V DC
Input Value Condition
10.50V DC High Limit 10500 1050 32767 17202
10.00V DC High Range 10000 1000 32767 16383
0.00V DC Low Range 0 0 -32768 0
0.00V DC Low Limit 0 0 -32768 0
5.25V DC High Limit 5250 525 32767 17407
5.00V DC High Range 5000 500 32767 16383
1.00V DC Low Range 1000 100 -32768 0
0.50V DC Low Limit 500 50 -32768 -2048
5.25V DC High Limit 5250 525 32767 17202
5.00V DC High Range 5000 500 32767 16383
0.00V DC Low Range 0 0 -32768 0
0.00V DC Low Limit 0 0 -32768 0
Engineering
Units
Engineering
Units x 10
Raw /
Proportional
PID
40 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 41
Table 13 - Analog Input Data Format for RTD Input Type
System Operation and Configuration Chapter 3
Input Range Input Value Condition
850.0 °C High Limit 8500 850 32767 16383
850.0 °C High Range 8500 850 32767 16383
RTD 100 Ω, 200 Ω, 500 Ω, 1000 Ω Pt 385
RTD 100 Ω, 200 Ω, 500 Ω, 1000 Ω Pt 3916
RTD 10 Ω Cu 426
RTD 100 Ω Ni 618
RTD 120 Ω Ni 672
RTD 100 Ω NiFe 518
-200.0 °C Low Range -2000 -200 -32768 0
-200.0 °C Low Limit -2000 -200 -32768 0
1562.0 °F High Limit 15620 1562 32767 16383
1562.0 °F High Range 15620 1562 32767 16383
-328.0 °F Low Range -3280 -328 -32768 0
-328.0 °F Low Limit -3280 -328 -32768 0
630.0 °C High Limit 6300 630 32767 16383
630.0 °C High Range 6300 630 32767 16383
-200.0 °C Low Range -2000 -200 -32768 0
-200.0 °C Low Limit -2000 -200 -32768 0
1166.0 °F High Limit 11660 1166 32767 16383
1166.0 °F High Range 11660 1166 32767 16383
-328.0 °F Low Range -3280 -328 -32768 0
-328.0 °F Low Limit -3280 -328 -32768 0
260.0 °C High Limit 2600 260 32767 16383
260.0 °C High Range 2600 260 32767 16383
-100.0 °C Low Range -1000 -100 -32768 0
-100.0 °C Low Limit -1000 -100 -32768 0
500.0 °F High Limit 5000 500 32767 16383
500.0 °F High Range 5000 500 32767 16383
-148.0 °F Low Range -1480 -148 -32768 0
-148.0 °F Low Limit -1480 -148 -32768 0
260.0 °C High Limit 2600 260 32767 16383
260.0 °C High Range 2600 260 32767 16383
-100.0 °C Low Range -1000 -100 -32768 0
-100.0 °C Low Limit -1000 -100 -32768 0
500.0 °F High Limit 5000 500 32767 16383
500.0 °F High Range 5000 500 32767 16383
-148.0 °F Low Range -1480 -148 -32768 0
-148.0 °F Low Limit -1480 -148 -32768 0
260.0 °C High Limit 2600 260 32767 16383
260.0 °C High Range 2600 260 32767 16383
-80.0 °C Low Range -800 -80 -32768 0
-80.0 °C Low Limit -800 -80 -32768 0
500.0 °F High Limit 5000 500 32767 16383
500.0 °F High Range 5000 500 32767 16383
-112.0 °F Low Range -1120 -112 -32768 0
-112.0 °F Low Limit -1120 -112 -32768 0
200.0 °C High Limit 2000 200 32767 16383
200.0 °C High Range 2000 200 32767 16383
-100.0 °C Low Range -1000 -100 -32768 0
-100.0 °C Low Limit -1000 -100 -32768 0
392.0 °F High Limit 3920 392 32767 16383
392.0 °F High Range 3920 392 32767 16383
-148.0 °F Low Range -1480 -148 -32768 0
-148.0 °F Low Limit -1480 -148 -32768 0
Engineering
Units
Engineering
Units x 10
Raw /
Proportional
PID
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 41
Page 42
Chapter 3 System Operation and Configuration
Table 14 - Analog Input Data Format for Resistance Input Type
Input Range Input Value Condition
150.00 Ω High Limit 15000 1500 32767 16383
Resistance 0…50 Ω
Resistance 0…750 Ω
Resistance 0…3000 Ω
Resistance 0…6000 Ω (PTC / NTC)
150.00 Ω High Range 15000 1500 32767 16383
0.00 Ω Low Range 0 0 -32768 0
0.00 Ω Low Limit 0 0 -32768 0
750.0 Ω High Limit 7500 750 32767 16383
750.0 Ω High Range 7500 750 32767 16383
0.0 Ω Low Range 0 0 -32768 0
0.0 Ω Low Limit 0 0 -32768 0
3000.0 Ω High Limit 30000 3000 32767 16383
3000.0 Ω High Range 30000 3000 32767 16383
0.0 Ω Low Range 0 0 -32768 0
0.0 Ω Low Limit 0 0 -32768 0
6000 Ω High Limit 6000 600 32767 16383
6000 Ω High Range 6000 600 32767 16383
0 Ω Low Range 0 0 -32768 0
0 Ω Low Limit 0 0 -32768 0
Engineering
Units
Engineering
Units x 10
Raw /
Proportional
PID
The performance for the input channels of the E200 Analog I/O Expansion Module is dependent on the filter setting for each channel. The total scan time for the input channels of the module is determined by adding the conversion time for all enabled input channels.
Table 15 - Analog Input Channel Conversion Time
Input Type Filter Frequency Conversion Time
17 Hz 153 ms
Current, Volta ge, 2-Wire RTD, Resistance
3-Wire RTD
4 Hz 512 ms
62 Hz 65 ms
470 Hz 37 ms
17 Hz 306 ms
4 Hz 1024 ms
62 Hz 130 ms
470 Hz 74 ms
Example:
• Channel 00 is configured for a 3-wire RTD and 4 Hz filter (conversion time = 1024 ms).
• Channel 01 is configured for 17 Hz voltage (conversion time = 153 ms).
• Channel 02 is configured for 62 Hz current (conversion time = 65 ms).
The E200 Analog I/O Expansion Module input channel scan time is 1242 ms (1024+153+65).
Analog Output Channel
Ta b l e 1 6 shows the values that you can program the isolated analog output to provide.
42 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 43
System Operation and Configuration Chapter 3
Table 16 - Universal Analog Output Signals
Signal Type Possible Values
Current 0…20 mA 4…20 mA
Voltage 0…10V DC 1…5V DC 0…5V DC
The analog outputs can report data as a percent of range. Ta b l e 1 7
and Ta b l e 1 8 display
the data ranges for all available analog output types.
Table 17 - Analog Output Data Format for Current Output Type
Output Range Output Signal Condition % Range
21.000 mA High Limit 106.25%
4…20 mA
0…20 mA
20.000 mA High Range 100.00%
4.000 mA Low Range 0.00%
3.000 mA Low Limit -6.25%
21.00 mA High Limit 105.00%
20.00 mA High Range 100.00%
0.00 mA Low Range 0.00%
0.00 mA Low Limit 0.00%
Table 18 - Analog Output Data Format for Voltage Output Type
Output Range Output Value Condition % Range
10.50V DC High Limit 105.00%
0…10 V DC
1…5 V DC
0…5 V DC
10.00V DC High Range 100.00%
0.00V DC Low Range 0.00%
0.00V DC Low Limit 0.00%
5.25V DC High Limit 106.25%
5.00V DC High Range 100.00%
1.00V DC Low Range 0.00%
0.50V DC Low Limit -6.25%
5.25V DC High Limit 105.00%
5.00V DC High Range 100.00%
0.00V DC Low Range 0.00%
0.00V DC Low Limit 0.00%
The analog output can be used to communicate E200 diagnostic information via an analog signal to distributed control systems, programmable logic controllers, or panel­mounted analog meters. The analog output can represent one of the following E200 diagnostic parameters:
•Average %FLA
•%TCU
• Ground Fault Current
• Current Imbalance
•Average L-L Voltage
•Voltage Imbalance
•Total kW
•Total kVAR
•Total kVA
• Total Power Factor
• User-defined Value
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 43
Page 44
Chapter 3 System Operation and Configuration
Table 19 - Analog Output Selection Type
Output Selection Low Range High Range
Average % FLA 0% 100%
Scaled Average % FLA 0% 200%
% TCU 0% 100%
Ground Fault Current
Internal, 0.50…5.00 A 0.50 A 5.00 A
External, 0.02…0.10 A 0.02 A 0.10 A
External, 0.10…0.50 A 0.10 A 0.50 A
External, 0.20…1.00 A 0.20 A 1.00 A
External, 1.00…5.00 A 1.00 A 5.00 A
Current Imbalance 0% 100%
Average L-L Voltage 0V (PT Primary) V
Voltage Imbalance 0% 100%
Total kW 0 kW (FLA1 x PT Primary x 1.732) V
Total kVAR 5.25V DC (FLA1 x PT Primary x 1.732) V
Total kVA 5.00V DC (FLA1 x PT Primary x 1.732) V
Total Power Factor -50% (Lagging) +50% (Leading)
User-defined Value -32768 32767
The E200 Analog I/O Expansion Module output channel update rate is 10 ms.
Analog Modules
Table 20 - Analog Module 1 Channel Descriptions
Name
Input Channel 00 Type 437 • defines the type of analog signal that Input Channel 00 of Analog Module 1 monitors
Input Channel 00 Format 438 • defines the data format for how the analog reading is reported
Input Channel 00 Temperature Unit 439 • defines the temperature unit for RTD sensor readings
Input Channel 00 Filter Frequency 440 • defines update rate for the input channels of the analog module
Input Channel 00 Open Circuit State 441 • defines what the input channel reports when the input channel has an open circuit
Input Channel 00 RTD Type Enable 442 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Input Channel 01 Type 446 • defines the type of analog signal that Input Channel 01 of Analog Module 1 monitors
Input Channel 01 Format 447 • defines the data format for how the analog reading is reported
Input Channel 01 Temperature Unit 448 • defines the temperature unit for RTD sensor readings
Input Channel 01 Filter Frequency 449 • defines update rate for the input channels of the analog module
Input Channel 01 Open Circuit State 450 • defines what the input channel reports when the input channel has an open circuit
Input Channel 01 RTD Type Enable 451 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Input Channel 02 Type 455 • defines the type of analog signal that Input Channel 02 of Analog Module 1 monitors
Input Channel 02 Format 456 • defines the data format for how the analog reading is reported
Input Channel 02 Temperature Unit 457 • defines the temperature unit for RTD sensor readings
Input Channel 02 Filter Frequency 458 • defines update rate for the input channels of the analog module
Input Channel 02 Open Circuit State 459 • defines what the input channel reports when the input channel has an open circuit
Input Channel 02 RTD Type Enable 460 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Output Channel 00 Type 464 • defines the type of analog signal that Output Channel 00 of Analog Module 1 provides
Output Channel 00 Selection 465 • defines the E200 relay parameter that Output Channel 00 represents
Output Channel 00 Expansion Bus Fault Action 466 • defines the value that Output Channel 00 provides when there is an E200 Expansion Bus fault
Output Channel 00 Protection Fault Action 467 • defines the value that Output Channel 00 provides when the E200 is in a tripped state
(1) Open circuit detection is always enabled for this input channel.
Parameter
No.
Description
(1)
(1)
(1)
44 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 45
Table 21 - Analog Module 2 Descriptions
System Operation and Configuration Chapter 3
Name
Parameter
No.
Description
Input Channel 00 Type 468 • defines the type of analog signal that Input Channel 00 of Analog Module 2 monitors
Input Channel 00 Format 469 • defines the data format for how the analog reading is reported
Input Channel 00 Temperature Unit 470 • defines the temperature unit for RTD sensor readings
Input Channel 00 Filter Frequency 471 • defines update rate for the input channels of the analog module
Input Channel 00 Open Circuit State 472 • defines what the input channel reports when the input channel has an open circuit
(1)
Input Channel 00 RTD Type Enable 473 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Input Channel 01 Type 477 • defines the type of analog signal that Input Channel 01 of Analog Module 2 monitors
Input Channel 01 Format 478 • defines the data format for how the analog reading is reported
Input Channel 01 Temperature Unit 479 • defines the temperature unit for RTD sensor readings
Input Channel 01 Filter Frequency 480 • defines update rate for the input channels of the analog module
Input Channel 01 Open Circuit State 481 • defines what the input channel reports when the input channel has an open circuit
(1)
Input Channel 01 RTD Type Enable 482 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Input Channel 02 Type 486 • defines the type of analog signal that Input Channel 02 of Analog Module 2 monitors
Input Channel 02 Format 487 • defines the data format for how the analog reading is reported
Input Channel 02 Temperature Unit 488 • defines the temperature unit for RTD sensor readings
Input Channel 02 Filter Frequency 489 • defines update rate for the input channels of the analog module
Input Channel 02 Open Circuit State 490 • defines what the input channel reports when the input channel has an open circuit
(1)
Input Channel 02 RTD Type Enable 491 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Output Channel 00 Type 464 • defines the type of analog signal that Output Channel 00 of Analog Module 2 provides
Output Channel 00 Selection 496 • defines the E200 relay parameter that Output Channel 00 represents
Output Channel 00 Expansion Bus Fault Action 497
Output Channel 00 Protection Fault Action 498
(1) Open circuit detection is always enabled for this input channel.
• defines the value that the E200 Anal og I/O Expa nsion Mod ule Outpu t Channel 0 0 provides w hen there i s an E200 Expansion Bus fault
• defines the value that the E200 Analog I/O Expansion Module Output Channel 00 provides when the E200 is in a tripped state
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 45
Page 46
Chapter 3 System Operation and Configuration
Table 22 - Analog Module 3 Channel Descriptions
Name
Parameter
No.
Description
Input Channel 00 Type 499 • defines the type of analog signal that Input Channel 00 of Analog Module 3 monitors
Input Channel 00 Format 500 • defines the data format for how the analog reading is reported
Input Channel 00 Temperature Unit 501 • defines the temperature unit for RTD sensor readings
Input Channel 00 Filter Frequency 502 • defines update rate for the input channels of the analog module
Input Channel 00 Open Circuit State 503 • defines what the input channel reports when the input channel has an open circuit
(1)
Input Channel 00 RTD Type Enable 504 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Input Channel 01 Type 508 • defines the type of analog signal that Input Channel 01 of Analog Module 3 monitors
Input Channel 01 Format 509 • defines the data format for how the analog reading is reported
Input Channel 01 Temperature Unit 510 • defines the temperature unit for RTD sensor readings
Input Channel 01 Filter Frequency 511 • defines update rate for the input channels of the analog module
Input Channel 01 Open Circuit State 512 • defines what the input channel reports when the input channel has an open circuit
(1)
Input Channel 01 RTD Type Enable 513 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Input Channel 02 Type 517 • defines the type of analog signal that Input Channel 02 of Analog Module 3 monitors
Input Channel 02 Format 518 • defines the data format for how the analog reading is reported
Input Channel 02 Temperature Unit 519 • defines the temperature unit for RTD sensor readings
Input Channel 02 Filter Frequency 520 • defines update rate for the input channels of the analog module
Input Channel 02 Open Circuit State 521 • defines what the input channel reports when the input channel has an open circuit
(1)
Input Channel 02 RTD Type Enable 522 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Output Channel 00 Type 526 • defines the type of analog signal that Output Channel 00 of Analog Module 3 provides
Output Channel 00 Selection 527 • defines the E200 relay parameter that Output Channel 00 represents
Output Channel 00 Expansion Bus Fault Action 528
Output Channel 00 Protection Fault Action 529
(1) Open circuit detection is always enabled for this input channel.
• defines the value that the E200 Anal og I/O Expa nsion Mod ule Outpu t Channel 0 0 provides w hen there i s an E200 Expansion Bus fault
• defines the value that the E200 Analog I/O Expansion Module Output Channel 00 provides when the E200 is in a tripped state
46 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 47
Table 23 - Analog Module 4 Channel Descriptions
System Operation and Configuration Chapter 3
Name
Input Channel 00 Type 530 • defines the type of analog signal that Input Channel 00 of Analog Module 4 monitors
Input Channel 00 Format 531 • defines the data format for how the analog reading is reported
Input Channel 00 Temperature Unit 532 • defines the temperature unit for RTD sensor readings
Input Channel 00 Filter Frequency 533 • defines update rate for the input channels of the analog module
Input Channel 00 Open Circuit State 534 • defines what the input channel reports when the input channel has an open circuit
Input Channel 00 RTD Type Enable 535 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Input Channel 01 Type 539 • defines the type of analog signal that Input Channel 01 of Analog Module 4 monitors
Input Channel 01 Format 540 • defines the data format for how the analog reading is reported
Input Channel 01 Temperature Unit 541 • defines the temperature unit for RTD sensor readings
Input Channel 01 Filter Frequency 542 • defines update rate for the input channels of the analog module
Input Channel 01 Open Circuit State 543 • defines what the input channel reports when the input channel has an open circuit
Input Channel 01 RTD Type Enable 544 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Input Channel 02 Type 548 • defines the type of analog signal that Input Channel 02 of Analog Module 4 monitors
Input Channel 02 Format 549 • defines the data format for how the analog reading is reported
Input Channel 02 Temperature Unit 550 • defines the temperature unit for RTD sensor readings
Input Channel 02 Filter Frequency 551 • defines update rate for the input channels of the analog module
Input Channel 02 Open Circuit State 552 • defines what the input channel reports when the input channel has an open circuit
Input Channel 02 RTD Type Enable 556 • defines the type of RTD to monitor when the input channel type is configured to scan an RTD sensor
Output Channel 00 Type 557 • defines the type of analog signal that Output Channel 00 of Analog Module 4 provides
Output Channel 00 Selection 558 • defines the E200 relay parameter that Output Channel 00 represents
Output Channel 00 Expansion Bus Fault Action 559
Output Channel 00 Protection Fault Action 560
(1) Open circuit detection is always enabled for this input channel.
Parameter
No.
Description
(1)
(1)
(1)
• defines the value that the E200 Anal og I/O Expa nsion Mod ule Outpu t Channel 0 0 provides w hen there i s an E200 Expansion Bus fault
• defines the value that the E200 Analog I/O Expansion Module Output Channel 00 provides when the E200 is in a tripped state

Introduction to Operating Modes

The E200 relay supports a number of Operating Modes, which consist of configuration rules and logic to control typical full-voltage motor starters, including:
•Overload
•Non-Reversing Starter
•Reversing Starter
• Wye/Delta (Star/Delta) Starter
•Two-Speed Starter
•Monitor
The default Operating Mode (Parameter 195) for the E200 relay is Overload (Network) in which the E200 relay operates like a traditional overload relay in which one of the output relays is assigned as a Trip Relay or Control Relay. Use commands to control any output relays that are assigned as Normal output relays or Control Relays. Invalid configuration of the output relays causes the E200 relay to go into Invalid Configuration Mode and trip on a configuration trip. Operating Modes on page 49 describes the functionality of the available Operating Modes for the E200 relay and their associated configuration rules.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 47
Page 48
Chapter 3 System Operation and Configuration
Notes:
48 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 49
Chapter 4
Operating Modes
The E200 Electronic Overload Relay supports up to 54 operating modes, which consist of configuration rules and logic to control typical full-voltage motor starters, including:
•Overload
•Non-reversing starter
•Reversing starter
• Wye/Delta (Star/Delta) starter
•Two-speed starter
•Monitoring device
This chapter explains the configuration rules, logic, and control wiring that is required for the available operating modes. The default Operating Mode (Parameter 195) for the E200 relay is Overload (Network)—even though the E200 relay is non networked. In this mode, the E200 relay operates like a traditional overload relay in which one of the output relays is assigned as a Trip Relay or Control Relay. Use commands via the operator control/diagnostic station to control any output relays that are assigned as Normal output relays or Control Relays. Invalid configuration of the output relays causes the E200 relay to go into Invalid Configuration Mode and trip on a configuration trip.

Overload Operating Modes

The overload-based operating modes of the E200 relay make the device operate as a traditional overload relay, in which it interrupts the control circuit of a contactor coil with a normally closed trip relay or a normally open control relay. There are four overload-based operating modes to choose from:
•Network – Because the E200 is non-networked, the overload outputs cannot be
controlled over a network. This default mode allows the device to function as a normally closed overload relay.
• Operator Station
•Local I/O
•Custom
The E200 relay is wired as a traditional overload relay with one of the output relays configured as a normally closed trip relay. Figure 6 reversing starter. Relay 0 is configured as a trip relay, and Relay 1 is configured as a normally open control relay, which receives commands to energize the contactor coil from an automation controller.
You can also wire the E200 relay as a control relay so that the relay is controlled by local means and opens when a trip event occurs. Figure 7 reversing starter with Relay 0 configured as a control relay. Relay 0 receives control commands to energize or de-energize the contactor coil locally or from an external source. Relay 0 also goes to an open state when there is a trip event.
is a wiring diagram of a non-
is a wiring diagram of a non-
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 49
Page 50
Chapter 4 Operating Modes
(1) Contact shown with supply voltage applied.
Relay 0 configured as a trip relay
(1)
Relay 1
R13 R14 R03 R04
Motor
A1 A2
(1) Contact shown with supply voltage applied.
Relay 0 configured as a control relay
(1)
R03 R04
Motor
A1 A2
Tri p Re lay
Trip Reset
Device Status 0 Tri p Pres et
Figure 6 - Trip Relay Wiring Diagram
For Control Module firmware v3.000 and higher, you can also wire the E200 relay as a control relay so that the relay that is controlled by the communication network opens when a trip event occurs. Figure 7
is a wiring diagram of a non-reversing starter with Relay 0 configured as a control relay. Relay 0 receives control commands from an automation controller to energize or de-energize the contactor coil. Relay 0 also goes to an open state when there is a trip event.
Figure 7 - Control Relay Wiring Diagram
50 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Figure 8 - Timing Diagram
Overload (Network)
The default Operating Mode (Parameter 195 = 2) of the E200 relay is Overload (Network), in which the E200 operates as a traditional overload relay with one output
relay that is assigned as a normally closed trip relay or a normally open control relay. Use network commands to control the control relay or any of the remaining output relays that are assigned as normal output relays.
The reset button of the E200 Operator Station is enabled for this operating mode. The E200 relay's default Operating Mode (Parameter 195 = 2) is Network Overload
(note: Since the E200 is non-networked, the overload outputs cannot be controlled over a network.), in which the E200 operates as a traditional overload relay with one output relay that is assigned as a normally closed trip relay or a normally open control relay. Use commands locally or via external means to control the control relay or any of the remaining output relays that are assigned as normal output relays.
Page 51
Operating Modes Chapter 4
The reset button of the E300/E200 Operator Station is enabled for this operating mode.
Rules
1. You must assign one output relay as a trip relay or control relay. Set any of the Output Ptxx Assignments (Parameters 202…204) to Trip Relay or Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 2
Overload (Operator Station)
Operating Mode Overload (Operator Station) (Parameter 195 = 26) operates as a traditional overload relay with one output relay that is assigned as a normally closed trip relay or a normally open control relay. The Overload (Operator Station) operating mode is used when an external source uses the start and stop keys of the E200 Operator Station for its motor control logic. Use commands locally or via external means to control the control relay or any of the remaining output relays that are assigned as normal output relays.
The reset button of the E200 Operator Station is enabled, and the Local/Remote yellow LED is illuminated to indicate that the operator station is being used for local control.
Rules
1. You must assign one output relay as a trip relay or control relay. Set any of the Output Ptxx Assignments (Parameters 202…204) to Trip Relay or Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
4. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
Or
• Option Match Warning must be enabled in WarningEnableC
(Parameter 192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type (Parameter
224)
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 51
Page 52
Chapter 4 Operating Modes
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 26.
Overload (Local I/O)
Operating Mode Overload (Local I/O) (Parameter 195 = 35) operates as a traditional overload relay with one output relay that is assigned as a normally closed trip relay or a normally open control relay. The Overload (Local I/O) operating mode is used for standalone applications or automation systems that do not use an E200 Operator Station. Use the digital inputs of the E200 locally for the motor control logic. The E200 relay can use network commands to control the control relay or any of the remaining output relays that are assigned as Normal output relays. The reset button of the E200 Operator Station is disabled, and a digital input that is assigned as a trip reset is required.
Rules
1. You must assign one output relay as a trip relay or control relay. Set any of the Output Ptxx Assignments (Parameters 202…204) to Trip Relay or Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
4. Operator Station Option Match Trip or Warning must be enabled.
5. Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
Or
• Option Match Warning must be enabled in WarningEnableC (Parameter
192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
6. Communication Fault & Idle Override (Parameter 346) must be enabled.
7. Network Fault Override (Parameter 347) must be enabled.
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 35.
Overload (Custom)
Operating Mode Overload (Custom) (Parameter 195 = 49) operates as a traditional overload relay with one output relay that is assigned as a normally closed trip relay or a normally open control relay. The Overload (Custom) operating mode is used for applications that require customized DeviceLogix programs. This operating mode requires minimal configuration rules.
52 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 53
Operating Modes Chapter 4
Rules
1. Set any of the Output Ptxx Assignments (Parameters 202…204) to Trip Relay or Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
DeviceLogix Program
The last saved DeviceLogix program is executed in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 49.

Non-reversing Starter Operating Modes

The non-reversing starter-based operating modes of the E200 relay provide the control logic for a non-reversing full voltage starter. A normally open control relay controls the contactor coil. When a trip event occurs, the control relay remains open until the E200 receives a trip reset command. There are 15 non-reversing starter-based operating modes to choose from:
•Network
• Network with Feedback
• Operator Station
• Operator Station with Feedback
• Local I/O – Two-wire Control
• Local I/O with Feedback – Two-wire Control
• Local I/O – Three-wire Control
• Local I/O with Feedback – Three-wire Control
• Network & Operator Station
• Network & Operator Station with Feedback
• Network & Local I/O – Two-wire Control
• Network & Local I/O with Feedback – Two-wire Control
• Network & Local I/O – Three-wire Control
• Network & Local I/O with Feedback – Three-wire Control
•Custom
Non-reversing Starter (Network)
Operating Mode Non-Reversing Starter (Network) (Parameter 195 = 3) uses the network tag LogicDefinedPt00Data in Output Assembly 144 to control Relay 0, which controls the contactor coil. LogicDefinedPt00Data is a maintained value, so the non­reversing starter remains energized when LogicDefinedPt00Data has a value of 1. Program the appropriate state of the starter by using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Output Pt00 Assignment (Parameters 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 53
.
Page 54
Chapter 4 Operating Modes
Control Power
E200 Relay
Relay 0
R03 R04
Run
Relay 0
Trip Reset
Tri p St atu s
Tri p Even t
Run/Stop
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay can be controlled locally and opens when a trip event occurs. Figure 9 starter with Output Relay 0 configured as a control relay.
Figure 9 - Non-reversing Starter (Network) Wiring Diagram
is a wiring diagram of a non-reversing
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 3.
Timing Diagram
Figure 10 - Non-reversing Starter (Network) Timing Diagram
Non-reversing Starter (Network) with Feedback
Operating Mode Non-Reversing Starter (Network) with Feedback (Parameter 195 = 4) uses the network tag LogicDefinedPt00Data in Output Assembly 144 to control Relay 0, which controls the contactor coil. LogicDefinedPt00Data is a maintained value, so the non-reversing starter remains energized when LogicDefinedPt00Data has a value of 1. Use the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3 state of the starter.
The auxiliary contact from the contactor of the non-reversing starter is wired into Input 0. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
The reset button of the E200 Operator Station is enabled for this operating mode.
to program the appropriate
54 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 55
Operating Modes Chapter 4
Control Power
E200 Relay
Relay 0
R03 R04
Run
Run Aux
IN 0
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay and opens when a trip event occurs. Figure 11 is a wiring diagram of a non-reversing starter with the contactor auxiliary wired to Input 0 and Output Relay 0 configured as a control relay.
Figure 11 - Non-reversing Starter (Network) with Feedback Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 4.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 55
Page 56
Chapter 4 Operating Modes
Normal Operation Trip Event
Feedback Timeout Tri p
Timer
Tri p St atu s
Tri p R ese t
Run/Stop
Relay 0
Feedback Timeout
Feedback
Timing Diagram
Figure 12 - Non-reversing Starter (Network) with Feedback Timing Diagram
Non-reversing Starter (Operator Station)
Operating Mode Non-Reversing Starter (Operating Station) (Parameter 195 = 27) uses the Operator Station’s “I” and “0” keys to control Relay 0, which controls the contactor coil. These keys are momentary push buttons, so the non-reversing starter remains energized when you release the “I” button. The E200 relay issues a trip or warning event if the E200 Operator Station disconnects from the base relay.
The reset button of the E200 Operator Station is enabled, and the Local/Remote yellow LED is illuminated to indicate that the operator station is being used for local control.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
4. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
Or
56 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 57
Operating Modes Chapter 4
Control Power
E200 Relay
Relay 0
R03 R04
Run
0-StopI-Run
Tri p Ev ent
Tri p
Trip Reset
Stop
Relay 0
Start
• Option Match Warning must be enabled in WarningEnableC (Parameter
192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay, and it opens when a trip event occurs.
Figure 13
configured as a control relay.
Figure 13 - Non-reversing Starter (Operator Station) Wiring Diagram
is a wiring diagram of a non-reversing starter with Output Relay 0
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 27.
Timing Diagram
Figure 14 - Non-reversing Starter (Operator Station) Timing Diagram
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 57
Page 58
Chapter 4 Operating Modes
Non-reversing Starter (Operator Station) with Feedback
Operating Mode Non-Reversing Starter (Operator Station) with Feedback (Parameter 195 = 28) uses the E200 Operator Station “I” and “0” keys to control Relay 0, which controls the contactor coil. These keys are momentary push buttons, so the non­reversing starter remains energized when you release the “I” button. The E200 relay issues a trip or warning event if the E200 Operator Station disconnects from the base relay.
The auxiliary contact from the contactor of the non-reversing starter is wired into Input 0. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
The reset button of the E200 Operator Station is enabled, and the Local/Remote yellow LED is illuminated to indicate that the operator station is being used for local control.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
4. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type (Parameter
224)
Or
• Option Match Warning must be enabled in WarningEnableC (Parameter
192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type (Parameter
224)
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
7. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled locally and opens when a trip event occurs. Figure 15 with the contactor auxiliary wired to Input 0 and Output Relay 0 configured as a control relay.
is a wiring diagram of a non-reversing starter
58 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 59
Operating Modes Chapter 4
Control Power
E200 Relay
Relay 0
R03 R04
Run
0-Stop
I-Run
Run Aux
IN 0
Start
Tri p Even t
Feedba ck Timeo ut Tri p
Timer
Tri p St atu s
Trip Reset
Stop
Relay 0
Feedback Timeout
Feedba ck IN 0
Figure 15 - Non-reversing Starter (Operator Station) with Feedback Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 28.
Timing Diagram
Figure 16 - Non-reversing Starter (Operator Station) with Feedback Timing Diagram
Non-reversing Starter (Local I/O) – Two-wire Control
Operating Mode Non-Reversing Starter (Local I/O) – Two Wire Control (Parameter 195 = 36) uses Input 0 to control Output Relay 0, which controls the contactor coil. Input 0 is a maintained value, so the non-reversing starter remains energized when Input 0 is active.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 59
Page 60
Chapter 4 Operating Modes
Control Power
E200 Relay
Relay 0
R03 R04
Run
Run/Stop
IN 0
IMPORTANT
The Non-reversing Starter (Local I/O) – Two-wire Control operating mode uses the signal from Input 0 to control the starter. When an E200 relay powers up, the starter energizes if Input 0 is active.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Communication Fault & Idle Override (Parameter 346) must be enabled.
4. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled by the state of Input 0 and opens when a trip event occurs. Fig ure 17 reversing starter with Output Relay 0 configured as a control relay.
Figure 17 - Non-reversing Starter (Local I/O) – Two-wire Control Wiring Diagram
is a wiring diagram of a non-
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 36.
60 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 61
Operating Modes Chapter 4
Relay 0
Tri p Re set
Tri p St atu s
Tri p Even t
Run/Stop
Timing Diagram
Figure 18 - Non-reversing Starter (Local I/O) – Two-wire Control Timing Diagram
Non-reversing Starter (Local I/O) – Two-wire Control with Feedback
Operating Mode Non-Reversing Starter (Local I/O) – Two Wire Control with Feedback (Parameter 195 = 37) uses the state of Input 1 to control Output Relay 0, which controls the contactor coil. Input 0 is a maintained value, so the non-reversing starter remains energized when Input 1 is active.
The auxiliary contact from the non-reversing starter’s contactor is wired into Input 0. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
The reset button of the E200 Operator Station is enabled for this operating mode.
IMPORTANT
The Non-reversing Starter (Local I/O) – Two-wire Control with Feedback operating mode uses the state of Input 1 to control the starter. When the E200 relay powers up, the starter energizes if Input 1 is active.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
4. Communication Fault & Idle Override (Parameter 346) must be enabled.
5. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled by the state if Input 1 and opens when a trip event occurs. Fig ure 19 reversing starter with Output Relay 0 configured as a control relay.
is a wiring diagram of a non-
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 61
Page 62
Chapter 4 Operating Modes
Control Power
E200 Relay
Relay 0
R03 R04
Run
Run/Stop
IN 0
IN 1
Run Aux
Relay 0
Run/Stop
Normal Operation
Feedback Timeout Tri p
Timer
Tri p St atu s
Tri p Re set
Feedba ck
Feedback TimeoutTri p Ev ent
Figure 19 - Non-reversing Starter (Local I/O) – Two-wire Control with Feedback Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 37.
Timing Diagram
Figure 20 - Non-reversing Starter (Local I/O) – Two-wire Control with Feedback Timing Diagram
Non-reversing Starter (Local I/O) – Three-wire Control
Operating Mode Non-Reversing Starter (Local I/O) – Three Wire Control (Parameter 195 = 38) uses an active state in Input 1 (normally open momentary push button) to energize Output Relay 0, which controls the contactor coil, and a de-active state in Input 0 is used (normally closed push button) to de-energize Output Relay 0. Both Input 0 and Input 1 are momentary values, so the non-reversing starter only energizes if Input 0 is active and Input 1 is momentarily active.
The reset button of the E200 Operator Station is enabled for this operating mode.
62 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 63
Operating Modes Chapter 4
Control Power
E200 Relay
Relay 0
R03 R04
Run
IN 0
IN 1
Stop
Run
Tri p Even t
Tri p Re set
Relay 0
Stop
Start
Tri p
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Communication Fault & Idle Override (Parameter 346) must be enabled.
4. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is energized when Input 0 is active and Input 1 is momentarily active. Output Relay 0 de-energizes when Input 0 is momentarily de-active or when a trip event occurs. Figure 21 non-reversing starter with three wire control and an Output Relay 0 configured as a control relay.
Figure 21 - Non-reversing Starter (Local I/O) – Three-wire Control Wiring Diagram
is a wiring diagram of a
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 38.
Timing Diagram
Figure 22 - Non-reversing Starter (Local I/O) – Three-wire Control Timing Diagram
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 63
Page 64
Chapter 4 Operating Modes
Control Power
E200 Relay
Relay 0
R03 R04
Run
Run Aux
IN 0
IN 1
IN 2
Run
Stop
Non-reversing Starter (Local I/O) – Three-wire Control with Feedback
Operating Mode Non-Reversing Starter (Local I/O) – Three Wire Control with Feedback (Parameter 195 = 39) uses an active state in Input 1 (normally open
momentary push button) to energize Output Relay 0, which controls the contactor coil, and a de-active state in Input 2 is used (normally closed momentary push button) to de-energize Output Relay 0. Both Input 1 and Input 2 are momentary values, so the non-reversing starter only energizes if Input 2 is active and Input 1 is momentarily active.
The auxiliary contact from the non-reversing starter’s contactor is wired into Input 0. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Three digital inputs must be available on the Control Module
2. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled by the state if Input 1 and opens when a trip event occurs. Fig ure 23 reversing starter with three wire control and Output Relay 0 configured as a control relay.
Figure 23 - Non-reversing Starter (Local I/O) – Three-wire Control with Feedback Wiring Diagram
is a wiring diagram of a non-
64 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on powerup or when Operating Mode (Parameter 195) is set to a value of 39.
Page 65
Operating Modes Chapter 4
Tri p Ev ent
Feedback Timeout Tri p
Tri p St atu s
Tri p Re set
Relay 0
Feedback Timeout
Stop
Start
Timer
Feedback IN 0
Timing Diagram
Figure 24 - Non-reversing Starter (Local I/O) – Three-wire Control with Feedback Timing Diagram
Non-reversing Starter (Network & Operator Station)
Operating Mode Non-Reversing Starter (Network& Operator Station) (Parameter 195 = 11) uses the network tag LogicDefinedPt00Data in Output Assembly 144 in Remote control mode and the E200 Operator Station’s “I” and “0” keys in Local control mode to control Relay 0, which controls the contactor coil. LogicDefinedPt00Data is a maintained value, so the non-reversing starter remains energized when LogicDefinedPt00Data has a value of 1 in Remote control mode. Program the appropriate state of the starter by using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in
Chapter 3
The E200 Operator Station “I”, “0”, and “Local/Remote” keys are momentary push buttons. Press and release the “I” button in Local control mode to energize the starter. Press and release the “0” button in Local control mode to de-energize the starter.
To change between Local and Remote control mode, press and release the “Local/ Remote” button on the E200 Operator Station. The LED above “Local/Remote” button illuminates yellow in Local control mode and red in Remote control mode.
The E200 relay issues a trip or warning event if the E200 Operator Station disconnects from the base relay.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
.
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 65
Page 66
Chapter 4 Operating Modes
Control Power
E200 Relay
Relay 0
R03 R04
Run
0-StopI-Run
4. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type (Parameter
224)
Or
• Option Match Warning must be enabled in WarningEnableC (Parameter
192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type (Parameter
224)
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled locally and opens when a trip event occurs. Figure 25 with Output Relay 0 configured as a control relay.
is a wiring diagram of a non-reversing starter
Figure 25 - Non-reversing Starter (Network & Operator Station) Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 11.
66 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Non-reversing Starter (Network & Operator Station) with Feedback
Operating Mode Non-Reversing Starter (Network& Operator Station) with Feedback (Parameter 195 = 12) uses the network tag LogicDefinedPt00Data in Output Assembly 144 in Remote control mode and the E200 Operator Station’s “I” and “0” keys in local control mode to control Relay 0, which controls the contactor coil. LogicDefinedPt00Data is a maintained value, so the non-reversing starter remains energized when LogicDefinedPt00Data has a value of 1 in Remote control mode. Program the appropriate state of the starter by using the Network Communication
Page 67
Operating Modes Chapter 4
Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
The E200 Operator Station’s “I”, “0”, and “Local/Remote” keys are momentary push buttons. Press and release the “I” button in Local control mode to energize the starter. Press and release the “0” button in Local control mode to de-energize the starter.
To change between Local and Remote control mode press and release the “Local/ Remote” button on the E200 Operator Station. The LED above “Local/Remote” button illuminates yellow in Local control mode and red in Remote control mode.
The auxiliary contact from the non-reversing starter’s contactor is wired into Input 0. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 relay issues a trip or warning event.
The E200 relay issues a trip or warning event if the E200 Operator Station disconnects from the base relay.
The reset button of the E200 Operator Station is enabled for this operating mode.
.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
4. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type (Parameter
224)
Or
• Option Match Warning must be enabled in WarningEnableC (Parameter
192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type (Parameter
224)
5. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
6. Communication Fault & Idle Override (Parameter 346) must be enabled.
7. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled locally and opens when a trip event occurs. Figure 26 with the contactor auxiliary wired into Input 0 and Output Relay 0 configured as a control relay.
is a wiring diagram of a non-reversing starter
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 67
Page 68
Chapter 4 Operating Modes
Relay 0
R03 R04
Run
0-StopI-Run
Control Power
E200 Relay
Run Aux
IN 0
Figure 26 - Non-reversing Starter (Network & Operator Station) with Feedback Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 12.
Non-reversing Starter (Network & Local I/O) – Two-wire Control
Operating Mode Non-Reversing Starter (Network & Local I/O) – Two Wire Control (Parameter 195 = 16) uses the network tag LogicDefinedPt00Data in Output Assembly 144 in Remote control mode and Input 0 in Local control mode to control Relay 0, which controls the contactor coil. Input 1 determines whether the motor starter is in Remote or Local control mode. LogicDefinedPt00Data is a maintained value, so the non-reversing starter remains energized when LogicDefinedPt00Data has a value of 1 in Remote control mode. Program the appropriate state of the starter by using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
In Local control mode, the state of Input 0 controls Output Relay 0, which controls the contactor coil. Input 0 is a maintained value, so the non-reversing starter remains energized when Input 0 is active.
Use Input 1 to select between Local and Remote control mode. Activate Input 1 to select Remote control mode. De-activate Input 1 to select Local control mode.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Communication Fault & Idle Override (Parameter 346) must be enabled.
4. Network Fault Override (Parameter 347) must be enabled.
68 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 69
Operating Modes Chapter 4
Control Power
E200 Relay
Relay 0
R03 R04
Run
IN 0
Run/Stop
IN 1
Local Inputs/ Controller
Relay 0
Tri p Re set
Tri p St atu s
Tri p Eve nt
Run/Stop
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled locally and opens when a trip event occurs. Figure 27
is a wiring diagram of a non-reversing starter
with Output Relay 0 configured as a control relay.
Figure 27 - Non-reversing Starter (Network & Local I/O) – Two-wire Control Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 16.
Timing Diagram
Figure 28 - Non-reversing Starter (Network & Local I/O) – Two-wire Control Timing Diagram
Non-reversing Starter (Network & Local I/O) with Feedback – Two-wire Control
Operating Mode Non-Reversing Starter (Network & Local I/O) with Feedback – Two Wire Control (Parameter 195 = 17) uses the network tag LogicDefinedPt00Data in
Output Assembly 144 in Remote control mode and Input 2 in Local control mode to control Relay 0, which controls the contactor coil. Input 3 determines whether the motor starter is in Remote or Local control mode. LogicDefinedPt00Data is a maintained value, so the non-reversing starter remains energized when LogicDefinedPt00Data has a value of 1 in Remote control mode. Program the
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 69
Page 70
Chapter 4 Operating Modes
Control Power
E200 Relay
Relay 0
R03 R04
Run
IN 0
Run/Stop
IN 3
IN 2
Run Aux
Local Input s/ Control ler
appropriate state of the starter by using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in
Chapter 3
.
In Local control mode, the state of Input 2 controls Output Relay 0, which controls the contactor coil. Input 2 is a maintained value, so the non-reversing starter remains energized when Input 2 is active.
Use Input 3 to select between Local and Remote control mode. Activate Input 3 to select Remote control mode. De-activate Input 3 to select Local control mode.
The auxiliary contact from the non-reversing starter’s contactor is wired into Input 0. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Three digital inputs must be available on the Control Module
2. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled locally and opens when a trip event occurs. Figure 29
is a wiring diagram of a non-reversing starter
with Output Relay 0 configured as a control relay.
Figure 29 - Non-reversing Starter (Network & Local I/O) with Feedback – Two-wire Control Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 17.
70 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 71
Operating Modes Chapter 4
Relay 0
Tri p Ev ent
Run/Stop
Normal Operation
Feedback Timeout Tri p
Timer
Tri p S tat us
Tri p R ese t
Feedback
Feedback Timeout
Timing Diagram
Figure 30 - Non-reversing Starter (Network & Local I/O) with Feedback – Two-wire Control Timing Diagram
Non-reversing Starter (Network & Local I/O) – Three-wire Control
Operating Mode Non-Reversing Starter (Network& Operator Station) – Three Wire Control (Parameter 195 = 18) uses the network tag LogicDefinedPt00Data in Output
Assembly 144 in Remote control mode and Input 1 & Input 2 in Local control mode to control Relay 0, which controls the contactor coil. LogicDefinedPt00Data is a maintained value, so the non-reversing starter remains energized when LogicDefinedPt00Data has a value of 1 in Remote control mode. Program the appropriate state of the starter by using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in
Chapter 3
Local control mode uses a normally open momentary push button that is wired to Input 1 to energize Output Relay 0, which controls the contactor coil. A normally closed momentary push button that is wired to Input 2 de-energizes Output Relay 0. The non-reversing starter only energizes if Input 2 is active and Input 1 is momentarily active.
Use Input 3 to select between Local and Remote control mode. Activate Input 3 to select Remote control mode. De-activate Input 3 to select Local control mode.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
.
1. Three digital inputs must be available on the Control Module
2. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Communication Fault & Idle Override (Parameter 346) must be enabled.
5. Network Fault Override (Parameter 347) must be enabled.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 71
Page 72
Chapter 4 Operating Modes
Control Power
E200 Relay
Relay 0
R03 R04
Run
IN 1
IN 2
Local Inputs/ Contro ller
IN 3
Stop
Run
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled locally and opens when a trip event occurs. Figure 31 with Output Relay 0 configured as a control relay.
Figure 31 - Non-reversing Starter (Network & Local I/O) – Three-wire Control Wiring Diagram
is a wiring diagram of a non-reversing starter
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 18.
Non-reversing Starter (Network & Local I/O) with Feedback – Three-wire Control
Operating Mode Non-Reversing Starter (Network& Operator Station) with Feedback – Three Wire Control (Parameter 195 = 19) uses the network tag LogicDefinedPt00Data
in Output Assembly 144 in Remote control mode and Input 1 & Input 2 in Local control mode to control Relay 0, which controls the contactor coil. LogicDefinedPt00Data is a maintained value, so the non-reversing starter remains energized when LogicDefinedPt00Data has a value of 1 in Remote control mode. Program the appropriate state of the starter by using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
Local control mode uses a normally open momentary push button that is wired to Input 1 to energize Output Relay 0, which controls the contactor coil. A normally closed momentary push button that is wired to Input 2 de-energizes Output Relay 0. The non-reversing starter only energizes if Input 2 is active and Input 1 is momentarily active.
Use Input 3 to select between Local and Remote control mode. Activate Input 3 to select Remote control mode. De-activate Input 3 to select Local control mode.
The auxiliary contact from the non-reversing starter’s contactor is wired into Input 0. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
The reset button of the E200 Operator Station is enabled for this operating mode.
.
72 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 73
Operating Modes Chapter 4
Run
Control Power
E200 Relay
Relay 0
R03 R04
Run
IN 0
IN 1
IN 2
Run Aux
Local Inputs/ Control ler
IN 3
Stop
Rules
1. Three digital inputs must be available on the Control Module
2. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay in which the relay is controlled locally and opens when a trip event occurs. Figure 32 with Output Relay 0 configured as a control relay.
Figure 32 - Non-reversing Starter (Network & Local I/O) with Feedback – Three-wire Control Wiring Diagram
is a wiring diagram of a non-reversing starter
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 19.
Non-reversing Starter (Custom)
Operating Mode Non-Reversing Starter (Custom) (Parameter 195 = 50) operates as a non-reversing starter one output relay that is assigned as a normally open control relay. The Non-reversing Starter (Custom) operating mode is used for applications that want customized DeviceLogix programs. This operating mode requires minimal configuration rules.
Rules
1. Set any of the Output Ptxx Assignments (Parameters 202…204) to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 73
Page 74
Chapter 4 Operating Modes
(1) Contact shown with supply voltage applied.
Relay 0 configured as a control relay
(1)
R03 R04
Motor
A1 A2
Tri p Re lay
Trip Reset
Device Status 0 Tri p Pres et
Wiring Diagram
The E200 relay can also be wired as a control relay so that the relay opens when a trip event occurs. Figure 33 configured as a control relay. Relay 0 receives control commands from an automation controller to energize or de-energize the contactor coil. Relay 0 also goes to an open state when there is a trip event.
Figure 33 - Control Relay Wiring Diagram
is a wiring diagram of a non-reversing starter with Relay 0
DeviceLogix Program
The last saved DeviceLogix program is executed in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 50.

Reversing Starter Operating Modes

Timing Diagram
Figure 34 - Non-reversing Starter (Custom) Timing Diagram
The non-reversing starter-based operating modes of the E200 relay provide the control logic for a reversing full-voltage starter. Two normally open control relays control the forward and reverse contactor coils. When a trip event occurs, both control relays remain open until the E200 receives a trip reset command. There are 11 reversing starter-based operating modes to choose from:
•Network
• Network with Feedback
• Operator Station
• Operator Station with Feedback
• Local I/O – Two-wire Control
• Local I/O with Feedback – Two-wire Control
• Local I/O – Three-wire Control
• Network & Operator Station
• Network & Local I/O – Two-wire Control
• Network & Local I/O – Three-wire Control
•Custom
74 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 75
Operating Modes Chapter 4
Control Power
E200 Relay
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
Reversing Starter (Network)
Operating Mode Reversing Starter (Network) (Parameter 195 = 5) uses network tags LogicDefinedPt00Data in Output Assembly 144 to control Relay 0, which controls the
forward contactor coil, and LogicDefinedPt01Data in Output Assembly 144 to control Relay 1, which controls the reversing contactor coil. Both LogicDefinedPt00Data and LogicDefinedPt01Data are maintained values, so the reversing starter remains energized when LogicDefinedPt00Data or LogicDefinedPt01Data has a value of 1. Program the appropriate state of the starter using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in
Chapter 3
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
.
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
Wiring Diagram
Output Relay 0 is wired as a control relay to the forward contactor and Output Relay 1 is wired as a control relay to the reversing contactor. Both relays are controlled locally and open when a trip event occurs. Figure 35 with Output Relay 0 and Output Relay 1 configured as control relays.
Figure 35 - Reversing Starter (Network) Wiring Diagram
is a wiring diagram of a reversing starter
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 5.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 75
Page 76
Chapter 4 Operating Modes
Tri p Even t
Tri p St atu s
Tri p Re set
Forwa rd (Relay 0)
Reverse (Relay 1)
For ward
Reverse
Timing Diagram
Figure 36 - Reversing Starter (Network) Timing Diagram
Reversing Starter (Network) with Feedback
Operating Mode Reversing Starter (Network) with Feedback (Parameter 195 = 6) uses network tags LogicDefinedPt00Data in Output Assembly 144 to control Relay 0, which controls the forward contactor coil, and LogicDefinedPt01Data in Output Assembly 144 to control Relay 1, which controls the reversing contactor coil. Both LogicDefinedPt00Data and LogicDefinedPt01Data are maintained values, so the reversing starter remains energized when LogicDefinedPt00Data or LogicDefinedPt01Data has a value of 1. Program the appropriate state of the starter using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
The auxiliary contact from the forward contactor is wired into Input 0, and the auxiliary contact from the reversing contactor is wired into Input 1. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
.
Wiring Diagram
Output Relay 0 is wired as a control relay to the forward contactor and Output Relay 1 is wired as a control relay to the reversing contactor. Both relays are controlled locally and open when a trip event occurs. Figure 37
76 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
is a wiring diagram of a reversing starter
Page 77
Operating Modes Chapter 4
Control Power
E200 Relay
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
IN 0
IN 1
Run Forward Aux
Run Reverse Aux
Tri p Even t
Tri p St atu s
Trip Reset
Forward ( Relay 0)
Reverse (Relay 1)
Feedback Timeout Tri p
Feedback Timeout
Forward Feedback IN 0
Reverse Feedback IN 1
Timer
with Output Relay 0 and Output Relay 1 configured as control relays and the contactor auxiliary contacts wired to Input 0 and Input 1.
Figure 37 - Reversing Starter (Network) with Feedback Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 6.
Timing Diagram
Figure 38 - Reversing Starter (Network) with Feedback Timing Diagram
Reversing Starter (Operator Station)
Operating Mode Reversing Starter (Operating Station) (Parameter 195 = 29) uses the E200 Operator Station’s “I” key to control Output Relay 0, which controls the forward contactor coil. The “II” key controls Output Relay 1, which controls the reversing contactor coil. The “0” key de-energizes Output Relay 0 and Output Relay 1. These keys are momentary push buttons, so the reversing starter remains energized when you
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 77
Page 78
Chapter 4 Operating Modes
release the “I” or “II” button. The “0” button must be pressed before changing to another direction. The E200 relay issues a trip or warning event if the E200 Operator Station disconnects from the base relay.
The E200 Operator Station’s Reset button is enabled, and the Local/Remote yellow LED is illuminated to indicate that the operator station is being used for local control.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
5. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type (Parameter
224)
Or
• Option Match Warning must be enabled in WarningEnableC
(Parameter 192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
6. Communication Fault & Idle Override (Parameter 346) must be enabled.
7. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay to the forward contactor, and Output Relay 1 is wired as a control relay to the reversing contactor. Both relays open when a trip event occurs. Figure 39 Output Relay 1 configured as control relays.
is a wiring diagram of a reversing starter with Output Relay 0 and
78 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 79
Operating Modes Chapter 4
Control Power
E200 Relay
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
I-Run Forward
II-Run Reverse
0-Stop
Tri p Ev ent
Tri p St atu s
Trip Reset
Forward (Relay 0)
Reverse (Relay 1)
Forwa rd
Reverse
Stop
Figure 39 - Reversing Starter (Operator Station) Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 29.
Timing Diagram
Figure 40 - Reversing Starter (Operator Station) Timing Diagram
Reversing Starter (Operator Station) with Feedback
Operating Mode Reversing Starter (Operator Station) with Feedback (Parameter 195 =
30) uses the E200 Operator Station’s “I” and “0” keys to control Relay 0, which controls the contactor coil. These keys are momentary push buttons, so the reversing starter remains energized when you release the “I” button.The “0” button must be pressed before changing to another direction. The E200 relay issues a trip or warning event if the E200 Operator Station disconnects from the base relay.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 79
Page 80
Chapter 4 Operating Modes
The auxiliary contact from the reversing starter’s contactor is wired into Input 0. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The E200 Operator Station’s Reset button is enabled, and the Local/Remote yellow LED is illuminated to indicate that the operator station is being used for local control.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
5. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
Or
• Option Match Warning must be enabled in WarningEnableC
(Parameter 192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
6. Communication Fault & Idle Override (Parameter 346) must be enabled.
7. Network Fault Override (Parameter 347) must be enabled.
8. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay to the forward contactor and Output Relay 1 is wired as a control relay to the reversing contactor. Both relays open when a trip event occurs. Figure 41 Output Relay 1 configured as control relays and the contactor auxiliary contacts wired to Input 0 and Input 1.
is a wiring diagram of a reversing starter with Output Relay 0 and
80 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 81
Operating Modes Chapter 4
Control Power
E200 Relay
IN 0
IN 1
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
Run Forward Aux
Run Reverse Aux
I-Run Forward
II-Run Reverse
0-Stop
Trip Event Feedback Timeout
Stop
Tri p St atu s
Tri p Re set
Forward (Relay 0 )
Reverse (Relay 1)
For ward
Reverse
Feedback Timeout Tri p
Timer
Forward Feedback
Reverse Feedback
Figure 41 - Reversing Starter (Operator Station) with Feedback Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 30.
Timing Diagram
Figure 42 - Reversing Starter (Operator Station) with Feedback Timing Diagram
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 81
Page 82
Chapter 4 Operating Modes
Control Power
E200 Relay
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
IN 0
IN 1
Run Forward/Stop
Run Reverse/Stop
Reversing Starter (Local I/O) – Two-wire Control
Operating Mode Reversing Starter (Local I/O) – Two Wire Control (Parameter 195 =
40) uses Input 0 to control Output Relay 0, which controls the contactor coil of the forward contactor, and Input 1 to control Output Relay 1, which controls the contactor coil of the reversing contactor. Both Input 0 and Input 1 are maintained signals, so the reversing starter remains energized when either Input 0 or Input 1 is active. Both Input 0 and Input 1 must be in a de-active state before changing to another direction
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The reset button of the E200 Operator Station is enabled for this operating mode.
IMPORTANT
The Reversing Starter (Local I/O) – Two-wire Control operating mode uses the signal from Input 0 or Input 1 to control the starter. When an E200 relay powers up, the starter energizes if either Input 0 or Input 1 is active.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Communication Fault & Idle Override (Parameter 346) must be enabled.
5. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay to the forward contactor and Output Relay 1 is wired as a control relay to the reversing contactor. Both relays open when a trip event occurs. Figure 43 Output Relay 1 configured as control relays.
Figure 43 - Reversing Starter (Local I/O) – Two-wire Control Wiring Diagram
is a wiring diagram of a reversing starter with Output Relay 0 and
82 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 40.
Page 83
Operating Modes Chapter 4
Tri p Ev ent
Tri p St atu s
Tri p Re set
Forward (Relay 0)
Reverse (Relay 1)
Forwa rd
Reverse
Timing Diagram
Figure 44 - Reversing Starter (Local I/O) – Two-wire Control Timing Diagram
Reversing Starter (Local I/O) – Two-wire Control with Feedback
Operating Mode Reversing Starter (Local I/O) – Two Wire Control (Parameter 195 =
41) uses Input 0 to control Output Relay 0, which controls the contactor coil of the forward contactor, and Input 1 to control Output Relay 1, which controls the contactor coil of the reversing contactor. Both Input 0 and Input 1 are maintained signals, so the reversing starter remains energized when either Input 0 or Input 1 is active. Both Input 0 and Input 1 must be in a de-active state before changing to another direction.
The auxiliary contact from the starter’s forward contactor is wired into Input 0, and the auxiliary contact from the starter’s reversing contactor is wired into Input 1. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The reset button of the E200 Operator Station is enabled for this operating mode.
IMPORTANT
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
The Reversing Starter (Local I/O) – Two-wire Control operating mode uses the signal from Input 0 or Input 1 to control the starter. When an E200 relay powers up, the starter energizes if either Input 0 or Input 1 is active.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 83
Page 84
Chapter 4 Operating Modes
Control Power
E200 Relay
IN 0
IN 1
IN 2
IN 3
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
Run Forward Aux
Run Reverse Aux
Run Forward/Stop
Run Reverse/Stop
Trip Event Feedback Timeout
Stop
Tri p St atu s
Tri p Re set
Forward (Relay 0 )
Reverse (Relay 1)
For ward
Reverse
Feedback Timeout Tri p
Timer
Forward Feedback
Reverse Feedback
Wiring Diagram
Output Relay 0 is wired as a control relay to the forward contactor and Output Relay 1 is wired as a control relay to the reversing contactor. Both relays open when a trip event occurs. Figure 45 Output Relay 1 configured as control relays and the contactor auxiliary contacts wired to Input 0 and Input 1.
Figure 45 - Reversing Starter (Local I/O) – Two-wire Control with Feedback Wiring Diagram
is a wiring diagram of a reversing starter with Output Relay 0 and
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 41.
Timing Diagram
Figure 46 - Reversing Starter (Operator Station) with Feedback Timing Diagram
84 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 85
Operating Modes Chapter 4
Control Power
E200 Relay
IN 0
IN 1
IN 2
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
Run Forward
Run Reverse
Stop
Reversing Starter (Local I/O) – Three-wire Control
Operating Mode Reversing Starter (Local I/O) – Three Wire Control (Parameter 195 =
42) uses a normally open momentary push button in Input 0 to energize Output Relay 0, which controls the forward contactor coil. A normally open momentary push button in Input 1 energizes Output Relay 1, which controls the reversing contactor coil. A normally closed push button in Input 2 de-energizes Output Relay 0 and Output Relay 1. Both Input 0, Input 1, and Input 2 are momentary signals, so the reversing starter only energizes if Input 2 is active and Input 0 or Input 1 is momentarily active.
Input 2 must be momentarily de-active before changing to another direction. InterlockDelay (Parameter 215) defines the minimum time delay when switching
direction. The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Four digital inputs must be available on the Control Module
2. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
3. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
4. Overload Trip must be enabled in TripEnableI (Parameter 183).
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Figure 47 is a wiring diagram of a reversing starter with three wire control and Output
Relay 0 and Output Relay 1 configured as control relays.
Figure 47 - Reversing Starter (Local I/O) – Three-wire Control Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 42.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 85
Page 86
Chapter 4 Operating Modes
Tri p Even t
Stop
Forwa rd
Reverse
Tri p St atu s
Tri p Re set
Forward (Relay 0)
Reverse (Relay 1)
Timing Diagram
Figure 48 - Reversing Starter (Local I/O) – Three-wire Control Timing Diagram
Reversing Starter (Network & Operator Station)
Operating Mode Reversing Starter (Network& Operator Station) (Parameter 195 = 13) in Remote control mode uses network tags LogicDefinedPt00Data in Output Assembly 144 to control Relay 0, which controls the forward contactor coil, and LogicDefinedPt01Data in Output Assembly 144 to control Relay 1, which controls the reversing contactor coil. Both LogicDefinedPt00Data and LogicDefinedPt01Data are maintained values, so the reversing starter remains energized when LogicDefinedPt00Data or LogicDefinedPt01Data has a value of 1. Program the appropriate state of the starter using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
In Local control mode, the E200 Operator Station’s “I” key is used to control Output Relay 0, which controls the forward contactor coil. The “II” key controls Output Relay 1, which controls the reversing contactor coil. The “0” key de-energizes Output Relay 0 and Output Relay 1. These keys are momentary push buttons, so the reversing starter remains energized when you release the “I” or “II” button. The “0” button must be pressed before changing to another direction.
To change between Local and Remote control mode press and release the “Local/ Remote” button on the E200 Operator Station. The LED above “Local/Remote” button illuminates yellow in Local control mode and red in Remote control mode.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The E200 relay issues a trip or warning event if the E200 Operator Station disconnects from the base relay.
The reset button of the E200 Operator Station is enabled for this operating mode.
.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
86 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 87
Operating Modes Chapter 4
I-Run Forward
II-Run Reverse
0-Stop
Control Power
E200 Relay
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
4. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
5. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
Or
• Option Match Warning must be enabled in WarningEnableC
(Parameter 192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type (Parameter
224)
6. Communication Fault & Idle Override (Parameter 346) must be enabled.
7. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 and Output Relay 1 are wired as a control relays in which the relay is controlled by the communication network or E200 Operator Station, and both output relays open when a trip event occurs. Figure 49 with Output Relay 0 and Output Relay 1 configured as control relays.
is a wiring diagram of a reversing starter
Figure 49 - Reversing Starter (Network & Operator Station) Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 13.
Reversing Starter (Network & Local I/O) – Two-wire Control
Operating Mode Reversing Starter (Network& Operator Station) (Parameter 195 = 20) in Remote control mode uses network tags LogicDefinedPt00Data in Output Assembly 144 to control Relay 0, which controls the forward contactor coil, and LogicDefinedPt01Data in Output Assembly 144 to control Relay 1, which controls the
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 87
Page 88
Chapter 4 Operating Modes
Run Forward/Stop
Run Reverse/Stop
Control Power
E200 Relay
IN 0
IN 1
Local Input s/ Control ler
IN 3
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
reversing contactor coil. Both LogicDefinedPt00Data and LogicDefinedPt01Data are maintained values, so the reversing starter remains energized when LogicDefinedPt00Data or LogicDefinedPt01Data has a value of 1. Program the appropriate state of the starter using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
.
In Local control mode, Input 0 is used to control Output Relay 0, which controls the contactor coil of the forward contactor, and Input 1 is used to control Output Relay 1, which controls the contactor coil of the reversing contactor. Both Input 0 and Input 1 are maintained signals, so the reversing starter remains energized when either Input 0 or Input 1 is active. Both Input 0 and Input 1 must be in a de-active state before changing to another direction.
Use Input 3 to select between Local and Remote control mode. Activate Input 3 to select Remote control mode. De-activate Input 3 to select Local control mode.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Three digital inputs must be available on the Control Module
2. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
3. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
4. Overload Trip must be enabled in TripEnableI (Parameter 183).
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 and Output Relay 1 are wired as a control relays in which the relay is controlled by the communication network or Input 0 & Input 1. Both output relays open when a trip event occurs. Figure 50 Output Relay 0 and Output Relay 1 configured as control relays.
Figure 50 - Reversing Starter (Network & Local I/O) – Two-wire Control Wiring Diagram
is a wiring diagram of a reversing starter with
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 20.
88 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 89
Operating Modes Chapter 4
Tri p Ev ent
For ward
Reverse
Tri p St atu s
Trip Reset
Forwa rd (Relay 0)
Reverse (Relay 1)
Timing Diagram
Figure 51 - Reversing Starter (Network & Local I/O) – Two-wire Control Timing Diagram
Reversing Starter (Network & Local I/O) – Three-wire Control
Operating Mode Reversing Starter (Network& Operator Station) (Parameter 195 = 21) in Remote control mode uses network tags LogicDefinedPt00Data in Output Assembly 144 to control Relay 0, which controls the forward contactor coil, and LogicDefinedPt01Data in Output Assembly 144 to control Relay 1, which controls the reversing contactor coil. Both LogicDefinedPt00Data and LogicDefinedPt01Data are maintained values, so the reversing starter remains energized when LogicDefinedPt00Data or LogicDefinedPt01Data has a value of 1. Program the appropriate state of the starter using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
Local control mode uses a normally open momentary push button in Input 0 to energize Output Relay 0, which controls the forward contactor coil. A normally open momentary push button in Input 1 energizes Output Relay 1, which controls the reversing contactor coil. A normally closed push button in Input 2 de-energizes Output Relay 0 and Output Relay 1. Both Input 0, Input 1, and Input 2 are momentary signals, so the reversing starter only energizes if Input 2 is active and Input 0 or Input 1 is momentarily active.
Input 2 must be momentarily de-active before changing to another direction. Use Input 3 to select between Local and Remote control mode. Activate Input 3 to
select Remote control mode. De-activate Input 3 to select Local control mode. InterlockDelay (Parameter 215) defines the minimum time delay when switching
direction. The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Four digital inputs must be available on the Control Module
2. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
3. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
4. Overload Trip must be enabled in TripEnableI (Parameter 183).
.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 89
Page 90
Chapter 4 Operating Modes
Run Forward
Run Reverse
Stop
Local Inputs/ Controller
Control Power
E200 Relay
IN 0
IN 1
IN 2
IN 3
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 and Output Relay 1 are wired as a control relays in which the relay is controlled by the communication network or Input 0, Input 1, and Input 2. Both output relays open when a trip event occurs. Figure 52 starter with Output Relay 0 and Output Relay 1 configured as control relays.
Figure 52 - Reversing Starter (Network & Local I/O) – Three-wire Control Wiring Diagram
is a wiring diag ram of a reversing
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 21.
Reversing Starter (Custom)
Operating Mode Reversing Starter (Custom) (Parameter 195 = 51) operates as a reversing starter with two output relays that are assigned as normally open control relays. The Reversing Starter (Custom) operating mode is used for applications that want customized DeviceLogix programs. This operating mode requires minimal configuration rules.
Rules
1. Set two of the Output Ptxx Assignments (Parameters 202…204) to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
Wiring Diagram
Figure 53 is a wiring diagram of a reversing starter with Output Relay 0 and Output
Relay 1 configured as control relays. Both Output Relay 0 and Output Relay 1 go to an open state when there is a trip event.
90 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 91
Operating Modes Chapter 4
Control Power
E200 Relay
Relay 0
R03 R04
Run Forward
Relay 1
R13 R14
Run Reverse
Tri p Re lay
Trip Reset
Device Status 0 Tri p Pres et
Figure 53 - Reversing Starter (Custom) Wiring Diagram
DeviceLogix Program
The last saved DeviceLogix program is executed in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 50.
Timing Diagram

Two-speed Starter Operating Modes

Figure 54 - Reversing Starter (Custom) Timing Diagram
The two-speed starter-based operating modes of the E200 relay provide the control logic for a two-speed full-voltage starter. Two normally open control relays control the high-speed and low-speed contactor coils. When a trip event occurs, both control relays remain open until the E200 receives a trip reset command. There are 11 two­speed starter-based operating modes to choose from:
•Network
• Network with Feedback
• Operator Station
• Operator Station with Feedback
• Local I/O – Two-wire Control
• Local I/O with Feedback – Two-wire Control
• Local I/O – Three-wire Control
• Network & Operator Station
• Network & Local I/O – Two-wire Control
• Network & Local I/O – Three-wire Control
•Custom
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 91
Page 92
Chapter 4 Operating Modes
Control Power
E200 Relay
Relay 0
R03 R04
Relay 1
R13 R14
Run Fast
Run Slow
Two-speed Starter (Network)
Operating Mode Two Speed Starter (Network) (Parameter 195 = 9) uses network tags LogicDefinedPt00Data in Output Assembly 144 to control Relay 0, which controls the
high-speed contactor coil, and LogicDefinedPt01Data in Output Assembly 144 to control Relay 1, which controls the low-speed contactor coil. Both LogicDefinedPt00Data and LogicDefinedPt01Data are maintained values, so the two-speed starter remains energized when LogicDefinedPt00Data or LogicDefinedPt01Data has a value of 1. Program the appropriate state of the starter using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
.
Wiring Diagram
Output Relay 0 is wired as a control relay to the high-speed contactor and Output Relay 1 is wired as a control relay to the low-speed contactor. In this configuration, both relays are controlled locally and open when a trip event occurs. Figure 55 wiring diagram of a two-speed starter with Output Relay 0 and Output Relay 1 configured as control relays.
Figure 55 - Two-speed Starter (Network) Wiring Diagram
is a
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 9.
92 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 93
Timing Diagram
Tri p Even t
Run Fast
Run Slow
Fast (Relay 0)
Slow (Relay 1)
Tri p St atu s
Tri p Re set
Figure 56 - Two-speed Starter (Network) Timing Diagram
Operating Modes Chapter 4
Two-speed Starter (Network) with Feedback
Operating Mode Two-speed Starter (Network) with Feedback (Parameter 195 = 10) uses network tags LogicDefinedPt00Data in Output Assembly 144 to control Relay 0, which controls the high-speed contactor coil and LogicDefinedPt01Data in Output Assembly 144 to control Relay 1, which controls the low-speed contactor coil. Both LogicDefinedPt00Data and LogicDefinedPt01Data are maintained values, so the two-speed starter remains energized when LogicDefinedPt00Data or LogicDefinedPt01Data has a value of 1. Program the appropriate state of the starter using the Network Communication Fault and Network Communication Idle parameters (Parameters 569 – 573) described in Chapter 3
The auxiliary contact from the high-speed contactor is wired into Input 0, and the auxiliary contact from the low-speed contactor is wired into Input 1. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
.
Wiring Diagram
Output Relay 0 is wired as a control relay to the high-speed contactor and Output Relay 1 is wired as a control relay to the low-speed contactor. In this configuration, both relays are controlled locally and open when a trip event occurs. Figure 57 wiring diagram of a Two-speed Starter with Output Relay 0 and Output Relay 1
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 93
is a
Page 94
Chapter 4 Operating Modes
Control Power
E200 Relay
IN 0
IN 1
Relay 0
R03 R04
Relay 1
R13 R14
Run Fast
Run Slow
Run Fast Aux
Run Slow Aux
Trip Event Feedback Timeout
Run Fast
Run Slow
Fast (Rel ay 0)
Slow (Relay 1)
Tri p St atu s
Tri p Re set
Timer
Feedback Timeout Tri p
Fast Fe edba ck
Slow Feedback
configured as control relays and the contactor auxiliary contacts wired to Input 0 and Input 1.
Figure 57 - Two-speed Starter (Network) with Feedback Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 10.
Timing Diagram
Figure 58 - Two-speed Starter (Network) with Feedback Timing Diagram
Two-speed Starter (Operator Station)
Operating Mode Two Speed Starter (Operating Station) (Parameter 195 = 33) uses the E200 Operator Station’s “I” key to control Output Relay 0, which controls the high­speed contactor coil. The “II” key controls Output Relay 1, which controls the low­speed contactor coil. The “0” key de-energizes Output Relay 0 and Output Relay 1.
94 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 95
Operating Modes Chapter 4
These keys are momentary push buttons, so the two-speed starter remains energized when you release the “I” or “II” button.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The E200 relay issues a trip or warning event if the E200 Operator Station disconnects from the base relay.
The E200 Operator Station’s Reset button is enabled, and the Local/Remote yellow LED is illuminated to indicate that the operator station is being used for local control.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
5. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
Or
• Option Match Warning must be enabled in WarningEnableC (Parameter
192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
6. Communication Fault & Idle Override (Parameter 346) must be enabled.
7. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay to the high-speed contactor, and Output Relay 1 is wired as a control relay to the low-speed contactor. Both relays open when a trip event occurs. Figure 59 Relay 0 and Output Relay 1 configured as control relays.
is a wiring diagram of a two-speed starter with Output
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 95
Page 96
Chapter 4 Operating Modes
I-Run Fast
II-Run Slow
0-Stop
Control Power
E200 Relay
Relay 0
R03 R04
Relay 1
R13 R14
Run Fast
Run Slow
Tri p Ev ent
Run Fast
Run Slow
Fast (Relay 0)
Slow (Relay 1)
Tri p St atu s
Tri p Re set
Stop
Figure 59 - Two-speed Starter (Operator Station) Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 33.
Timing Diagram
Figure 60 - Two-speed Starter (Operator Station) Timing Diagram
Two-speed Starter (Operator Station) with Feedback
Operating Mode Two Speed Starter (Operator Station) with Feedback (Parameter 195 =
34) uses the E200 Operator Station’s “I” and “0” keys to control Relay 0, which controls the contactor coil. These keys are momentary push buttons, so the two-speed starter remains energized when you release the “I” button. The E200 relay issues a trip or warning event if the E200 Operator Station disconnects from the base relay.
96 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 97
Operating Modes Chapter 4
The auxiliary contact from the two-speed starter’s contactor is wired into Input 0. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The E200 Operator Station Reset button is enabled, and the Local/Remote yellow LED is illuminated to indicate that the operator station is being used for local control.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
5. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC (Parameter 186)
• Operator Station must be enabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
Or
• Option Match Warning must be enabled in WarningEnableC (Parameter
192)
• Operator Station must be disabled in Mismatch Action (Parameter 233)
• An operator station must be selected in Operator Station Type
(Parameter 224)
6. Communication Fault & Idle Override (Parameter 346) must be enabled.
7. Network Fault Override (Parameter 347) must be enabled.
8. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay to the high-speed contactor and Output Relay 1 is wired as a control relay to the low-speed contactor. Both relays open when a trip event occurs. Figure 61 Relay 0 and Output Relay 1 configured as control relays and the contactor auxiliary contacts wired to Input 0 and Input 1.
is a wiring diagram of a two-speed starter with Output
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 97
Page 98
Chapter 4 Operating Modes
I-Run Forward
II-Run Reverse
0-Stop
Control Power
E200 Relay
Relay 0
R03 R04
Relay 1
R13 R14
Run Fast
Run Slow
Run Fast Aux
Run Slow Aux
IN 0
IN 1
Tri p Eve nt
Feedback Timeout
Run Fast
Run Slow
Stop
Fast (Relay 0)
Slow (Relay 1)
Fast Feedback
Slow Feedback
Trip Status
Tri p Re set
Timer
Feedback Timeout Tri p
Figure 61 - Two-speed Starter (Operator Station) with Feedback Wiring Diagram
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 34.
Timing Diagram
Figure 62 - Two-speed Starter (Operator Station) with Feedback Timing Diagram
98 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Page 99
Operating Modes Chapter 4
Control Power
E200 Relay
IN 0
IN 1
Relay 0
R03 R04
Relay 1
R13 R14
Run Fast
Run Slow
Run Fast/Stop
Run Slow/Stop
Two-speed Starter (Local I/O) – Two-wire Control
Operating Mode Two Speed Starter (Local I/O) – Two Wire Control (Parameter 195 =
46) uses Input 0 to control Output Relay 0, which controls the contactor coil of the high-speed contactor, and Input 1 to control Output Relay 1, which controls the contactor coil of the low-speed contactor. Both Input 0 and Input 1 are maintained signals, so the two-speed starter remains energized when either Input 0 or Input 1 is active.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The reset button of the E200 Operator Station is enabled for this operating mode.
IMPORTANT
The Two-speed Starter (Local I/O) – Two-wire Control operating mode uses the signal from Input 0 or Input 1 to control the starter. When an E200 relay powers up, the starter energizes if either Input 0 or Input 1 is active.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Communication Fault & Idle Override (Parameter 346) must be enabled.
5. Network Fault Override (Parameter 347) must be enabled.
Wiring Diagram
Output Relay 0 is wired as a control relay to the high-speed contactor and Output Relay 1 is wired as a control relay to the low-speed contactor. Both relays open when a trip event occurs. Figure 63 Relay 0 and Output Relay 1 configured as control relays.
Figure 63 - Two-speed Starter (Local I/O) – Two-wire Control Wiring Diagram
is a wiring diagram of a two-speed starter with Output
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on power-up or when Operating Mode (Parameter 195) is set to a value of 46.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019 99
Page 100
Chapter 4 Operating Modes
Tri p Even t
Run Fast
Run Slow
Fast (Rel ay 0)
Slow (Relay 1)
Tri p St atu s
Tri p Re set
Timing Diagram
Figure 64 - Two-speed Starter (Local I/O) – Two-wire Control Timing Diagram
Two-speed Starter (Local I/O) – Two-wire Control with Feedback
Operating Mode Two Speed Starter (Local I/O) – Two Wire Control (Parameter 195 =
47) uses Input 0 to control Output Relay 0, which controls the contactor coil of the high-speed contactor and Input 1 to control Output Relay 1, which controls the contactor coil of the low-speed contactor. Both Input 0 and Input 1 are maintained signals, so the two-speed starter remains energized when either Input 0 or Input 1 is active.
The auxiliary contact from the starter’s high-speed contactor is wired into Input 0, and the auxiliary contact from the starter’s low-speed contactor is wired into Input 1. If a feedback signal is not received before the time identified in Feedback Timeout (Parameter 213), the E200 Relay issues a trip or warning event.
InterlockDelay (Parameter 215) defines the minimum time delay when switching direction.
The reset button of the E200 Operator Station is enabled for this operating mode.
IMPORTANT
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Output Pt01 Assignment (Parameter 203) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Feedback Timeout Trip in TripEnableC (Parameter 186) or Feedback Timeout Warning in WarningEnableC (Parameter 192) must be enabled.
5. Communication Fault & Idle Override (Parameter 346) must be enabled.
6. Network Fault Override (Parameter 347) must be enabled.
The Two-speed Starter (Local I/O) – Two-wire Control operating mode uses the signal from Input 0 or Input 1 to control the starter. When an E200 relay powers up, the starter energizes if either Input 0 or Input 1 is active.
100 Rockwell Automation Publication 193-UM017A-EN-P - April 2019
Loading...