CompactLogix 5480 Controller Catalog Number 5069-L46ERMW
TopicPage
Summary of Changes1
CompactLogix 5380 Controllers2
Compact GuardLogix 5380 Controllers8
CompactLogix 5480 Controller14
Controller Use with Other Devices22
Ethernet Node Limits25
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controller
Accessories
Additional Resources29
26
Summary of Changes
This publication was revised for these changes:
• To add catalog numbers 5069-L320ERMK, 5069-L330ERMK, and 5069-L350ERMK.
• To add the CompactLogix™ 5480 controller.
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
CompactLogix 5380 Controllers
CompactLogix 5380 controllers are part of the Logix 5000™ family of controllers. The controllers provide a scalable
controller solution to address a wide variety of applications. The applications range from standalone systems to more
complex systems with devices that are connected to the controller via an EtherNet/IP™ network.
The controllers are mounted on a DIN rail. They can monitor and control local and remote I/O modules, and other
devices connected to an EtherNet/IP network. The CompactLogix 5380 controllers support this functionality:
• Use of Compact 5000™ I/O module as local I/O and remote I/O modules.
• Use Compact 5000 I/O modules, and other I/O modules, as remote I/O modules.
• Support for Integrated Motion over an EtherNet/IP network (not all controllers).
• Use of Dual-IP mode or Linear/DLR mode.
• Use of two Ethernet ports that let the controller connect to EtherNet/IP device-level and
• Use of 1784-SD1 or 1784-SD2 Secure Digital (SD) card for nonvolatile memory.
• USB programming port for temporary connection.
enterprise-level networks.
2Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
Features - CompactLogix 5380 Controllers
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Feature
Controller tasks
• Continuous
• Periodic
• Event
5069-L306ER,
5069-L306ERM
32 tasks
1000 programs/task
All event triggers
5069-L310ER,
5069-L310ER-NSE,
5069-L310ERM
5069-L320ER,
5069-L320ERM,
5069-L320ERMK
5069-L330ER,
5069-L330ERM,
5069-L330ERMK
5069-L340ER,
5069-L340ERM
5069-L350ERM,
5069-L350ERMK
5069-L380ERM 5069-L3100ERM
1 - USB port
Built-in
communication
ports
2 - Ethernet ports
IMPORTANT: Consider the following:
– When the controller operates in Dual-IP mode, each Ethernet port requires a unique IP address.
– When the controller operates in Linear/DLR mode, the controller uses only one IP address.
USB port
communication
Ethernet
performance
EtherNet/IP modes
supported
EtherNet/IP
network topologies
supported
EtherNet/IP nodes
supported, max
Socket interfaces
supported, max
Integrated motion
USB 2.0, Type B
Full speed (12 Mbps)
Programming, configuration, firmware update, and on-line edits only
10 Mbps, 100 Mbps, 1 Gbps
Full-duplex only
Dual-IP mode (Available with the Studio 5000 Logix Designer® application, version 29.00.00 or later)
Linear/DLR mode
DLR
Star
Linear
1624406090120150180
(1)
32
As many as two
axes
(5069-L306ERM
controller only)
As many as four axes
(5069-L310ERM
controller only
As many as eight
axes
(5069-L320ERM
and
5069-L320ERMK
controllers only)
As many as 16
axes
(5069-L330ERM
and
5069-L330ERMK
controllers only)
As many as 20
axes
(5069-L340ERM
controller only)
As many as 24
axes
As many as 28
axes
As many as 32
axes
Ladder Diagram (LD)
Programming
languages
Structured Text (ST)
Function Block Diagram (FBD)
Sequential Function Chart (SFC)
(1) The maximum number of nodes that are listed represents when the controller is used with the Logix Designer application, version 31 or later. Some controllers can be used with earlier Logix Designer application versions. The
maximum number of nodes that a controller supports can be fewer in Logix Designer application, versions 30 or earlier.
Rockwell Automation Publication 5069-TD002G-EN-P - January 20193
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
1784-SD1 card
1784-SD2 card (shipped with the controller)
881631
18…32V DC
450 mA
(5)
31313131
MOD Power inrush 850 mA for 125 ms
MOD Power
passthrough
MOD Power current
rating, max
SA Power voltage
(2)
ranges
SA Power current,
(2)
max
SA Power
passthrough
SA Power current
rating, max
Power dissipation,
max
Thermal
dissipation, max
9.55 A @ 18…32V DC
(1)
10 A
Do not exceed 10 A current draw at the MOD Power RTB.
0…32V DC
0…240V AC, 47…63 Hz
ATEX/IECEX, 125V AC max
10 mA (DC power)
25 mA (AC power)
9.95 A @ 0…32V DC
9.975 A @ 0…240V AC, 47…63 Hz
(2), (3)
ATEX/IECEX, 125V AC max
10 A (AC or DC power)
(2)
Do not exceed 10 A current draw at the SA Power RTB.
8.5 W
29 BTU/hr
300V (continuous), Basic Insulation Type, SA, and MOD Power to Backplane
300V (continuous), Basic Insulation Type, SA to MOD Power
300V (continuous), Basic Insulation Type, Ethernet to Backplane
300V (continuous), Double Insulation Type, Ethernet to MOD Power
300V (continuous), Double Insulation Type, Ethernet to SA Power
Isolation voltage
50V (continuous), Functional Insulation Type, Ethernet to USB
300V (continuous), Basic Insulation Type, USB to Backplane
300V (continuous), Double Insulation Type, USB to MOD Power
300V (continuous), Double Insulation Type, USB to SA Power
No isolation between Ethernet ports
Type tested at 1500V AC for 60 s
Weight, approx0.768 kg (1.693 lb)
Dimensions
(HxWxD), approx
143.97 x 98.10 x 136.81 mm (5.67 x 3.86 x 5.39 in.)
LocationDIN rail mount (horizontal mount only)
DIN rail
Compatible zinc-plated, chromate steel DIN rail.
EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.)
4Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Attribute
5069-L306ER,
5069-L306ERM
5069-L310ER,
5069-L310ER-NSE,
5069-L310ERM
5069-L320ER,
5069-L320ERM,
5069-L320ERMK
5069-L330ER,
5069-L330ERM,
5069-L330ERMK
5069-L340ER,
5069-L340ERM
5069-L350ERM,
5069-L350ERMK
5069-L380ERM 5069-L3100ERM
RTBs are available in separately ordered 5069 RTB kits. The MOD power connection uses a 4-point RTB, and the SA power connection uses a 6-point RTB. The
Removable
terminal block
following kits are available:
• Kit catalog number 5069-RTB64-SCREW contains RTB catalog numbers 5069-RTB6-SCREW and 5069-RTB4-SCREW.
• Kit catalog number 5069-RTB64-SPRING contains RTB catalog numbers 5069-RTB6-SPRING and 5069-RTB4-SPRING.
Terminal block
torque
5069-RTB4-SCREW & 5069-RTB6-SCREW: 0.4 N•m (3.5 lb•in)
5069-RTB4-SPRING & 5069-RTB6-SPRING: Torque does not apply
5069-RTB4-SCREW, 5069-RTB6-SCREW connections:
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire that is rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max diameter including insulation,
single wire connection only
Wire size
5069-RTB4-SPRING, 5069-RTB6-SPRING connections:
0.5…1.5 mm
2
(22…16 AWG) solid or stranded copper wire that is rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max diameter including insulation,
single wire connection only
Ethernet connections:
Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2
Insulation
stripping length
Wire category
5069-RTB4-SCREW, 5069-RTB6-SCREW connections: 12 mm (0.47 in.)
5069-RTB4-SPRING, 5069-RTB6-SPRING connections: 10 mm (0.39 in.)
3 - on USB port
(4)
1 - on power ports
2 - on Ethernet ports
Enclosure None (open-style)
North American
temperature code
ATEX temperature
code
IECEx temperature
code
(1) Maximum level of MOD Power current that the controller can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(2) SA power specifications are based on the number and type of Compact 5000 I/O modules that are used in the system. If the set of I/O modules that are used in the system require AC and DC voltage, you must install a 5069-FPD
field potential distributor to separate the module types.
(3) Maximum level of SA Power current that the controller can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(4) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication
(5) When you use these controllers with the Studio 5000 Logix Designer application, version 29.00.00, the application limits the number of local I/O modules in the project to 16. For more information, see the Rockwell Automation®
Knowledgebase article #942580, ‘5380 CompactLogix controllers limited to 16 local 5069 modules in version 29 of Studio 5000® environment.The document is available at http://www.rockwellautomation.com/knowledgebase.
With the Logix Designer application, version 30.00.00 or later, the controllers support as many as 31 local I/O modules.
T4
T4
T4
1770-4.1.
Rockwell Automation Publication 5069-TD002G-EN-P - January 20195
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
± 4 kV at 5 kHz on power ports
± 2 kV at 5 kHz on Ethernet ports
± 1 kV line-line (DM) and ± 2 kV line-earth (CM) on power ports
± 2 kV line-earth (CM) on Ethernet ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
10 ms interruption on MOD Power port
6Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
Certifications - CompactLogix 5380 Controllers
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL
File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
RCM
Australian Radiocommunications Act, compliant with:
• EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1455X
when used at or below 125V AC
IECEx System, compliant with:
• IEC 600079-0: General Requirements
IECEx
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0007X
when used at or below 125V AC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
• Article 58-2 of Radio Waves Act, Clause 3
IMPORTANT: This certification does not apply to the following catalog numbers: 5069-L320ERMK,
5069-L330ERMK, 5069-L350ERMK
EACRussian Customs Union TR CU 020/2011 EMC Technical Regulation
EtherNet/IPODVA conformance tested to EtherNet/IP specifications
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 5069-TD002G-EN-P - January 20197
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Compact GuardLogix 5380 Controllers
Compact GuardLogix™ 5380 controllers are part of the Logix 5000 family of controllers. The controllers provide a
scalable controller solution to address a wide variety of applications. The applications range from standalone systems to
more complex systems with devices that are connected to the controller via an EtherNet/IP network.
The controllers can function in the same way as CompactLogix 5380 controllers and also provide the functionality to
perform safety functions. You can use the controller to achieve up to SIL 2/PLd (Category 3) with the use of the safety
task and safety I/O. A major benefit of this system is that it is still one project, safety and standard together.
During development, safety and standard have the same rules; multiple programmers, online editing, and forcing are all
allowed. Once the safety system is validated and the safety signature applied, safety memory is protected, the safety logic
cannot be modified, and all safety functions operate with a safety integrity of SIL 2.
The controllers are mounted on a DIN rail. They can monitor and control local and remote I/O modules, and other
devices connected to an EtherNet/IP network. The controllers support this functionality:
• Use of Compact 5000 I/O standard and safety modules as local I/O and remote I/O modules
• Use Compact 5000 I/O modules, and other I/O modules, as remote I/O modules.
• Support for Integrated Motion over an EtherNet/IP network (not all controllers)
• Use of Dual-IP mode or Linear/DLR mode
• Use of two Ethernet ports that let the controller connect to EtherNet/IP device-level and enterprise-level
networks
• Use of 1784-SD1 or 1784-SD2 Secure Digital (SD) card for nonvolatile memory
• USB programming port for temporary connection
Compact GuardLogix 5380 controllers are available with a conformal coating. The conformal coating provides a layer of
protection against contaminants and humidity to help protect the assembly and extend product life in harsh, corrosive
environments. Products with a conformal coating have a ‘K’ suffix at the end of the catalog number.
8Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
Features - Compact GuardLogix 5380 Controllers
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Feature
Controller tasks
• Continuous
• Periodic
• Event
Built-in
communication ports
USB port
communication
Ethernet
performance
EtherNet/IP modes
supported
EtherNet/IP network
topologies supported
EtherNet/IP nodes
supported, max
Socket interfaces
supported, max
Integrated motion
Programming
languages
5069-L320ERS2,
5069-L306ERS2,
5069-L306ERMS2
31 standard tasks, 1 safety task
1000 programs/task
All event triggers
1 USB port
2 Ethernet ports
IMPORTANT: Consider the following:
– When the controller operates in Dual-IP mode, each Ethernet port requires a unique IP address.
– When the controller operates in Linear/DLR mode, the controller uses only one IP address.
USB 2.0, Type B
Full speed (12 Mbps)
Programming, configuration, firmware update, and on-line edits only
10 Mbps, 100 Mbps, 1 Gbps
Full-duplex only
Dual-IP mode
Linear/DLR mode
DLR
Star
Linear
1624406090120150180
32
As many as two axes
(5069-L306ERMS2
controller only)
Ladder Diagram (LD)
Structured Text (ST)
Function Block Diagram (FBD)
Sequential Function Chart (SFC)
Safety Task supports only RLL and the additional safety application instructions
1784-SD1 card
1784-SD2 card (shipped with the controller)
88163131313131
18…32V DC SELV/PELV
(5)
475 mA
MOD Power inrush 1200 mA for 125 ms
MOD Power
passthrough
voltage range
MOD Power current
rating, max
SA Power voltage
(2)
ranges
SA Power current,
(2)
max
18…32V DC @ 4.525 A
(1)
5 A
Do not exceed 5 A current draw at the MOD Power RTB.
0…32V DC SELV/PELV
(5)
10 mA (DC power)
SA Power
passthrough
voltage ranges
(3)
0…32V DC @ 9.99 A
(2)
SA Power current
rating, max
(2)
Power dissipation,
max
Thermal
dissipation, max
Isolation voltage
10 A (DC power)
Do not exceed 10 A current draw at the SA Power RTB.
9.0 W
30.9 BTU/hr
300V (continuous), Basic Insulation Type, SA and MOD Power to Backplane
300V (continuous), Basic Insulation Type, SA to MOD Power
300V (continuous), Basic Insulation Type, Ethernet to Backplane
300V (continuous), Double Insulation Type, Ethernet to MOD Power
300V (continuous), Double Insulation Type, Ethernet to SA Power
50V (continuous), Functional Insulation Type, Ethernet to USB
300V (continuous), Basic Insulation Type, USB to Backplane
300V (continuous), Double Insulation Type, USB to MOD Power
300V (continuous), Double Insulation Type, USB to SA Power
No isolation between Ethernet ports
Type tested at 1500V AC for 60 seconds
10Rockwell Automation Publication 5069-TD002G-EN-P - January 2019