CompactLogix 5480 Controller Catalog Number 5069-L46ERMW
TopicPage
Summary of Changes1
CompactLogix 5380 Controllers2
Compact GuardLogix 5380 Controllers8
CompactLogix 5480 Controller14
Controller Use with Other Devices22
Ethernet Node Limits25
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controller
Accessories
Additional Resources29
26
Summary of Changes
This publication was revised for these changes:
• To add catalog numbers 5069-L320ERMK, 5069-L330ERMK, and 5069-L350ERMK.
• To add the CompactLogix™ 5480 controller.
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
CompactLogix 5380 Controllers
CompactLogix 5380 controllers are part of the Logix 5000™ family of controllers. The controllers provide a scalable
controller solution to address a wide variety of applications. The applications range from standalone systems to more
complex systems with devices that are connected to the controller via an EtherNet/IP™ network.
The controllers are mounted on a DIN rail. They can monitor and control local and remote I/O modules, and other
devices connected to an EtherNet/IP network. The CompactLogix 5380 controllers support this functionality:
• Use of Compact 5000™ I/O module as local I/O and remote I/O modules.
• Use Compact 5000 I/O modules, and other I/O modules, as remote I/O modules.
• Support for Integrated Motion over an EtherNet/IP network (not all controllers).
• Use of Dual-IP mode or Linear/DLR mode.
• Use of two Ethernet ports that let the controller connect to EtherNet/IP device-level and
• Use of 1784-SD1 or 1784-SD2 Secure Digital (SD) card for nonvolatile memory.
• USB programming port for temporary connection.
enterprise-level networks.
2Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
Features - CompactLogix 5380 Controllers
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Feature
Controller tasks
• Continuous
• Periodic
• Event
5069-L306ER,
5069-L306ERM
32 tasks
1000 programs/task
All event triggers
5069-L310ER,
5069-L310ER-NSE,
5069-L310ERM
5069-L320ER,
5069-L320ERM,
5069-L320ERMK
5069-L330ER,
5069-L330ERM,
5069-L330ERMK
5069-L340ER,
5069-L340ERM
5069-L350ERM,
5069-L350ERMK
5069-L380ERM 5069-L3100ERM
1 - USB port
Built-in
communication
ports
2 - Ethernet ports
IMPORTANT: Consider the following:
– When the controller operates in Dual-IP mode, each Ethernet port requires a unique IP address.
– When the controller operates in Linear/DLR mode, the controller uses only one IP address.
USB port
communication
Ethernet
performance
EtherNet/IP modes
supported
EtherNet/IP
network topologies
supported
EtherNet/IP nodes
supported, max
Socket interfaces
supported, max
Integrated motion
USB 2.0, Type B
Full speed (12 Mbps)
Programming, configuration, firmware update, and on-line edits only
10 Mbps, 100 Mbps, 1 Gbps
Full-duplex only
Dual-IP mode (Available with the Studio 5000 Logix Designer® application, version 29.00.00 or later)
Linear/DLR mode
DLR
Star
Linear
1624406090120150180
(1)
32
As many as two
axes
(5069-L306ERM
controller only)
As many as four axes
(5069-L310ERM
controller only
As many as eight
axes
(5069-L320ERM
and
5069-L320ERMK
controllers only)
As many as 16
axes
(5069-L330ERM
and
5069-L330ERMK
controllers only)
As many as 20
axes
(5069-L340ERM
controller only)
As many as 24
axes
As many as 28
axes
As many as 32
axes
Ladder Diagram (LD)
Programming
languages
Structured Text (ST)
Function Block Diagram (FBD)
Sequential Function Chart (SFC)
(1) The maximum number of nodes that are listed represents when the controller is used with the Logix Designer application, version 31 or later. Some controllers can be used with earlier Logix Designer application versions. The
maximum number of nodes that a controller supports can be fewer in Logix Designer application, versions 30 or earlier.
Rockwell Automation Publication 5069-TD002G-EN-P - January 20193
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
1784-SD1 card
1784-SD2 card (shipped with the controller)
881631
18…32V DC
450 mA
(5)
31313131
MOD Power inrush 850 mA for 125 ms
MOD Power
passthrough
MOD Power current
rating, max
SA Power voltage
(2)
ranges
SA Power current,
(2)
max
SA Power
passthrough
SA Power current
rating, max
Power dissipation,
max
Thermal
dissipation, max
9.55 A @ 18…32V DC
(1)
10 A
Do not exceed 10 A current draw at the MOD Power RTB.
0…32V DC
0…240V AC, 47…63 Hz
ATEX/IECEX, 125V AC max
10 mA (DC power)
25 mA (AC power)
9.95 A @ 0…32V DC
9.975 A @ 0…240V AC, 47…63 Hz
(2), (3)
ATEX/IECEX, 125V AC max
10 A (AC or DC power)
(2)
Do not exceed 10 A current draw at the SA Power RTB.
8.5 W
29 BTU/hr
300V (continuous), Basic Insulation Type, SA, and MOD Power to Backplane
300V (continuous), Basic Insulation Type, SA to MOD Power
300V (continuous), Basic Insulation Type, Ethernet to Backplane
300V (continuous), Double Insulation Type, Ethernet to MOD Power
300V (continuous), Double Insulation Type, Ethernet to SA Power
Isolation voltage
50V (continuous), Functional Insulation Type, Ethernet to USB
300V (continuous), Basic Insulation Type, USB to Backplane
300V (continuous), Double Insulation Type, USB to MOD Power
300V (continuous), Double Insulation Type, USB to SA Power
No isolation between Ethernet ports
Type tested at 1500V AC for 60 s
Weight, approx0.768 kg (1.693 lb)
Dimensions
(HxWxD), approx
143.97 x 98.10 x 136.81 mm (5.67 x 3.86 x 5.39 in.)
LocationDIN rail mount (horizontal mount only)
DIN rail
Compatible zinc-plated, chromate steel DIN rail.
EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.)
4Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Attribute
5069-L306ER,
5069-L306ERM
5069-L310ER,
5069-L310ER-NSE,
5069-L310ERM
5069-L320ER,
5069-L320ERM,
5069-L320ERMK
5069-L330ER,
5069-L330ERM,
5069-L330ERMK
5069-L340ER,
5069-L340ERM
5069-L350ERM,
5069-L350ERMK
5069-L380ERM 5069-L3100ERM
RTBs are available in separately ordered 5069 RTB kits. The MOD power connection uses a 4-point RTB, and the SA power connection uses a 6-point RTB. The
Removable
terminal block
following kits are available:
• Kit catalog number 5069-RTB64-SCREW contains RTB catalog numbers 5069-RTB6-SCREW and 5069-RTB4-SCREW.
• Kit catalog number 5069-RTB64-SPRING contains RTB catalog numbers 5069-RTB6-SPRING and 5069-RTB4-SPRING.
Terminal block
torque
5069-RTB4-SCREW & 5069-RTB6-SCREW: 0.4 N•m (3.5 lb•in)
5069-RTB4-SPRING & 5069-RTB6-SPRING: Torque does not apply
5069-RTB4-SCREW, 5069-RTB6-SCREW connections:
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire that is rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max diameter including insulation,
single wire connection only
Wire size
5069-RTB4-SPRING, 5069-RTB6-SPRING connections:
0.5…1.5 mm
2
(22…16 AWG) solid or stranded copper wire that is rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max diameter including insulation,
single wire connection only
Ethernet connections:
Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2
Insulation
stripping length
Wire category
5069-RTB4-SCREW, 5069-RTB6-SCREW connections: 12 mm (0.47 in.)
5069-RTB4-SPRING, 5069-RTB6-SPRING connections: 10 mm (0.39 in.)
3 - on USB port
(4)
1 - on power ports
2 - on Ethernet ports
Enclosure None (open-style)
North American
temperature code
ATEX temperature
code
IECEx temperature
code
(1) Maximum level of MOD Power current that the controller can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(2) SA power specifications are based on the number and type of Compact 5000 I/O modules that are used in the system. If the set of I/O modules that are used in the system require AC and DC voltage, you must install a 5069-FPD
field potential distributor to separate the module types.
(3) Maximum level of SA Power current that the controller can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(4) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication
(5) When you use these controllers with the Studio 5000 Logix Designer application, version 29.00.00, the application limits the number of local I/O modules in the project to 16. For more information, see the Rockwell Automation®
Knowledgebase article #942580, ‘5380 CompactLogix controllers limited to 16 local 5069 modules in version 29 of Studio 5000® environment.The document is available at http://www.rockwellautomation.com/knowledgebase.
With the Logix Designer application, version 30.00.00 or later, the controllers support as many as 31 local I/O modules.
T4
T4
T4
1770-4.1.
Rockwell Automation Publication 5069-TD002G-EN-P - January 20195
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
± 4 kV at 5 kHz on power ports
± 2 kV at 5 kHz on Ethernet ports
± 1 kV line-line (DM) and ± 2 kV line-earth (CM) on power ports
± 2 kV line-earth (CM) on Ethernet ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
10 ms interruption on MOD Power port
6Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
Certifications - CompactLogix 5380 Controllers
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
c-UL-us
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL
File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
CE
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
RCM
Australian Radiocommunications Act, compliant with:
• EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
Ex
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO 15 ATEX 1455X
when used at or below 125V AC
IECEx System, compliant with:
• IEC 600079-0: General Requirements
IECEx
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 15.0007X
when used at or below 125V AC
Korean Registration of Broadcasting and Communications Equipment, compliant with:
KC
• Article 58-2 of Radio Waves Act, Clause 3
IMPORTANT: This certification does not apply to the following catalog numbers: 5069-L320ERMK,
5069-L330ERMK, 5069-L350ERMK
EACRussian Customs Union TR CU 020/2011 EMC Technical Regulation
EtherNet/IPODVA conformance tested to EtherNet/IP specifications
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 5069-TD002G-EN-P - January 20197
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Compact GuardLogix 5380 Controllers
Compact GuardLogix™ 5380 controllers are part of the Logix 5000 family of controllers. The controllers provide a
scalable controller solution to address a wide variety of applications. The applications range from standalone systems to
more complex systems with devices that are connected to the controller via an EtherNet/IP network.
The controllers can function in the same way as CompactLogix 5380 controllers and also provide the functionality to
perform safety functions. You can use the controller to achieve up to SIL 2/PLd (Category 3) with the use of the safety
task and safety I/O. A major benefit of this system is that it is still one project, safety and standard together.
During development, safety and standard have the same rules; multiple programmers, online editing, and forcing are all
allowed. Once the safety system is validated and the safety signature applied, safety memory is protected, the safety logic
cannot be modified, and all safety functions operate with a safety integrity of SIL 2.
The controllers are mounted on a DIN rail. They can monitor and control local and remote I/O modules, and other
devices connected to an EtherNet/IP network. The controllers support this functionality:
• Use of Compact 5000 I/O standard and safety modules as local I/O and remote I/O modules
• Use Compact 5000 I/O modules, and other I/O modules, as remote I/O modules.
• Support for Integrated Motion over an EtherNet/IP network (not all controllers)
• Use of Dual-IP mode or Linear/DLR mode
• Use of two Ethernet ports that let the controller connect to EtherNet/IP device-level and enterprise-level
networks
• Use of 1784-SD1 or 1784-SD2 Secure Digital (SD) card for nonvolatile memory
• USB programming port for temporary connection
Compact GuardLogix 5380 controllers are available with a conformal coating. The conformal coating provides a layer of
protection against contaminants and humidity to help protect the assembly and extend product life in harsh, corrosive
environments. Products with a conformal coating have a ‘K’ suffix at the end of the catalog number.
8Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
Features - Compact GuardLogix 5380 Controllers
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Feature
Controller tasks
• Continuous
• Periodic
• Event
Built-in
communication ports
USB port
communication
Ethernet
performance
EtherNet/IP modes
supported
EtherNet/IP network
topologies supported
EtherNet/IP nodes
supported, max
Socket interfaces
supported, max
Integrated motion
Programming
languages
5069-L320ERS2,
5069-L306ERS2,
5069-L306ERMS2
31 standard tasks, 1 safety task
1000 programs/task
All event triggers
1 USB port
2 Ethernet ports
IMPORTANT: Consider the following:
– When the controller operates in Dual-IP mode, each Ethernet port requires a unique IP address.
– When the controller operates in Linear/DLR mode, the controller uses only one IP address.
USB 2.0, Type B
Full speed (12 Mbps)
Programming, configuration, firmware update, and on-line edits only
10 Mbps, 100 Mbps, 1 Gbps
Full-duplex only
Dual-IP mode
Linear/DLR mode
DLR
Star
Linear
1624406090120150180
32
As many as two axes
(5069-L306ERMS2
controller only)
Ladder Diagram (LD)
Structured Text (ST)
Function Block Diagram (FBD)
Sequential Function Chart (SFC)
Safety Task supports only RLL and the additional safety application instructions
1784-SD1 card
1784-SD2 card (shipped with the controller)
88163131313131
18…32V DC SELV/PELV
(5)
475 mA
MOD Power inrush 1200 mA for 125 ms
MOD Power
passthrough
voltage range
MOD Power current
rating, max
SA Power voltage
(2)
ranges
SA Power current,
(2)
max
18…32V DC @ 4.525 A
(1)
5 A
Do not exceed 5 A current draw at the MOD Power RTB.
0…32V DC SELV/PELV
(5)
10 mA (DC power)
SA Power
passthrough
voltage ranges
(3)
0…32V DC @ 9.99 A
(2)
SA Power current
rating, max
(2)
Power dissipation,
max
Thermal
dissipation, max
Isolation voltage
10 A (DC power)
Do not exceed 10 A current draw at the SA Power RTB.
9.0 W
30.9 BTU/hr
300V (continuous), Basic Insulation Type, SA and MOD Power to Backplane
300V (continuous), Basic Insulation Type, SA to MOD Power
300V (continuous), Basic Insulation Type, Ethernet to Backplane
300V (continuous), Double Insulation Type, Ethernet to MOD Power
300V (continuous), Double Insulation Type, Ethernet to SA Power
50V (continuous), Functional Insulation Type, Ethernet to USB
300V (continuous), Basic Insulation Type, USB to Backplane
300V (continuous), Double Insulation Type, USB to MOD Power
300V (continuous), Double Insulation Type, USB to SA Power
No isolation between Ethernet ports
Type tested at 1500V AC for 60 seconds
10Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
143.97 x 98.10 x 136.81 mm (5.67 x 3.86 x 5.39 in.)
LocationDIN rail mount (horizontal mount only)
DIN rail
Compatible zinc-plated, chromate steel DIN rail.
EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.)
RTBs are available in separately ordered 5069 RTB kits. The MOD power connection uses a 4-point RTB, and the SA power connection uses a 6-point RTB. The following kits are
Removable terminal
block
available:
• Kit catalog number 5069-RTB64-SCREW contains RTB catalog numbers 5069-RTB6-SCREW and 5069-RTB4-SCREW
• Kit catalog number 5069-RTB64-SPRING contains RTB catalog numbers 5069-RTB6-SPRING and 5069-RTB4-SPRING
Terminal block torque
5069-RTB4-SCREW & 5069-RTB6-SCREW: 0.4 N•m (3.5 lb•in)
5069-RTB4-SPRING & 5069-RTB6-SPRING: Torque does not apply
5069-RTB4-SCREW, 5069-RTB6-SCREW connections:
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14 in.) max diameter including insulation, single wire connection only
Wire size
5069-RTB4-SPRING, 5069-RTB6-SPRING connections:
0.5…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11 in.) max diameter including insulation, single wire connection only
Ethernet connections:
Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2
Insulation stripping
length
Wire category
5069-RTB4-SCREW, 5069-RTB6-SCREW connections: 12 mm (0.47 in.)
5069-RTB4-SPRING, 5069-RTB6-SPRING connections: 10 mm (0.39 in.)
3 - on USB port
(4)
1 - on power ports
2 - on Ethernet ports
Enclosure None (open-style)
North American
temperature code
ATEX temperature
code
IECEx temperature
code
(1) Maximum level of MOD Power current that the controller can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(2) SA power specifications are based on the number and type of Compact 5000 I/O modules that are used in the system. For example, if the set of I/O modules that are used in a Compact GuardLogix 5380 controller system includes
modules that use AC SA power, you must include a 5069-FPD field potential distributor in the system. In a Compact GuardLogix 5380 controller system, modules that use AC SA power must be installed to the right of a 5069-FPD
field potential distributor.
(3) Maximum level of SA Power current that the controller can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(4) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication
(5) For Functional Safety applications, SELV/PELV power supplies are required for both MOD power and SA power.
T4
T4
T4
1770-4.1.
I
Rockwell Automation Publication 5069-TD002G-EN-P - January 201911
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
0 °C < Ta < +60 °C (+32 °F < Ta < +140 °F) with 152.4 mm (6 in.) clearance on left, top, and bottom sides
0 °C < Ta < +55 °C (+32 °F < Ta < +131 °F) with 101.7 mm (4 in.) clearance on left, top, and bottom sides
0 °C < Ta < +50 °C (+32 °F < Ta < +122 °F) with 50.8 mm (2 in.) clearance on left, top, and bottom sides
-40…+85 °C
(-40…+185 °F)
5…95% noncondensing
5 g @ 10…500 Hz
30 g
50 g
6 kV contact discharges
8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
3V/m with 1 kHz sine-wave 80% AM from 2700…6000 MHz
± 4 kV at 5 kHz on power ports
± 2 kV at 5 kHz on Ethernet ports
± 1 kV line-line (DM) and ± 2 kV line-earth (CM) on power ports
± 2 kV line-earth (CM) on Ethernet ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
10 ms interruption on MOD Power port
12Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL
File E194810.
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2006/42/EC MD, compliant with:
• EN 60204-1; Electrical equipment of machines
• EN ISO 13849-1; Safety-related parts of control systems
• EN 62061; Functional safety of safety-related control systems
• Cat. 3/PL d according to EN ISO 13849-1, and SIL 2 according to EN 62061/IEC 61508
• TÜV 01/205/5632
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
• EN 61000-6-4; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
• EN 60079-0; General Requirements
• EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• DEMKO17ATEX1976X
IECEx System, compliant with:
• IEC 600079-0: General Requirements
• IEC 60079-15; Potentially Explosive Atmospheres, Protection "n"
• II 3 G Ex nA IIC T4 Gc
• IECEx UL 17.0122X
TÜV Certified for Functional Safety
(2)
:
• Capable of SIL 2, CAT. 3/PL d
Korean Registration of Broadcasting and Communications Equipment, compliant with:
• Article 58-2 of Radio Waves Act, Clause 3
Rockwell Automation Publication 5069-TD002G-EN-P - January 201913
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
CompactLogix 5480 Controller
The CompactLogix 5480 controller is part of the Logix 5000 family of controllers. The controller is a real-time
controller with Windows 10 IoT Enterprise commercial operating system (COS) running in parallel to the Logix control
engine.
The CompactLogix 5480 controller delivers scalable control that is ideal for mid-size to large applications that require
high-performance control and data throughput. The CompactLogix 5480 controllers also provide a truly integrated
motion solution.
The controllers are mounted on a DIN rail. They can monitor and control local and remote I/O modules, and other
devices connected to an EtherNet/IP network. The CompactLogix 5480 controller supports this functionality for use
with the control engine:
• Use of Compact 5000 I/O module as local I/O and remote I/O modules.
• Use Compact 5000 I/O modules, and other I/O modules, as remote I/O modules.
• Support for Integrated Motion over an EtherNet/IP network.
• Use of three Ethernet ports that can connect to enterprise-level and device-level EtherNet/IP networks, including
star, linear, and DLR EtherNet/IP network topologies
• Support for Linear/DLR and Dual-IP mode
• Use of USB port for firmware updates and programming
• Use of 1784-SD1 or 1784-SD2 Secure Digital (SD) card for nonvolatile memory.
The COS lets you perform tasks on the controller that must be performed on an external workstation in other
Logix 5000 control systems. The CompactLogix 5480 controller comes with following for use in Windows-based
applications:
• Embedded Ethernet port to connect the COS to an EtherNet/IP network or Enterprise network
• Two USB 3.0 ports to connect peripherals such as a keyboard and mouse
• DisplayPort to connect a monitor
• Support for the installation and use of Rockwell Automation® applications, such as FactoryTalk® View Site Edition
14Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Features - CompactLogix 5480 Controllers
Feature5069-L46ERMW
Controller tasks
• Continuous
• Periodic
• Event
Built-in communication ports
USB port communication
Ethernet performance
EtherNet/IP modes supported
EtherNet/IP network topologies supported
EtherNet/IP nodes supported, max250
Socket interfaces supported, max32
Integrated motion
Total axis count512 (Any combination of physical, virtual, or consumed axes.)
Virtual axis, max512
Position-loop axis, max150
Axes/ms, max100
Programming languages
32 tasks
1000 programs/task
All event triggers
Logix control engine use:
• 3 - Ethernet, 10 Mbps/100 Mbps/1 Gbps
• 1- USB client
IMPORTANT: Consider the following:
• When the controller operates in Dual-IP mode, each Ethernet port requires a unique IP address.
• When the controller operates in Linear/DLR mode, the controller uses only one IP address.
Windows 10 use:
• 1 - Ethernet, 10 Mbps/100 Mbps/1 Gbps
Logix control engine use:
• USB 2.0, Type B
• Full speed (480 Mbps)
• Programming, configuration, firmware update, and on-line edits only
Windows 10 use:
• 2 - USB 3.0 ports to connect peripherals such as a keyboard and mouse
10 Mbps, 100 Mbps, 1 Gbps
Full-duplex only
Dual-IP mode
Linear/DLR mode
DLR
Star
Linear
Ladder Diagram (LD)
Structured Text (ST)
Function Block Diagram (FBD)
Sequential Function Chart (SFC)
Rockwell Automation Publication 5069-TD002G-EN-P - January 201915
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Dimensions (HxWxD), approx166.20 x 130.21 x 126.54 mm (6.54 x 5.13 x 4.98 in.)
LocationDIN rail mount (horizontal mount only)
DIN rail
Removable terminal block
Terminal block torque
Windows 10 (commercial operating system on controller)
• RAM - 6 GB
• SSD: 64 GB
1784-SD1 card
1784-SD2 card (shipped with the controller)
6 A @ 18…32V DC
10 A
Do not exceed 10 A current draw at the MOD power RTB.
0…32V DC
0…240V AC, 47…63 Hz
10 mA (DC power)
25 mA (AC power)
9.99 A @ 0…32V DC
9.975 A @ 0…240V AC, 47…63 Hz
Do not exceed 10 A current draw at the SA power RTB.
300V (continuous), Basic Insulation Type, SA, and MOD Power to Backplane
300V (continuous), Basic Insulation Type, SA to MOD Power
300V (continuous), Basic Insulation Type, Ethernet to Backplane
300V (continuous), Double Insulation Type, Ethernet to MOD Power
300V (continuous), Double Insulation Type, Ethernet to SA Power
50V (continuous), Functional Insulation Type, Ethernet to USB ports and DisplayPort
300V (continuous), Basic Insulation Type, USB ports, and DisplayPort to Backplane
300V (continuous), Double Insulation Type, USB ports, and DisplayPort to MOD Power
300V (continuous), Double Insulation Type, USB ports, and DisplayPort to SA Power
No isolation between Ethernet ports
Type tested at 1500V AC for 60 s
Compatible zinc-plated, chromate steel DIN rail.
• EN50022 - 35 x 7.5 mm (1.38 x 0.30 in.)
• EN50022 - 35 x 15 mm (1.38 x 0.60 in.)
RTBs ship with the controller
5069-RTB4-SCREW, 5069-RTB6-SCREW
5069-RTB4-L4UPSRTB
5069-RTB4-SCREW, 5069-RTB6-SCREW, and 5069-L4UPSRTB connections: 0.4 N•m (3.5 lb•in)
ATTENTION: Do not wire more than two conductors on one RTB terminal.
(5)
16Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
0.5...1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5 mm (0.14
in.) max diameter including insulation, single wire connection only
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Wire size
5069-L4UPSRTB connections:
0.5...1.5 mm
2
(22…16 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 2.9 mm (0.11
in.) max diameter including insulation, single wire connection only
Ethernet connections:
Ethernet Cabling and Installation according to IEC 61918 and IEC 61784-5-2
Insulation stripping length5069-RTB4-SCREW, 5069-RTB6-SCREW, and 5069-L4UPSRTB connections: 12 mm (0.47 in.)
3 - on USB ports and DisplayPort
2 - on power ports
Wire category
(4)
2 - on Ethernet ports
Enclosure None (open-style)
(1) Maximum level of MOD Power current that the controller can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(2) SA power specifications are based on the number and type of Compact 5000 I/O modules that are used in the system. If the set of I/O modules that are used in the system require AC and DC voltage, you must install a 5069-FPD
field potential distributor to separate the module types.
(3) Maximum level of SA Power current that the controller can pass through to the next module in the system. The specific level of current passed through varies based on system configuration.
(4) Use this Conductor Category information for planning conductor routing. See the Industrial Automation Wiring and Grounding Guidelines, publication
(5) Remember, MOD power usage includes the total power that the controller and local Compact 5000 I/O modules use. If you connect external power to both sets of MOD power RTB terminals, however, the local Compact 5000 I/O
modules can draw a maximum of 10 A in addition to the current that the controller draws.
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
3V/m with 1 kHz sine-wave 80% AM from 2700…6000 MHz
± 2 kV at 5 kHz on power ports
± 1 kV at 5 kHz on Ethernet ports
Rockwell Automation Publication 5069-TD002G-EN-P - January 201917
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
± 500V line-line (DM) and ± 1 kV line-earth (CM) on power ports
± 1 kV line-earth (CM) on Ethernet ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz on power and Ethernet ports
30 A/m long duration at 60 Hz
10 ms interruption on MOD Power port
Certifications - CompactLogix 5480 Controller
Certification
c-UL-usUL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
CE
RCM
KC
EAC
EtherNet/IPODVA conformance tested to EtherNet/IP specifications
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
(1)
5069-L46ERMW
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61000-6-4; Industrial Emissions
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2014/35/EU LVD, compliant with:
• EN 61010-2-201; Control Equipment Safety Requirements
European Union 2011/65/EU RoHS, compliant with:
• EN 50581; Technical documentation
Australian Radiocommunications Act, compliant with:
• EN 61000-6-4; Industrial Emissions
Korean Registration of Broadcasting and Communications Equipment, compliant with:
• Article 58-2 of Radio Waves Act, Clause 3
Russian Customs Union TR CU 020/2011 EMC Technical Regulation
Russian Customs Union TR CU 004/2011 LV Technical Regulation
18Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Controller Minimum Spacing Requirements
The minimum distance between the CompactLogix 5380 system or Compact GuardLogix 5380 system and enclosure
walls, wireways, and adjacent equipment varies based on the current operating temperature.
The minimum distances on all sides of the system are as follows:
• CompactLogix 5380 Controller
– 50.80 mm (2.00 in.) at 55 °C (131 °F)
– 101.60 mm (4.00 in) at 60 °C (140 °F)
• Compact GuardLogix 5380 Controller
– 50.8 mm (2.00 in.) at 50 °C (122 °F)
– 101.7 mm (4.00 in.) at 55 °C (131 °F)
– 152.4 mm (6.00 in) at 60 °C (140 °F)
End cap
Top
CompactLogix 5380 or
Bottom
Compact GuardLogix
5380 Controller
Compact 5000 I/O
Compact 5000 I/O
SideSide
Rockwell Automation Publication 5069-TD002G-EN-P - January 201919
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
The minimum distance on of a system that includes only a CompactLogix 5480 controller is as follows:
• 25.00 mm (0.98 in.) between the sides and the cabinet
• 25.00 mm (0.98 in.) between the front of the controller and the cabinet
• 50.00 mm (1.96 in.) between the top and bottom and the cabinet
We recommend that you install the controller near the bottom of the enclosure, where ambient temperature is
lower.
Top
End cap
Cabinet
SideSide
Bottom
IMPORTANTCompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 systems can only be mounted horizontally.
20Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Controller Dimensions
IMPORTANT: The graphics show a CompactLogix 5380 controller. The dimensions are the same on Compact GuardLogix 5380 controllers.
123.00 mm
(4.84 in.)
101.66 mm
(4.00 in.)
98.10 mm
(3.86 in.)
136.81 mm
(5.39 in.)
143.97 mm
(5.67 in.)
MOD Power
137.84 mm
(5.43 in.)
SA Power
130.31 mm
(5.13 in.)
CompactLogix 5480
133.66 mm
(5.26 in.)
130.21 mm
(5.13 in.)
126.54 mm
(4.98 in.)
166.20 mm
(6.54 in.)
160.00 mm
(6.30 in.)
120.02 mm
(4.73 in.)
Rockwell Automation Publication 5069-TD002G-EN-P - January 201921
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Controller Use with Other Devices
Your controller can control and communicate with the following devices:
Control I/O Modules
•
Communicate with Display Devices
•
•
Communicate with Other Controllers
Control I/O Modules
The CompactLogix 5380 and Compact GuardLogix 5380 controllers can monitor and control local and remote
I/O modules.
Local I/O Modules
• A CompactLogix 5380 and CompactLogix 5480 system supports Compact 5000 I/O standard modules as local
I/O modules.
• A Compact GuardLogix 5380 system supports Compact 5000 I/O standard and safety modules as local modules.
The number of local I/O modules that are supported in a CompactLogix 5380 system or Compact GuardLogix 5380
system varies by controller catalog number.
(1) When you use these controllers with the Logix Designer application, version 29.00.00, the application limits the number of local I/O modules in the project to 16. For more information, see the Rockwell
Automation® Knowledgebase article #942580, ‘5380 CompactLogix controllers limited to 16 local 5069 modules in version 29 of Studio 5000.’ The document is available at
www.rockwellautomation.com/knowledgebase. With the Logix Designer application, version 30.00.00 or later, the controllers support 31 local I/O modules.
, 5069-L330ERMK
(1)
Standard I/O Modules
31—
Any Combination of Standard and
Safety I/O Modules
http://
22Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Remote I/O Modules
The controllers can connect to these remote I/O modules over an EtherNet/IP network.
IMPORTANTFor maximum performance, we recommend that you use Compact 5000 I/O modules when you use remote I/O modules.
CompactLogix 5380 controllers, Compact GuardLogix 5380, and CompactLogix 5480 controllers support the remote
I/O modules in this table. The I/O modules that are listed are standard I/O modules.
Module TypeI/O Module Family
Chassis-based I/O1746 SLC™ I/O
1756 ControlLogix® I/O
1769 Compact I/O™
Compact 5000 I/O standard modules
In-cabinet I/O1734 POINT I/O™
1794 FLEX™ I/O
On-Machine I/O1732 ArmorBlock® I/O
1738 ArmorPOINT® I/O
Only Compact GuardLogix 5380 controllers support the remote I/O modules in this table. The I/O modules that are
listed are safety I/O modules.
Module TypeI/O Module Family
Chassis-based I/OCompact 5000 I/O safety modules
In-cabinet I/OCompactBlock™ Guard I/O™
POINT Guard I/O™
On-Machine™ I/O1732 ArmorBlock® Guard I/O™
Communicate with Display Devices
The controller can communicate with these display devices over an EtherNet/IP network.
Device TypeDisplay
Allen-Bradley® integrated-display rotating media (HDD) and
solid-state (SSD) computers
Industrial computers
Graphic terminals
Message displaysInView™ message displays
Allen-Bradley-integrated display computers with keypad
Allen-Bradley non-display computers
PanelView™ Plus and PanelView CE terminals
PanelView standard terminals
Rockwell Automation Publication 5069-TD002G-EN-P - January 201923
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Communicate with Other Controllers
The controller can communicate with these programmable controllers.
Controller TypeController Family
CompactLogix 5370
CompactLogix 5380
CompactLogix 5480
Compact GuardLogix 5370 (safety)
Compact GuardLogix 5380 (safety)
ControlLogix 5570
ControlLogix 5580
Programmable automation
controller
Programmable logic
controllers
(1) These controllers require a built-in Ethernet port or a 1761-NET-ENI, EtherNet/IP RS-232-C interface to communicate
with a CompactLogix 5380 controller over an EtherNet/IP network.
(2) These controllers require a 1761-NET-ENI, EtherNet/IP RS-232-C interface to communicate with a
CompactLogix 5380 controller over an EtherNet/IP network.
GuardLogix 5570 (safety)
GuardLogix 5580 (safety)
1756 Armor™ ControlLogix (safety)
1756 Armor™ GuardLogix® (safety)
1768 Compact GuardLogix (safety)
1768 CompactLogix
1769 Modular CompactLogix
1769 Packaged CompactLogix
1789 SoftLogix™ 5800
PowerFlex® with DriveLogix™
1785 PLC-5®
1747 SLC™
1761 MicroLogix™
1762 MicroLogix
(1)
(1)
(2)
(2)
1763 MicroLogix
1764 MicroLogix
(2)
1766 MicroLogix
24Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Ethernet Node Limits
When you configure a CompactLogix 5380, Compact GuardLogix 5380, or CompactLogix 5480 control system,
consider the number of Ethernet nodes that are used. The number of Ethernet nodes that you can include in the I/O
configuration section in the Logix Designer application project is limited.
Maximum Number of Ethernet Nodes
The number of nodes that are supported in a Logix Designer application project varies by CompactLogix 5380 or
Compact GuardLogix 5380 controller.
The maximum number of nodes that are listed represents when the controller is used with the Logix Designer
application, version 31 or later. You can use CompactLogix 5380 controllers with earlier Logix Designer application
versions. The maximum number of nodes that a controller supports can be fewer in Logix Designer application, versions
30 or earlier.
Any devices that you add directly to the I/O configuration section are counted toward the Ethernet node limit. The
following are examples of devices that must be counted:
• Remote communication adapters
• Devices with an embedded Ethernet port, such as I/O modules, drives, and linking devices
• Remote controllers when a produce/consume connection is established between the two controllers
• HMI devices that are included in the I/O configuration tree
• Third-party devices that are directly connected to the EtherNet/IP network
Rockwell Automation Publication 5069-TD002G-EN-P - January 201925
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controller Accessories
The following accessories are used with a CompactLogix 5380, Compact GuardLogix 5380, or CompactLogix 5480
controller:
End Cap
•
•
Memory Cards
•
Removable Terminal Kits - Not used with CompactLogix 5480 controllers because the required RTBs ship with
the controllers.
•
Ethernet Communication Cables
End Cap
You must install an end cap, catalog number 5069-ECR, on the right side of the last module in a CompactLogix 5380,
Compact GuardLogix 5380, or CompactLogix 5480 control system. The end cap is shipped with the controller.
SHOCK HAZARD: The end cap covers the exposed interconnections on the last module in the system. If you do not install the
end cap before powering the system, equipment damage or injury from electric shock can result.
Memory Cards
Memory cards, also known as Secure Digital (SD) cards, offer nonvolatile memory to store a user program and tag data
on a controller. Through the Logix Designer application, you can manually trigger the controller to save to or load from
nonvolatile memory or configure the controller to load from nonvolatile memory on powerup.
A 1784-SD2 card ships with the controller. If you need additional SD cards, we recommend that you use one that is
available from Rockwell Automation. The 1784-SD1 (1 GB) and 1784-SD2 (2 GB) cards are available.
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Certifications - 1784 Memory Cards
Certification
CE
RCM
KC
(1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
(1)
1784-SD1, 1784-SD2
European Union 2014/30/EU EMC Directive, compliant with:
• EN 61000-6-4; Industrial Emissions
• EN 61326-1; Meas./Control/Lab., Industrial Requirements
• EN 61000-6-2; Industrial Immunity
• EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
Australian Radiocommunications Act, compliant with:
• AS/NZS CISPR 11; Industrial Emissions
Korean Registration of Broadcasting and Communications Equipment, compliant with:
• Article 58-2 of Radio Waves Act, Clause 3
Rockwell Automation Publication 5069-TD002G-EN-P - January 201927
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Removable Terminal Kits
You can order RTBs to connect MOD power and SA power to CompactLogix 5380 and Compact GuardLogix 5380
controllers. The RTBs are used to connect wiring to the controllers. The MOD power connection uses a 4-point RTB,
and the SA power connection uses a 6-point RTB.
CompactLogix 5380 and Compact GuardLogix Controllers - RTBs
Cat. No.Description
Contains the following:
5069-RTB64-SCREW
5069-RTB64-SPRING
• 5069-RTB6-SCREW - 6-point RTB that uses screw-type terminals
• 5069-RTB4-SCREW - 4-point RTB that uses screw-type terminals
Contains the following:
• 5069-RTB6-SPRING - 6-point RTB that uses spring-type terminals to connect SA power to the controller.
• 5069-RTB4-SPRING - 4-point RTB that uses spring-type terminals to connect MOD power to the controller.
Ethernet Communication Cables
AttributeValue
Connector typeRJ45 male to RJ45 male
Connector angleStraight-through
LengthVaries by catalog number
Connector
Number
1White/OrangeBI_DA+TxData +
2OrangeBI_DA-TxData -
3White/GreenBI_DB+Recv Data +
4BlueBI_DC+Unused—
5White/BlueBI_DC-Unused—
6GreenBI_DB-Recv Data -
7White/BrownBI_DD+Unused—
8BrownBI_DD-Unused—
Color
1585J 8-pin Cables
with Support for 10/
100/1000 Mbps
1585J 8-pin Cables
with Support for
10/100 Mbps
1585J 4-pin Cables
with Support for
10/100 Mbps
28Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Industrial Automation Wiring and Grounding Guidelines, publication
Product Certifications website,
certification/overview.page
5069-TD001
1769-SG001Describes how to design and select components for your CompactLogix controller system.
5069-UM002Describes how to use CompactLogix 5480 controllers.
5000-UM004Describes how to configure and operate Compact 5000 I/O digital and safety modules.
5000-UM005Describes how to configure and operate Compact 5000 I/O analog modules.
ENET-UM004
IA-AT003
http://www.rockwellautomation.com/
1770-4.1Provides general guidelines for installing a Rockwell Automation industrial system.
http://www.rockwellautomation.com/global/
Provides specifications, wiring diagrams, and functional block diagrams for
Compact 5000 I/O modules and EtherNet/IP adapters.
Describes how to use CompactLogix 5380 and Compact GuardLogix 5380 controllers.
Describes how to configure and operate a Compact 5000 I/O high-speed counter module.
Describes how to replace the following:
• ControlLogix 5560/5570 controller with a ControlLogix 5580 controller
• CompactLogix 5370 L3 controllers with a CompactLogix 5380 controller
Describes how to use Compact 5000 I/O and FLEX 5000™ I/O EtherNet/IP
communication modules.
Provides information on CIP Sync™ and the IEEE 1588-2008 Precision Time Protocol.
Provides information on tools that you can use in the selection, development,
commissioning, and maintenance stages of the Integrated Architecture lifecycle.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at
http://www.rockwellautomation.com/global/literature-library/
overview.page. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
Rockwell Automation Publication 5069-TD002G-EN-P - January 201929
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Notes:
30Rockwell Automation Publication 5069-TD002G-EN-P - January 2019
Notes:
CompactLogix 5380, Compact GuardLogix 5380, and CompactLogix 5480 Controllers Specifications
Rockwell Automation Publication 5069-TD002G-EN-P - January 201931
Rockwell Automation Support
Use the following resources to access support information.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat,
User Forums, and Product Notification Updates.
Local Technical Support Phone NumbersLocate the phone number for your country.
Find the Direct Dial Code for your product. Use the
Direct Dial Codes
code to route your call directly to a technical support
engineer.
Literature Library
Product Compatibility and Download Center
(PCDC)
Installation Instructions, Manuals, Brochures, and
Technical Data.
Get help determining how products interact, check
features and capabilities, and find associated
firmware.
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Armor, Armor GuardLogix, ArmorBlock, ArmorBlock Guard I/O, ArmorPoint, Compact 5000, Compact I/O, CompactBlock, CompactBlock Guard I/O, CompactLogix, ControlLogix, DriveLogix, FactoryTalk, FLEX, FLEX 5000,
Guard I/O, GuardLogix, InView, Logix 5000, MicroLogix, On-Machine, PanelView, PLC-5, POINT I/O, POINT Guard I/O, PowerFlex, Rockwell Automation, Rockwell Software, SLC, SoftLogix, Studio 5000, and Studio 5000 Logix Designer are
trademarks of Rockwell Automation, Inc.
CIP Sync and EtherNet/IP are trademarks of ODVA.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400