INSTALLATION AND OPERATING INSTRUCTIONS
BULLETIN 802T, PLUGĆIN LIMIT SWITCH
WARNING: To avoid electrical shock and/or unintended operation of equipment, disconnect all
power to the limit switch and the controlled equipment before proceeding with any repair or adjustment of the limit switch.
MOUNTING
Position the conduit entering the switch such that any fluid inside
the conduit will not drain into the switch enclosure. Apply sealing
compound to conduit threads to prevent against entrance of
fluids through the threads.
The base may be mounted by either of two methods:
1. Two #10–32 tapped holes are provided for rear
mounting.
CAUTION: Make sure the screws used for rear
mounting are not so long as to interfere with the
screws used to secure the front to the base.
LEVER POSITIONING
The lever on rotary actuated devices is adjustable to any position
through 360 ° around the shaft. Loosen the nut, move lever to desired position and securely retighten the nut. (See Figure 2 below).
FIGURE 2
LOCK PIN NUT
2. Two clearance holes for #10 screws are provided for
front mounting.
WIRING
CAUTION: The contacts in each switching element
must have the same polarity. The circuit diagram is
shown on the nameplate
The pressure type connector terminals in the base will accept
No. 12 A WG and smaller solid or stranded wire. For proper tightening, it is suggested that nothing smaller than No. 18 AWG be
used. Before inserting wire under the pressure plates, strip the
insulation approximately 3/8 inch. Tighten all pressure plate terminals whether used or not, to avoid interference with the switch
cover.
A grounding screw is located in the terminal base enclosure near
the conduit opening. If the grounding screw has a self lifting pressure plate and a wire barrier, the proper installed position of the
ground wire is between the pressure plate and the wire barrier
in a direction parallel to the edge of the casting. Be sure the
ground wire does not interfere with the gasket or with the switch
portion of the device.
After wiring has been completed, check that all wires are in the
wiring cavity of the terminal block so they will not interfere with
the switch when it is plugged into the terminal block. Recheck all
wiring terminal screws for tightness.
Note: For switches which have been factory wired, check wire
color and their position in the terminal block for proper circuit hookup.
When the switch has been plugged into the terminal block, securely tighten the two cover screws to compress the body gasket.
ACTUATOR HEAD POSITIONING
The actuator head may be placed in any of four positions on the
switch body. Loosen the four captive screws. Place the head in
the desired position and securely retighten the four screws. (See
Figure 1 below).
FIGURE 1
CHANGING DIRECTION OF ACTUATION
The switch action of most lever operated limit switches may be
adjusted to operate with either a clockwise, a counterclockwise,
or both direction movement of the shaft. The maintained and
neutral position style of devices operate in both directions and
cannot be changed.
To change actuation direction, follow the steps below:
Important: These procedures must be performed in a clean en-
vironment to avoid introduction of dirt into the operating mechanism.
Step 1. Loosen the four head mounting screws and re-
move the operating head from the switch body.
Step 2. Locate the plunger on the underside of the operat-
ing head.
Step 3. Pull the plunger outward and rotate it in steps of
90° to provide the operating mode desired. The
respective settings are shown in Figure 3.
Step 4. Make sure the plunger is pushed back inward and
the “O” ring is properly seated before the operating head is reattached to the switch body.
Step 5. Securely retighten (approx. 12–18 in.-lbs.) the op-
erating head mounting screws.
Step 6. Check for desired actuation mode.
FIGURE 3
PLUNGER
SETTING
ACTUATION
REQUIRED
CCW ONLY CW & CCW CW ONLY
RENEWAL PARTS
If renewal parts or additional lubricant is required, give the bulletin number, catalog number, and series letter found on the nameplate.
Publication 40146–752–02(A)
July 1993
Printed in USA

RENSEIGNEMENTS • INSTALLATION ET OPÉRATION
DES INTERRUPTEURS DE POSITION ENFICHABLES DU BULLETIN 802T
ATTENTION: Toujours couper toutes sources d’ali-
mentation à l’interrupteur et l’appareil sous com-
mande avant de faire l’entretien ou le rêglage sur
l’interrupteur. Ceci êvitera les chocs êlectriques ou
une opêration inattendue de l’appareil sous commande.
MONTAGE
Le conduit doit être placé de façon à éviter l’entrée des liquides
dans l’interrupteur. Sceller aussi les filets du conduit.
1. Montage par l’arrière – Deux trous filetés à No. 10-32
sont fournis.
À NOTER: Choisir les vis d’une longueur compatible
aux vis d’avant, pour éviter l’interférence.
2. Montage par l’avant – Deux trous de débourrage (vis
No. 10) sont fournis.
CÀBLAGE
1. Polarité
Les contacts doivent être branchés à la même polarité.
Voir le schéma des connexions sur la plaque signalétique.
2. Bornes de Connexion à Pression
La gamme des fils à employer est de 18 AWG jusqu’a 12
AWG.
Dénuder les fils 3/8″.
Serrer toutes les vis pour éviter l’interférence avec le couv-
ercle de l’interruptuer.
Une vis de mise à la terre est fournie dans le boitier.
S’sssurer qu’il n’existe pas d’interférence entre les fils et
l’interrupteur avant de l’enficher.
Bien serrer les deux vis du couvercle pour comprimer le
joint d’étanchéité.
3. Interrupteurs Câblés à L’usine
S’assurer de la bonne disposition des branchements ainsi
que de la position des fils sur les bornes.
LA TÊTE DE COMMANDE
On peut installer la tête de commande en quatre oreintations.
Pour changer les positions, désserrer les vis, pivoter la tête de
commande, resserrer les quatre vis. (Ill. 1)
Ill. 1
LEVIERS (Type à levier seulement)
Les leviers sont ajustables dans un champ de mouvement de
360°. Déserrer la cheville de sécurité, bouger le levier jusqu’ à
la position requise er serrer l’écrou, (voir Ill.2).
Ill. 2
Cheville de
Sècurite
CHANGEMENT DE LA DIRECTION DE
FONCTIONNEMENT
La plupart des interrupteurs de position sont réglables pour éllecluer un fonctionnement on sons horologique sons anti-horologique ou dans les deux directions.
Les interrupteurs maintenus et à position neutre ne sont pas
changeables ils fonctionnement dans deux directions seulement.
À NOTER: Toujours régler ces interrupteurs dans les
conditions environnantes propres pour éviter l’entrée
des saletés dans le mécanisme.
1. Desserrez les quatre vis de montage de la tête et enle-
vez la tête d’opération du corps de l’interrupteur.
2. Localisez le plongeur en-dessous de la tête d’opération.
3. Tirez le plongeur vers l’ extérieur et tournez le avec un
pas de 90° afin d’obtenir le mode désiré. Voir reglages
respectif en Ill. 3.
4. Faites sûr le plongeur est repoussé dans l’ intérieur et
que le joint est proprement placé avant la tête d’opération est réattaché au corps de l’interrupteur.
5. Reserrez (approximativement 1,36 Nm – 2.03 nm) les
vis de montage de la tête.
6. Vérifiez le mode d’action désiré.
Ill. 3
Ecrou
Position du
plongeur
Fonctionnement
desiré
Antihorologique Horologique et Horologique
Uniquement Antihorologique Uniquement
PIÉCES DE RECHANGE OU LUBRIFIANT ADDITIONNEL
Votre commande doit inclure le numéra de catalogue et la lettre
de série.
40146–752–02(A)
July 1993
Imprimé aux. È.U.