INSTALLATION AND OPERATING INSTRUCTIONS
BULLETIN 802T, PLUGĆIN LIMIT SWITCH
WARNING: To avoid electrical shock and/or unin­tended operation of equipment, disconnect all power to the limit switch and the controlled equip­ment before proceeding with any repair or adjust­ment of the limit switch.
MOUNTING
Position the conduit entering the switch such that any fluid inside the conduit will not drain into the switch enclosure. Apply sealing compound to conduit threads to prevent against entrance of fluids through the threads.
The base may be mounted by either of two methods:
1. Two #10–32 tapped holes are provided for rear mounting.
CAUTION: Make sure the screws used for rear mounting are not so long as to interfere with the screws used to secure the front to the base.
LEVER POSITIONING
The lever on rotary actuated devices is adjustable to any position through 360 ° around the shaft. Loosen the nut, move lever to de­sired position and securely retighten the nut. (See Figure 2 be­low).
FIGURE 2
LOCK PIN NUT
2. Two clearance holes for #10 screws are provided for front mounting.
WIRING
CAUTION: The contacts in each switching element
must have the same polarity. The circuit diagram is shown on the nameplate
The pressure type connector terminals in the base will accept No. 12 A WG and smaller solid or stranded wire. For proper tight­ening, it is suggested that nothing smaller than No. 18 AWG be used. Before inserting wire under the pressure plates, strip the insulation approximately 3/8 inch. Tighten all pressure plate ter­minals whether used or not, to avoid interference with the switch cover.
A grounding screw is located in the terminal base enclosure near the conduit opening. If the grounding screw has a self lifting pres­sure plate and a wire barrier, the proper installed position of the ground wire is between the pressure plate and the wire barrier in a direction parallel to the edge of the casting. Be sure the ground wire does not interfere with the gasket or with the switch portion of the device.
After wiring has been completed, check that all wires are in the wiring cavity of the terminal block so they will not interfere with the switch when it is plugged into the terminal block. Recheck all wiring terminal screws for tightness.
Note: For switches which have been factory wired, check wire
color and their position in the terminal block for proper cir­cuit hookup.
When the switch has been plugged into the terminal block, se­curely tighten the two cover screws to compress the body gas­ket.
ACTUATOR HEAD POSITIONING
The actuator head may be placed in any of four positions on the switch body. Loosen the four captive screws. Place the head in the desired position and securely retighten the four screws. (See Figure 1 below).
FIGURE 1
CHANGING DIRECTION OF ACTUATION
The switch action of most lever operated limit switches may be adjusted to operate with either a clockwise, a counterclockwise, or both direction movement of the shaft. The maintained and
neutral position style of devices operate in both directions and cannot be changed.
To change actuation direction, follow the steps below: Important: These procedures must be performed in a clean en-
vironment to avoid introduction of dirt into the oper­ating mechanism.
Step 1. Loosen the four head mounting screws and re-
move the operating head from the switch body.
Step 2. Locate the plunger on the underside of the operat-
ing head.
Step 3. Pull the plunger outward and rotate it in steps of
90° to provide the operating mode desired. The respective settings are shown in Figure 3.
Step 4. Make sure the plunger is pushed back inward and
the “O” ring is properly seated before the operat­ing head is reattached to the switch body.
Step 5. Securely retighten (approx. 12–18 in.-lbs.) the op-
erating head mounting screws.
Step 6. Check for desired actuation mode.
FIGURE 3
PLUNGER
SETTING
ACTUATION
REQUIRED
CCW ONLY CW & CCW CW ONLY
RENEWAL PARTS
If renewal parts or additional lubricant is required, give the bulle­tin number, catalog number, and series letter found on the name­plate.
Publication 40146–752–02(A)
July 1993
Printed in USA
Page 2
RENSEIGNEMENTS INSTALLATION ET OPÉRATION
DES INTERRUPTEURS DE POSITION ENFICHABLES DU BULLETIN 802T
ATTENTION: Toujours couper toutes sources d’ali- mentation à l’interrupteur et l’appareil sous com- mande avant de faire lentretien ou le rêglage sur linterrupteur. Ceci êvitera les chocs êlectriques ou une opêration inattendue de lappareil sous com­mande.
MONTAGE
Le conduit doit être placé de façon à éviter l’entrée des liquides dans linterrupteur. Sceller aussi les filets du conduit.
1. Montage par larrière – Deux trous filetés à No. 10-32 sont fournis.
À NOTER: Choisir les vis d’une longueur compatible aux vis d’avant, pour éviter l’interférence.
2. Montage par lavant – Deux trous de débourrage (vis No. 10) sont fournis.
CÀBLAGE
1. Polarité
Les contacts doivent être branchés à la même polarité. Voir le schéma des connexions sur la plaque signalétique.
2. Bornes de Connexion à Pression La gamme des fils à employer est de 18 AWG jusqua 12 AWG.
Dénuder les fils 3/8. Serrer toutes les vis pour éviter linterférence avec le couv-
ercle de l’interruptuer. Une vis de mise à la terre est fournie dans le boitier. Ssssurer quil nexiste pas dinterférence entre les fils et
linterrupteur avant de lenficher. Bien serrer les deux vis du couvercle pour comprimer le
joint d’étanchéité.
3. Interrupteurs Câblés à Lusine Sassurer de la bonne disposition des branchements ainsi que de la position des fils sur les bornes.
LA TÊTE DE COMMANDE
On peut installer la tête de commande en quatre oreintations. Pour changer les positions, désserrer les vis, pivoter la tête de commande, resserrer les quatre vis. (Ill. 1)
Ill. 1
LEVIERS (Type à levier seulement)
Les leviers sont ajustables dans un champ de mouvement de 360°. Déserrer la cheville de sécurité, bouger le levier jusqu’ à la position requise er serrer l’écrou, (voir Ill.2).
Ill. 2
Cheville de Sècurite
CHANGEMENT DE LA DIRECTION DE FONCTIONNEMENT
La plupart des interrupteurs de position sont réglables pour élle­cluer un fonctionnement on sons horologique sons anti-horologi­que ou dans les deux directions.
Les interrupteurs maintenus et à position neutre ne sont pas changeables ils fonctionnement dans deux directions seule­ment.
À NOTER: Toujours régler ces interrupteurs dans les conditions environnantes propres pour éviter l’entrée des saletés dans le mécanisme.
1. Desserrez les quatre vis de montage de la tête et enle- vez la tête d’opération du corps de linterrupteur.
2. Localisez le plongeur en-dessous de la tête dopération.
3. Tirez le plongeur vers l extérieur et tournez le avec un
pas de 90° afin dobtenir le mode désiré. Voir reglages respectif en Ill. 3.
4. Faites sûr le plongeur est repoussé dans l intérieur et que le joint est proprement placé avant la tête dopéra­tion est réattaché au corps de linterrupteur.
5. Reserrez (approximativement 1,36 Nm – 2.03 nm) les vis de montage de la tête.
6. Vérifiez le mode daction désiré.
Ill. 3
Ecrou
Position du
plongeur
Fonctionnement
desiré
Antihorologique Horologique et Horologique
Uniquement Antihorologique Uniquement
PIÉCES DE RECHANGE OU LUBRIFIANT ADDITIONNEL
Votre commande doit inclure le numéra de catalogue et la lettre de série.
40146–752–02(A)
July 1993
Imprimé aux. È.U.
Loading...