Allen-Bradley 800HL-FPX Installation Manual

Page 1
Technical Data

Hazardous Location Push Button Specifications

Bulletin Numbers
Topic Page Topic Page
800H Type 7&9 Hazardous Location Push Buttons 800G Hazardous Location Push Buttons
Specifications (Bul. 800H) 5 Specifications (Bul. 800G) 37
Push Pull Units (Bul. 800H) 13 Configurable Ganged Assembled Stations (Bul. 800G) 43
Selector Switch Units (Bul. 800H) 17 Push Button Units (Bul. 800G) 44
Pilot Light Devices (Bul. 800H) 21 Selector Switch Units (Bul. 800G) 46
Specialty Units (Bul. 800H) 23 Pilot Lights (Bul. 800G) 47
Station Design Guidelines (Bul. 800H) 25 Enclosures (Bul. 800G) 48
Approximate Dimensions & Shipping Weights (Bul. 800H) 27 Back-of-Panel Components (Bul. 800G) 49
800R 30.5 mm Push Button Stations Hermetically Sealed for Division 2 Approximate Dimensions (Bul. 800G) 51
Specifications (Bul. 800R) 33
Approximate Dimensions & Shipping Weights (Bul. 800R) 36
800G, 800H, and 800R

Summary of Changes

Topic Page
Updated cable glands in Tabl e 13
Updated Complete Ass embled Stations (Bul. 800G) cat. no. explanation tables 42
Updated Configurable Ganged Assembled Stations (Bul. 800G) cat. no. explanation tables 43
Updated Plastic (Base mount only) cat. no. explanation tables 48
37
Page 2
Hazardous Location Push Button Specifications

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website,
http://www.rockwellautomation.com/global/certification/overview.page
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Allen-Bradley, PenTUFF, Rockwell Automation, Rockwell Software, and LISTEN. THIN K. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
2 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 3

Product Description (Bul. 800H)

Type 3 Flange Seal Sealing Wells Sealed Switch Contact Blocks
Application
When properly mounted in a Type 7 & 9 enclosure, Bulletin 800H Type 7 & 9 operators are designed to meet the requirements of the National Electrical Code for Class I, Divisions 1 & 2, Groups B, C & D Hazardous Gas; Class II, Divisions 1 & 2, Groups E, F and G Hazardous Dust; and, Class III Hazardous Fiber Locations. In addition, the single-gang shallow base, Cat. No. 800H-IHZX7, meets Class I, Group B requirements. This Type 7 & 9 equipment is listed by Underwriters Laboratories, Inc.
Per National Electrical Code: Zone 1: In Class I, Zone 1 locations, all wiring methods permitted for Class I, Division 1 locations and Class I, Zone 0 or Zone 1
locations, including requirements for sealing, shall be permitted.
Zone 2: In Class I, Zone 2 locations, all wiring methods permitted for Class I, Division 2, Class I, Division 1 or Division 2, and ClassI, Zone 0 or Zone 1 locations, including requirements for sealing, shall be permitted.
Operator Construction
The Allen-Bradley line of hazardous location devices features copper-free (less than 0.4 of 1% copper content) die cast aluminum bushings and mounting rings, Type #316 stainless steel operating shafts and an O-ring seal for added corrosion resistance. These components mount into a threaded hole (3/4 in.-14 NPSM) in a suitable enclosure.
Bulletin 800H Type 7 & 9 components are available in two basic formats: standard barrel (Bulletin 800H) and long barrel (Bulletin800HL). Standard barrel devices are suitable for mounting in panel thickness up to 1 in. thick. Long barrel devices are suitable for mounting in panel thickness greater than 1 in. and no thicker than 2-1/2 in. Both style operators offer a unique locking bracket, which provides an anti-turn feature to prevent the operator from coming loose. The mounting rings in front of the panel are knurled to provide a second way to tighten each unit into the panel.
Outdoor Use
Bulletin 800H Type 7 & 9 stations and enclosures are not configured for outdoor use as standard. A Type 3 rating is available, while maintaining Type 7 & 9 integrity of the enclosure, by the addition of a Type 3 sealing flange and an approved drain. The sealing flange that is shown in Figure 1 using sealing nuts to seal the push button operators along with the sealing flange. Sealing nuts are available as accessories (see our website
.)
can be purchased as an option or as an accessory. A Type 4 rating can be achieved by
Elimination of Conduit Seal Off Requirement
Bulletin 800H Type 7 & 9 units can be installed with various sealing options. By using a flanged sealing well, these stations can be installed without a conduit seal off in most applications (subject to applicable codes and laws). The sealing wells that are shown in Figure 1 outdoor applications.
Sealed switch contact blocks are another way to help eliminate the need for conduit seal fittings in most applications (subject to applicable codes and laws). Sealed switch contact blocks can be purchased as an option on assembled stations by changing the Bulletin No. from 800H to 800R. Sealed switch contact blocks can be ordered as an accessory (see our website button station with a sealed switch contact block is shown in Figure 1
Figure 1 - Sealing Options
can be purchased as an option or as an accessory. Sealing wells have an integral Type 3 flange seal for
). A push
.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 3
Page 4
Product Description (Bul. 800H)
Notes:
4 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 5

Specifications (Bul. 800H)

ATTENTION: Performance data that is given in this publication is provided only as a guide for you to determine suitability and does not constitute a performance warranty of any kind. Such data may represent the results of accelerated testing at elevated stress levels, and you are responsible for correlating the data to actual application requirements. ALL WARRANTIES AS TO ACTUAL PERFORMANCE, WHETHER EXPRESS OR IMPLIED, ARE EXPRESSLY DISCLAIMED.
Table 1 - Electrical Ratings
Contact Ratings See the contact ratings on page 6.
Dielectric Strength 2200V for 1 minute, 1300V for 1 minute (Logic Reed)
Electrical Design Lifecycles 1 000 000 at max. rated load, 200 000 at max. rated load (Logic Reed)
Table 2 - Mechanical Ratings
Vibration 10…2000 Hz 1.52 mm displacement (peak-to-peak) max/10 G max (except Logic Reed)
Shock 1/2 cycle sine-wave for 11 ms ≥ 25 G (contact fragility) and no damage at 100 G
Degree of Protection Type 7 & 9 Explosion Proof (Type 3 and Type 4 ratings available with accessories)
Mechanical Design Lifecycles
Push Buttons 250 000 min
Potentiometers 100 000 min
All other devices 200 000 min
Contact O peration Shallow and mini contact blocks: slow double make and break
Logic Reed and sealed switch contact blocks: snap-action
Wire Guage/Terminal Screw Torque # 18…12 AWG/6…8 lb•in
Typical Operating Forces
Operators without contact blocks: Flush, extended, standard mushroom, jumbo mushroom: 2.9 lb max
Jumbo and extended aluminum mushroom head: 3.95 lb max Maintained selector switch: 4.0 in•lb max
Spring-return Selector Switches 5 in•lb to stop, 0.2 in•lb to return
Illuminated Push Buttons and Push-to-test Pilot Lights
2-Position Push-Pull 9 lb max push or pull
3-Position Push-Pull 12 lb max push to in position or pull to center position
Contact Blocks 800T-XA: 1 lb
5.6 lb max
(15 lb max pull to out position)
Logi c Reed : 1 lb max Sealed Switch: 3 lb max at 0.205 in. plunger travel Stackable Sealed Switch: 1 lb max
Table 3 - Environmental
Temperature Range
Humidity 50% at 40 °C (104 °F)
Operating temperatures below freezing are based on the absence of freezing moisture and liquids.
Operating –20…+55 °C (–4…+13 °F)
Storage –40…+85 °C (–40…+185 °F)
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 5
Page 6
Specifications (Bul. 800H)
Standard Contact Ratings
Maximum thermal continuous current Ith 10 A AC/2.5 A DC. Bulletin 800H Type 7 & 9 units with Cat. No. 800T-XA contacts have ratings as follows:
Table 4 - Standard Contact Ratings
Max. Operational
Volt s U
e
AC 600 AC-15 A600
DC 600 DC-13 Q600
For applications below 24V and 24 mA, PenTUFF™, Logic Reed, or stackable sealed switch contacts are recommended.
Utilization Category Rated Operational Currents
IEC NEMA Volts U
Sealed Switch Contact Ratings
Maximum continuous current Ith 5 A.
Table 5 - Sealed Switch Contact Ratings
Max. Operational
Volt s U
e
AC 600 AC-15 B600
DC 300 DC-13 P300
Utilization Category Rated Operational Currents
IEC NEMA Volts U
e
120…600 7200VA 720VA
72…120 60 A 720VA
24…28 60 A 10 A
28…600 69VA
24…28 2.5 A
e
120…600 3600VA 360VA
0…120 30 A 3 A
24…300 138VA
0…28 5.0 A
Make Break
Make Break
Stackable Sealed Switch Contact Ratings
Maximum continuous current Ith 3 A. Bulletin 800T units have control circuit ratings with sealed switch contact blocks as follows:
Table 6 - Stackable Sealed Switch Contact Ratings
Max. Operational
Volt s U
e
AC 300 AC-15 C300
DC 150 DC-13 Q150
6 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Utilization Category Rated Operational Currents
IEC NEMA Volts U
120…300 1800VA 180VA
0…120 15 A 1.5 A
24…150 69VA
0…24 2.5 A
e
Make Break
Page 7
Logic Reed Contact Ratings
Maximum: 150V AC, 0.15 A, 8VA and 30V DC, 0.06 A, 1.8VA.
Should only be used with resistive loads.
PenTUFF (Low Voltage) Contact Ratings
Minimum DC: 5V, 1 mA Maximum thermal continuous current I Bulletin 800H units with Cat. No. 800T-XAV contacts have ratings as follows:
Table 7 - PenTUFF (Low Voltage) Contact Ratings
2.5 A AC/1.0 A DC.
th
Specifications (Bul. 800H)
Max. Operational
Volt s U
e
AC 300 AC-15 C300
DC 150 DC-13 R150
Utilization Category Rated Operational Currents
IEC NEMA Volts U
Standards Compliance
UL508, UL698, UL1203, UL1604, CSA C22.2 No. 14, CSA C22.2 No. 25, CSA C22.2 No. 30
Certifications
Enclosures:
UL Listed (File No. E71673 Guide No. NNNY) CSA (File No. LR11924)
Devices:
UL Listed (File No. E10314 Guide No. NOIV) CSA (File No. LR11924)
e
120…300 1800VA 180VA
0…120 15 A 1.5 A
24…150 28VA
0…24 1.0 A
Make Break
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 7
Page 8
Specifications (Bul. 800H)
Notes:
8 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 9

Momentary Contact Push Buttons Units (Bul. 800H)

Flush Head Uni t
Cat. No. 800H-AP1A
Extended Head Unit
Cat. No. 800H-BP6B
Mushroom Head Unit
Cat. No. 800H-DP6A
Non-Illuminated
800 H AP 1 A
abcde
a
Barrel Type
Code Description
H Standard barrel
HL Long barrel
b
Operator Type
Code Description
AP Flush head
BP Ex tended head
DP Mushroom head
DPX Mushroom head (less color cap)
c
Color Cap
Code Description
Blank Used only when operator type
Code DPX (Table b) is ordered
1 Green
2Black
3Orange
4Gray
6Red
7Blue
9Yellow
d
Special Mushroom Head
Code Description
Blank No special head
J Jumbo mushroom head — plastic
L Jumbo mushroom head — metal
Special mushroom head options only apply to mushroom head
operator type code DP (Table b).
e
Contact Blocks
Standard
Code Description
Blank No contacts
D1 1 N.O.
D2 1 N.C.
D5 1 N.O. (Mini)
D6 1 N.C. (Mini)
A2 2 N.O.
A4 2 N.C.
A 1 N.O. - 1 N.C.
B 2 N.O. - 2 N.C.
H 3 N.O. - 3 N.C.
C 4 N.O. - 4 N.C.
PenTUFF™ (Low Voltage)
Code Description
D1V 1 N.O.
D2V 1 N.C.
AV 1 N.O. - 1 N.C.
BV 2 N.O. - 2 N.C.
HV 3 N.O. - 3 N.C.
CV 4 N.O. - 4 N.C.
For sealed switch and Logic Reed contact blocks, consult your
local Rockwell Automation sales office or Allen-Bradley distributor.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 9
Page 10
Momentary Contact Push Buttons Units (Bul. 800H)
Dual Momentary Contact Push Button Units
800 H DP H 16 AAXX 64
abcd e f
a
d
Dual Push Button Unit
Cat. No. 800H-DPH16AXX64
f
Barrel Type
Code Description
H Standard barrel
HL Long barrel
b
Operator Type
Code Description
DP Dual push button
c
Mounting
Code Description
H Horizontal
B Vertical
Color of Button
Code Description
16 Left green flush/right red extended
22 Left black flush/right black flush
e
Contact Blocks
Code Contact Arrangement
Left button (horizontal)
Top but ton
(vertical)
AAXX 1 N.O. - 1 N.C. 1 N.O. - 1 N.C.
AAAA 2 N.O. - 2 N.C. 2 N.O. - 2 N.C.
For sealed switch and Logic Reed contact blocks, consult your
local Rockwell Automation sales office or Allen-Bradley distributor.
Right button
(horizontal)
Bottom button
(vertical)
Marking
Code Description
Left button
(horizontal)
Top but ton
(vertical)
Blank No mark specified No mark specified
64 START STOP
50 ON OFF
51 FORWARD REVERSE
57 OPEN CLOSE
66 UP DOWN
99
Marking specified Marking specified
To order with special marking, please specify; seven characters
maximum per button, single line only.
Right button
(horizontal)
Bottom button
(vertical)
10 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 11
Illuminated
800 H PPB H 16 M
abcdef
Momentary Contact Push Buttons Units (Bul. 800H)
Extended Head with Guard
Cat. No. 800H-PPB16M
a
Barrel Type
Code Description
H Standard barrel
HL Long barrel
b
Power Module Type
Code Description
PPB Transformer (or dual input)
QPB Full voltage/Universal
c
Illumination Options
Code Description
Blank Incandescent
HLED
Dual Input
D Diode type, incandescent
T Transformer — relay type, incandescent
TH Transformer —relay type, LED
Diode type dual input provides circuit isolation via opposing
diodes. Not recommended for use with solid-state outputs and neon indicators.
d
Volt age
Code Description
Tra nsf orm er
16 120V AC 50/60 Hz
26 240V AC 50/60 Hz
46 480V AC 50/60 Hz
56 600V AC 50/60 Hz
Full Voltage — Incandescent
24 24V AC/DC
10 120V AC/DC
20 240V AC/DC
Universal — LED
2 12…130V AC/DC
Dual Input
16 120V AC
24 24V AC/DC
Dual input diode only.
e
Lens Color
Code Description
Blank No lens, with standard contacts 1 N.O. - 1 N.C.
X No lens provided with any contacts ordered other
than standard 1 N.O. - 1 N.C.
M Multi-color
Multi-color insert packet includes amber, blue, green, red,
and white.
f
Contact Blocks
Code Description
Standard
Blank 1 N.O. - 1 N.C.
X No contacts
D1 1 N.O.
D2 1 N.C.
A2 2 N.O.
A4 2 N.C.
PenTUFF (Low Volt age)
D1V 1 N.O.
D2V 1 N.C.
AV 1 N.O. - 1 N.C.
For sealed switch and Logic Reed contact blocks, consult your
local Rockwell Automation sales office or Allen-Bradley distributor.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 11
Page 12
Momentary Contact Push Buttons Units (Bul. 800H)
Notes:
12 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 13

Push Pull Units (Bul. 800H)

2-Position Push-Pull
Cat. No. 800H-FPX6A5
Non-illuminated
2-position
800 H FPX 1 A1
abcde
a
Barrel Type
Code Description
H Standard barrel
HL Long barrel
b
Operator Type
Code Description
FPX Push-pull unit
c
Head Type
Code Description
Blank Mushroom head
J Jumbo mushroom head
Normally closed late break contac t. When button is pushed from
the OUT to the IN position, the mechanical detent action of the operator occurs before electrical contacts change state. When the button is pulled from the IN to the OUT position, the electrical contacts change state before the mechanical detent occurs.
d
Color Cap
Code Description
Blank No cap
1 Green
2Black
4Gray (silver)
6Red
7Blue
9 Yellow (gold)
e
Contact Blocks
Operator Position
Code
Out In
Standard
Blank No contacts
A1
A5
D1 O X 1 N.O.
D4 X O 1 N.C.L.B.
D1V O X 1 N.O.
AV
O X
X X
PenTUFF ™ (Low Voltage)
O X
Note: X = Closed/O = Open
X O
O O
X O
Description
1 N.O. - 1 N.C.L.B.
2 N.C.L.B.
1 N.O. - 1 N.C.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 13
Page 14
Push Pull Units (Bul. 800H)
3-Position Push-Pull
Cat. No. 800H-FPXM6A7
3-position
800 H FPX M 1 A7
abcdef
a
Barrel Type
Code Description
H Standard barrel
HL Long barrel
b
Operator Type
Code Description
FPX Push-pull unit
c
Head Type
Code Description
Blank Mushroom head
J Jumbo mushroom head
Not valid with color cap option code Blank (Table e)
d
Operator Function
Operator Position
Code
Out Center In
M Momentary Maintained Mai ntained
N Momentary Maintained Momentar y
e
Color Cap
Code Description
Blank No cap
1 Green
2Black
4Gray (silver)
6Red
7Blue
9 Yellow (gold)
f
Contact Blocks
Standard
Operator Position
Code
Out Center In
Blank No contacts
AOXO
A1 O
A7
B6
AV
O
O
X
X
X
O
X
X
X
O
X
X
PenTUFF (Low Voltage)
O
O
X
O
Note: X = Closed/O = Open
X O
X O
O O
O O
X O
Description
1 N.O. - 1 N.C.
1 N.O. -
1 N.C.L.B.
1 N.C. -
1 N.C.L.B.
2 N.C. -
2 N.C.L.B.
1 N.O. - 1 N.C.
14 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 15
Illuminated
2- and 3-position
800 H FPX PH 16 M A1
abcdef g
Push Pull Units (Bul. 800H)
a
Barrel Type
Code Description
HStandard barrel
HL Long barrel
b
Operator Type
Code Description
FPX Push-pull unit
c
Operator Function
2-Position
Code Description
Blank Push-pull
3-Position
Operator Position
Code
Out Center In
MMom.Main.Main.
NMom.Main.Mom.
Note Mom. = Momentary
Main. = Maintained
Code Description
P Incandescent
PH LED
Q Incandescent
QH Universal LED
D Dual input — diode
DT Dual input — transformer relay
DTH Dual input transformer — relay
Diode type dual input provides circuit
isolation via opposing diodes. Not recommended for use with solid-state outputs and neon indicators.
d
Illumination Options
Transformer
Full Voltage
Dual Input
LED
e
Volt age
Code Description
Transformer
16 120V AC 50/60 Hz
26 240V AC 50/60 Hz
46 480V AC 50/60 Hz
56 600V AC 50/60 Hz
Full Voltage — Incandescent
24 24V AC/DC
10 120V AC/DC
20 240V AC/DC
Universal — LED
2 12…130V AC/DC
Universal — LED
16 120V AC 24 24V AC/DC
Dual input diode only.
Table 1 - Target Selection
2-Position Contact
Description
g
Code
A, AV, R
A1
A2
A5
D1, D1V, D1R O X N.O.
D4 X ON.C.L.B.————
O X
O X
O X
X O
— —
— —
X O
X O
O X
X O
N.O. N.C.
N.O.
N.C.L.B.
N.O. N.O.
N.C.L.B N.C.L.B.
N.C.
N.C.L.B.
O X
O X
— —
— —
X X
O O
O X
— —
— —
O X
3-Position
— —
— —
CodeOut In Out Center In
X O
X O
O O
A, AV, AR
f
Color Cap
Code Description
Blank No lens with no contacts
X No lens with contacts M Multi-color
Multi-color insert packet includes amber,
blue, green, red, and white.
g
Contact Blocks
Code Description
Standard
Blank No contacts
D1 1 N.O. D4 1 N.C.L.B.
A 1 N.O. - 1 N.C.
A1 1 N.O. - 1 N.C.L.B.
A2 2 N.O.
A5 2 N.C.L.B. A7 1 N.C. - 1 N.C.L.B.
PenTUFF Low Voltag e
D1V 1 N.O.
D2V 1 N.C.
AV 1 N.O. - 1 N.C.
Logic Reed
D1R 1 N.O.
D2R 1 N.C.
AR 1 N.O. - 1 N.C.
A2R 2 N.O.
g
A1
A7
A4R 2 N.C.
Normally closed late break contact. When
button is pushed from the OUT to the IN position, the mechanical detent action of the operator occurs before electrical contacts change state. When the button is pulled from the IN to the OUT position, the electrical contacts cha nge state before the mechanical detent occurs.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 15
Page 16
Push Pull Units (Bul. 800H)
Notes:
16 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 17
Non-illuminated
Standard Knob Operator
Cat. No. 800H-HP2KB6AXXX
Knob Lever Operator
Cat. No. 800H-HP17KB6AXXX
Metal Wing Lever Operator
Cat. No. 800H-HP11KBAXXX
2-position

Selector Switch Units (Bul. 800H)

800 H HP A 2 KB6 AXXX
abcde f
800 H HP 31 KB6 AXXX
abc1d
a
Barrel Type
Code Description
H Standard barrel
HL Long barrel
b
Number of Positions
Code Description
HP 2-position
c
Knob Insert Colors
Code Description
Blank White
X Packet of colored inserts
Metal Wing Lever Colors
ARed
Blank Gray
Each standard and knob lever operator is factory-assembled
with a white insert. Other colors are available, factory­assembled, if ordered in quantities of 10 or more.
One insert of each color (blue, green, orange, red, and yellow).
c
1
Key Removal Position
Code Description
Maintained
31 Key removal — left 32 Key removal — right 33 Key removal — both
Spring Return from Left
42 Key removal — right
Spring Return from Right
48 Key removal — left
1
d
Operator Type and Function
Code Description
Standard Knob
2Maintained 4 Spring return from left
5 Spring return from right
Knob Lever
17 Maintained 18 Spring return from left
19 Spring return from right
Metal Wing Lever
11 Maintained 15 Spring return from left
16 Spring return from right
Target tables are reversed.
d
1
Optional Keys
Code D Series Key No. Code T Series Key No.
Blank D018 (std. key) 15 T112
03 D020 16 T115
04 D025 17 T324
05 D335 18 T382
06 D429 19 T404
07 D461 20 T171
08 D111 21 T484
09 D587 22 T547
10 D682 23 T569
11 D713 24 T692
12 D900 25 T752
13 D992 26 T178
14 D118
ef
(Knob/Wing Lever)
(Cylinder Loc k)
e
Cam Option
Code Description
KB6 Cam for maintained operators
KL8 Cam for spring return operators
f
Contact Blocks
2-position
Code
Blank No contacts
DXXX 1 N.O. O X
EXXX 1 N.C. X O
MXXX 2 N.O.
NXXX 2 N.C.
AXXX 1 N.O. - 1 N.C.
AAXX 2 N.O. - 2 N.C.
HXXX 1 N.O. O X
UXXX 1 N.C. X O
FXXX 1 N.O. - 1 N.C.
FFXX 2 N.O. - 2 N.C.
Contact
Configuration
Standard
O O
X X
O
X
O
X
O
X
PenTUFF ™ (Low Voltage)
O
X
O
X
O
X
Note: X = Closed/O = Open
X X
O O
X O
X O X O
X O
X O X
O
Target tables are reversed.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 17
Page 18
Selector Switch Units (Bul. 800H)
Standard Knob Operator
Cat. No. 800H-JP2KB7AXXX
Knob Lever Operator
Cat. No. 800H-JP17KB7AXXX
Metal Wing Lever Operator
Cat. No. 800H-JP11KB7AXXX
3-position
800 H JP 2 KB7 AAXX
abcde f
800 H JP 41 KB7 AAXX
abc1d
a
Barrel Type
Code Description
HStandard barrel
HL Long barrel
b
Number of Positions
Code Description
JP 3-position
c
Knob Insert Colors
Code Description
Blank White knob insert or
cylinder lock operator
X Packet of colored inserts
Metal Wing Lever Colors
ARed
Blank Gray
Each standard and knob lever operator is
factory-assembled with a white insert. Other colors are available, factory­assembled, if ordered in quantities of 10 or more.
One insert of each color (blue, green,
orange, red, and yellow).
Table 1 - Cam and Contact Block Functionality Table
Code Description
41 Left 42 Center 43 Right 44 All 45 Left and center 46 Right and left 47 Right and center
Spring Return from Left
50 Center 52 Right 51 Right and center
Spring Return from Right
69 Left 38 Center 73 Left and center
Spring Return from Both
631 Center
c
1
Cylinder Lock Operator
Locking Position
Maintained Position
1
ef
d
Operator Type and Function
Code Description
Standard Knob
2 Maintained 4Spring return from left 5 Spring return from right
91 Spring return from both
Knob Lever
17 Maintained 18 Spring return from left 19 Spring return from right 20 Spring return from both
Metal Wing Lever
11 Maintained 15 Spring return from left 16 Spring return from right
141 Spring return from both
Wing levers are not suitable with KE7 cam
).
code (Ta bl e 1
d
1
Operator Type and Function
Code Key Number
Blank D018 (standard key)
Note: See page 17
for additional key codes.
(Knob/Wing Lever)
(Cylinder Loc k)
e
Cam Option
Code Description
KB7 Standard cam KB7 KA1 Cam KA1 KA7 Cam KA7
Note: For more cam descriptions, see Tabl e 1
f
Contact Block Options
Code Description
Blank AXXX
AAXX
AAAA
No contacts
Two contact targets for a given cam as
shown in the W (white side) column
of Tab l e 1
Two contact targets for a given cam as
shown in the W (white side) column
and 2 contact targets for the
of Tabl e 1
same cam as shown in the B (black
side) column of Tab l e 1. (One Cat. No.
800T-XA contact block per side. Two
contact blocks total.)
Four contact targets for a given cam as
shown in the W (white side) column
and 4 contact targets for the
of Tabl e 1
same cam as shown in the B (black side) column of Tab l e 1 800T-XA contact blocks per side. Four
contact blocks total.)
.
.
. (Two Cat. No.
Contact Block
Suffix Code
Note: X = Closed, O = Open
18 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Contact
Block
Side
White
Black
White
Black
Cam Codes
KB7
Circuits
A XOOXOOOOXOOXXOOOOXXOOXOXXOXXOXXOXOOXXOOXOO B OOXOXOOXOOXOOXOOXOOXXOXOOXOOXOOXOXOOOOXOXO A XOOXOOOOXOOXXOOXOOOOXOOXXOOOOXXOOOOXXOOOOX B OOXOXOOXOXOOOOXOXOXXOOXOOXOXXOOXXXXOOXXXXO A XOOXOOOOXOOXXOOOOXXOOXOXXOXXOXXOXOOXXOOXO O B OOXOXOOXOOXOOXOOXOOXXOXOOXOOXOOXOXOOOOXOXO A XOOXOOOOXOOXXOOXOOOOXOOXXO OOOX XOOOOXXOOO OX B OOXOXOOXOXOOOOXOXOXXOOXOOX OXXOOXXXXOOXXXXO
KA1 KA7 KC1 KC7 KD7 KE7 KQ1 KQ7 KR1 KR7 KT1 KT7 KU7
(Std.)
Page 19
4-position
Selector Switch Units (Bul. 800H)
800 H NP 2 KF4 AAXX
abcde f
800 H NP 31 KF4 AAXX
abc1d
a
Barrel Type
Code Description
HStandard barrel
HL Long barrel
b
Number of Positions
Code Description
NP 4-position
c
Knob Insert Colors
Code Description
Blank White
X Packet of colored inserts
Metal Wing Lever Colors
ARed
Blank Gray
Each standard and knob lever operator is
factory-assembled with a white insert. Other colors are available, factory­assembled, if ordered in quantities of 10 or more.
One insert of each color (blue, green,
orange, red, and yellow).
Table 1 - Selector Switch Cam Targets
Key Removal Position and
Code Description
31 Key removal position 1 32 Key removal position 2 33 Key removal position 3 34 Key removal position 4 61 Key removal all positions
Spring Return from Position 1 to 2
132 Key removal position 2 133 Key removal position 3 134 Key removal position 4 154 Key removal positions 2, 3, and 4
Spring Return from Position 4 to 3
231 Key removal position 1 232 Key removal position 2 233 Key removal position 3 251 Key removal positions 1, 2, and 3
c
1
Operator Function
Maintained
1
ef
Operator Type and Function
Code Description
Standard Knob
2 Maintained 3 Spring return position 1 to 2 9 Spring return from position 4 to 3
Knob Lever
17 Maintained 29 Spring return from position 1 to 2 30 Spring return from position 4 to 3
Metal Wing Lever
11 Maintained 13 Spring return from position 1 to 2 14 Spring return from position 4 to 3
Optional D-Series Keys
Code Description
Blank D018 (standard key)
Devices are supplied with two keys.
Replacement part number for standard D018 key is X-181170.
Cam Option
Code Description
KF4 F cam (standard) KG4 G cam KK4 K cam
KM4 M cam
KP4 P cam KH4 Overlapping cam
(Knob/Wing Lever)
(Cylinder Loc k)
d
Contact Block Options
Code Description
Blank AAXX
AAAA
PenTUFF (Low Voltage)
d
1
FFXX
FFFF
e
f
No contacts
Two contact targets for a given cam as
shown in the W (white side) column
and two contact targets for
of Tab le 1
the same cam as shown in the B
(black side) column of Tabl e 1 . (One
Cat. No. 800T-XA contact block per
side. Two contact blocks total)
Four contact targets for a given cam as
shown in the W (white side) column
and four contact targets for
of Tab l e 1
the same cam as shown in the B
(black side) column of Ta b l e 1
Cat. No. 800T-XA contact blocks per
side. Four contact blocks total.)
Two contact targets for a given cam as
shown in the W (white side) column
and two contact targets for
of Tab le 1
the same cam as shown in the B
(black side) column of Tabl e 1 . (One
Cat. No. 800T-XAV contact block per
side. Two contact blocks total)
Four contact targets for a given cam as
shown in the W (white side) column
and four contact targets for
of Tab l e 1
the same cam as shown in the B
(black side) column of Ta b l e 1
Cat. No. 800T-XAV contact blocks per
side. Four contact blocks total.)
. (Two
. (Two
AAAA
FFFF
Contact
Block
Side
White
Black
White
Black
KF4 KG4 KK4 KM4 KP4 KN4
Circuits
AXOOOX XOOOOXXXOOOOOOXOXOO BOXOOOOXOXXOOOXXOOXOOOOOX AOOOXXOOOXOOXOOOXOOXXOOXO
BOOXOOOOXOXXOOXOOXOOOXOOO
AXOOOX XOOOOXXXOOOOOOXOXOO BOXOOOOXOXXOOOXXOOXOOOOOX AOOOXXOOOXOOXOOOXOOXXOOXO BOOXOOOOXOXXOOXOOXOOOXOOO
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 19
Contact B lock
Suffix Code
AAAA
FFFF
Not available with wing lever operator.Overlapping cam.
Note: X = Closed, O = Open For additional targets and overlapping cams, see Publication 800T-2.8
Cam Codes
.
Page 20
Selector Switch Units (Bul. 800H)
Notes:
20 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 21

Pilot Light Devices (Bul. 800H)

Tra ns fo rm er Ty pe Pi lo t L ig ht
Cat. No. 800H-PP16M
Push-to-test Pilot Light
Cat. No. 800H-PPT16M
Pigtail Pilot Light
Cat. No. 800H-LP24M
NORMAL
TEST
COM
TEST
NORMAL
TEST
800 H PP T 16 M
abcde f
a
Barrel Type
Code Description
H Standard barrel
HL Long barrel
b
Power Module Type
Code Description
PP Transformer (or dual input)
QP Full voltage/Universal LP Pigtail — full voltage
LPK Pigtail — full voltage (for dual push buttons)
Lamp test option is not available with pigtail.
Code Description
Blank No test option
TPush-to-test D Dual input — diode
DT Dual input — transformer relay
Only available with power module type code PP (Table b).
Code Description
Blank Incandescent
HLED
LED illumination option is not available with diode-type dual-
input lamp test options.
Typical Pilot Light Wiring Diagrams
See applicable codes and laws.
Push-to-test Pilot Light Device
Dual Input Diode Pilot Device
c
Lamp Test Options
d
Illumination Option
e
Voltage
Code Description
Tra nsf orm er
16 120V AC, 50/60 Hz
26 240V AC, 50/60 Hz
46 480V AC, 50/60 Hz
56 600V AC, 50/60 Hz
Full Voltage — Incandescent
24 24V AC/DC
10 120V AC/DC
20 240V AC/DC
Universal — LED
2 12…130V AC/DC
Dual Input
16 120V AC 24 24V AC/DC
Pigtail
24 24V AC/DC
10 120V AC/DC
20 240V AC/DC
Dual input diode only.
Dual Input Pilot Light TypicalApplication
f
Lens Color
Code Description
Blank No lens with no contacts
M Multi-color
Dual Input Pilot Light Transformer Type Device
NORMAL
TEST
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 21
Multi-color insert packet includes amber, blue, green, red,
and white.
Page 22
Pilot Light Devices (Bul. 800H)
Notes:
22 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 23
Potentiometer Units ➊➋
800 H UP 13

Specialty Units (Bul. 800H)

ab
a
Barrel Type
Code Description
H Standard barrel
HL Long barrel
Potentiometer Units
Cat. No. 800H-UP24
b
Resistance
Code Description
13 1 kΩ
19 2.5 kΩ
24 5 kΩ
29 10 kΩ
Single-turn operation with 312° rotation.Rated for 300V AC/DC, 2W maximum.For operator only (no resistive element), order catalog
number 800H-NP37 which is for use with Type J potentiometers having a shaft length of 7/8 in. (22.2 mm) and a shaft diameter of 1/4 in. (6.3 mm).
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 23
Page 24
Specialty Units (Bul. 800H)
Notes:
24 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 25

Station Design Guidelines (Bul. 800H)

(Also see Applicable Codes and Standards)
1. Push-to-test pilot lights, illuminated push buttons, push-to-pull units, 4-position selector switches, and all operators with two contact blocks that are fastened along side one another or with a power module and contact block along side one another must be installed in a single-hole cover. Illuminated operators that use the Universal LED module must also be installed in a single-hole cover.
2. Dual push button units can only be installed in a single-hole cover or the specially designed two-hole cover (catalog number 800H-NP33), which can accommodate the dual push button and the special pigtail pilot light (catalog number 800H-LPK10R).
3. When two components are installed in one cover, contact blocks are restricted to one side of the operator. Contact blocks of each operator must face each other.
4. One level of contact blocks is maximum in a shallow base or deep base when used with a sealing well. Contact blocks, except sealed switch type, can be mounted two deep in other bases.
5. If sealed switch contact blocks or a sealing well are used, a deep enclosure is required.
6. Push buttons/pilot lights:
a. START push buttons should be green or black flush, installed to the left or above STOP push buttons. b. EMERGENCY STOP push buttons should be a red mushroom. c. STOP push buttons should be red extended, installed to the right or below START push button. d. STOP push buttons should be installed in the last position (bottom or right) of each unit when required. e. Pilot lights should be installed in the first position (top or left side) of each unit when required.
Design Guideline #1
Push-to-test pilot lights, illuminated push buttons, push-pull units, 4-position selector switches, all operators with two contact blocks that are fastened along side one another or with a power module and contact block along side one another must be installed in a single-hole cover. Illuminated operators that use the Universal LED module must also be installed in a single-hole cover.
Design Guideline #2
Dual push button units can only be installed in a single­hole cover or the specially designed two-hole cover (catalog number 800HNP33), which can accommodate the dual push button and the special pigtail pilot light (catalog number 800H-LPK10R).
Design Guideline #3
When two components are installed in one cover, contact blocks are restricted to one side of the operator. Contact blocks of each operator must face each other.
Design Guideline #4
One level of contact blocks is maximum in a shallow base or deep base when used with a sealing well. Contact blocks, except sealed switch type, can be mounted two deep in other bases.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 25
Page 26
Station Design Guidelines (Bul. 800H)
Bases for Multi-gang Stations
Example: 7-gang base with 1-in. through-feed conduit consists of:
3-catalog number 800H-NP42B
1-catalog number 800H-NP43B
1-catalog number 800H-NP44B
1-catalog number 800H-NP45
1-catalog number 800H-NP46B
6-catalog number 800H-NP7
Plus up to four 1-in. plugs (catalog number 800H-NP11) to close unused conduit openings.
WARNING: Do not assemble more than eight enclosure gangs together, to avoid exceeding the internal volume for which the flame path of these enclosures is designed.
1-in. conduit through-feed (all gangs).
26 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 27

Approximate Dimensions & Shipping Weights (Bul. 800H)

Ø
Standard Legend Plate
(used with two-hole cover)
Jumbo Legend Plate
(used with one-hole cover)
Maximum
Standard Barrel
[devices fit panels up to 1 in. (25.4 mm)]
Long Barrel
[devices fit panels up to 2-1/2 in. (63.5 mm)]
Dimensions in inches (millimeters). D imensions are not intended to be used for manufacturing purposes.
Ø
Note: Mounting hole requirements for components — 3/4 in. - 14 NPSM. ➋
Sketch illustrates the minimum distance between center lines when mounting Bulletin 800H units with legend plates either side by side or one above the other in non Allen-Bradley enclosures. Minimum spacing without
legend plate: When units are mounted so that the contact block terminals face each other, the 2-1/4 in. (57.2 mm) dimension must be used to get proper electrical clearance. When control units are mounted so that the contact block terminals do not face each other, the 1-27/32 in. (46.8 mm) dimension can be used.
External thread major diameter: 1.034 in. max., 1.024 in. min.
Internal thread minor diameter: 0.958 in. min., 0.970 in. max.
Panel Thickness Requirements
Maximum
This dimension for push buttons only.
When mounting in a panel thicker than 2-1/8 in. (54 mm) a locking bracket is not required.
Push Buttons
Dual Head
Dim. A B C
Standard Barrel
Long B arrel
3-5/16
(84.1)
4-19/32
(116.7)
4-3/16
(106.4)
5-15/32
(138.9)
4-7/16 (112.7)
5-23/32
(145.2)
Ship. Wt.
[oz (kg)]
10-3/8
(0.30)
13
(0.37)
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 27
Page 28
Approximate Dimensions & Shipping Weights (Bul. 800H)
Ø
Ø
Ø
Ø
Mushroom Head Push Button with Extra Long Guard
Flush Head Extended Head
Ø
Standard Operator Knob Lever Operator
Wing Lever Operator Cylinder Lock Operator
Dimensions in inches (millimeters). D imensions are not intended to be used for manufacturing purposes.
Push Buttons
Ø
Standard Barrel Long Barrel
Type
A BC
[oz (kg)] A BC
Mushroom, Flush, and Extended Head 3-3/16 (81) 4-1/8 (105) 4-3/8 (111) 9-7/8 (0.28) 5 (127) 5-7/8 (149.2) 6-1/8 (155.6) 13-5/16 (0.38)
Extra Long Guard 3-3/16 (81) 4-1/8 (105) 4-3/8 (111) 10-7/8 (0.31) 5 (127) 5-7/8 (149.2) 6-1/8 (155.6) 14-5/16 (0.40)
Ship. Wt.
Ship. Wt.
[oz (kg)]
When using sealed switch contact block, this dimension is 4-1/16 in. (103 mm).When using sealed switch contact block, this dimension is 5-7/8 in. (149.2 mm).
Selector Switches
Ø
Type
A BC
Standard and Knob Lever 3-3/16 (81) 4-1/8 (105) 4-3/8 (111) 9-1/2 (0.27) 5 (127) 5-7/8 (149.2) 6-1/8 (155.6) 14-3/8 (0.41)
Wing Lever 3-3/16 (81) 4-1/8 (105) 4-3/8 (111) 10-1/2 (0.30) 5 (127) 5-7/8 (149.2) 6-1/8 (155.6) 15 (0.42)
Cylinder Lock 3-3/16 (81) 4-1/8 (105) 4-3/8 (111) 11-1/4 (0.32) 5 (127) 5-7/8 (149.2) 6-1/8 (155.6) 16 (0.45)
Standard Barrel Long Barrel
Ship. Wt.
[oz (kg)] A BC
Ship. Wt.
[oz (kg)]
When using sealed switch contact block, this dimension is 4-1/16 in. (103 mm).When using sealed switch contact block, this dimension is 5-7/8 in. (149.2 mm).
28 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 29
Approximate Dimensions & Shipping Weights (Bul. 800H)
Transformer Type Full Voltage, Dual Input, or Neon Type
Ø
Non-illuminated Illuminated
Dimensions in inches (millimeters). D imensions are not intended to be used for manufacturing purposes.
Illuminated Push Buttons or Push-to-test Pilot Lights
Description Style A B C Ship. Wt. [oz (kg)]
Standard Barrel 3-5/32 (80.2) 3-29/32 (99) 4-1/8 (105) 14 (0.40)
Tra ns for me r Typ e
Full Voltage, Dual Input, or Neon Type
When using sealed switch contact block, add 7/8 in. (22.2 mm) to the listed dimension.
Long Barrel 5-1/16 (128.6) 5-13/16 (147.6) 6-1/16 (154) 16-3/16 (0.45)
Standard Barrel 3-1/32 (77) 3-29/32 (99) 4-1/8 (105) 11-5/8 (0.33)
Long Barrel 4-15/16 (125.4) 5-13/16 (147.6) 6-1/16 (154) 13-7/16 (0.38)
Push-Pull Units
Note: Jumbo Head
Ø
Ø
Description Style A B C D Ship. Wt. [oz (kg)]
Standard Barrel 3-9/16 (90.5) 4-9/16 (115.9) 4-5/8 (117.5) 2-1/8 (54) 15-1/2 (0.44)
Illuminated Transformer Type
Illuminated Full Voltage Type
Non-illuminated Push-Pull Units
Long Barrel 4-21/32 (118.3) 5-13/32 (137) 5-21/32 (143.7) 2-1/8 (54) 17-7/16 (0.49)
Standard Barrel 3-7/16 (87.3) 4-9/16 (115.9) 4-5/8 (117.5) 1-31/32 (50) 12-13/16 (0.33)
Long Barrel 4-17/32 (115.1) 5-13/32 (137) 5-21/32 (143.7) 1-31/32 (50) 14-3/4 (0.41)
Standard Barrel 3-1/2 (88.9) 4-3/8 (111.1) 4-5/8 (117.5) 11-1/8 (0.32)
Long Barrel 4-17/32 (115.1) 5-13/32 (137) 5-21/32 (143.7) 12-5/16 (0.34)
When using sealed switch contact block, add 7/8 in. (22.2 mm) to the listed dimension.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 29
Page 30
Approximate Dimensions & Shipping Weights (Bul. 800H)
Ø
Ø
LEADS
Ø
Ø
Transformer Type Full Voltage, Pigtail Type
Full Voltage, Dual Input
or Neon Type
Ø
Ø
Dimensions in inches (millimeters). D imensions are not intended to be used for manufacturing purposes.
Pilot Lights
Description Style A Ship. Wt. [oz (kg)]
Transformer type and dual-input transformer-type pilot lights
Full voltage, neon, or dual-input diode and resistor-type pilot lights
Full-voltage pigtail-type pilot lights
Potentiometer Units
Ø
Ø
Standard Barrel 3-5/32 (80) 8-9/16 (0.24)
Long Barrel 4-9/16 (115.9) 30-1/4 (0.85)
Standard Barrel 3-1/32 (77) 5-13/16 (0.17)
Long Barrel 4-7/16 (112.7) 27-1/2 (0.77)
Standard Barrel 2-3/16 (55.5) 5-5/8 (0.16)
Long Barrel 3-43/64 (94) 8-5/16 (0.24)
Style A Ship. Wt. [oz (kg)]
Standard Barrel 3-1/8 (79.5) 5-3/8 (0.16)
Long Barrel 4-1/2 (114.3) 8 (0.23)
30 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 31
Dimensions in inches (millimeters). D imensions are not intended to be used for manufacturing purposes.
Figure 1
Shallow Base Station Lever Type
Figure 2
Shallow Base Station Component Type
1-Gang (one or two devices)
Shipping Weight 3 lb (1.36 kg)
Shipping Weight 3-1/2 lb (1.58 kg)
Figure 3
Deep Base Station Lever Type
1-Gang
Figure 4
Deep Base Component Lever Type
1-Gang (one or two devices)
Shipping Weight 4 lb (1.81 kg)
Shipping Weight 4-1/2 lb (2.04 kg)
Shallow Base Stations
Approximate Dimensions & Shipping Weights (Bul. 800H)
3/4 in.-14 NPT
Deep Base Stations
Optional Conduit Entry 3/4-14 NPT or 1-11 1/2 NPT
Ø
4 Mtg. Holes
3/4 in.-14 NPT
Ø
4 Mtg. Holes
Optional Conduit Entry 3/4-14 NPT or 1-11 1/2 NPT
Ø
2 Mtg. Holes
3/4-14 NPT Optional 1-11 1/2 NPT
3/4-14 NPT Optional 1-11 1/2 NPT
Ø
2 Mtg. Holes
When using a flange seal, an approved drain fitting must be provided (refer to National Electrical Code).
When used, add the following to the max. depth: flange seal adds 3/16 in. (4.8 mm); sealing well with integral flange seal adds 1/2 in. (12.7 mm).
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 31
Page 32
Approximate Dimensions & Shipping Weights (Bul. 800H)
Conduit Entry
Conduit Entry
Pipe Plug
Pipe Plug
Pipe Plug
Optional
Optional
Conduit Entry
Conduit Entry
Pipe Plug
Pipe Plug
Pipe Plug
Pipe Plug
Optional
Optional
Conduit Entry
Conduit Entry
Pipe Plug
Pipe Plug
Conduit Entry
Conduit Entry
Pipe Plug
Conduit Entry
Figure 3
Control Station, 2-Gang (up to four devices)
Figure 4
Control Station, 3-Gang (up to six devices)
Shipping Weight 10 lb (4.54 kg)
Shipping Weight 16 lb (7.26 kg)
Figure 5
Control Station, 2-Gang (up to four devices)
Figure 6
Control Station, 4-Gang (up to eight devices)
Shipping Weight 10 lb (4.54 kg)
Shipping Weight 20 lb (9.07 kg)
Figure 7
Control Station, 6-Gang (up to 12 devices)
Figure 8
Control Station, 8-Gang (up to 16 devices)
Shipping Weight 32 lb (14.5 kg)
Shipping Weight 40 lb (18.1 kg)
Dimensions in inches (millimeters). D imensions are not intended to be used for manufacturing purposes.
Factory-Assembled Stations
For depth dimensions, refer to Figure 3 or 4 on page 31.
Conduit Entry
Conduit Entry
32 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 33

Specifications (Bul. 800R)

ATTENTION: Performance data that is given in this publication is provided only as a guide for you to determine suitability and does not constitute a performance warranty of any kind. Such data may represent the results of accelerated testing at elevated stress levels, and you are responsible for correlating the data to actual application requirements. ALL WARRANTIES AS TO ACTUAL PERFORMANCE, WHETHER EXPRESS OR IMPLIED, ARE EXPRESSLY DISCLAIMED.
Table 8 - Electrical Ratings
Contact Ratings See the contact ratings on page 34
Dielectric Strength 2200V for 1 minute, 1300V for 1 minute (Logic Reed)
Electrical Design Lifecycles 1 000 000 at maximum rated load, 200 000 at maximum rated load (Logic Reed)
Table 9 - Mechanical Ratings
Vibration 10…2000 Hz 1.52 mm displacement (peak-to-peak) max/10 G max (except Logic Reed)
Shock 1/2 cycle sine-wave for 11 ms ≥25 G (contact fragility) and no damage at 100 G
Degree of Protection Type 4/4X/13, 4/13; Watertight/Corrosion-Resistant IEC 529 IP66/65
Mechanical Design Lifecycles
Push Buttons (Momentary, Non-Illuminated)
(Momentary, Illuminated)
(Push-Pull/Twist-to-Release)
Selector Switches (Non-Illuminated)
(Illuminated)
All other devices 200 000 min
Contact O peration Logic Reed and sealed switch contact blocks: single break magnetic
Typical Operating Forces
Operators without contact blocks: Flush, extended, standard mushroom, jumbo plastic mushroom: 2 lb max
Spring-return Selector Switches 3.6 in•lb to stop
Illuminated Push Buttons and Push-to-test Pilot Lights
3-Position Push-Pull 8 lb max push to in position or pull to center position
Push-Pull and Push-Pull/Twist 9 lb max push or pull
Contact Blocks Logic Reed
Sealed Switch Stackable Sealed Switch
1 000 0000 min 250 000 min 250 000 min
1 000 000 min 200 000 min
Maintained selector switch: 3.6 in•lb max
0.2 in•lb to return
5 lb max
(15 lb max pull to out position)
30 in•oz max twist, 6 in•oz minimum return
1 lb max 3 lb max at 0.205 in. plunger travel 1 lb max
Table 10 - Environmental
Temperature Range
Humidity 50% at 40 °C (104 °F)
Operating temperatures below freezing are based on the absence of freezing moisture and liquids. Consult your local Rockwell Automation sales office or Allen-Bradley distributor for use in lower temperature applications.
Operating -40…+55 °C (-40…+131 °F)
Storage -40…+85 °C (-40…+185 °F)
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 33
Page 34
Specifications (Bul. 800R)
Control Stations
Bulletin 800R control stations are designed for Division 2 hazardous locations. They consist of Bulletin 800H (Type 4/4X/13) or Bulletin 800T (Type 4/13) operators with sealed contact blocks. Bulletin 800R units are available as factory assembled stations or as components for field assembly.
Hazardous Locations
Since the contacts are enclosed in a hermetically sealed chamber, the contact block is suitable for use in Class I, Division 2 Groups A, B, C, and D hazardous locations and is listed by Underwriters Laboratories for this class of service. Complete stations as shown on our website Bulletin 800T and 800H sections are also suitable for Class I, Division 2 locations providing they are suitably mounted by the customer in an enclosure as required for the application and by applicable codes and laws.
Note: Allen-Bradley Logic Reed contact blocks are also listed by Underwriters Laboratories for the Division 2 hazardous locations that are listed above.
WARNING: The complete stations and individual components that are listed on our website are not suitable for use in Class I Division 1 hazardous locations. For Class I and II Division 1 hazardous locations, order Bulletin 800H Type 7 & 9 stations and
units.
can be used for Class I, Division 2 applications. The individual components that are shown in the
Sealed Switch Contact Ratings
Maximum continuous current Ith 5 A. Bulletin 800T and 800H units have control circuit ratings with sealed switch contact blocks as follows:
Table 11 - Sealed Switch Contact Ratings
Max. Operational
Volt s U
e
AC 600 AC-15 B600
DC 300 DC-13 P300
Utilization Category Rated Operational Currents
IEC NEMA Volts U
120…600 3600VA 360VA
0…120 30 A 3VA
24…300 138VA
0…24 5 A
e
Make Break
Stackable Sealed Switch Contact Ratings
Maximum continuous current Ith 2.5 A. Bulletin 800T and 800H units have control circuit ratings with sealed switch contact blocks as follows:
Table 12 - Sealed Switch Contact Ratings
Max. Operational
Volt s U
e
AC 300 AC-15 C300
DC 150 DC-13 Q150
Utilization Category Rated Operational Currents
IEC NEMA Volts U
120…300 1800VA 180VA
0…120 15 A 1.5A
24…150 69VA
0…24 2.5 A
e
Make Break
34 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 35
Logic Reed Contact Ratings
Maximum DC: 30V, 0.06 A max AC: 150V, 0.15 A
Should only be used with resistive loads.
Standards Compliance
ISA 12.12.01
CSA C22.2, No. 213
Certifications
UL Listed (File No. E10314, Guide No. NOIV)
CSA Certified (File No. LR11924)
Specifications (Bul. 800R)
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 35
Page 36

Approximate Dimensions & Shipping Weights (Bul. 800R)

Type 4/4X/13
Stainless Steel
Watertight/Oiltight/
Corrosion-Resistant Enclosure
Type 4/4X/13
Rosite Glass Polyester
Watertight/Oiltight/
Corrosion-Resistant Enclosure
Type 4/13
Cast Aluminum Enclosure
Watertight/Oiltight
Type 4/4X/13
Booted Flush and Extended
Head Push Button
Type 4/4X/13
Pilot Light
Type 4/13 and Type 4/4X/13
Bootless Flush and Extended
Head Push Button
Type 4/13
Pilot Light
Type 4/13 and Type 4/4X/13
Standard Knob Selector
Switches
Dimensions in inches (millimeters). D imensions are not intended to be used for manufacturing purposes.
Selector switch is 1-5/32 (29.4) max; pilot light is 1-7/32 (31).Selector switch is 1-3/32 (27.8) max; pilot light is 1-5/32 (29.4) max.Selector switch is 1-7/32 (30.9) max; pilot light is 1-9/32 (32.5).
Number of Units
Dimension
A 5-5/32 (135) 7 (178) 8-27/32 (225) 10-11/16 (271) 12-17/32 (318) 14-3/8 (360)
B 6-13/32 (163) 8-1/4 (210) 10-1/8 (257) 11-31/32 (304) 14-1/32 (359) 15-7/8 (403)
Pip Tap Size 3/4 1
A 4-1/2 (114) 4-1/2 (114) 6-1/4 (159) 8 (203) 12-1/8 (308) 12-1/8 (308)
B 7-1/32 (181) 7-1/32 (181) 8-23/32 (221) 10-21/32 (271) 14-7/8 (378) 14-7/8 (378)
C 5-7/8 (149) 5-7/8 (149) 7-9/16 (192) 9-1/2 (241) 13-1/2 (343) 13-1/2 (343)
Pipe Tap Size 3/4 1
A 2-3/4 (69.8) 4-1/2 (114) 6-1/4 (159) 8 (203) 12-1/8 (308)
B 4-3/16 (106) 5-7/8 (149) 7-9/16 (192) 9-1/2 (241) 13-1/2 (343)
Condui t
Opening
123456
Stainless Steel Type 4/4X/13
Glass Polyester Type 4/4X/13
Cast Aluminum Type 4/13
3/4 in.
14 N.P.T.
—1 in.
11-1/2 N.P.T.
Mounting Instructions for Panel Mounting
Min vertical spacing dimension for jumbo legend
plate is 2-15/32 (62.7).
Operator Extension in Front of Panel
36 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 37

Specifications (Bul. 800G)

ATTENTION: Performance data that is given in this publication is provided only as a guide for you to determine suitability and does not constitute a performance warranty of any kind. Such data may represent the results of accelerated testing at elevated stress levels, and you are responsible for correlating the data to actual application requirements. ALL WARRANTIES AS TO ACTUAL PERFORMANCE, WHETHER EXPRESS OR IMPLIED, ARE EXPRESSLY DISCLAIMED.
Standard Assembled Stations
Table 13 - Mechanical Ratings
Protection Type II 2G Ex edm IIC T6
AEx edm IIC T6
Ex edm IIC T6
Certification PTB 01 ATEX 1036 UL E10314 CE0044
Rated Insulation Voltage, Max 690V AC
Rated Current Dependent on components used
Degree of Protection IP66, Type 4X: -20…60 °C (-4…140 °F)
IP54: -55…60 °C (-67…140 °F)
Enclosure Material
Enclosure Thermoplastic
Seals EPDM
Cable Glands
Standard 1/2 in. NPT conduit
Custom Metal M20x1.5 for cable Ø8.5…14.5 mm (inner
sheath); 12…20 mm (outer sheath);
0.8…1.3mm (armor)
Metal M25 for cable Ø12…20 mm (inner sheath); 16…26 mm (outer sheath);
1.0…1.6 mm (armor)
3/4 in. NP T conduit
Wire/Cable Size 2.5 mm
PE Conductor Terminals 4 x 2.5 mm
Storage Temperature -55…+70 °C (-67…+158 °F)
Operational Temperature Range
2
(12 AWG) stranded max
2
(12 AWG) stranded max
-55…+60 °C (-67…+140 °F)
Assembled Stations
Bulletin 800G control stations are designed for Class I, Zone 1 and 2 and Class 1/Division 2 hazardous location applications. They consist of Bulletin 800G front-of-panel components with back-of-panel components: contact blocks or power modules. Bulletin 800G units are available as factory assembled stations or as components for component replacement. A third party must inspect and certify field assembled stations that are used in a Class I, Zone1 or Zone 2 application.
Components
Since the back-of-panel components are enclosed in a flame­proof enclosure, they are suitable for use in Class I, Zone 1
and Zone 2 Groups IIA, IIB, and IIC and Class I/Division 2, Groups A, B, C, and D hazardous locations and is listed by Underwriters Laboratories and certified by PTB for this class of service. The components have “d” and “e” protection
methods except for the cable termination. Cable termination has only “d” protection method, which is restricted by the cable and not the contacts.
WARNING: The assembled stations and individual components that are listed on our website suitable for the use in Zone 0, Class I/Division 1 and Class II/Division 1 and Division 2 applications. For Class I and II/Division 1 hazardous locations, order Bulletin 800H Type 7 & 9 stations and units. For Class II/ Division 2 hazardous locations, order Bulletin 800R stations.
are not
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 37
Page 38
Specifications (Bul. 800G)
B
/ MTTFD/LambdaD Specifications
10D
Table 14 - Non-Illuminated Components
Description Cat. No. B
Front of Panel
Push Button (Non-illuminated – Flush) 800G-F_
Momentary Mushroom Push Button 800G-M2
Double Push Button (Non-illuminated – Flush)
Key Release Mushroom Push Button 800G-MKE
Key Release Push Button 800G-K_
2-Position Selector Switch (Knob) 800G-S_2_
3-Position Selector Switch (Knob) 800G-S_3_
2-Position Key Selector Switch (Key Operated) 800G-KS_2_
3 Position Key Selector Switch (Key Operated) 800G-KS_3_
Push-Pull Mushroom Push Button 800G-MPE 140,000
Back of Panel
Base Mount Contact Block (Screw Termination) 800G-XB_
Latch Mount Contact Block (Cable Termination) 800G-XLC3_
800G-U2FX
800G-V2FX
Value [cycles]
10D
5,800,000
12,000
1,200,000Latch Mount Contact Block (Screw Termination) 800G-XLS_
The B
value [cycles] states the number of switching cycles up to which 10% of the elements failed dangerously. The determination was done via a statistical evaluation of field data.
10D
Table 15 - Illuminated Components
Description Cat. No. MTTF
Illuminated Push Button
Push Button (Illuminated – Flush) 800G-LF*
Used with one of the following:
Base Mount Power Module with Contact Block
(Screw Termination)
Latch Mount Power Module with Contact Block
(Screw Termination)
Latch Mount Power Module with Contact Block
(Cable Termination)
Pilot Light 800G-P*
Used with one of the following:
Base Mount Power Module (Screw Termination) 800G-DB*
Latch Mount Power Module (Screw Termination) 800G-DLS*
Latch Mount Power Module (Cable Termination) 800G-DLC3*
The operating hours of all delivered products or comparable product clusters are determined and divided by the number of reports of failures for that product. The result is the MTTFD or LambdaD rating we can offer for the
products our customers received.
800G-DB*X*
800G-DLS*X*
800G-DLC3*X*
Pilot Light
(Years) LambdaD (Dangerous Failures/Year)
D
3.92E+02 Years 2.91E-07
9.34E+03 Years 1.22E-08
38 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 39
Specifications (Bul. 800G)
Back-of-Panel Components
Contact Block
Table 16 - Electrical Ratings
Screw Termination Cable Termination
Rated Insulation Voltage 690V 400V (Limited by the cable, not the contacts)
Rated Voltage 250V (per ATEX certificates) 24V 250V (per ATEX certificates) 24V
Rated Operating Currents 16 A 10 A 1 A 16 A 10 A 1 A
Utilization Category AC-12 AC-15 DC-13 AC-12 AC-15 DC-13
Thermal Continuous Current 16 A at 40 °C (104 °F), 11 A at 60 °C (140 °F) 16 A at 40 °C (104 °F), 11 A at 60 °C (140 °F)
Contact Rating per UL 508 A600 P600 A600 P600
Max. Rated Voltage per UL Contact Rating 600V 600V 600V 600V
Max. “Make” Current at Rated Voltage per UL Contact Rating
Max. “Break” Current at Rated Voltage per UL Contact Rating
Thermal Continuous Test Current per UL Contact Rating 10 A 5 A 10 A 5 A
Short Circuit Protection 10 A Slow Blow, Type DT, gl 10 A Slow Blow, Type DT, gl
12 A 0.2 A 12 A 0.2 A
1.2 A0.2 A1.2 A0.2 A
Table 17 - Mechanical Ratings
Screw Termination Cable Termination
Protection Type II 2G Ex de IIC
Certification PTB 01 ATEX 1040U UL E10314 PTB 01 ATEX 1039X UL E10314
Contact Options 1 N.O. - 1 N.C.
Contact Material AgSnO
Housing Material Thermoplastic Thermoplastic
Physical Shock Resistance DIN IEC 68 part 2-27, 30 g 18 ms DIN IEC 68 part 2-27, 30 g 18 ms
Design Life 1 000 000 cycle mechanical life 1 000 000 cycle mechanical life
Operating Force (Maximum) 22.2 N (5 lb) to open N.C.
Temperature (Storage/Transport) -55…70 °C (-67…158 °F) -55…70 °C (-67…158 °F)
Operational Temperature Range -55…60 °C (-67…140 °F) -55…60 °C (-67…140 °F)
Wire/Cable Size
2.5 mm
Degree of Protection IP20, with operators and enclosure IP66 With operators IP67
Mounting Base Mount: Secures to rail integral to enclosure base
Panel Mount: Secures to operator with integral latch
Class I, Zone 1 AEx de IIC
Class I, Zone 1 Ex de IIC
2 N.O. 2 N.C.
2
15.6 N (3.5 lb) to close N.O.
28.9 N (6.5 lb) full travel
2
(12 AWG) stranded max.
22.2 N (5 lb) to open N.C.
15.6 N (3.5 lb) to close N.O.
28.9 N (6.5 lb) full travel
3 m (9.8 ft) long cable
Panel Mount: Secures to operator with integral latch
II 2G Ex d IIC T6
Class I, Zone 1 AEx d IIC T6
Class I, Zone 1 Ex d IIC T6
1 N.O. - 1 N.C.
2 N.O.
2 N.C.
AgSnO
2
2
4 x 1.5 mm
(9.1 mm/0.36 in. OD)
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 39
Page 40
Specifications (Bul. 800G)
Power Module
Table 18 - Electrical Ratings
Screw Termination Cable Termination
Rated Insulation Voltage 300V 300V
Power Consumption ≤1 W ≤1 W
Lamp Multi-LED (Red, Yellow, Green, White, Blue) Multi-LED (Red, Yellow, Green, White, Blue)
Rated Voltage 12…60V DC
12…250V AC
Table 19 - Mechanical Ratings
Screw Termination Cable Termination
Protection Type II 2G Ex de IIC
Class I, Zone 1 AEx de IIC
Class I, Zone 1 Ex de IIC
Certification PTB 01 ATEX 1037U UL E10314 PTB 01 ATEX 1038X UL E10314
Housing Material Thermoplastic Thermoplastic
Physical Shock Resistance DIN IEC 68 part 2-27, 30 g, 18 ms DIN IEC 68 part 2-27, 30 g, 18 ms
Design Life 100 000 hours 100 000 hours
Temperature (Storage/Transport) -55…70 °C (-67…158 °F) -55…70 °C (-67…158 °F)
Operational Temperature Range -55…60 °C (-67…140 °F) -55…60 °C (-67…140 °F)
Wire/Cable Size
Degree of Protection IP20, with operators and enclosure IP66 With operators IP67
Mounting Base Mount: Secures to rail integral to enclosure base
Panel Mount: Secures to operator with integral latch
2
(12 AWG) stranded max.
2.5 mm
Panel Mount: Secures to operator with integral latch
24…60V DC
24…60V AC and 110…250V AC
II 2G Ex d IIC T6
Class I, Zone 1 AEx d IIC T6
Class I, Zone 1 Ex d IIC T6
3 m (9.8 ft) long cable
(9.1 mm/0.36 in. OD)
4 x 1.5 mm
2
Power Module/Contact Block Combination
Table 20 - Electrical Ratings
Screw Termination Cable Termination
Rated Insulation Voltage 300V 300V
Power Consumption ≤1 W ≤1 W
Lamp Multi-LED (red, yellow, green, white, blue) Multi-LED (red, yellow, green, white, blue)
Rated Voltage 24…48V DC
24…250V AC
Contact Rating per UL 508 A600 P600 A600 P600
Thermal Continuous Current 1 A 0.25 A 1 A 0.25 A
Max. Rated Voltage 600V 600V 600V 600V
40 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
24…48V DC
24…250V AC
Page 41
Specifications (Bul. 800G)
Power Module/Contact Block Combination, Cont’d.
Table 21 - Mechanical Ratings
Screw Termination Cable Termination
Protection Type II 2G EEx de IIC
Class I, Zone 1 AEx de IIC
Class I, Zone 1 Ex de IIC
Certification PTB 01 ATEX 1037U UL E10314 PTB 01 ATEX 1038X UL E10314
Housing Material Thermoplastic Thermoplastic
Physical Shock Resistance DIN IEC 68 part 2-27, 30 g, 18 ms DIN IEC 68 part 2-27, 30 g, 18 ms
Design Life 100 000 hours 100 000 hours
Temperature (Storage/Transport) -55…70 °C (-67…158 °F) -30…70 °C (-22…158 °F)
Operational Temperature Range -55…60 °C (-67…140 °F) -30…60 °C (-22…140 °F)
Wire/Cable Size
Degree of Protection IP20, with operators and enclosure IP66 With operators IP67
Mounting Base Mount: Secures to rail integral to enclosure base
Panel Mount: Secures to operator with integral latch
2
(12 AWG) stranded max.
2.5 mm
Panel Mount: Secures to operator with integral latch
II 2G EEx d IIC T6
Class I, Zone 1 AEx d IIC T6
Class I, Zone 1 Ex d IIC T6
3 m (9.8 ft) long cable
(9.1 mm/0.36 in. OD)
4 x 1.5 mm
2
Front-of-Panel Operators
Table 22 - Mechanical Ratings
Device
Push Button
Selector Switch
Key Release
Push Button
Key Release
Mushroom
Mushroom
E-stop
Pilot Light (Red,
Yellow, White,
Green, Blue)
Hole Plug
Illuminated
Push Button
Key Selector Switch
Operational
Temperature Operating Force
-55…+70 °C
(-67…+158 °F)
-55…+70 °C
(-67…+158 °F)
-55…+70 °C
(-67…+158 °F)
-55…+70 °C
(-67…+158 °F)
-55…+70 °C
(-67…+158 °F)
-55…+70 °C
(-67…+158 °F)
-55…+70 °C
(-67…+158 °F)
-55…+70 °C
(-67…+158 °F)
-55…+70 °C
(-67…+158 °F)
-55…+70 °C
(-67…+158 °F)
6.7 N (1.5 lb)
15.6 N (3.5 lb)
15.6 N (3.5 lb)
6.7 N (1.5 lb)
44.5 N Push/89 N Pull
(10 lb Push/20 lb Pull)
—N/A4 Nm
—N/A7 Nm
6.7 N (1.5 lb) 1 x 10
1,000,000 cycles 7 N•m
Mechanical Design Life
1,000,000 cycles
6000 cycles
Impact
Resistance Materials
7 N•m
6
7 N•m
Thermoplastic
Housing
EPDM Seals
Ingress
Protection Ex Protection Type
IP66:
-20…+70 °C
(-4…+158 °F)
IP54:
-55…-20 °C (-67…-4 °F)
Typ e 4X:
-20…+70 °C
(-4…+158 °F)
II 2G EEx e II
PTB 01 ATEX 1035U
UL E10314
Excludes contact block.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 41
Page 42

Complete Assembled Stations (Bul. 800G)

Cond uit
Size Position 1 Position 2 Position 3
800G – 2 F 3 M F 4 N 3
abcdbcdbcd e
Entry
a
Enclosure Size
Code Description
11-hole
22-hole
33-hole
b
Operator/Meter
Code Description
B Key release mushroom push button D Momentary mushroom push button E Push-pull mushroom push button F Non-illuminated flush push button H 2-position selector switch
J 3-position selector switch
K Key release push button L Illuminated push button — flush NHole plug PPilot light
Only available in red.
Only available in black.
Only available in white, black, green, red, or yellow.
Only available in white, green, red, yellow, and blue.
Only available for 3-position selector switch.
For use with illuminated push button only.
For through-feed enclosure, selected conduit entry is applied for
both bottom and top entry.
c
Push Button Color/Text
Code Description
1White
2Black
3 Green
4Red
5Yellow
6Blue
A START (green background/white text)
B STOP (red background/white text)
G I (green background/white text)
H O (red background/white text)
J ON (green background/white text)
K OFF (red background/white text)
Key Release
1 Lockable in initial position,
key removal in initial position
2 Lockable in both positions,
key removal in both positions
3 Lockable in depressed position,
key removal in depressed position
Selector Switch
M Maintained in all positions
B Spring return from both positions L Spring return from left R Spring return from right
d
Contact Block/Lamp Module
Code Description
A 1 N.O. - 1 N.C. base mount
M 2 N.O. base mount
N 2 N.C. base mount
D Lamp module base mount
(same color as requested lens color in Table c)
X N/A (hole plug) K 1 N.O. with lamp module L 1 N.C. with lamp module
e
Conduit Entry
Code Description
Bottom Entry
Blank M20X1.5 threaded hole
1 1/2 in. NPT conduit hub
2 3/4 in. NPT conduit hub
5 M20 blind plug
6 M25 blind plug
8 1 M20 metal cable gland
9 1 M25 metal cable gland
0 2 M20 metal cable gland
Top Ent ry
A M20X1.5 threaded hole
B 1/2 in. NPT conduit hub
C 3/4 in. NPT conduit hub
F M20 blind plug
G M25 blind plug
J 1 M20 metal cable gland
K 1 M25 metal cable gland
L 2 M20 metal cable gland
Through Feed
M M20X1.5 threaded hole
N 1/2 in. NPT conduit hub
P 3/4 in. NPT conduit hub
T M20 blind plug
U M25 blind plug
W 1 M20 metal cable gland
X 1 M25 metal cable gland
Y 2 M20 metal cable gland
42 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 43

Configurable Ganged Assembled Stations (Bul. 800G)

Enclosure Size Position 1 Position 2 Position 3
Station
3
Station
1
Note: Up to 31 characters after “800G-”
a1 is the enclosure size for station
1, a2 for station 2, and a3 for station 3. If there are two enclosures that are ganged together, leave a3 blank. If there are three enclosures that are ganged together, complete a3 with the appropriate value.
800G – 2 2 3 F A M F B N
a1 a2 a3 b c d b c d b c d
Position 1 Position 2 Position 3
P5DE4N
bcdbcdbcd
Position 1 Position 2 Position 3 Conduit Entry
K3AL6KJMA4
bcdbcdbcde
Station
2
a1, a2, a3
Enclosure Size
Code Description
11-hole 22-hole 33-hole
b
Operator/Meter
Code Description
B Key release mushroom push button D Momentary mushroom push button E Push-pull mushroom push button F Non-illuminated flush push button H 2-position selector switch
J 3-position selector switch
K Key release push button L Illuminated push button — flush NHole plug PPilot light
Only available in red.
Only available in black.
Only available in white, black, green, red, or yellow.
Only available in white, green, red, yellow, and blue.
Only available for 3-position selector switch.
For use with illuminated push button only.
For through-feed enclosure, selected conduit entry is applied for
both bottom and top entry.
c
Push Button Color/Text
Code Description
1White 2Black 3 Green 4Red 5Yellow 6Blue
A START (green background/white text)
B STOP (red background/white text) G I (green background/white text)
H O (red background/white text)
J ON (green background/white text) K OFF (red background/white text)
Key Release
1 Lockable in initial position, key removal in initial
position
2 Lockable in both positions, key removal
in both positions
3 Lockable in depressed position, key
removal in depressed position
Selector Switch
M Maintained in all positions
B Spring return from both positions L Spring return from left R Spring return from right
d
Contact Block/Lamp Module
Code Description
A 1 N.O. - 1 N.C. base mount M 2 N.O. base mount N 2 N.C. base mount
D Lamp module base mount (same color as
requested lens color in Table c)
X N/A (hole plug) K 1 N.O. with lamp module L 1 N.C. with lamp module
e
Conduit Entry
Code Description
Bottom Entry
Blank M20X1.5 threaded hole
1 1/2 in. NPT conduit hub 2 3/4 in. NPT conduit hub 5 M20 blind plug 6 M25 blind plug 8 1 M20 metal cable gland 9 1 M25 metal cable gland 0 2 M20 metal cable gland
Top Ent ry
A M20X1.5 threaded hole B 1/2 in. NPT conduit hub C 3/4 in. NPT conduit hub F M20 blind plug G M25 blind plug
J 1 M20 metal cable gland K 1 M25 metal cable gland L 2 M20 metal cable gland
Through Feed
M M20X1.5 threaded hole N 1/2 in. NPT conduit hub
P 3/4 in. NPT conduit hub T M20 blind plug
U M25 blind plug
W 1 M20 metal cable gland
X 1 M25 metal cable gland Y 2 M20 metal cable gland
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 43
Page 44

Push Button Units (Bul. 800G)

Cat. No. 800G-F3
Cat. No. 800G-U2FX
Cat. No. 800G-LF3
Non-Illuminated — Flush
800G F 3
ab
a
Operator Construction
Code Description
F Flush operator
Code Description
1White
2Black
3Green
4Red
5Yellow
b
Color
Double Push Button, Non-Illuminated — Flush
800G U 2FX
a
a
Base
Code Description
U Curved base for use with Bul. 800G enclosures
V Flat base for use with customer provided enclosures
Illuminated — Flush
800G LF 3
ab
a
Operator Construction
Code Description
LF Illuminated flush operator
44 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Code Description
1White
3Green
4Red
5Yellow
6Blue
b
Color
Page 45
Push Button Units (Bul. 800G)
Momentary Mushroom
Cat. No. 800G-M2
Key Release Mushroom
Cat. No. 800G-MKE
Push-Pull Mushroom
Cat. No. 800G-MPE
Cat. No. 800G-K14
Mushroom — Non-Illuminated and Key Release
800G M 2
ab
a
Operator Style
Code Description
MMomentary
MP Push-pull MK Key release
Only available in E-stop, code E from Table b.
Key Release
800G K 14
ab
a
Operator Style
Code Description
K Key release push button
b
Color or Feature
Code Description
2 Black with black bezel
E Red E-stop with yellow bezel and printing on head
b
Locking Position
Code Description
14 Lockable in initial position; key removal in initial position
16 Lockable in both positions; key removal in both positions
24 Lockable in depressed position; key removal in depressed position
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 45
Page 46

Selector Switch Units (Bul. 800G)

Key Operated Switch
Cat. No. 800G-KSM33H
Knob Selector Switch
Cat. No. 800G-SM3
Knob and Key Operated
2-Postion Target Table 3-Postion Target Table
Contact Type
N.O. O X
N.C. X O
800G S M3
abcd
a
Operator Style
Code Description
SKnob
KS Key operated
b
No. of Positions/Functions
Code Description
M2 2-position maintained
B3 3-position spring return left and right to center
L3 3-position spring return left to center
M3 3-position maintained
R2 2-position spring return right to left
R3 3-position spring return right to center
Only available with key selector (code KS from Table a).Only available with knob selector (code S from Table a).
Pos. on Latch
Contact Type
N.O.
N.C.
or Base
Top O O X
Bottom X O O
Top X X O
Bottom O X X
c
Key Removal
Code Description
Blank For knob selector switches
1Left 2Right 3All 4Center 5 Left/center 6 Left/right 7 Right/center
d
Knob Position
Code Description
Blank For latch mount or base mount in horizontal Bulletin 800G enclosure
H For base mount in vertical Bulletin 800G enclosure
46 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 47

Pilot Lights (Bul. 800G)

Cat. No. 800G-P3
800G P 3
ab
a
Operator Style
Code Description
PPilot light
b
Lens Color
Code Description
1White
3Green
4Red
5Yellow
6Blue
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 47
Page 48

Enclosures (Bul. 800G)

Cat. No. 800G-1P
Plastic (Base mount only)
800G 3 P T 1
abcd
a
Enclosure Size
Code Description
11-hole
22-hole
33-hole
b
Enclosure Style
Code Description
PPlastic
c
Conduit Entry
Code Description
Blank Bottom feed
T Top feed
F Through feed
X No holes
d
Conduit Style
Code Description
Blank M20 x 1.5 threaded hole
1 1/2 in. NPT conduit hub
2 3/4 in. NPT conduit hub
5 M20 blind plug
6 M25 blind plug
8 M20 metal cable gland
9 M25 metal cable gland
0 Two M20 metal cable glands
48 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 49

Back-of-Panel Components (Bul. 800G)

Base Mount
Cat. No. 800G-XBA
Latch Mount Screw Termination
Cat. No. 800G-XLSA
Base Mount
Cat. No. 800G-DBG
Latch Mount Screw Termination
Cat. No. 800G-DLSG
Base Mount
Cat. No. 800G-DBGXK
Latch and Base Mount Contact Block
800G XLS A
ab
a
Contact Block/Latch Type
Code Description
XB Base mount
XLS Latch mount with screw termination
XLC3 Latch mount with 3 m (9.84 ft) cable termination
Code Description
A 1 N.O. - 1 N.C.
M2 N.O.
N2 N.C.
Latch and Base Mount Power Module
800G DB G
ab
a
Power Module/Latch Type
Code Description
DB Base mount
DLS Latch mount with screw termination
DLC3 Latch mount with 3 m (9.84 ft) cable termination
Bulletin 800G LED modules can only be powered from dry contact circuits (with no leakage current in
the OFF state).
Code Description
WWhite
GGreen RRed YYellow BBlue
b
Contact Configuration
b
Color
Power Module with Contact Block
800G DB G XK
abc
a
Power Module/Latch Type
Code Description
DB DB Base
DLS Latch mount with screw termination
DLC3 Latch mount with 3 m (9.84 ft) cable termination
Bulletin 800G LED modules can only be powered from dry
contact circuits (with no leakage current in the OFF s tate).
Code Description
WWhite
GGreen RRed YYellow BBlue
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 49
b
Color
c
Contact Con figuration
Code Description
XK 1 N.O. XL 1 N.C.
Page 50
Back-of-Panel Components (Bul. 800G)
Legend Frame
Cat. No. 800G-110
Adhesive Back Legend Pla te
Cat. No. 800G-17SE100
Adhesive Back Legend Plate
Cat. No. 800G-17SE100
Legend Plates
800G 11 S E 166 K
abcde
a
Type
Code Description
11 Legend plate and frame
17 Legend plate only
b
Insert Color
Code Description
S Silver background with black legend text
Code Description
EEnglish
FFrench
GGerman
TItalian
SSpanish
U Universal symbol
c
Language
d
Legend Identification
See our website
e
Type
Code Description
K 0.080 size font
Special Engraving
Besides the standard text and symbols that are listed on our website, special legend plates are readily available. To ord er:
Select font code from table below.
Specify desired text (reference table below for restriction on characters and number of lines).
Type o f Legend Size Font Size Font Code
Legend Plate 30 x 4 mm Small K SAMPLE 19 1
Approximate
Size
Max.
Characters/Line
Max. Number
of Lines Example
800G-17SE100K
STARTER
Example (Legend Plate
800G-11SE100K STARTER
with Frame)
800G AEL S LINE 1 , LINE 2 , LINE 3
ab c d e
a
Insert Color
Code Description
AEL Enclosure identification label with silver
background and black text
Code Description
S 0.10 size font
L 0.14 size font
Special Engraving
To ord er:
Select desired font code table below (notes the max. characters and max. no. of lines).
Specify desired text (reference table below for restriction on characters and number of lines).
Type of Legend Size Font Size Font Code
Enclosure ID Label 50 x 15 mm
Standard S SAMPLE 25 3 800G-AELS MACHINE 1, L-R27
Large L SAMPLE 19 2 800G-AELL MACH 1
b
Font Size
Approximate
Size
Max. Characters/
Line
Example of customer specified text that is based on max.
separated by a comma, the following text is engraved on
Max. Number of
c, d, e
Customize d Text
characters per line and max. number of lines. When
the next line.
Lines Example
50 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 51

Approximate Dimensions (Bul. 800G)

Push Buttons
Mushroom
Pilot Light
2-Position Selector Switch
E-stop
Key Release
3-Position Selector Switch
Key Release Mushroom
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 51
Page 52
Approximate Dimensions (Bul. 800G)
Cable Termination
Screw Termination
Base Mount
Cable Termination
Screw Termination
Base Mount
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Contact Block
Power Module
52 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 53
Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
70
(2.750)
16.5
(0.650)
3
(0.118)
40
(1.578)
Ø30
(1.181)
40
(1.57)
16.5 (0.65)
30.3
(1.19)
70
(2.76)
3 (0.12)
Single Unit
Tri ple U nit
Double Unit
Vertical and Horizontal Spacing
Mounting Dimension
Approximate Dimensions (Bul. 800G)
Rockwell Automation Publication 800-TD011D-EN-P - March 2019 53
Page 54
Approximate Dimensions (Bul. 800G)
Notes:
54 Rockwell Automation Publication 800-TD011D-EN-P - March 2019
Page 55
Page 56
Rockwell Automation Support
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support software service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/ updates, support chats and forums, technical information, FAQs, and to sign up for product notification updates.
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/services/online-phone
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Wor ldwi de Locator
Rockwell Automation representative.
at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
New Product Satisfaction Return
you can find technical and application notes, sample code, and links to
for software
.
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
, available at http://www.rockwellautomation.com/literature/.
Publication 800-TD011D-EN-P - March 2019
Supersedes Publication 800-TD011C-EN-P - December 2015 Copyright © 2019 Rockwell Auto mation, Inc. All rights reserved. Pr inted in the U.S.A.
Loading...