TROUBLESHOOTING
12-4 SM YUD 2-A.1 GB
12.1.3.4 Outdoor Unit Diagnostics and Corrective Actions
Indoor
indicators
ODU
indicators
Failure Possible Reasons/Corrective actions
E5 PH DC over voltage protection
z AC power supply is higher than 265V
z Outdoor PCB circuit malfunction
E5 P8
Heat sink overheating
protection
z Insufficient grease on heatsink or poor connection of
heatsink to PCB
z Outdoor PCB problem.
E5 Pc Current sensor failure PCB is damaged
E5 P7 HST failure PCB is damaged
E5 P5
Compressor phase current
detection problem
Phase current detection circuit for compressor has problem.
E5 PL DC under voltage protection
z AC power supply voltage is less than 150VAC
z Outdoor PCB circuit malfunction
E5 Lc Compressor startup failure
z Compressor wiring mistake
z Over charged system
z System not balanced before compressor starting
z Compressor problem
E5 Hc PFC protection
z PFC module assembly problem.
z Poor heat exchange of Heatsink
z PFC reactor problem.
z Abnormal power voltage
z PFC circuit problem on PCB
E5 LE Compressor lock
z Compressor wiring mistake
z Over charged system
z System not balanced before compressor starting
z Compressor problem
E5 P0 IPM reset
E5 H7
Desynchronizing of
compressor
z Abnormal power input voltage.
z Compressor wiring mistake.
z Liquid and gas valve are not open.
z EEV damaged or not proper working
z Poor heat exchange.
z Over charged system.。
E5 Ld
Lack phase protection of
compressor
z Phase current detection circuit for compressor has
problem.
z Comp wiring mistake
E5 P6
Communication malfunction
between driver and main
controller
z Wiring mistakes
z ODU PCB problem
E5 H5 IPM protection
z Abnormal power input voltage.
z Compressor wiring mistake.
z Liquid and gas valve are not open.
z EEV damaged or not proper working
z Poor heat exchange.
z Over charged system.
E5 LF Compressor over speed
E5 Pd Sensor connection protection
z Compressor wiring mistake
z The compressor wire go cross the relative current sensor
z IPM damage
E5 PE Temperature shift protection
E5 P9 AC contactor protection
E1 E1
High-pressure switch
protection
z Refrigerant was superabundant
z Poor heat exchange (including blockage and bad radiating
environment )
z Too high ambient temperature
E3 E3
Low-pressure switch
protection
z Refrigerant leakage
z Poor heat exchange (including blockage and bad radiating
environment )
z EEV connection problem or damage
E4 E4
Compressor over heating
protection
z EEV connection problem or damage
z Refrigerant leakage
z Poor heat exchange