AIREDALE SN09D, SN12D, SR09D, SR15D, SR12D Technical Manual

...
Page 1
SmartCool™ Downow
6 to 200kW
SN, SR and SD
SmartCool Chilled Water
Technical Manual
Page 2
SmartCool™ 6 - 200kW
Customer Services
Warranty, Commissioning & Maintenance
As standard, Airedale guarantees all non consumable parts only for a period of 12 months, variations tailored to suit product and application are also available; please contact Airedale for full terms and details. To further protect your investment in Airedale products, Airedale can provide full commissioning services,
Introduction
comprehensive maintenance packages and service cover 24 hours a day, 365 days a year (UK mainland). For a free quotation contact Airedale or your local Sales Engineer. All Airedale products are designed in accordance with EU Directives regarding prevention of build up of water, associated with the risk of contaminants such as legionella. For effective prevention of such risk it is necessary that the equipment is maintained in accordance with Airedale recommendations.
SafeCool
In addition to commissioning, a 24 hour, 7 days a week on-call service is available throughout the year to UK mainland sites. This service will enable customers to contact a duty engineer outside normal working hours and receive assistance over the telephone. The duty engineer can, if necessary, attend site, usually within 24 hours or less. Full details will be forwarded on acceptance of the maintenance agreement.
Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance
CAUTION
being carried out in accordance with the recommendations provided during the warranty period. Failure to have the maintenance procedures carried out will invalidate the warranty and any liabilities by Airedale International Air Conditioning Ltd.
Precision Air Conditioning
Spares
A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on request.
Training
As well as our comprehensive range of products, Airedale offers a modular range of Refrigeration and Air Conditioning Training courses, for further information please contact Airedale.
Customer Services
For further assistance, please e-mail: enquiries@airedale.com or telephone: UK Sales Enquiries + 44 (0) 113 239 1000 enquiries@airedale.com International Enquiries + 44 (0) 113 239 1000 enquiries@airedale.com Spares Hot Line + 44 (0) 113 238 7878 spares@airedale.com Airedale Service + 44 (0) 113 239 1000 service@airedale.com Technical Support + 44 (0) 113 239 1000 tech.support@airedale.com Training Enquiries + 44 (0) 113 239 1000 training@airedale.com For information, visit us at our web site: www.airedale.com
Airedale Ltd. endeavours to ensure that the information in this document is correct and fairly stated, but none of the statements are to be relied upon as a statement or representation of fact. Airedale Ltd. does not accept liability for any error or omission, or for any reliance placed on the information contained in this document. The development of Airedale products and services is continuous and the information in this document may not be up to date. It is important to check the current position with Airedale Ltd. at the address stated. This document is not part of a contract or licence unless expressly agreed. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, recording, or information storage and retrieval systems, for any purpose other than the purchaser’s personal use, without the express written permission of Airedale Ltd. ©2018 Airedale International Air Conditioning Limited. All rights reserved. Printed in the UK.
2
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 3
SmartCool™ 6 - 200kW
Environmental Considerations
Units with supply water temperatures below +5°C
● Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be exposed to freezing temperatures.
Units subject to ambient temperatures lower than 0°C
● Glycol of an appropriate concentration (1) must be used within the system to ensure adequate freeze protection. Please ensure that the concentration is capable of protection to at least 3K lower than ambient.
● Water / glycol solution should be constantly circulated through all waterside pipework and coils to avoid static water from freezing.
● Ensure that pumps are started and running even during shut down periods, when the ambient is within 3K of the solution freeze point (1) (i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).
● Additional trace heating is provided for interconnecting pipework.
(1) Refer to your glycol supplier for details.
Environmental Policy
It is our policy to:
● Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
● Train personnel in sound environmental practices.
● Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
● Manufacture products in a responsible manner with minimum impact on the environment.
● Reduce our use of chemicals and minimise their release to the environment.
● Measure, control and verify environmental performance through internal and external audits.
● Continually improve our environmental performance.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives: Electromagnetic Compatibility Directive (EMC) 2014/30/EU Machinery Directive (MD) 89/392/EEC version 2006/42/EC Pressure Equipment Directive (PED) 2014/68/EU Ecodesign 2009/125/EC To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the Declaration of Conformity, supplied with each product.
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
3
Page 4
SmartCool™ 6 - 200kW
Health and Safety
IMPORTANT
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit.
Safety
Introduction
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/ electrical equipment, care must be taken if you are to obtain the best results.
When working with any air conditioning units ensure that the electrical isolator is switched off prior
CAUTION
Electrical installation commissioning and maintenance work on this equipment should be undertaken by competent and trained personnel in accordance with local relevant standards and codes of practice. A full hazard data sheet in accordance with COSHH regulations is available should this be required.
to servicing or repair work and that there is no power to any part of the equipment.
Also ensure that there are no other power feeds to the unit such as fi re alarm circuits, BMS circuits
etc.
Personal Protective Equipment
Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning equipment.
Manual Handling
Some operations when servicing or maintaining the unit may require additional assistance with regard to manual handling. This requirement is down to the discretion of the engineer. Remember do not perform a lift that exceeds your ability.
Pressure Equipment Directive (2014/68/EU)
Precision Air Conditioning
Minimum and Maximum Operation Temperature (TS) and Pressure (PS)
Waterside
Allowable Temperature Range (TS) = Min -5°C* to Max 40°C** Maximum Allowable Pressure (PS) = 10 Barg
*Based on the waterside temperature in the unit off state in the lowest permitted ambient temperature. **Based upon maximum machine running temperatures.
Ecodesign Directive 2009/125/EC
The product range within this document is designed in accordance to the European Ecodesign Directive 2009/125/EC. The appendix at the rear section of the manual gives the product compliancy metrics. Products sold outside of the EU are exempt from this directive.
4
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 5
SmartCool™ 6 - 200kW
Contents
Introduction 7
Construction 8
SN, SR Units 8
SD Units 8
System Congurations 9
SN, SR Nomenclature 11
SD Nomenclature 11
Unit Overview 12
SN, SR Range 12
SD Range 12
Chilled Water Components 14
Airow Components 19
Electrical Components 21
Electric Heating 23
Humidication 24
Controls 28
General Features 34
Installation Data 36
Dimensions 36
Lifting 38
Positioning & Levelling 38
Unpacking 38
Minimum Unit Clearance SN, SR 39
Minimum Unit Clearance SD 40
Incoming Services 44
Glycol 47
Water Detection Tape Installation 48
pLAN Termination 49
Technical Data SN C000 Units 50
Mechanical and Electrical Data 50
Waterside Pressure Drop Data 51
Measurement of Sound Data 52
Sound Data 53
Interconnecting Wiring 54
Technical Data SR C000 Units 55
Mechanical and Electrical Data 55
Waterside Pressure Drop Data 56
Sound Data 57
Interconnecting Wiring 58
Technical Data SR C0C0 Units 59
Mechanical and Electrical Data 59
Waterside Pressure Drop Data 60
Sound Data 61
Interconnecting Wiring 62
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
5
Page 6
SmartCool™ 6 - 200kW
Precision Air Conditioning
Contents
Technical Data SD CH00 Units 63
Mechanical and Electrical Data 63
Waterside Pressure Drop Data 64
Introduction
Sound Data 66
Interconnecting Wiring 67
Technical Data SD CL00 Units 68
Mechanical and Electrical Data 68
Waterside Pressure Drop Data 69
Sound Data 71
Interconnecting Wiring 72
Technical Data SD CHCH Units 73
Mechanical and Electrical Data 73
Waterside Pressure Drop Data 74
Sound Data 76
Interconnecting Wiring 77
Technical Data SD CLCL Units 78
Mechanical and Electrical Data 78
Waterside Pressure Drop Data 79
Sound Data 81
Interconnecting Wiring 82
After Sales 83
6
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 7
SmartCool™ 6 - 200kW

Introduction

Designed to provide environmental precision air conditioning for applications such as telecommunication facilities, data centers, computer rooms, clean rooms and laboratories.
Full function units provide full control of temperature, humidity and ltration.
The modular design of the SmartCool allows grouping of differing model types and capacities to be installed side by side.
The exibility of this type of installation provides for multi-circuit functionality.
SN, SR
Range Performance (kW)
SN C000 SR C000 SR C0C0
(1)
(1)
(1)
13 – 36
35 – 98
25 – 70
Range Performance (kW)
SD CH00 SD CHCH SD CL00 SD CLCL
SD
(1)
(1)
(2)
(2)
105 – 255
75 – 184
92 – 215
75 – 185
Introduction
(1)
Based on nominal unit capacities 24°C 45% RH 7°C /12°C Water
(2)
Based on nominal unit capacities 35°C 24% RH 18°C / 24°C Water
)
ir
A
y
r
D
J/g
(
n
io
at
ASHRAE Allowable Operating Envelope
1
ASHRAE Recommended Operating Envelope
2
Airedale Extended Operating Envelope
1 + 2
Airedale Operating Envelope
5
0
Bulb Temperature (°C)
et
W
10
1
5
r
u
at
s
t
a
y
p
l
a
h
t
n
E
2
5
0
0
0
1
%
9
80
0
2
0
7
1
e
v
i
0
Relat
6
%
0
5
0
4
2
%
0
2
%
0
1
Moisture Content Operating Band
Moisture Content kg/kg Dry Air
15
1050 20 25 30 35 40
18 27
Dry Bulb Temperature (°C)
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
7
Page 8
SmartCool™ 6 - 200kW
Precision Air Conditioning
Precision Air Conditioning System
The computer room air conditioning equipment shall be designed specically for precision temperature and humidity control applications. It shall automatically monitor and control cooling, heating, humidication, de-humidication and ltering functions for the conditioned space. The system shall be built to the highest quality engineering and
manufacturing standards and shall be subject to a functional test prior to leaving the factory.

Construction

Introduction

SN, SR Units

The cabinet shall be manufactured using an external aluminium extrusion frame with aluminium corners.
Panels shall be completely removable to gain unequalled access during installation as required. The galvanised sheet
steel panels and aluminium frame and corners shall be coated with an epoxy baked powder paint to provide a durable nish.
Standard unit colour shall be Black Grey to RAL 7021.
Cabinets shall be lined internally with various thickness re resistant foam (BS 476) for thermal and acoustic insulation.
The insulation density shall not be less than 75 kg/m³.
The cabinet doors shall be full height, hinged and key lock secured. The hinge arrangement shall allow exible door
opening/removal for improved access.
A propriety rubberised door seal shall reduce sound breakout and eradicate air leakage. In-seal type foam based door
seals shall not be acceptable.
The control panel is mounted on hinges to allow easy removal of lters and access to several electrical components. The unit design shall incorporate a series of M6 xings to the top and bottom face to ease customer ductwork connection
and reduce installation time.

SD Units

The cabinet shall be manufactured using steel frame. Panels shall be completely removable to gain unequalled access during installation as required. The galvanised sheet
steel panels shall be coated with an epoxy baked powder paint to provide a durable nish.
Standard unit colour shall be Black Grey to RAL 7021.
Cabinets shall be lined internally with various thickness re resistant foam (BS 476) for thermal and acoustic insulation.
The insulation density shall not be less than 75 kg/m³.
The cabinet doors shall be full height, hinged and key lock secured. The hinge arrangement shall allow exible door
opening/removal for improved access.
A propriety rubberised door seal shall reduce sound breakout and eradicate air leakage. In-seal type foam based door
seals shall not be acceptable.
The unit design shall incorporate a series of M6 xings to the top and bottom face to ease customer ductwork
connection and reduce installation time.
8
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 9
SmartCool™ 6 - 200kW
System Congurations
SN, SR Range SD Range
Introduction
SN C000 Units
● Fans located within unit
● Separate oorstand (min 350mm)
SR C000 / C0C0 Units
● Fans located within unit
● Separate oorstand (min 350mm)
SD CL00 / CLCL Units
● Fans located within oorstand
● Floorstand integral to unit (min 600mm)
SD CH00 / CHCH Units
● Fans located within oorstand
● Floorstand integral to unit (min 600mm)
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
9
Page 10
SmartCool™ 6 - 200kW
Single Circuit System Conguration
(SN C000, SR C000, CL00, CH00)
Introduction
Precision Air Conditioning
Dual Circuit System Conguration
(SR C0C0, SD CLCL, SD CHCH)
10
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 11
SmartCool
Regular Cas e (890m m deep)
Narrow Case (60 0mm deep)
2 220V / 3Ph / 60Hz
2 220V / 3Ph / 60Hz
SmartCool™ 6 - 200kW

SN, SR Nomenclature

S Product Nam e
R
Variant
N
06 09 963 m m
Cas e Width
12 1242 mm 15 1521 mm 18 1800 mm
D
Flow Configuration
010
Nom inal Co oling Ca pacity (kW)
095
-
Separator
-
C000 Single Circuit CW
Cooling Configuration
C0C0 Dual Circuit CW
-
Separator
-
0 400V / 3Ph +N / 50Hz
Power Supply
1 380V / 3Ph +N / 60Hz
684 m m
Downflow
Introduction
S R 12 D 0 55 - - C000 - 0

SD Nomenclature

S Product Name SmartCool
D Product Variant Dedicated Chil led Water
18 1800 mm 22 2200 mm 25 Case Width 2500 mm 31 3100 mm 35 3500 mm
D
Flow Conguraon
085-255 Nomi nal Cooling Capacity (kW)
- Separator
C Chilled Water
H Coil Streamed For High Flow
Coil Type
L Coil Streamed For Low Flow
C Chil led Water Circuit
Second Circuit
0 No Chi lled Water Circuit
H Coil Streamed For High Flow
Coil Type Second Circuit
L Coil Streamed For Low Flow
- Separator
0 400V / 3Ph + N / 50Hz 1 Power Supply 380V
Downow
/ 3Ph +N / 60Hz
S D 31 D 215 - C H 0 0 - 0
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
11
Page 12
SmartCool™ 6 - 200kW

Unit Overview

SN, SR Range

Cooling Coil
Introduction
Electric Heat
Precision Air Conditioning
Hinged Control Panel
Humidication
Chilled Water Valves Fans

SD Range

Air Filters
Humidier
Chilled Water Pipework
Floor Height
Floorstand
Fixed Control Panel
12
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 13
SmartCool™ 6 - 200kW
Chilled Water Components
SN, SR Range
Cooling Coil
Chilled Water Valves
Introduction
SD Range
Pipework Connections
Cooling Coil
Valves
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
13
Page 14
SmartCool™ 6 - 200kW

Chilled Water Components

Precision Air Conditioning
System Conguration
Range
Number of Circuits
SN SR SD
Single Single Dual Single Dual
Introduction
Hydrophilic Epoxy Coated RTPF Chilled Water Coil
0-10 Volts Chilled Water Regulating Valve (2 Way)
0-10 Volts Chilled Water Regulating Valve (3 Way)
0-10 Volts Chilled Water Regulating Valve (2 x 2-Way) Auto Commission
Pressure Independant Control Valve (PICV)
Chilled Water
Brazed Connections
Threaded Connections
Grooved Connections
Flanged Connections
Standard Features Optional Features – Feature Not Available
Chilled Water Coil
Chilled water coils shall be ideally positioned to optimise airow and heat transfer, they shall be manufactured from plain copper tubes with mechanically bonded aluminium ns. Fins shall be coated with a non-stick acrylic lm (hydrophilic) to provide additional corrosion protection and efcient surface water removal for improved performance. Plain aluminium
shall not be acceptable. The cooling coil shall be mounted over a full width stainless steel condensate tray. A 22mm
condensate drain hose connection shall be available. For control of water ow, various valve options shall be tted. The factory test pressure shall not be less than 20 Barg and the maximum operating pressure shall be less than 10.
Sweat copper pipe for brazed connection shall be standard. Optional threaded and Grooved connections shall be available.
14
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 15
SmartCool™ 6 - 200kW
Water Connection Types
SN06 SN09 SN12 SR09 SR12 SR15 SR18 SD18 SD22 SD25 SD31 SD35
Sweat Copper Connection
Threaded Pipe Connection
Grooved Water Connection
Flanged Connection
Standard Features Optional Features Feature Not Available
Threaded Water Pipe Connection
As an alternative to brazed water pipe connections, BSP brass male taper threaded connections shall be factory tted.
● ○
Nominal Diameter (mm)
DN15 15 1/2 DN20 22 3/4 DN25 28 1 DN32 35 1 1/4 DN40 42 1 1/2 DN50 54 2 DN65 67 2 1/2
Pipe Size (mm) Nominal Pipe size (Inch)
Introduction
Grooved Water Connections
Grooved water connections shall be avaliable enabling easy pipework termination.
Flanged Connections
For spool and unit termination, two types of ange shall be available. For the spool termination, a bespoke ange design shall incorporate a ange prole and gasket conguration. For the unit termination, a PN16 round bi-metallic ange shall be used. The unit termination end shall require staggering by 100mm to allow tting of the anges as shown.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
15
Page 16
SmartCool™ 6 - 200kW
Chilled Water Valves
Chilled Water Valve Options
SN06 SN09 SN12 SR09 SR12 SR15 SR18 SD18 SD22 SD25 SD31 SD35
2 Port Chilled Water Valves
Introduction
2 Port Chilled Water Valves with 2 Port Commissioning Valve
3 Port Chilled Water Valves
3 Port Chilled Water Valves with Bypass
Standard Features Optional Features – Feature Not Available
0-10 Volts DC 3 Port Chilled Water Regulating Valve (SN, SR Units)
– ○
Precision Air Conditioning
BL
BI
WTS
BI
Inlet
Coil(s)
DR
BI
M
BI
Outlet 0-10V DC 3 Port Regulating Valve
0-10 Volts DC 3 Port Chilled Water Regulating Valve with Bypass (SN, SR Units)
Coil(s)
BL
DR
BI
BI
0-10V DC 3 Port Regulating Valve
WTS
Bypass Valve
M
BI
Inlet
BI
Outlet
16
M
2 Port Regulating Valve
0-10V DC 3 Port Regulating Valve
M
BI
BL
Binder Point
Bleed Valve
Drain Valve
DR
Water Temperature Sensor
WTS
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
0-10V DC 2 Port Regulating Valve
Page 17
SmartCool™ 6 - 200kW
0-10 Volts DC 2 Port Chilled Water Regulating Valve (SN, SR, SD Units)
For systems with variable speed pumps and water ow, a 2 port control valve can be tted. The two port valve has a shut
off pressure of 13.6 Barg.
BL
BI
2 Port Valve
M
WTS
BI
Inlet
Coil(s)
DR
BI
Outlet
0-10 Volts DC 2 Port Chilled Water Regulating Valve with bypass for auto commissioning (SD Units)
For systems with variable speed pumps and water ow, a 2 port control valve can be tted The two port valve has a shut
off pressure of 13.6 Barg.
A bypass leg tted with a further 2 port valve enables auto commissioning. The auto commissioning shall be enabled by using a differential pressure transducer to maintain balanced water ow through the bypass. The controller maintains the same pressure drop through the coil and the bypass. A xed owrate is
required for this initial commissioning to occure.
BL
BI
2 Port Valve
WTS
BI
Introduction
Coil(s)
BI
BL
Binder Point
Bleed Valve
M
Inlet
Bypass Valve
DR
Outlet
M
2 Port Regulating Valve
0-10V DC 3 Port Regulating Valve
M
0-10V DC 2 Port Regulating Valve
Drain Valve
DR
Water Temperature Sensor
WTS
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
17
Page 18
SmartCool™ 6 - 200kW
Precision Air Conditioning
Pressure Independant Control Valve (PICV)
Pressure Independant Control Vales (PICV) tted to the SmartCool ensure that constant waterow is achieved. The PICV valves maintain the design owrate based upon the valve setup.
SN / SR Units
Introduction
DN20 DN25 DN32 DN40
SN06D-C000
SN09D-C000
SN12D-C000
SR09D-C000
SR12D-C000
SR15D-C000
SR18D-C000
Standard Features Optional Features Feature Not Available
Valve
SD Units
Valve
Unit DN20 DN25 DN32 DN40 DN50 DN65 DN80 DN100
SD18D-CH00 SD22D-CH00 SD25D-CH00 SD31D-CH00 SD35D-CH00 SD18D-CL00 SD22D-CL00 SD25D-CL00 SD31D-CL00 SD35D-CL00 SD18D-CHCH SD22D-CHCH SD25D-CHCH SD31D-CHCH SD35D-CHCH SD18D-CLCL SD22D-CLCL SD25D-CLCL SD31D-CLCL SD35D-CLCL
- - -
- - -
- - -
- - - -
- - - -
- - -
- - -
- - -
- - - -
- - - -
-
-
- -
- -
 
-
-
- -
 
 
 
   
     
- -
- - -
- -
- - -
- -
-
-
-
-
-
-
-
-
-
18
Standard Features Optional Features – Feature Not Available
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 19
SmartCool™ 6 - 200kW
Airow Components
System Conguration
Range SN SR SD
Number of Circuits Single Single Dual Single Dual
EC Backward Curved Centrifugal Fans in Unit
EC Backward Curved Centrifugal Fans in Floorstand
G4 Air Filtration
High Grade F7 Filtration
Airow Monitoring
Chilled Water
Airow Switch
Constant Air Volume
Constant Pressure Control
Standard Features Optional Features – Feature Not Available
Fan & Motor Assembly
Backward curved impellers, direct drive centrifugal fan assemblies shall be used with integral EC motors. They shall be dynamically balanced for quiet operation.
Fan speed, air ow and external static pressure shall be controlled by the use of a voltage controller which shall maintain
optimised performance and reduce energy consumption. Designed for high corrosion resistance, the impellers shall be composite plastic with a galvanised rotor.
– –
● ○ ○ ○
● ○ ○ ○
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
19
Page 20
SmartCool™ 6 - 200kW
Electronically Commutated (EC) Fan Motor
EC motors incorporate integrated electronics to convert AC power to DC for efcient and accurate speed control and are
adjustable via the microprocessor display keypad.
The fans offer maximum air ow performance while keeping sound levels to a minimum. It gives the exibility of connecting to AC mains with the efciency and simple speed control of a DC motor. The EC fan offers signicant power reduction in comparison with an equivalent AC fan at modulated fan speeds. The inbuilt EC fan
Introduction
control module allows for fan speed modulation from 15-100%. A standard AC fans modulating range is typically 40 -100% of full fan speed.
Standard voltage regulated (VR) fan speed controllers offer a linear response. The illustration on the right shows a comparison of the typical power input required by each method.
Precision Air Conditioning
Input Power
Airflow
Key
EC (Electronically Commutated) Fan Speed Control
Regulated (VR) Fan Speed Control
Standard Filtration
Pleated disposable panel lters in a rigid frame. Conform to ISO16890:2016 with ltration classes of ISO-C-85 (SN) ISO-C-75 (SR) and ISO-C-80 (SD)
Access and removal from unit front. As standard the microprocessor provides an alarm following a pre set run time limit
being exceeded.
High Grade ISO-1-60 Filtration
Pleated disposable panel lters conforming to ISO 16890:2016 with ltration class of ISO-C-60 shall be provided.
Air Flow Switch
An adjustable differential pressure switch shall activate a visual alarm at the status panel and break the power supply in the event of a fan or motor failure.
20
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 21
SmartCool™ 6 - 200kW

Electrical Components

Range SN SR SD
Number of Circuits Single Single Dual Single Dual
Door Interlocked Mains Isolator
Electrical Switch Gear
Customer Connection Terminals
Power Monitoring
Phase Monitoring Relay
Electrical
Standard Features Optional Features – Feature Not Available
* Fitted as standard when dual power supply is tted.
Ultra Capacitive Module (Controller Power Backup)*
Dual Power Supply
Variable Humidication
Electric Heating
Modulating Electric Heating
Introduction
System Conguration
● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
21
Page 22
SmartCool™ 6 - 200kW
Electrical Panels
The control panel contains the necessary contactors, transformer, sub circuit protection, volt free contacts for a common
alarm and mains and inter-connecting terminals. The panel is situated within the cabinet and is hinged to allow for
essential maintenance of other components within the unit (SN, SR Units only). The electrical control panels are wired to the latest European standards and codes of practice.
Control Panel Closed (SN, SR Units)
Introduction
Precision Air Conditioning
Control Panel Closed
Control Panel Open (SN,SR Units)
SD Units
Optional Control Panel
Control Panel Open
Standard Control Panel
22
Optional control panels are tted
dependant on which optional
features are tted
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Optional Control Panel
Page 23
SmartCool™ 6 - 200kW

Electric Heating

SN, SR Units
These shall be multi-stage nned electric heating elements complete with auto and manual reset overheat cut-out protection, element shall be phase balanced for increased efciency.
The electric heating elements are designed to be located between coil blocks, prior to fans. This enables the unit to
effectively re-heat the air and evenly distribute the temperature within the oor void. All sizes of electric heating are congurable based upon customer requirements. A maximum bank of 7.5kW is allocated per coil block. The avaliable heating shall be 3kW, 6kW or 7.5kW. Consequently the level of conguration is dependent on the number of coils in the unit.
SD Units
These shall be multi-stage nned electric heating elements complete with auto and manual reset overheat cut-out protection, element shall be phase balanced for increased efciency.
The electric heating elements are designed to be located within the unit’s fan module. This enables the unit to effectively
re-heat the air and evenly distribute the temperature within the oor void. All sizes of electric heating are congurable
based upon customer requirements. A bank of 7.5kW is allocated per fan and as standard each can be downsized in banks of 7.5kW. Consequently the level
of conguration is dependent on the number of fans in the unit.
Electric Heating Thyristor Control
In addition to the electric heat option a 0 – 100% Thyristor shall be provided to deliver accurate heating control.
Introduction
SN06 SN09 SN12 SR09 SR12 SR15 SR18 SD18 SD22 SD25 SD31 SD35
3kW Electric Heat
6kW Electric Heat
7.5kW Electric Heat
15kW Electric Heat
22.5kW Electric Heat
30kW Electric Heat
Standard Features Optional Features – Feature Not Available
– – – – ○ – ○ – ○ –
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
23
Page 24
SmartCool™ 6 - 200kW
Humidication
SN and SR Ranges
The SmartCool SN and SR range have congurable humidication selections delivering 3, 8,15 kg/hr:
● SN06 congurable with 3kg/hr only
● SN09 - SR15 congurable between 3 - 8kg/hr
Introduction
● SR15 - SR18 congurable between 3 -15kg/hr
Precision Air Conditioning
SD Range
The SmartCool SD Range has congurable humidication selections delivering 3, 8,15 or 30 kg/hr
● SD18 congurable between 3 - 8 kg/hr
● SD22 - SD35 congurable between 3 - 30 kg/hr
The exibility of the humidication options across the SmartCool SD range enables the humidication to be congured to
meet the customers design requirements and conditions.
Note: the 30 kg/hr option utilises 2 x 15 kg/hr bottles.
Humidication Sizes
24
SN06 SN09 SN12 SR09 SR12 SR15 SR18 SD18 SD22 SD25 SD31 SD35
3kg/hr Humidication
8kg/hr Humidication
15kg/hr Humidication
30kg/hr Humidication
Standard Features Optional Features – Feature Not Available
Inlet and Drain Connections
The humidiers have a 3/4” BSPF Braided Flexible Hose inlet connection and a 22mm drain hose connection. The humidier drain pump has a owrate of 7.0l/m.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 25
SmartCool™ 6 - 200kW
Humidication
Control Principles
In a humidier with electrodes, steam shall be produced by passing a current between electrode plates to generate heat.
The higher the current being passed between the electrodes, the greater the quantity of steam that is produced. To modulate the rate of steam production, this system shall vary the level of water within the cylinder, thereby increasing the immersion level of the electrodes and the current being passed between them. The more conducting area that is available to pass current between the electrodes, the larger the amount of steam that shall be produced. Modulated by the controller, the water level is varied so that the level of steam being produced ensures that the room
humidity set-point is continually maintained within a tight tolerance.
Optimised Lifetime
The life span of the Airedale humidication system shall be optimised by the inclusion of a water conductivity sensor
into the bottle feed. This sensor shall determine the conductivity level of the supply water and by using an algorithm embedded in the software, determines the frequency that the bottle should be drained.
Example: (Optimised Lifetime with High Water Conductivity Supply)
As liquid water is boiled off into steam, mineral deposits are left in solution increasing the conductivity of the water. To counter this, the intelligent software increases the frequency of drain meaning that the replenishing supply water keeps the concentration of minerals diluted. By maintaining an acceptable mineral concentration, the bottle lifespan is
maximised.
De-humidication
(With Electric Heating and Humidication only) Controlled by the microprocessor the de-humidication feature reduces fan speeds by 20% (adjustable). The reduction of fan speed increases de-humidication which means that the time taken to reduce the room humidity to the required level
is drastically decreased, along with the energy required to do so.
The return temperature is monitored during de-humidication to ensure that the temperature does not fall to a critical level. If the temperature reaches the low limit de-humidication is cancelled until the return air temperature increases.
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
25
Page 26
SmartCool™ 6 - 200kW
Precision Air Conditioning
Humidier - Intelligent Modulation
Humidication shall be provided by an electrode boiler. The sealed humidier design shall ensure that only clean sterile
steam is supplied to the conditioned area and corrosive salts and minerals are held in the disposable bottle. The steam
shall be distributed through a sparge pipe tted to the coil assembly.
Featuring modulating capacity output control as standard, the system shall provide continuous modulation of steam
output in response to a proportional control signal. The output control shall range from 20%-100% of the humidier rated
Introduction
value and be designed to give an approximate steam output of +/- 5% at 25°C (at the sensor), thus ensuring precise
control of the conditioned space. The cylinder operating life time shall be automatically optimised via the integrated water conductivity sensor, which
combined with the controls shall monitor and regulate the water rell cycle to reduce excessive salt deposits and the
progressive wear of the cylinder.
All humidier parameters and alarms shall be accessible and adjustable via the microprocessor display keypad unit, main features shall include not less than:
● Supply water conductivity (µS/cm)
● Actual steam output (kg/h)
● Required steam output (kg/h)
● Actual current rating (A)
● Required current rating (A)
● Status mode (Start Up, Running, Filling, Draining)
Water Conductivity & Cylinder Type
Three different cylinders shall be available which correspond to the supply water conductivity. The cylinder type shall be matched with the standard conductivity of the supply water to ensure optimum performance and to increase the life span of the cylinder. 1 Low Conductivity (Soft Water) 100 to 350 µS/cm 2 Standard Conductivity (Moderate / Hard Water) 350 to 750 µS/cm 3 High Conductivity (Very Hard Water) 750 to 1250 µS/cm Conductivity is a measure of the ability of water to pass an electric current, measured in micro Siemens / centimetre (µS/ cm).
As standard the humidier shall be tted with the standard conductivity cylinder which shall cover the majority of water
supplies. Where the water conductivity is known, please specify at order. For further details please contact Airedale.
26
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 27
SmartCool™ 6 - 200kW
Dual Power Supply
The SmartCool range shall be designed with dual power supply capability, so that in the event of a power failure the supply can be switched from utility to an alternative power supply (such as second utility or generator). A dual power supply changeover switch shall be provided to enable continuous power to the SmartCool in order to reduce unit downtime and therefore loss of cooling to a minimum. For the dual power supply feature to operate effectively the two incoming power supplies must have the same voltage and frequency. During changeover of power there is an interval of 180ms with no power. For critical applications a power backup module can be added to maintain power to the unit controls, allowing for immediate reinstatement of cooling following changeover.
The option as standard offers switch position status and supply priority set, both of which are congurable via the unit’s
display.
Supply priority set is fully congurable via the unit’s display and is used to set which of the two power supplies power will
be drawn from when both power supplies are active. Switch position status indicates to the end user which position the switch is currently in i.e. A or B and is shown via the unit’s display.
When the dual power supply is tted the UltraCap UPS is tted as standard.
Ultracap UPS
The Ultracap module is an external backup device for the controller. The module guarantees temporary power to the
controller in the event of power failures and allows for enough time to keep the controller running with time to change power supplies. The module is made using Ultracap storage capacitors (EDLC = Electric Double Layer Capacitor), which are recharged independently by the module.
These ensure reliability in terms of much longer component life than a module made with lead batteries: the life of the
Ultracap module is at least 10 years.
When the dual power supply is tted the Ultracap UPS is tted as standard.
Energy Manager
Analysis of system energy consumption can be monitored via a dedicated LCD display. Unit parameters can be adjusted via the unit microprocessor control to affect energy usage in line with the system need.
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
27
Page 28
SmartCool™ 6 - 200kW

Controls

Introduction
Precision Air Conditioning
Display for illustration only
System Conguration
Number of Circuits Single Single Dual Single Dual
PCO5 Microprocessor
Airetronix Controls
Vu™ Touch Screen Display
PGD1 Display (Door Mounted)
PGD1 Display with Audible Alarm (Door Mounted)
PDG Touch Display
Constant Air Volume
Constant Pressure Control
Temperature Control
Temperature & Humidity Control
Controls
Supply Air Temp Control
NTC Water Temperature Sensor / Probe
Filter Change Switch
BMS and SNMP Compatibility
Drip Tray Level Detection
Fire Detection
Smoke Detection
Water Detection
Range SN SR SD
● ○ ○ ○ ○ ○ ○ ○ ○ ○
● ○ ○ ○
● ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
28
Standard Features Optional Features – Feature Not Available
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 29
SmartCool™ 6 - 200kW
Vu™
The units shall be supplied with a European ROHS Directive 2002/95/EC compatible microprocessor controller connected to a 4.3” colour resistive TFT LCD touch screen display.
The microprocessor controller offers powerful analogue and digital control to meet a wide range of monitoring and control features including a real time clock and industry standard communication port and network connections.
All the SmartCool products feature a 32 bit microprocessor, offering signicant calculation power and operation
processing speed. Also featured is the facility to adjust and display control settings by local operator, for information and control.
Display / Keypad
The 4.3” touchscreen Vu™ display provides important unit status and allows page navigation with a swipe. The default screen shows the unit status and room condition (°C/RH %). Further screens offer adjustment to parameters, ne-tuning
of setpoints (via a rotating control wheel) and scrollable data tables. Trends of system information can be analysed and managed via the Vu™ allowing for easy system optimisation.
The operating status of the unit can also be easily be determined “at a glance” with a colour coded LED bar.
Introduction
Home
Main Menu
Current Alarms (and no. of alarms)
Help Screen
Unit Status
Network Address
Temperature
Humidity
Setpoint
Fan
Cooling
Heang
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
29
Page 30
SD - 4 Stages
SmartCool™ 6 - 200kW
Precision Air Conditioning
PGD1
The units shall be supplied with a European ROHS Directive 2002/95/EC compatible microprocessor controller connected to an 8 x 22 back-lit LCD keypad display. LEDs shall not be acceptable.
The microprocessor controller offers powerful analogue and digital control to meet a wide range of monitoring and control features including a real time clock and Industry standard communication port and network connections. All the boards feature a 16 bit microprocessor, and consequently the calculation power and operation processing speed
Introduction
have been signicantly increased.
Also featured are a visual alarm and the facility to adjust and display control settings by local operator for information and control.
Display / Keypad
The display keypad features a simple array of keys to navigate through the in built menus.
With an 8 x 22 character (132 x 64 pixel) screen size, back lit in white for improved contrast, the larger screen shall provide for user friendly viewing and easy status recognition by displaying a combination of text and icons.
The default screen shall show the unit status and room condition (°C/RH %) without the need for interrogation and an easy to navigate menu structure for further interrogation and adjustment shall be provided.
Fan Operating
Cooling - Variable
Heating - Various Stages SN - 2 Stages SR - 3 Stages
De-humidication
Humidication - Variable
30
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 31
SmartCool™ 6 - 200kW
Controls
Password Protection
The control system integrity shall be maintained by restricting access with a password PIN number.
IMPORTANT
To change the PIN , please contact Airedale at time of order with the preferred 4 digit number.
Remote On/Off
Terminals for interlocking shall be provided to enable or disable the unit remotely.
Fire Shut Down
Terminals for interlocking shall be provided to shut down the unit in the event of re.
Evaporator Fan Hours Run Log & Reset
Shall allow the user to monitor the running times of the evaporator fans and reset after maintenance. Hours run log or visual service indicator shall be provided.
Evaporator Fan Speed Control
Evaporator fan speed control shall be easily set via the display keypad and can be incrementally increased or decreased
to meet on site airow and external static pressure requirements.
Filter Change Alarm
Filter change shall be managed by the software, and shall be based on fan(s) hours run with an alarm being generated
when the pre-set run time limit has been exceeded. The set-point value shall be adjusted to suit each application and is
factory set to 4000 hours.
Standard Network Features
As standard the controller shall be capable of providing a platform for the following and shall be enabled on request for 2
to 8 units, please specify at order:
Networking
A Local Area Network (pLAN ) shall be used to connect up to 8 units to offer intercommunication and Run / Standby control. This also allows the connection of computers, printers and modems on the same communications ring. For further details, please contact Airedale Controls.
Introduction
CAUTION
When adding to an existing network, please consult Airedale to ensure strategy compatibility.
Run / Standby Operation
The controller shall enable units to operate in run/standby mode, with up to 8 units networked together, without the need
for additional hardware or controllers. Standby units shall be congured to start when the run unit has a critical alarm.
Smart Key
A smart key shall be supplied to offer software back-up of the control strategy. The key shall feature simple plug in
operation and allow transfer of software programs from the key to the microprocessor and vice versa. The use of a service laptop shall not be necessary.
Audible Alarm
The display keypad shall be upgraded to include audible alerts.
Water Detector
Three methods shall be available:
1. A solid state (probe) sensor shall be supplied loose for remote mounting on site.
2. Tape suitable for sensing water droplets shall be supplied loose for remote mounting on site. Standard tape length 10m.
3. Condensate drain tray level detection.
Fire Detection
Shall be supplied loose for installation in the return air stream to shut down the unit in the event of an unusually high return air temperature.
Smoke Detector
Shall be supplied loose for remote mounting to shut down the unit and activate the alarm upon sensing the presence of smoke.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
31
Page 32
SmartCool™ 6 - 200kW
Precision Air Conditioning
Controls
Temperature Control
A temperature sensor shall be mounted in the return air side of the unit to sense the return dry bulb condition (cooling only variants). A combined temperature and humidity sensor shall be supplied on full function units.
The temperature sensor shall be an NTC type thermistor with an accuracy of not less than +/ - 5% at 25°C at the sensor.
The microprocessor shall sense the return air conditions and maintain the return air temperature and humidity by
Introduction
controlling cooling, heating, humidication and dehumidication outputs accordingly. The microprocessor shall monitor and display the following values as a minimum:
● Return Air Temperature
● Return Air Humidity (Optional on Full Function units)
● Fan run hours
● Coil Temperature Sensor (Indoor)
The maintenance of key components such as air lters shall be monitored via a service indicator which visually
demonstrates the status relative to the component service intervals.
Alarm Log
The controller shall log and allow viewing of not less than the last 100 conditions recorded in descending chronological order through the keypad display.
The standard display keypad shall visually display operating alarms, however, as an optional extra, a display keypad with
audible alarms is available.
Supply Air Temperature Control
Modulation of unit capacity to ensure that user dened supply air set points shall be maintained and / or a high / low
return air temperature alarm. During peak demand, the standby units shall temperature assist.
Duty Rotation
Networked units shall be congured to duty rotate, providing equal hours run of fans.
BMS Interface Cards
BMS Interface Card controlled units shall be interfaced with most BMS, factory tted, please contact Airedale.
A wide range of protocols shall be accommodated through the use of interface devices. Available as a standard option
are: ModBus / Jbus, and Carel.
For interfaces such as SNMP, LonWorks, Metasys and BACnet, please contact Airedale.
Also available shall be Airedale’s own supervisory plug-in BMS card pCOWEB.
Based on Ethernet TCP/IP secure technology with SNMP features.
It shall require no proprietary cabling or monitoring software and be supplied pre - programmed with an IP address for
ease of set up. Cables to the BMS to be supplied by others.
32
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 33
SmartCool™ 6 - 200kW
Controls
Constant Pressure Control
Constant pressure control is a method of controlling air pressure within a space, such as a oor void or a duct. The air
pressure is controlled using a variable speed fan that is modulated to maintain a given set point. Constant pressure control monitors the air pressure differential between two points. In a typical application (shown
below) the pressure under the raised oor (red) is compared to the room pressure (blue).
Introduction
The two pressure points, positive and negative, are routed back to an air differential pressure sensor inside the CRAC unit. The value from the air pressure sensor is compared to the set point and a fan speed demand is generated, to maintain the required pressure differential.
It is the responsibility of the installer to t the air pressure sensor(s). The sensor shall be be located under the false oor with the 6mm amtronix tubing routed back into the control panel of the unit (the tubing must not be obstructed /
damaged to ensure accurate pressure control). The contant pressure system shall be commissioned by Airedale following routing of tubing from the pressure diffuser and the unit.
A maximum of 8m/s air velocity is allowed at the diffuser so consideration must be made to its location.
Constant Air Volume
Constant air volume is a method of automatically adjusting the unit fan speed to deliver a specic air volume.
When faced with a change in system resistance, the fan speed modulates to obtain the air volume set point. Constant air volume monitors the air pressure differential between two points. These two pressure points, positive and negative, are routed back to an air differential pressure sensor inside the unit.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
33
Page 34
SmartCool™ 6 - 200kW

General Features

Introduction
Precision Air Conditioning
System Conguration
Range SN SR SD
Circuits Single Single Dual Single Dual
Condensate Pump (Hot or Cold Water)*
Condensate Drain Tray Monitoring
Straight and “L” Shaped Ceiling Duct Extensions
Open Floorstand
General
Front and Rear Floorstands (enclosed)
UPS Floorstand
Sterling Board LAT (Wooden Case) Packing
Standard Features Optional Features – Feature Not Available
○ ○
○ ○ ○ ○ ○ ○ – ○
*Condensate pump type depends if humidication is selected.
Open & Enclosed Floorstand
Open or enclosed oor stands shall be available, complete with adjustable feet and oor tile lip. Enclosed oor stands shall incorporate an air turning vane (SN,SR only). The height of the oor stand shall be specied at order.
Discharge Air Conguration
Standard conguration shall be downow “draw through” design.
Straight and L shaped Ceiling Duct Extension
Straight and ‘L’ shaped duct extensions up to a height of 1350mm shall be constructed and nished to match the unit. For extensions greater than 1350mm, please contact Airedale. Height shall be specied at order.
Sterling Board LAT (Wooden Case) Packing
Units shall be supplied complete with additional LAT corner protection and cross braces to afford extra transit protection.
Sterling board heat treated man made material shall be used (including pallet) to comply with phytosanity import regulations, please contact Airedale for this option.
34
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 35
SmartCool™ 6 - 200kW
Condensate Pumps
The SmartCool condensate pump shall be either hot water (full function units when a humidier is tted) or cold water
type (cooling only).
Performance
The following graphs illustrate the TOTAL static (head) pressure available. The system horizontal pipe losses and vertical lift should be factored in when calculating the condensate pump performance.
Cold Water (Cooling only units)
SN, SR Units
6
The cold water condensate pump has
10mm quarter turn plastic “barbed”
connection.
The discharge line from the pump should rise no more than 4 metres before being interrupted with a swan neck air break and tundish.
SD Units
5
4
3
Head (m)
2
1
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0
Flow Rate (l/min)
9
8
7
6
5
4
Head (m)
3
2
1
0
2.0 2.5 3.0 3.5 4 .0 4.5 5.0 5.5 6.0
Flowrate l/min
Introduction
Hot Water (Full function units, SN,SR,SD type units)
The hot water condensate pump
12
uses 10mm (3/8”) copper tube when
connecting to the discharge stub of the
10
8
6
Head (m)
4
pump.
The discharge line from the pump should rise no more than 6 metres vertically and no more than 8 metres in total length before being interrupted
2
0
5.0
9.07.0 13.0 15.011.0
Flow Rate (l/min)
with a swan neck air break and tundish.
Condensate Drain Tray Monitoring
A oat level switch shall be incorporated into the unit drain tray for indication of a high water alarm.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
35
Page 36
SmartCool™ 6 - 200kW

Installation Data

Dimensions

SN/SR
Installation
Precision Air Conditioning
Height
Depth
Detail of the doors and return air ducting centres is available from the general arrangement drawings upon request.
Length
Length Height Depth
SN06D mm 684 1980 600
SN09D mm 963 1980 600
SN12D mm 1242 1980 600
SR09D mm 963 1980 890
SR12D mm 1242 1980 890
SR15D mm 1521 1980 890
SR18D mm 1800 1980 890
36 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 37
Installation Data
Dimensions
SD
SmartCool™ 6 - 200kW
Installation
Depth
Length
Height
C
Length Height Depth
SD18D mm 1800 1980 890
SD22D mm 2200 1980 890
SD25D mm 2500 1980 890
SD31D mm 3100 1980 890
SD35D mm 3500 1980 890
Detail of the doors and return air ducting centres is available from the general arrangement drawings upon request.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
37
Page 38
SmartCool™ 6 - 200kW
Precision Air Conditioning
Installation Data

Lifting

Whenever a unit is lifted, it should be from the base and, where possible, with all packing and protection in position. If any type of slinging is used, due care should be taken to ensure that the slings do not crush the casework.
IMPORTANT
If the unit is dropped, it should immediately be checked for damage and reported to Airedale.

Positioning & Levelling

The unit should be positioned on a stable and even base. With the use of a spirit level the base should be levelled to ensure good condensate removal and prevent door misalignment. Positioning the unit should be achieved by the use of rollers or skids. Crowbars must not be used as they impose a point load on the unit frame which may cause damage and distortion.
● Check the unit is as ordered. Discrepancies or transit damage should be reported to Airedale immediately.
Installation
● This small footprint unit is relatively tall and heavy. Care should be taken during handling and lifting, that the unit is well supported and properly balanced.
● Observe airow and maintenance clearances
● Check all services are present and accessible
CAUTION
Airedale will accept no responsibility for mishandling during the positioning of the equipment.

Unpacking

The unit is to be carefully unpacked. Inspected and any damage reported to Airedale immediately.
All packaging is to be recycled accordingly.
38 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 39
Positioning

Minimum Unit Clearance SN, SR

Open and Enclosed Floorstand Option
SmartCool™ 6 - 200kW
D
Installation
A B C - Floorstand
(3)
SN06D mm 684 600
SN09D / SR09D mm 963 880
SN12D / SR12D mm 1242 880
SR15D
mm 1521 880
Min 350 – Max 750
(+ 50mm Feet Adjustable
+/-20mm)
(4)
SR18D mm 1800 880
Minimum Ceiling Clearance- (D)
Forward Only
Forward and
1 Side
Forward and
2 Sides
All Faces
SN06D mm 720 500 380 250
SN09D / SR09D mm 720 500 380 250
SN12D / SR12D mm 720 500 380 250
SR15D mm 740 550 440 280
SR18D mm 750 590 480 300
(1) Shown with optional open oor stand.
(2) Shaded area indicates minimum service and maintenance requirements. The unit must be installed with allowance for carpet tile clearance.
(3) Dimension C denotes recommended minimum/maximum oor stand height, refer to Airedale for special applications, please specify at order. (4) Min = Threaded foot at minimum extension (additional to “C” dimension). Max = Threaded foot at maximum extension (additional to “C” dimension).
Packed Dimensions
For specic markets units shall be shipped, mounted on wooden pallet and covered with polythene. The pallet shall be mechanically xed to the unit for transportation only (Please contact Airedale for this option). Add 50mm to length and
width and 160mm to height.
WIDTH + 50mm
DEPTH + 50mm
HEIGHT + 160mm
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
39
Page 40
SmartCool™ 6 - 200kW
Positioning
Installation

Minimum Unit Clearance SD

Open and Enclosed Floorstand Option
Precision Air Conditioning
A B C - Floorstand
SD18D mm 1800 880
SD22D mm 2200 880
SD25D mm 2500 880
SD31D mm 3100 880
SD35D mm 3500 880
Minimum Ceiling Clearance- (D)
SD18D mm 720 500 380 250
SD22D mm 720 500 380 250
SD25D mm 720 500 380 250
SD31D mm 740 550 440 280
SD35D mm 750 590 480 300
(1) Shown with standard open oor stand.
(2) Shaded area indicates minimum service and maintenance requirements. The unit must be installed with allowance for carpet tile clearance.
(3) Dimension C denotes recommended minimum/maximum oor stand height, refer to Airedale for special applications, please specify at order.
Forward Only
Forward and
1 Side
Min 600 – Max 750
Forward and
2 Sides
(3)
All Faces
40 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 41
Pipework Schematics
SN/SR Single Circuit
SmartCool™ 6 - 200kW
WTS
BI
OPTIONAL
BL BL
BI
M
or
DR
BI
Internal Pipework
BL BL BL BL
Installation
SN06
2 COILS
M
SN/SR09
3 COILS
SN/SR12 4 COILS
SR15
5 COILS
SR18
6 COILS
OPTIONAL
BI
BINDER POINT
BI
BL
BLEED VALVE
DR
DRAIN VALVE
2-WAY REGULATING BALL VALVE
OPTIONAL
Floor
Customer Connections
BI
External Pipework
WTS
M
WATER TEMPERATURE SENSOR
3-WAY REGULATING BALL VALVE (ACTUATOR DRIVEN)
THREADED CONNECTION (BSPT MALE)
Ensure binder points are installed on both inlet/outlet pipes post unit.
2-WAY REGULATING BALL VALVE (ACTUATOR DRIVEN)
M
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
41
Page 42
SmartCool™ 6 - 200kW
Pipework Schematics
SR Dual Circuit
Precision Air Conditioning
OPTIONAL
BI
WTS
OPTIONAL
OPTIONAL
BI
DR
M
or
BI
M
Installation
BL
BL
BI
BL
BL
BL
BL
BL
BL
BL
BL
BL
BL
M
WTS
BI
DR
BI
OPTIONAL OPTIONAL
BI
BINDER POINT
BI
BL
BLEED VALVE
DR
DRAIN VALVE
2-WAY REGULATING BALL VALVE
BI
M
or
Internal Pipework
Floor
Customer Connections
External Pipework
WATER TEMPERATURE SENSOR
WTS
3-WAY REGULATING BALL VALVE (ACTUATOR DRIVEN)
M
THREADED CONNECTION (BSPT MALE)
SR09
3 COILS
SR12
4 COILS
SR15
5 COILS
SR18
6 COILS
Ensure binder points are installed on both inlet/outlet pipes post unit.
2-WAY REGULATING BALL VALVE (ACTUATOR DRIVEN)
M
42 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 43
Pipework Schematics
SD Single Circuit
SmartCool™ 6 - 200kW
BL
CHILLED WATER COIL
OUTLET LEG
DR
OPTIONAL BYPASS LEG
M
PDZAL
M
BI
BL
Installation
DR
WTS
BI
INLET LEG
SD Dual Circuit
Dual circuit units have two single circuits duplicated.
BI
BL
BINDER POINT
BLEED VALVE
DR
WTS
DRAIN VALVE
WATER TEMPERATURE SENSOR
M
2 WAY REGULATING BALL VALVE (ACTUATOR DRIVEN)
PDZAL
DIFFERENTIAL PRESSURE TRANDUCER
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
43
Page 44
SmartCool™ 6 - 200kW

Incoming Services

SN Single Circuit
VIEW FROM ABOVE
Precision Air Conditioning
79
G
E
92
Installation
SR Single Circuit
F
B
179
105
A DIA 22mm WATER INLET B DIA 22mm WATER OUTLET E POWER (CONNECT VIA EXTERNAL CONNECTION BOX) F CONTROLS (CONNECT VIA CONNECTORS) G CONDENSATE DRAIN (TEE TO HUMIDIFIER DRAIN - IF USED) H HUMIDIFIER DRAIN (TEE TO CONDENSATE DRAIN) J HUMIDIFIER FILL
A
93
FRONT OF UNIT
186
72
684
H
J
70
163.8
G
600
80
79
521
451
272
E
VIEW FROM ABOVE
F
B
105
A
FRONT OF UNIT
963
199
75
254
129
A DIA 35mm WATER INLET B DIA 35mm WATER OUTLET E POWER (CONNECT VIA EXTERNAL CONNECTION BOX) F CONTROLS (CONNECT VIA CONNECTORS) G CONDENSATE DRAIN (TEE TO HUMIDIFIER DRAIN - IF USED) H HUMIDIFIER DRAIN (TEE TO CONDENSATE DRAIN) J HUMIDIFIER FILL
H
J
98
216
80
92
343
632.5
890
811
44 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 45
Incoming Services
SR Dual Circuit
SmartCool™ 6 - 200kW
E
D
VIEW FROM ABOVE
C
556
408
259
111
A DIA 42mm CIRCUIT 1 WATER INLET B DIA 42mm CIRCUIT 1 WATER OUTLET C DIA 42mm CIRCUIT 2 WATER INLET D DIA 42mm CIRCUIT 2 WATER OUTLET E POWER (CONNECT VIA EXTERNAL CONNECTION BOX) F CONTROLS (CONNECT VIA CONNECTORS) G CONDENSATE DRAIN (TEE TO HUMIDIFIER DRAIN - IF USED) H HUMIDIFIER DRAIN (TEE TO CONDENSATE DRAIN) J HUMIDIFIER FILL
105
B
A
FRONT OF UNIT
1800
199
J
75
G
92
79
Installation
890
811
F
80
H
98
216
632.5
343
SN, SR Electrical Power Connections
FRONT OF UNIT
HUMIDIFIER DRAIN
FLOOR LEVEL
HUMIDIFIER FILL
CUSTOMER POWER CONNECTIONS
HUMIDIFIER (OPTIONAL)
CONTROLS IN
CONDENSATE DRAIN
POWER IN
CONDENSATE PUMP (OPTIONAL)
VIEW ON RIGHT HAND SIDE
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
45
Page 46
SmartCool™ 6 - 200kW
Incoming Services
SD Single Circuit
1980
Installation
Precision Air Conditioning
SD Dual Circuit
FLOOR LEVEL
H
H VARIES CLIENT SPECIFIED FLOOR VOID
1980H
170
247
WATER INLET
WATER OUTLET
L
FLOOR LEVEL
29890
2ND GLAND POINT FOR DUAL POWER OPTION
106
POWER CABLE AND GLAND POINT
FLOOR LEVEL
H VARIES CLIENT SPECIFIED FLOOR VOID
170
115
236
WATER INLET CIRCUIT 2
WATER OUTLET CIRCUIT 2
WATER INLET CIRCUIT 1
WATER OUTLET
CIRCUIT 1
L
238
115
108
170
FLOOR LEVEL
36890
2ND GLAND POINT FOR DUAL POWER OPTION
POWER CABLE AND GLAND POINT
46 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 47

Glycol

Specic Heat Capacity (C
Water/Glycol
Temperature °C
20 4.183 3.972 3.815 3.645 3.468 25 4.181 3.981 3.826 3.660 3.485 30 4.179 3.989 3.838 3.674 3.502 35 4.178 3.998 3.849 3.688 3.518 40 4.179 4.007 3.861 3.702 3.535 45 4.181 4.015 3.872 3.716 3.552
0% / 0°C 10% / -4°C 20% / -9°C 30% / -15°C 40% / -23°C
Density (ρ) (kg/m³)
Water/Glycol
Temperature °C
20 998 1013 1030 1045 1060 25 997 1012 1028 1043 1058 30 996 1010 1026 1041 1055 35 994 1008 1024 1039 1053 40 992 1006 1022 1036 1050 45 990 1003 1020 1035 1048
0% / 0°C 10% / -4°C 20% / -9°C 30% / -15°C 40% / -23°C
SmartCool™ 6 - 200kW
) (kj/kg K)
p
Ethylene Glycol (Volume) / Freezing Point °C
Cp Cp Cp Cp Cp
Ethylene Glycol (Volume) / Freezing Point °C
ρ ρ ρ ρ ρ
Installation
Pressure Drop Correction Factor (Px)
Water/Glycol
Temperature
°C
20 0.983 1.0125 1.054 1.0958 1.15
(1) All data based upon ASHRAE fundamentals 2001.
0% 10% 20% 30% 40%
Px Px Px Px Px
Ethylene Glycol (Volume)
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
47
Page 48
SmartCool™ 6 - 200kW
Water Detector Tape Installation

Water Detection Tape Installation

Monitored by a sensing relay, the water detection tape will provide an alarm when in contact with several drops of conductive liquid. High humidity should normally not cause an alarm unless it results in condensation dripping on the tape surface or condensation present on the surface to which the tape is applied. The recommended installation process is as follows:
● When applying to a surface such as concrete, the most popular method is to press the tape fi rmly onto a
continuous fi lm of approved adhesive or glue. When properly glued to the fl oor the tape lies fl at on the fl oor avoiding “bridging” (where the detector lifts off the fl oor allowing water to run under the detector without detection)
and avoids damage to the detector
● When applying the tape directly to the piping, the tape is simply strapped to the pipe
● Care should be taken to prevent the wire detectors in the tape from coming into contact with any electrically conductive material causing a “fault” condition. Anything used in applying the tape which interferes with the
capability of the fl eece substrate may adversely affect the detector’s function
● The tape should not be installed under piping or equipment that can condense liquid as the condensation could drip on the tape causing an alarm
● The tape should not be installed directly under an air handling unit, but around the unit
● In the sub-fl oor of a computer room the tape should be installed after the raised fl oor, conduit and piping are
installed and the sub-fl oor cleaned and sealed
Any adhesive which alters the chemical composition of the tape must be avoided and any use thereof voids any warranty, expressed or implied. 3M Scotch-Weld™ 77 adhesive is strongly recommended to ensure the warranty will be maintained. When adhesive is used, adhesive with an
IMPORTANT
oily or greasy base MUST be avoided as this will affect the tape’s ability to detect moisture. When the use of an adhesive is not desirable or practical, staples, clips or other devices may be used. When applying the tape to piping a combination of glue and plastic or nylon straps or wire ties may be used. The straps or ties help to cut down installation time and secures the tape to the pipe while the adhesive cures and dries.
Precision Air Conditioning
Any electrically conductive attachment devices used must not touch the wires that are within the tape fabric. The maximum length of a detector loop, including wire and detector tape is 50 metres. However, this tape length is not practical for most applications. Where the tape is concealed or not easily accessible, tape runs should be limited to no more than 30 metres, and 10 to 15 metres per zone is generally used. If the water detector tape is to be attached to or covered by a metallic or
CAUTION
For further information, please refer to Airedale’s Technical Bulletin and Loose Part Instruction Manual.
conductive surface, care should be taken not to short the conductors. When installing tape to any surface, be careful not to short circuit or ground out the conductors (such as over/under conduit or sharp edges of cable trays etc.). This also applies to any covering which may be applied over the tape. Before installing the tape, be sure to inspect areas where the tape is to be applied for presence of chemical materials that could create problems. If in doubt, it is
recommended to clean the fl oor with a mild detergent.
48 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 49

pLAN Termination

Customer Side
SmartCool™ 6 - 200kW
Technic a l C0C0
RxTx -
RxTx +
CAUTION
RxTx -
RxTx +
GND
The plugged termination ensures that the connections are made simultaniously. Failure to attached the cables this way may cause damage to the controller.
GND
Panel Side
C000SN
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
49
Page 50
SmartCool™ 6 - 200kW

Technical Data SN C000 Units

Mechanical and Electrical Data

Precision Air Conditioning
Mechanical Capacity
Nom Cooling (Gross) (1) kW 12.8 16.8 21.7 26.9 31.3 36.3 Fan Power Input (Fan Gain) (2) kW 0.25 0.62 0.65 1.32 0.99 1.75
Dimensions -D(600) x H(1980)
Width mm 684 963 1242 Weight - Machine (3) kg 181 181 242 242 294 294
- Operating kg 194 194 262 262 319 319
Cooling Coil
Water volume l 13 13 19 19 25 25 Water ow rate l/s 0.61 0.8 1.03 1.28 1.49 1.73 Pressure drop kPa 18.7 31.8 23.2 35.4 24.8 32.9
Fan & Motor
Quantity x Motor Size (4) kW 1 x 0.78 1 x 0.78 1 x 2.5 1 x 2.5 1 x 2.4 1 x 2.4 Speed @25Pa ESP rpm 1954 2590 2120 2474 1985 2361
Speed @maximum ESP rpm 2680 2680 2970 2970 2400 2400 Maximum ESP Pa 552 87 1126 618 589 85 Nominal Airow m³/s 0.70 0.95 1.20 1.55 1.75 2.10
Connections
Water Inlet / Outlet mm 22.0 22.0 28.0 28.0 35.0 35.0
Filtration
Quantity 6 6 9 9 12 12
Electric Heating
Rating kW 3.0 3.0 6.0 6.0 6.0 6.0 Stage of Reheat 1 1 2 2 2 2
Humidier
Capacity kg/hr 3 3 8 8 8 8
SN06D010-C000
SN06D015-C000
SN09D020-C000
SN09D025-C000
SN12D030-C000
SN12D035-C000
Electrical Unit Data - Full Function (5)
C0C0 Technic a lC000 SN
Nominal Run Amps A 10.3 10.3 22.4 22.4 22.3 22.3 Recommended Mains Fuse Size A 16 16 32 32 32 32
Unit Data - Cooling Only
Nominal Run Amps A 2.55 2.55 5 5 4.9 4.9 Recommended Mains Fuse Size A 10 10 10 10 10 10 Max Mains Incoming Cable Size mm² 16 16 16 16 16 16
Fan and motor
Full Load Amps A 1.6 1.6 4 4 3.9 3.9
Electric Heat
Current Per Phase A 4.4 4.4 8.7 8.7 8.7 8.7
Humidier
Rating kW 2.25 2.25 6 6 6 6 Full Load Amps A 3.3 3.3 8.7 8.7 8.7 8.7
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP. (3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5)
Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
50 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 51
Technical Data SN C000 Units
2
 
 
M
Q
 
 
36
Kv

Waterside Pressure Drop Data

180
160
140
120
100
80
Pressure Drop (kPa)
60
40
20
0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50
1
Flow Rate (l/s)
SmartCool™ 6 - 200kW
2
3
Technic a l C0C0C000SN
1 SN06D010-C000 / SN06D015-C000 2 SN09D020-C000 / SN09D025-C000 3 SN12D030-C000 / SN12D035-C000
Includes coil, 2 or 3 port valve and pipework.
To calculate 3 port valve pressure drop:
∆P valve = where ∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
● Fluid 100% water.
Valve Kv M
SN06 C000 10.0 0.28 SN09 C000 16.0 0.44 SN12 C000 25.0 0.69
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
51
Page 52
(3)
(1)
SmartCool™ 6 - 200kW
Precision Air Conditioning

Measurement of Sound Data

All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated sound intensity meter in accordance with BS EN ISO9614 Part 1: 2009. All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO9614 Part 1:
2009.
Semi Hemispherical
Sound Pressure Levels are calculated from sound power using the semi-hemispherical method where the noise source is in junction with 2 boundaries i.e. the oor and 1 wall.
Free Field
For comparison, the semi hemispherical gures can typically be reduced by 6dB to provide free eld conditions.
IMPORTANT
The sound data quoted is based on the unit having a ducted return air and standard backwards curved EC motors tted,
refer to illustration below. Case breakout sound data is therefore independent of the discharge air and return air sound data.
For non-ducted return air applications, the overall case breakout sound levels may increase, due to the return air sound
being predominant.
Within the conditioned space, sound from in-room ducted discharge air grilles and other equipment will contribute to the
overall sound level and should therefore be considered as part of sound calculations. Specialist acoustic advice is recommended for noise critical applications.
(2)
(1) Return Air (2) Case Breakout (3) Discharge Air
52 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 53
Technical Data

Sound Data

Overall
Sound Measurement 63 125 250 500 1000 2000 4000 8000 Discharge Air 70 64 66 71 69 64 58 51 27
SN06D010-C000
SN06D015-C000
SN09D020-C000
SN09D025-C000
SN12D030-C000
SN12D035-C000
(1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air 68 64 66 69 68 63 58 50 26 Case Breakout 70 68 71 72 69 64 58 51 30 Sound Pressure @ 3m 56 53 57 58 54 50 44 37 15 Discharge Air 81 75 76 81 80 75 69 62 38 Return Air 79 75 76 79 79 73 68 61 37 Case Breakout 81 79 82 83 80 75 69 62 41 Sound Pressure @ 3m 66 64 67 68 65 61 54 48 26 Discharge Air 69 68 70 74 69 60 57 51 34 Return Air 68 68 70 72 68 58 56 50 34 Case Breakout 70 72 75 76 68 60 56 52 37 Sound Pressure @ 3m 56 57 61 61 54 45 42 37 23 Discharge Air 76 73 72 82 75 67 63 57 40 Return Air 75 73 72 80 74 65 62 56 39 Case Breakout 77 77 77 83 74 67 63 57 43 Sound Pressure @ 3m 62 62 63 69 60 52 48 43 29 Discharge Air 69 65 72 73 67 60 57 56 37 Return Air 68 65 72 71 66 58 56 55 36 Case Breakout 70 69 78 75 67 60 57 57 40 Sound Pressure @ 3m 55 55 63 60 52 45 42 42 26 Discharge Air 73 64 74 78 71 64 62 58 44 Return Air 72 64 73 76 70 62 61 57 43 Case Breakout 74 68 79 79 71 64 61 58 47 Sound Pressure @ 3m 59 53 64 65 56 49 47 44 32
dB(A)
SmartCool™ 6 - 200kW
Frequency (Hz) dB
Technic a l C0C0
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
C000SN
53
Page 54
N1
Neutral (Supply 1)
301
L1 (Supply 1)
302
L2 (Supply 1)
303
L3 (Supply 1)
N2
Neutral (Supply 2)
304
L1 (Supply 2)
305
L2 (Supply 2)
306
L3 (Supply 2)
PE
Protective Earth
502
Fire Detector
583
Fire Detector
583
Smoke Detector
584
Smoke Detector
502
Remote On/Off
522
Remote On/Off
2
Condensate Pump Supply (230V)
N (3*)
Condensate Pump Supply (230V)
534
Condensate Pump High Level Alarm
535
Condensate Pump High Level Alarm
609
Flood Detection Tape / Probe
610
Flood Detection Tape / Probe
810
Supply Air Temperature Sensor
811
Supply Air Temperature Sensor
560
Non-Critical Alarm N/O
561
Non-Critical Alarm Common
563
Critical Alarm N/O
564
Critical Alarm Common
565
Critical Alarm N/C
881
BMS Connection
882
BMS Connection
883
BMS Connection
Conn 15
Conn 16
Conn 17
Conn 14
Conn 14
PIN 1
SmartCool™ 6 - 200kW
Technical Data SN C000 Units

Interconnecting Wiring

Precision Air Conditioning
CONN17
CONN14
CONN16
CONN15
PIN 1
PIN 1
Pin No. Wire
1 502
2 583 or 584
3 2
4 N or 3
PIN 1
Pin No. Wire
1 502
2 522
3 560
4 561
5 563
6 564
7 565
Pin No. Wire
1 2
2 N or 3
3 PE
4 534
5 535
6 609
7 610
8 810
9 811
C0C0 Technic a lC000 SN
Pin No. Wire
1 881
2 882
3 883
54 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 55

Technical Data SR C000 Units

Mechanical and Electrical Data

SmartCool™ 6 - 200kW
Mechanical Capacity
Nom Cooling (Gross) (1) kW 34.7 42.3 50.3 60.1 70.0 76.3 84.6 98.3 Fan Power Input (Fan Gain) (2) kW 0.8 1.45 1.25 2.34 2.12 2.79 2.22 3.8
Dimensions -D(600) x H(1980)
Width mm 963 1242 1521 1800 Weight - Machine (3) kg 307 307 380 380 461 461 528 528
- Operating kg 337 337 420 420 512 512 593 593
Cooling Coil
Water volume l 30 30 40 40 51 51 65 65 Water ow rate l/s 1.65 2.01 2.4 2.86 3.33 3.63 4.03 4.68 Pressure drop kPa 25.9 37.4 30.8 41.9 46.8 54.4 35.3 46.3
Fan & Motor
Quantity x Motor Size (4) kW 1 x 1.96 1 x 1.96 1 x 2.9 1 x 2.9 2 x 1.96 2 x 1.96 2 x 2.9 2 x 2.9 Speed @25Pa ESP rpm 1174 1440 1313 1592 1276 1400 1227 1455
Speed @maximum ESP rpm 1560 1560 1660 1660 1560 1560 1660 1660 Maximum ESP Pa 463 202 508 129 354 227 557 325 Nominal Airow m³/s 1.85 2.30 2.70 3.30 3.80 4.20 4.60 5.50
Connections
Water Inlet / Outlet mm 35.0 35.0 42.0 42.0 42.0 42.0 54 54
Filtration
Quantity 9 9 12 12 15 15 18 18
Electric Heating
Rating kW 7.5 7.5 15 15 15 15 22.5 22.5 Stage of Reheat 1 1 2 2 2 2 3 3
Humidier
Capacity kg/hr 8 8 8 8 15 15 15 15
SR09D030-C000
SR09D040-C000
SR12D045-C000
SR12D055-C000
SR15D065-C000
SR15D075-C000
SR18D080-C000
SR18D095-C000
Technic a l C0C0C000SR
Electrical
Unit Data - Full Function
Nominal Run Amps A 26.4 26.4 35.8 35.8 50.6 50.6 58.7 58.7 Recommended Mains Fuse Size A 32 32 50 50 63 63 80 80
Unit Data - Cooling Only
Nominal Run Amps A 4 4 5.43 5.43 7 7 9.86 9.86 Recommended Mains Fuse Size A 10 10 10 10 10 10 16 16 Max Mains Incoming Cable Size mm² 16 16 35 35 35 35 70 70
Fan and motor
Full Load Amps A 3 3 4.5 4.5 3 3 4.5 4.5
Electric heat
Current Per Phase A 10.9 10.9 21.7 21.7 21.7 21.7 32.5 32.5
Humidier
Rating kW 6 6 6 6 11.25 11.25 11.25 11.25 Full Load Amps A 8.7 8.7 8.7 8.7 16.3 16.3 16.3 16.3
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP. (3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
(5)
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
55
Page 56
2
 
 
M
Q
 
 
36
Kv
SmartCool™ 6 - 200kW
Technical Data SR C000 Units

Waterside Pressure Drop Data

180
Precision Air Conditioning
160
140
120
100
80
Pressure Drop (kPa)
60
40
20
0
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00
4 SR09D030-C000 / SR09D040-C000
SR
5 SR12D045-C000 / SR09D055-C000 6 SR15D065-C000 / SR15D075-C000 7 SR18D080-C000 / SR18D095-C000
Includes coil, 2 or 3 port valve and pipework.
6 7
5
4
Flow Rate (l/s)
To calculate 3 port valve pressure drop:
∆P valve =
where
∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
Fluid 100% water.
C0C0 Technic a lC000
Unit Valve Kv M
SR09 C000 25.0 0.69 SR12 C000 40.0 1.11 SR15 C000 40.0 1.11 SR18 C000 63.0 1.75
56 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 57
Technical Data SR C000 Units

Sound Data

Overall
Sound Measurement 63 125 250 500 1000 2000 4000 8000 Discharge Air 74 73 71 72 73 71 65 56 26
SR09D030-C000
SR09D040-C000
SR12D045-C000
SR12D055-C000
SR15D065-C000
SR15D075-C000
SR18D080-C000
SR18D095-C000
(1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air 73 73 71 71 71 69 64 55 25 Case Breakout 75 76 76 74 72 71 64 56 29 Sound Pressure @ 3m 60 62 62 60 58 56 50 42 14 Discharge Air 80 78 77 78 78 76 70 61 31 Return Air 78 78 77 76 77 74 69 60 31 Case Breakout 80 82 82 80 78 76 70 62 34 Sound Pressure @ 3m 65 67 67 65 63 62 55 47 20 Discharge Air 76 73 76 75 74 73 67 61 37 Return Air 75 73 76 73 73 71 66 60 36 Case Breakout 77 76 81 77 74 73 66 61 40 Sound Pressure @ 3m 62 62 67 62 59 58 52 47 25 Discharge Air 82 78 81 80 79 79 73 67 43 Return Air 81 78 81 79 78 77 72 66 42 Case Breakout 82 82 87 82 79 79 72 67 46 Sound Pressure @ 3m 68 67 72 68 64 64 58 53 31 Discharge Air 79 78 76 77 78 76 70 61 31 Return Air 78 78 76 76 77 74 69 60 30 Case Breakout 80 81 82 79 77 76 69 61 34 Sound Pressure @ 3m 65 67 67 65 63 61 55 47 19 Discharge Air 82 80 79 80 80 78 72 63 34 Return Air 81 80 79 78 79 77 72 62 33 Case Breakout 82 84 84 82 80 78 72 64 37 Sound Pressure @ 3m 68 69 70 67 65 64 57 49 22 Discharge Air 78 74 77 76 75 74 68 62 38 Return Air 76 74 77 74 74 72 67 61 37 Case Breakout 78 78 82 78 75 74 68 62 41 Sound Pressure @ 3m 64 63 68 64 60 60 53 48 27 Discharge Air 82 78 82 81 80 79 73 67 43 Return Air 81 79 82 79 79 77 72 66 42 Case Breakout 83 82 87 83 79 79 72 67 46 Sound Pressure @ 3m 68 68 72 68 65 64 58 53 31
dB(A)
SmartCool™ 6 - 200kW
Frequency (Hz) dB
Technic a l C0C0C000SR
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
57
Page 58
PIN 1
SmartCool™ 6 - 200kW
Technical Data SR C000 Units

Interconnecting Wiring

Precision Air Conditioning
SR
C0C0 Technic a lC000
N1
301
302
303
N2
304
305
306
PE
502
583
583
584
502
522
2
N (3*)
534
535
609
610
810
811
560
561
563
564
565
881
882
883
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
Conn 17
Conn 14
Conn 16
Conn 14
Conn 15
CONN17
CONN14
CONN16
CONN15
PIN 1
PIN 1
Pin No. Wire
1 502
2 583 or 584
3 2
4 N or 3
PIN 1
Pin No. Wire
1 502
2 522
3 560
4 561
5 563
6 564
7 565
Pin No. Wire
1 2
2 N or 3
3 PE
4 534
5 535
6 609
7 610
8 810
9 811
Pin No. Wire
1 881
2 882
3 883
58 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 59

Technical Data SR C0C0 Units

Mechanical and Electrical Data

SmartCool™ 6 - 200kW
Mechanical Capacity
Nom Cooling (Gross) (1) kW 25.3 30.5 36.5 43.1 50.5 54.7 61.0 70.1 Fan Power Input (Fan Gain) (2) kW 0.81 1.47 1.26 2.36 2.15 2.82 2.25 3.86
Dimensions - D(600) x H(1980)
Width mm 963 1242 1521 1800 Weight - Machine (3) kg 320 320 380 380 464 464 540 540
- Operating kg 351 351 424 424 518 518 609 609
Cooling Coil
Water volume l 16 16 22 22 27 27 35 35 Water ow rate l/s 1.2 1.45 1.74 2.05 2.4 2.6 2.9 3.34 Pressure drop kPa 18.7 26.6 21.5 29.0 30.5 35.3 26.2 33.1
Fan & Motor
Quantity x Motor Size (4) kW 1 x 1.96 1 x 1.96 1 x 2.9 1 x 2.9 2 x 1.96 2 x 1.96 2 x 2.9 2 x 2.9 Speed @25Pa ESP rpm 1178 1444 1316 1595 1281 1404 1231 1460
Speed @maximum ESP rpm 1560 1560 1660 1660 1560 1560 1660 1660 Maximum ESP Pa 459 197 504 124 349 221 551 318 Nominal Airow m³/s 1.85 2.30 2.70 3.30 3.80 4.20 4.60 5.50
Connections
Water Inlet / Outlet mm 35.0 35.0 42.0 42.0 42.0 42.0 54 54
Filtration
Quantity 9 9 12 12 15 15 18 18
Electric Heating
Rating kW 7.5 7.5 7.5 7.5 15.0 15.0 15 15 Stage of Reheat 1 1 1 1 2 2 2 2
Humidier
Capacity kg/hr 3 3 3 3 8 8 8 8
SR09D020-C0C0
SR09D025-C0C0
SR12D030-C0C0
SR12D035-C0C0
SR15D040-C0C0
SR15D045-C0C0
SR18D050-C0C0
SR18D060-C0C0
Technic a l C0C0C0C0SR
Electrical Unit Data - Full Function (5)
Nominal Run Amps A 21.0 21.0 19.63 19.63 43 43 40.3 40.3 Recommended Mains Fuse Size A 25 25 25 25 50 50 50 50
Unit Data - Cooling Only
Nominal Run Amps A 4 4 5.43 5.43 7 7 9.86 9.86 Recommended Mains Fuse Size A 10 10 10 10 10 10 16 16 Max Mains Incoming Cable Size mm² 16 16 16 16 35 35 35 35
Fan and motor
Full Load Amps A 3 3 4.5 4.5 3 3 4.5 4.5
Electric heat
Current Per Phase A 10.9 10.9 10.9 10.9 21.7 21.7 21.7 21.7
Humidier
Rating kW 2.25 2.25 2.25 2.25 6 6 6 6 Full Load Amps A 3.3 3.3 3.3 3.3 8.7 8.7 8.7 8.7
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP. (3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
59
Page 60
2
 
 
M
Q
 
 
36
Kv
8
11
SmartCool™ 6 - 200kW
Technical Data SR C0C0 Units

Waterside Pressure Drop Data

90.0
Precision Air Conditioning
80.0
70.0
60.0
50.0
40.0
Pressure Drop (kPa)
30.0
20.0
10.0
0.0
0.00 1.00 2.00 3.00 4.00 5.00 6.00
8 SR09D020-C0C0 / SR09D025-C0C0 9 SR12D030-C0C0 / SR12D035-C0C0 10 SR15D040-C0C0 / SR15D045-C0C0 11 SR18D050-C0C0 / SR 18D060-C0C0
Includes coil, 2 or 3 port valve and pipework.
SR
To calculate 3 port valve pressure drop:
∆P valve =
10
9
Flow Rate (l/s)
where ∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
Fluid 100% water.
Valve Kv M
SR09 C0C0 16.0 0.44 SR12 C0C0 25.0 0.69 SR15 C0C0 25.0 0.69
C0C0 Technic a lC0C0
SR18 C0C0 40.0 1.11
60 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 61
Technical Data SR C0C0 Units

Sound Data

Overall
Sound Measurement 63 125 250 500 1000 2000 4000 8000 Discharge Air 74 73 71 72 73 71 65 56 26
SR09D020-C0C0
SR09D025-C0C0
SR12D030-C0C0
SR12D035-C0C0
SR15D040-C0C0
SR15D045-C0C0
SR18D050-C0C0
SR18D060-C0C0
(1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air 73 73 71 71 72 69 64 55 25 Case Breakout 75 77 77 74 72 71 64 56 29 Sound Pressure @ 3m 60 62 62 60 58 56 50 42 14 Discharge Air 80 78 77 78 78 76 70 61 31 Return Air 79 78 77 76 77 74 69 60 31 Case Breakout 80 82 82 80 78 76 70 62 34 Sound Pressure @ 3m 66 67 67 65 63 62 55 47 20 Discharge Air 77 73 76 75 74 73 67 61 37 Return Air 75 73 76 73 73 71 66 60 36 Case Breakout 77 76 81 77 74 73 66 61 40 Sound Pressure @ 3m 62 62 67 62 59 59 52 47 26 Discharge Air 82 78 81 81 79 79 73 67 43 Return Air 81 78 81 79 78 77 72 66 42 Case Breakout 82 82 87 82 79 79 72 67 46 Sound Pressure @ 3m 68 68 72 68 64 64 58 53 31 Discharge Air 80 78 76 78 78 76 70 61 31 Return Air 78 78 76 76 77 74 69 60 30 Case Breakout 80 82 82 79 77 76 70 61 34 Sound Pressure @ 3m 65 67 67 65 63 61 55 47 20 Discharge Air 82 80 79 80 80 78 72 63 34 Return Air 81 80 79 78 79 77 72 63 33 Case Breakout 82 84 84 82 80 78 72 64 37 Sound Pressure @ 3m 68 70 70 67 65 64 58 49 22 Discharge Air 78 74 77 76 76 74 68 62 38 Return Air 76 74 77 75 74 72 67 61 38 Case Breakout 78 78 82 78 75 74 68 63 41 Sound Pressure @ 3m 64 63 68 64 60 60 53 48 27 Discharge Air 82 79 82 81 80 79 73 67 43 Return Air 81 79 82 79 79 77 72 66 42 Case Breakout 83 82 87 83 79 79 72 67 46 Sound Pressure @ 3m 68 68 72 68 65 64 58 53 32
dB(A)
SmartCool™ 6 - 200kW
Frequency (Hz) dB
Technic a l C0C0C0C0SR
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
61
Page 62
PIN 1
SmartCool™ 6 - 200kW
Technical Data SR C0C0 Units

Interconnecting Wiring

Precision Air Conditioning
SR
N1
301
302
303
N2
304
305
306
PE
502
583
583
584
502
522
2
N (3*)
534
535
609
610
810
811
560
561
563
564
565
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
Conn 17
Conn 14
Conn 16
Conn 14
CONN17
CONN14
CONN16
CONN15
PIN 1
PIN 1
Pin No. Wire
1 502
2 583 or 584
3 2
4 N or 3
PIN 1
Pin No. Wire
1 502
2 522
3 560
4 561
5 563
6 564
7 565
Pin No. Wire
1 2
2 N or 3
3 PE
4 534
5 535
6 609
7 610
8 810
9 811
Pin No. Wire
1 881
2 882
3 883
C0C0 Technic a lC0C0
881
882
883
BMS Connection
BMS Connection
BMS Connection
Conn 15
62 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 63

Technical Data SD CH00 Units

Mechanical and Electrical Data

Mechanical
SmartCool™ 6 - 200kW
SD18D110-CH00
Capacity
Nom Cooling (Gross) (1) kW 105.3 132.4 174.7 216.5 255.2 Fan Power Input (Fan Gain) (2) kW 2.6 3.5 4.7 5.9 7.8
Dimensions - W x D(890) x H(1980) mm 1800 2200 2500 3100 3500 Weight - Machine Case (3) kg 463 525 588 690 745
- Fan Module kg 175 189 244 305 326
- Operating kg 699 787 919 1101 1190
Cooling Coil
Water Volume l 62 73 88 107 120 Water Flow Rate l/s 5.0 6.3 8.3 10.3 12.1 Pressure Drop kPa 35.7 55.6 77.2 76.3 106.5
Fan & Motor
Quantity x Motor Size (4) kW 2 x 2.9 2 x 2.9 3 x 2.9 4 x 2.9 4 x 2.9 Speed @ 25Pa ESP rpm 1330 1503 1409 1374 1532
Speed @ Maximum ESP rpm 1657 1657 1657 1657 1657 Maximum ESP Pa 485 266 392 428 225 Nominal Airow m³/s 5.7 6.7 8.8 11.3 13.0
Connections
Water Inlet / Outlet mm 54 54 67 67 67
Filtration
Quantity 6 6 6 9 9
Electric Heating
Rating kW 15.0 15.0 22.5 30.0 30.0 Stage of Reheat 2 2 3 4 4
Humidier
Capacity kg/hr 8 30 30 30 30 Rating kW 6.0 22.5 22.5 22.5 22.5 Full Load Amps A 8.7 32.6 32.6 32.6 32.6
SD22D140-CH00
SD25D175-CH00
SD31D215-CH00
SD35D255-CH00
Technic a l CH00SD
Electrical Unit Data - Full Function (5)
Nominal Run Amps A 40.3 64.2 79.4 94.7 94.7 Recommended Mains Fuse Size A 50 80 100 125 125
Unit Data - Cooling Only
Nominal Run Amps A 9.9 9.9 14.3 18.7 18.7 Recommended Mains Fuse Size A 16 16 20 25 25 Max Mains Incoming Cable Size mm² 35 70 70 70 70
Fan and Motor
Full Load Amps A 4.5 4.5 4.5 4.5 4.5
Electric heat
Current Per Phase A 21.7 21.7 32.5 43.4 43.4
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP. (3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
63
Page 64
2
 
 
M
Q
 
 
36
Kv
SmartCool™ 6 - 200kW
Technical Data SD CH00 Units

Waterside Pressure Drop Data

200.0
180.0
160.0
Precision Air Conditioning
140.0
120.0
100.0
80.0
60.0
Pressure Drop (kPa)
40.0
Technic a l
20.0
0.0
0.00 2.00 4.00 6.00 8.00 10.00 12.00
1 SD18D110-CH00-0 2 SD22D140-CH00-0 3 SD25D175-CH00-0
Includes coil, 2 port valve and pipework.
To calculate 3 port valve pressure drop:
1 and 2
3
Flow Rate (l/s)
SD18D110-CH00-0 SD22D140-CH00-0 SD25D175-CH00-0
∆P valve =
where ∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
CH00 SD
Fluid 100% water.
SD18D110-CH00 40 40 SD22D140-CH00 63 40 SD25D175-CH00 63 40
Kv Cooling Kv Bypass
64 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 65
Technical Data SD CH00 Units
2
 
 
M
Q
 
 
36
Kv
4
Waterside Pressure Drop Data
180.0
160.0
140.0
SmartCool™ 6 - 200kW
120.0
100.0
80.0
60.0
Pressure Drop (kPa)
40.0
20.0
0.0
0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00
4 SD31D215 - CH00 - 0 5 SD35D255 - CH00 - 0
Includes coil, port valve and pipework.
To calculate 3 port valve pressure drop:
∆P valve =
5
Technic a l CH00SD
Flow Rate (l/s)
SD31D215-CH00-0 SD35D225-CH00-0
where ∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
Fluid 100% water.
Kv Cooling Kv Bypass
SD31D215-CH00 63 63 SD35D255-CH00 63 63
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
65
Page 66
SmartCool™ 6 - 200kW
Technical Data SD CH00 Units

Sound Data

Precision Air Conditioning
Overall
Sound Measurement 63 125 250 500 1000 2000 4000 8000
Discharge Air 63 66 77 64 56 50 47 40 32
SD18D110-CH00
SD22D140-
CH00
SD25D175-
CH00
Technic a l
SD31D215-
CH00
SD35D255-
CH00
(1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air 58 64 71 59 53 47 47 40 32
Case Breakout 64 72 76 67 60 54 51 46 38
Sound Pressure @ 3m 50 57 62 52 46 39 36 32 23
Discharge Air 66 69 80 67 59 53 51 43 36
Return Air 61 67 74 62 55 50 51 43 35
Case Breakout 67 75 79 70 63 57 54 50 41
Sound Pressure @ 3m 53 60 65 55 49 43 39 35 27
Discharge Air 66 69 80 67 59 53 51 43 35
Return Air 61 67 74 62 56 50 50 43 35
Case Breakout 67 75 79 70 63 57 54 50 41
Sound Pressure @ 3m 53 60 65 55 49 43 39 35 26
Discharge Air 67 70 81 68 60 54 51 44 36
Return Air 62 68 75 63 56 50 51 43 36
Case Breakout 68 75 80 70 64 58 54 50 42
Sound Pressure @ 3m 53 61 66 56 49 43 40 36 27
Discharge Air 70 73 84 70 62 57 54 47 39
Return Air 65 71 78 66 59 54 54 47 39
Case Breakout 71 78 83 73 67 61 58 54 45
Sound Pressure @ 3m 56 64 68 59 52 46 43 39 30
dB(A)
Frequency (Hz) dB
CH00 SD
66 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 67
Technical Data SD CH00 Units

Interconnecting Wiring

SmartCool™ 6 - 200kW
N1
301
302
303
N2
304
305
306
PE
502
583
583
584
502
522
2
N (3*)
534
535
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
Technic a l CH00SD
609
610
810
811
560
561
563
564
565
881
882
883
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
67
Page 68
SmartCool™ 6 - 200kW

Technical Data SD CL00 Units

Mechanical and Electrical Data

Mechanical
Precision Air Conditioning
Technic a lSD
SD18D115-CL00
Capacity
Nom Cooling (Gross) (1) kW 91.6 110.2 144.3 186.4 215.4 Fan Power Input (Fan Gain) (2) kW 2.6 3.5 4.7 5.9 7.8
Dimensions - W x D(890) x H(1980) mm 1800 2200 2500 3100 3500 Weight - Machine Case (3) kg 463 525 588 690 745
- Fan Module kg 175 189 244 305 326
- Operating kg 699 787 919 1101 1190
Cooling Coil
Water Volume l 62 73 88 107 120 Water Flow Rate l/s 3.6 4.4 5.7 7.4 8.6 Pressure Drop kPa 25.9 39.5 62.4 67.1 95.1
Fan & Motor
Quantity x Motor Size (4) kW 2 x 2.9 2 x 2.9 3 x 2.9 4 x 2.9 4 x 2.9 Speed @ 25Pa ESP rpm 1334 1503 1409 1374 1532
Speed @ Maximum ESP rpm 1657 1657 1657 1657 1657 Maximum ESP Pa 485 266 392 428 225 Nominal Airow m³/s 5.7 6.7 8.8 11.3 13.0
Connections
Water Inlet / Outlet mm 54 54 67 67 67
Filtration
Quantity 6 6 6 9 9
Electric Heating
Rating kW 15.0 15.0 22.5 30.0 30.0 Stage of Reheat 2 2 3 4 4
Humidier
Capacity kg/hr 8 30 30 30 30 Rating kW 6.0 22.5 22.5 22.5 22.5 Full Load Amps A 8.7 32.6 32.6 32.6 32.6
SD22D145-CL00
SD25D180-CL00
SD31D235-CL00
SD35D270-CL00
CL00
Electrical Unit Data - Full Function (5)
Nominal Run Amps A 40.3 64.2 79.4 94.7 94.7 Recommended Mains Fuse Size A 50 80 100 125 125
Unit Data - Cooling Only
Nominal Run Amps A 9.9 9.9 14.3 18.7 18.7 Recommended Mains Fuse Size A 16 16 20 25 25 Max Mains Incoming Cable Size mm² 35 70 70 70 70
Fan and Motor
Full Load Amps A 4.5 4.5 4.5 4.5 4.5
Electric heat
Current Per Phase A 21.7 21.7 32.5 43.4 43.4
(1) Entering air 35°C / 24% RH water 18°C / 24°C
(2) Fan gain/ fan power input is shown for a unit delivering nominal air volume with 25Pa ESP. The fan gain / fan power values will change when selected with alternative airow or
ESP values.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other Fans are available, please contact airedale.
68 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 69
Technical Data SD CL00 Units
2
 
 
M
Q
 
 
36
Kv
1 and 3

Waterside Pressure Drop Data

300.0
280.0
260.0
240.0
220.0
200.0
180.0
160.0
140.0
120.0
100.0
80.0
Pressure Drop (kPa)
60.0
40.0
20.0
0.0
0.00 2.00 4.00 6.00 8.00 10.00 12.00
SD18D115-CL00-0 SD22D145-CL00-0 SD25D180-CL00-0
SmartCool™ 6 - 200kW
2
Technic a l SD CL00
Flow Rate (l/s)
1 SD18D115-CL00-0 2 SD22D145-CL00-0 3 SD25D180-CL00-0
Includes coil, 2 port valve and pipework.
To calculate 2 port valve pressure drop:
∆P valve =
where
∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
Fluid 100% water.
Kv Cooling Kv Bypass
SD18D115-CL00 40 40 SD22D145-CL00 63 40 SD25D180-CL00 63 40
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
69
Page 70
2
 
 
M
Q
 
 
36
Kv
SmartCool™ 6 - 200kW
Technical Data SD CL00 Units
Waterside Pressure Drop Data
300.00
250.00
Precision Air Conditioning
200.00
150.00
100.00
Pressure Drop (kPa)
50.00
Technic a lSD
0.00
0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00
4 SD31D235-CL00-0 5 SD35D270-CL00-0
Includes coil, 2 port valve and pipework.
To calculate 2 port valve pressure drop:
5
4
Flow Rate (l/s)
SD31D235-CL00-0 SD35D270-CL00-0
∆P valve =
where ∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
Fluid 100% water.
CL00
Kv Cooling Kv Bypass
SD31D235-CL00 63 63 SD35D270-CL00 63 63
70 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 71
Technical Data SD CL00 Units

Sound Data

SmartCool™ 6 - 200kW
Overall
Sound Measurement 63 125 250 500 1000 2000 4000 8000
Discharge Air 63 66 77 64 56 50 47 40 32
SD18D115-CL00
SD22D145-CL00
SD25D180-CL00
SD31D235-CL00
SD35D270-CL00
(1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air 58 64 71 59 53 47 47 40 32
Case Breakout 64 72 76 67 60 54 51 46 38
Sound Pressure @ 3m 50 57 62 52 46 39 36 32 23
Discharge Air 66 69 80 67 59 53 51 43 36
Return Air 61 67 74 62 55 50 51 43 35
Case Breakout 67 75 79 70 63 57 54 50 41
Sound Pressure @ 3m 53 60 65 55 49 43 39 35 27
Discharge Air 66 69 80 67 59 53 51 43 35
Return Air 61 67 74 62 56 50 50 43 35
Case Breakout 67 75 79 70 63 57 54 50 41
Sound Pressure @ 3m 53 60 65 55 49 43 39 35 26
Discharge Air 67 70 81 68 60 54 51 44 36
Return Air 62 68 75 63 56 50 51 43 36
Case Breakout 68 75 80 70 64 58 54 50 42
Sound Pressure @ 3m 53 61 66 56 49 43 40 36 27
Discharge Air 70 73 84 70 62 57 54 47 39
Return Air 65 71 78 66 59 54 54 47 39
Case Breakout 71 78 83 73 67 61 58 54 45
Sound Pressure @ 3m 56 64 68 59 52 46 43 39 30
dB(A)
Frequency (Hz) dB
Technic a l SD CL00
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
71
Page 72
SmartCool™ 6 - 200kW
Technical Data SD CL00 Units

Interconnecting Wiring

Precision Air Conditioning
N1
301
302
303
N2
304
305
306
PE
502
583
583
Technic a l
584
502
522
2
N (3*)
534
535
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
609
610
810
811
560
561
563
564
565
881
882
883
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
72 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 73

Technical Data SD CHCH Units

Mechanical and Electrical Data

Mechanical
SmartCool™ 6 - 200kW
SD18D085-CHCH
Capacity
Nom Cooling (Gross) (1) kW 75.2 98.3 128.4 155.0 183.6 Fan Power Input (Fan Gain) (2) kW 2.3 3.5 4.1 5.4 7.2
Dimensions - W x D(890) x H(1980) mm 1800 2200 2500 3100 3500 Weight - Machine Case (3) kg 477 547 618 727 788
- Fan Module kg 175 189 244 305 325
- Operating kg 702 798 940 1127 1221
Cooling Coil
Water Volume l 50 62 79 96 108 Water Flow Rate l/s 3.6 4.7 6.1 7.4 8.7 Pressure Drop kPa 23.0 39.5 43.5 37.1 51.3
Fan & Motor
Quantity x Motor Size (4) kW 2 x 2.9 2 x 2.9 3 x 2.9 4 x 2.9 4 x 2.9 Speed @ 25Pa ESP rpm 1266 1491 1337 1322 1479
Speed @ Maximum ESP rpm 1657 1657 1657 1657 1657 Maximum ESP Pa 538 287 463 473 302 Nominal Airow m³/s 5.3 6.5 8.2 10.7 12.4
Connections
Water Inlet / Outlet mm 54 54 67 67 67
Filtration
Quantity 6 6 6 9 9
Electric Heating
Rating kW 15.0 15.0 22.5 30.0 30.0 Stage of Reheat 2 2 3 4 4
Humidier
Capacity kg/hr 8 30 30 30 30 Rating kW 6.0 22.5 22.5 22.5 22.5 Full Load Amps A 8.7 32.6 32.6 32.6 32.6
SD22D105-CHCH
SD25D135-CHCH
SD31D165-CHCH
SD35D195-CHCH
Technic a l CHCHSD
Electrical Unit Data - Full Function (5)
Nominal Run Amps A 40.3 64.2 79.4 94.7 94.7 Recommended Mains Fuse Size A 50 80 100 125 125
Unit Data - Cooling Only
Nominal Run Amps A 9.9 9.9 14.3 18.7 18.7 Recommended Mains Fuse Size A 16 16 20 25 25 Max Mains Incoming Cable Size mm² 35 70 70 70 70
Fan and Motor
Full Load Amps A 4.5 4.5 4.5 4.5 4.5
Electric heat
Current Per Phase A 21.7 21.7 32.5 43.4 43.4
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP. (3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
73
Page 74
2
 
 
M
Q
 
 
36
Kv
SmartCool™ 6 - 200kW
Technical Data SD CHCH Units

Waterside Pressure Drop Data

140.0
120.0
Precision Air Conditioning
100.0
80.0
60.0
40.0
Pressure Drop (kPa)
Technic a l
20.0
0.0
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00
1 SD18D085-CHCH-0 2 SD22D105-CHCH-0 3 SD25D135-CHCH-0
Includes coil, 2 port valve and pipework.
2
1
3
Flow Rate (l/s)
SD18D085-CHCH-0 SD22D105-CHCH-0 SD25D135-CHCH-0
To calculate 2 port valve pressure drop:
∆P valve =
where
∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
CHCH SD
Fluid 100% water.
SD18D085-CHCH 40 40 SD22D105-CHCH 63 40 SD25D135-CHCH 63 40
Kv Cooling Kv Bypass
74 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 75
Technical Data SD CHCH Units
2
 
 
M
Q
 
 
36
Kv
Waterside Pressure Drop Data
120.00
SmartCool™ 6 - 200kW
100.00
80.00
60.00
40.00
Pressure Drop (kPa)
20.00
0.00
0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00
4 SD31D165-CHCH-0 5 SD35D195-CHCH-0
Includes coil, 2 port valve and pipework.
4 and 5
Technic a l CHCHSD
Flow Rate (l/s)
SD31D165-CHCH-0 SD35D195-CHCH-0
To calculate 2 port valve pressure drop:
∆P valve =
where
∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
Fluid 100% water.
Kv Cooling Kv Bypass
SD31D165-CHCH 63 63 SD35D195-CHCH 63 63
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
75
Page 76
SmartCool™ 6 - 200kW
Technical Data SD CHCH Units

Sound Data

Precision Air Conditioning
Overall
Sound Measurement 63 125 250 500 1000 2000 4000 8000 Discharge Air 62 65 76 63 55 49 46 39 31
SD18D085-CHCH
SD22D105-CHCH
SD25D135-CHCH
Technic a l
SD31D165-CHCH
SD35D195-CHCH
(1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air 57 63 70 58 52 46 46 38 31
Case Breakout 63 70 75 66 59 53 49 45 37
Sound Pressure @ 3m 49 56 61 51 45 38 35 31 22 Discharge Air 66 69 80 67 59 53 50 43 35
Return Air 61 67 74 62 55 50 50 43 35
Case Breakout 67 75 79 69 63 57 54 50 41
Sound Pressure @ 3m 53 60 65 55 48 42 39 35 26 Discharge Air 65 68 79 66 58 52 49 42 34
Return Air 60 66 73 61 54 49 49 41 34
Case Breakout 66 73 78 68 62 56 52 48 40
Sound Pressure @ 3m 52 59 64 54 48 41 38 34 25 Discharge Air 66 69 80 67 59 53 50 43 35
Return Air 61 67 74 62 55 50 50 42 35
Case Breakout 67 74 79 69 63 57 53 49 41
Sound Pressure @ 3m 53 60 65 55 49 42 39 35 26 Discharge Air 69 72 83 69 61 56 53 46 38
Return Air 64 70 77 65 58 52 53 46 38
Case Breakout 70 77 82 72 66 60 56 52 44
Sound Pressure @ 3m 55 63 67 58 51 45 42 38 29
dB(A)
Frequency (Hz) dB
CHCH SD
76 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 77
Technical Data SD CHCH Units

Interconnecting Wiring

SmartCool™ 6 - 200kW
N1
301
302
303
N2
304
305
306
PE
502
583
583
584
502
522
2
N (3*)
534
535
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
Technic a l CHCHSD
609
610
810
811
560
561
563
564
565
881
882
883
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
77
Page 78
SmartCool™ 6 - 200kW

Technical Data SD CLCL Units

Mechanical and Electrical Data

Mechanical
Precision Air Conditioning
SD18D090-CLCL
Capacity
Nom Cooling (Gross) (1) kW 75.3 96.7 117.6 158.8 185.4 Fan Power Input (Fan Gain) (2) kW 2.3 3.5 4.1 5.4 7.2
Dimensions - W x D(890) x H(1980) mm 1800 2200 2500 3100 3500 Weight - Machine Case (3) kg 477 547 618 727 788
- Fan Module kg 175 189 244 305 326
- Operating kg 702 798 940 1127 1221
Cooling Coil
Water Volume l 50 62 79 96 108 Water Flow Rate l/s 3.0 3.8 4.7 6.3 7.4
Technic a l
Pressure Drop kPa 23.1 41.0 25.5 49.7 72.1
Fan & Motor
Quantity x Motor Size (4) kW 2 x 2.9 2 x 2.9 3 x 2.9 4 x 2.9 4 x 2.9 Speed @ 25Pa ESP rpm 1266 1491 1337 1322 1479
Speed @ Maximum ESP rpm 1657 1657 1657 1657 1657 Maximum ESP Pa 538 287 463 473 302 Nominal Airow m³/s 5.3 6.5 8.2 10.7 12.4
Connections
Water Inlet / Outlet mm 54 54 67 67 67
Filtration
Quantity 6 6 6 9 9
Electric Heating
Rating kW 15.0 15.0 22.5 30.0 30.0 Stage of Reheat 2 2 3 4 4
Humidier
Capacity kg/hr 8 30 30 30 30 Rating kW 6.0 22.5 22.5 22.5 22.5 Full Load Amps A 8.7 32.6 32.6 32.6 32.6
SD22D120-CLCL
SD25D140-CLCL
SD31D190-CLCL
SD35D225-CLCL
Electrical
CLCL SD
Unit Data - Full Function (5) Nominal Run Amps A 40.3 64.2 79.4 94.7 94.7 Recommended Mains Fuse Size A 50 80 100 125 125
Unit Data - Cooling Only
Nominal Run Amps A 9.9 9.9 14.3 18.7 18.7 Recommended Mains Fuse Size A 16 16 20 25 25 Max Mains Incoming Cable Size mm² 35 70 70 70 70
Fan and Motor
Full Load Amps A 4.5 4.5 4.5 4.5 4.5
Electric heat
Current Per Phase A 21.7 21.7 32.5 43.4 43.4
(1) Entering air 35°C / 24% RH water 18°C / 24°C
(2) Fan gain/ fan power input is shown for a unit delivering nominal air volume with 25Pa ESP. The fan gain / fan power values will change when selected with alternative airow or
ESP values.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other Fans are available, please contact airedale.
78 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 79
Technical Data SD CLCL Units
2
 
 
M
Q
 
 
36
Kv
2

Waterside Pressure Drop Data

250.00
200.00
150.00
SmartCool™ 6 - 200kW
1
100.00
Pressure Drop (kPa)
50.00
0.00
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00
SD18D090-CLCL-0 SD22D120-CLCL-0 SD25D140-CLCL-0
1 SD18D090-CLCL-0 2 SD22D120-CLCL-0 3 SD25D140-CLCL-0
Includes coil, 2 port valve and pipework.
To calculate 3 port valve pressure drop:
∆P valve =
where
∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
Technic a l CLCLSD
3
Flow Rate (l/s)
Fluid 100% water.
Kv Cooling Kv Bypass
SD18D090-CLCL 40 40 SD22D120-CLCL 40 40 SD25D140-CLCL 63 63
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
79
Page 80
2
 
 
M
Q
 
 
36
Kv
SmartCool™ 6 - 200kW
Technical Data SD CLCL Units
Waterside Pressure Drop Data
250.00
Precision Air Conditioning
200.00
150.00
100.00
Pressure Drop (kPa)
Technic a l
50.00
0.00
4 SD31D190-CLCL-0 5 SD35D225-CLCL-0
5
4
0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00
Flow Rate (l/s)
SD31D190-CLCL-0 SD35D225-CLCL-0
Includes coil, 2 port valve and pipework.
To calculate 3 port valve pressure drop:
∆P valve =
where
∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
CLCL SD
Fluid 100% water.
SD31D190-CLCL 63 63 SD35D225-CLCL 63 63
Kv Cooling Kv Bypass
80 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 81
Technical Data SD CLCL Units

Sound Data

SmartCool™ 6 - 200kW
Overall
Sound Measurement 63 125 250 500 1000 2000 4000 8000
Discharge Air 62 65 76 63 55 49 46 39 31
SD18D090-CLCL
SD22D120-CLCL
SD25D135-CLCL
SD31D190-CLCL
SD35D225-CLCL
(1) dB(A) is the overall sound level, measured on the A scale (2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air 57 63 70 58 52 46 46 38 31
Case Breakout 63 70 75 66 59 53 49 45 37
Sound Pressure @ 3m 49 56 61 51 45 38 35 31 22
Discharge Air 66 69 80 67 59 53 50 43 35
Return Air 61 67 74 62 55 50 50 43 35
Case Breakout 67 75 79 69 63 57 54 50 41
Sound Pressure @ 3m 53 60 65 55 48 42 39 35 26
Discharge Air 65 68 79 66 58 52 49 42 34
Return Air 60 66 73 61 54 49 49 41 34
Case Breakout 66 73 78 68 62 56 52 48 40
Sound Pressure @ 3m 52 59 64 54 48 41 38 34 25
Discharge Air 66 69 80 67 59 53 50 43 35
Return Air 61 67 74 62 55 50 50 42 35
Case Breakout 67 74 79 69 63 57 53 49 41
Sound Pressure @ 3m 53 60 65 55 49 42 39 35 26
Discharge Air 69 72 83 69 61 56 53 46 38
Return Air 64 70 77 65 58 52 53 46 38
Case Breakout 70 77 82 72 66 60 56 52 44
Sound Pressure @ 3m 55 63 67 58 51 45 42 38 29
dB(A)
Frequency (Hz) dB
Technic a l CLCLSD
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
81
Page 82
SmartCool™ 6 - 200kW
Technical Data SD CLCL Units

Interconnecting Wiring

Precision Air Conditioning
N1
301
302
303
N2
304
305
306
PE
502
583
Technic a l
583
584
502
522
2
N (3*)
534
535
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
CLCL SD
609
610
810
811
560
561
563
564
565
881
882
883
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
82 SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 83
SmartCool™ 6 - 200kW

After Sales

After Sales
Warranty
All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by an Airedale engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or 18 months from the date of despatch, whichever is the sooner. Parts or Equipment supplied by Airedale for installation within the UK or for Export that are properly commissioned in
accordance with Airedale standards and specifi cation, not commissioned by an Airedale engineer; carry a 12 month
warranty on non consumable Parts only from the date of commissioning or 18 months from the date of despatch, whichever is the sooner.
Parts or equipment installed or commissioned not to acceptable Airedale standards or specifi cation invalidate all
warranty.
Warranty is only valid in the event that
In the period between delivery and commissioning the equipment:
is properly protected & serviced as per the Airedale installation & maintenance manual provided
where applicable the glycol content is maintained to the correct level.
In the event of a problem being reported and once warranty is confi rmed* as valid under the given installation and
operating conditions, the Company will provide the appropriate warranty coverage (as detailed above) attributable to the
rectifi cation of any affected Airedale equipment supplied (excluding costs for any specialist access or lifting equipment
that must be ordered by the customer).
*Once warranty is confi rmed, maintenance must be continued to validate the warranty period.
Any spare part supplied by Airedale under warranty shall be warranted for the unexpired period of the warranty or 3 months from delivery, whichever period is the longer. To be read in conjunction with the Airedale Conditions of Sale - Warranty and Warranty Procedure, available upon request.
Procedure
When a component part fails, a replacement part should be obtained through our Spares department. If the part is considered to be under warranty, the following details are required to process this requirement. Full description of part required, including Airedale’s part number, if known. The original equipment serial number. An appropriate purchase order number. A spares order will be raised under our warranty system and the replacement part will be despatched, usually within 24 hours should they be in stock. When replaced, the faulty part must be returned to Airedale with a suitably completed and securely attached “Faulty Component Return” (FCR) tag. FCR tags are available from Airedale and supplied with each Warranty order. On receipt of the faulty part, suitably tagged, Airedale will pass to its Warranty department, where it will be fully
inspected and tested in order to identify the reason for failure, identifying at the same time whether warranty is justifi ed
or not. On completion of the investigation of the returned part, a full “Report on Goods Returned” will be issued. On occasion the release of this complete report may be delayed as component manufacturers become involved in the investigation. When warranty is allowed, a credit against the Warranty invoice will be raised. Should warranty be refused the Warranty invoice becomes payable on normal terms.
Exclusions
Warranty may be refused for the following reasons.
• Misapplication of product or component
• Incorrect site installation
• Incomplete commissioning documentation
• Inadequate site installation
• Inadequate site maintenance
• Damage caused by mishandling
• Replaced part being returned damaged without explanation
• Unnecessary delays incurred in return of defective component
Returns analysis
All faulty components returned under warranty are analysed on a monthly basis as a means of verifying component and product reliability as well as supplier performance. It is important that all component failures are reported correctly.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_09_2018
83
Page 84