As standard, Airedale guarantees all non consumable parts only for a period of 12 months, variations tailored to suit
product and application are also available; please contact Airedale for full terms and details.
To further protect your investment in Airedale products, Airedale can provide full commissioning services,
Introduction
comprehensive maintenance packages and service cover 24 hours a day, 365 days a year (UK mainland).
For a free quotation contact Airedale or your local Sales Engineer.
All Airedale products are designed in accordance with EU Directives regarding prevention of build up of water,
associated with the risk of contaminants such as legionella.
For effective prevention of such risk it is necessary that the equipment is maintained in accordance with Airedale
recommendations.
SafeCool
In addition to commissioning, a 24 hour, 7 days a week on-call service is available throughout the year to UK mainland
sites. This service will enable customers to contact a duty engineer outside normal working hours and receive
assistance over the telephone. The duty engineer can, if necessary, attend site, usually within 24 hours or less.
Full details will be forwarded on acceptance of the maintenance agreement.
Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance
CAUTION
being carried out in accordance with the recommendations provided during the warranty period.
Failure to have the maintenance procedures carried out will invalidate the warranty and any
liabilities by Airedale International Air Conditioning Ltd.
Precision Air Conditioning
Spares
A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on
request.
Training
As well as our comprehensive range of products, Airedale offers a modular range of Refrigeration and Air Conditioning
Training courses, for further information please contact Airedale.
Customer Services
For further assistance, please e-mail: enquiries@airedale.com or telephone:
UK Sales Enquiries + 44 (0) 113 239 1000 enquiries@airedale.com
International Enquiries + 44 (0) 113 239 1000 enquiries@airedale.com
Spares Hot Line + 44 (0) 113 238 7878 spares@airedale.com
Airedale Service + 44 (0) 113 239 1000 service@airedale.com
Technical Support + 44 (0) 113 239 1000 tech.support@airedale.com
Training Enquiries + 44 (0) 113 239 1000 training@airedale.com
For information, visit us at our web site: www.airedale.com
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 3
SmartCool™ 6 - 200kW
Environmental Considerations
Units with supply water temperatures below +5°C
● Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can
be exposed to freezing temperatures.
Units subject to ambient temperatures lower than 0°C
● Glycol of an appropriate concentration (1) must be used within the system to ensure adequate freeze protection.
Please ensure that the concentration is capable of protection to at least 3K lower than ambient.
● Water / glycol solution should be constantly circulated through all waterside pipework and coils to avoid static
water from freezing.
● Ensure that pumps are started and running even during shut down periods, when the ambient is within 3K of the
solution freeze point (1) (i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).
● Additional trace heating is provided for interconnecting pipework.
(1) Refer to your glycol supplier for details.
Environmental Policy
It is our policy to:
● Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
● Train personnel in sound environmental practices.
● Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
● Manufacture products in a responsible manner with minimum impact on the environment.
● Reduce our use of chemicals and minimise their release to the environment.
● Measure, control and verify environmental performance through internal and external audits.
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:
Electromagnetic Compatibility Directive (EMC) 2014/30/EU
Machinery Directive (MD) 89/392/EEC version 2006/42/EC
Pressure Equipment Directive (PED) 2014/68/EU
Ecodesign 2009/125/EC
To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the
Declaration of Conformity, supplied with each product.
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
3
Page 4
SmartCool™ 6 - 200kW
Health and Safety
IMPORTANT
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be
read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit.
Safety
Introduction
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/
electrical equipment, care must be taken if you are to obtain the best results.
When working with any air conditioning units ensure that the electrical isolator is switched off prior
CAUTION
Electrical installation commissioning and maintenance work on this equipment should be undertaken by competent and
trained personnel in accordance with local relevant standards and codes of practice.
A full hazard data sheet in accordance with COSHH regulations is available should this be required.
to servicing or repair work and that there is no power to any part of the equipment.
Also ensure that there are no other power feeds to the unit such as fi re alarm circuits, BMS circuits
etc.
Personal Protective Equipment
Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning
equipment.
Manual Handling
Some operations when servicing or maintaining the unit may require additional assistance with regard to manual
handling. This requirement is down to the discretion of the engineer.
Remember do not perform a lift that exceeds your ability.
Pressure Equipment Directive (2014/68/EU)
Precision Air Conditioning
Minimum and Maximum Operation Temperature (TS) and Pressure (PS)
Waterside
Allowable Temperature Range (TS) = Min -5°C* to Max 40°C**
Maximum Allowable Pressure (PS) = 10 Barg
*Based on the waterside temperature in the unit off state in the lowest permitted ambient temperature.
**Based upon maximum machine running temperatures.
Ecodesign Directive 2009/125/EC
The product range within this document is designed in accordance to the European Ecodesign Directive 2009/125/EC.
The appendix at the rear section of the manual gives the product compliancy metrics. Products sold outside of the EU
are exempt from this directive.
4
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 5
SmartCool™ 6 - 200kW
Contents
Introduction 7
Construction 8
SN, SR Units 8
SD Units 8
System Congurations 9
SN, SR Nomenclature 11
SD Nomenclature 11
Unit Overview 12
SN, SR Range 12
SD Range 12
Chilled Water Components 14
Airow Components 19
Electrical Components 21
Electric Heating 23
Humidication 24
Controls 28
General Features 34
Installation Data 36
Dimensions 36
Lifting 38
Positioning & Levelling 38
Unpacking 38
Minimum Unit Clearance SN, SR 39
Minimum Unit Clearance SD 40
Incoming Services 44
Glycol 47
Water Detection Tape Installation 48
pLAN Termination 49
Technical Data SN C000 Units 50
Mechanical and Electrical Data 50
Waterside Pressure Drop Data 51
Measurement of Sound Data 52
Sound Data 53
Interconnecting Wiring 54
Technical Data SR C000 Units 55
Mechanical and Electrical Data 55
Waterside Pressure Drop Data 56
Sound Data 57
Interconnecting Wiring 58
Technical Data SR C0C0 Units 59
Mechanical and Electrical Data 59
Waterside Pressure Drop Data 60
Sound Data 61
Interconnecting Wiring 62
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
5
Page 6
SmartCool™ 6 - 200kW
Precision Air Conditioning
Contents
Technical Data SD CH00 Units 63
Mechanical and Electrical Data 63
Waterside Pressure Drop Data 64
Introduction
Sound Data 66
Interconnecting Wiring 67
Technical Data SD CL00 Units 68
Mechanical and Electrical Data 68
Waterside Pressure Drop Data 69
Sound Data 71
Interconnecting Wiring 72
Technical Data SD CHCH Units 73
Mechanical and Electrical Data 73
Waterside Pressure Drop Data 74
Sound Data 76
Interconnecting Wiring 77
Technical Data SD CLCL Units 78
Mechanical and Electrical Data 78
Waterside Pressure Drop Data 79
Sound Data 81
Interconnecting Wiring 82
After Sales 83
6
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 7
SmartCool™ 6 - 200kW
Introduction
Designed to provide environmental precision air conditioning for applications such as telecommunication facilities, data
centers, computer rooms, clean rooms and laboratories.
Full function units provide full control of temperature, humidity and ltration.
The modular design of the SmartCool allows grouping of differing model types and capacities to be installed side by side.
The exibility of this type of installation provides for multi-circuit functionality.
SN, SR
RangePerformance (kW)
SN C000
SR C000
SR C0C0
(1)
(1)
(1)
13 – 36
35 – 98
25 – 70
RangePerformance (kW)
SD CH00
SD CHCH
SD CL00
SD CLCL
SD
(1)
(1)
(2)
(2)
105 – 255
75 – 184
92 – 215
75 – 185
Introduction
(1)
Based on nominal unit capacities 24°C 45% RH 7°C /12°C Water
(2)
Based on nominal unit capacities 35°C 24% RH 18°C / 24°C Water
)
ir
A
y
r
D
J/g
(
n
io
at
ASHRAE Allowable Operating Envelope
1
ASHRAE Recommended Operating Envelope
2
Airedale Extended Operating Envelope
1 + 2
Airedale Operating Envelope
5
0
Bulb Temperature (°C)
et
W
10
1
5
r
u
at
s
t
a
y
p
l
a
h
t
n
E
2
5
0
0
0
1
%
9
80
0
2
0
7
1
e
v
i
0
Relat
6
%
0
5
0
4
2
%
0
2
%
0
1
Moisture Content
Operating Band
Moisture Content kg/kg Dry Air
15
10502025303540
1827
Dry Bulb Temperature (°C)
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
7
Page 8
SmartCool™ 6 - 200kW
Precision Air Conditioning
Precision Air Conditioning System
The computer room air conditioning equipment shall be designed specically for precision temperature and humidity
control applications. It shall automatically monitor and control cooling, heating, humidication, de-humidication
and ltering functions for the conditioned space. The system shall be built to the highest quality engineering and
manufacturing standards and shall be subject to a functional test prior to leaving the factory.
Construction
Introduction
SN, SR Units
The cabinet shall be manufactured using an external aluminium extrusion frame with aluminium corners.
Panels shall be completely removable to gain unequalled access during installation as required. The galvanised sheet
steel panels and aluminium frame and corners shall be coated with an epoxy baked powder paint to provide a durable
nish.
Standard unit colour shall be Black Grey to RAL 7021.
Cabinets shall be lined internally with various thickness re resistant foam (BS 476) for thermal and acoustic insulation.
The insulation density shall not be less than 75 kg/m³.
The cabinet doors shall be full height, hinged and key lock secured. The hinge arrangement shall allow exible door
opening/removal for improved access.
A propriety rubberised door seal shall reduce sound breakout and eradicate air leakage. In-seal type foam based door
seals shall not be acceptable.
The control panel is mounted on hinges to allow easy removal of lters and access to several electrical components.
The unit design shall incorporate a series of M6 xings to the top and bottom face to ease customer ductwork connection
and reduce installation time.
SD Units
The cabinet shall be manufactured using steel frame.
Panels shall be completely removable to gain unequalled access during installation as required. The galvanised sheet
steel panels shall be coated with an epoxy baked powder paint to provide a durable nish.
Standard unit colour shall be Black Grey to RAL 7021.
Cabinets shall be lined internally with various thickness re resistant foam (BS 476) for thermal and acoustic insulation.
The insulation density shall not be less than 75 kg/m³.
The cabinet doors shall be full height, hinged and key lock secured. The hinge arrangement shall allow exible door
opening/removal for improved access.
A propriety rubberised door seal shall reduce sound breakout and eradicate air leakage. In-seal type foam based door
seals shall not be acceptable.
The unit design shall incorporate a series of M6 xings to the top and bottom face to ease customer ductwork
connection and reduce installation time.
8
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 9
SmartCool™ 6 - 200kW
System Congurations
SN, SR RangeSD Range
Introduction
SN C000 Units
● Fans located within unit
● Separate oorstand (min 350mm)
SR C000 / C0C0 Units
● Fans located within unit
● Separate oorstand (min 350mm)
SD CL00 / CLCL Units
● Fans located within oorstand
● Floorstand integral to unit (min 600mm)
SD CH00 / CHCH Units
● Fans located within oorstand
● Floorstand integral to unit (min 600mm)
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
9
Page 10
SmartCool™ 6 - 200kW
Single Circuit System Conguration
(SN C000, SR C000, CL00, CH00)
Introduction
Precision Air Conditioning
Dual Circuit System Conguration
(SR C0C0, SD CLCL, SD CHCH)
10
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 11
SmartCool
Regular Cas e (890m m deep)
Narrow Case (60 0mm deep)
2220V / 3Ph / 60Hz
2220V / 3Ph / 60Hz
SmartCool™ 6 - 200kW
SN, SR Nomenclature
SProduct Nam e
R
Variant
N
06
09963 m m
Cas e Width
121242 mm
151521 mm
181800 mm
D
Flow Configuration
010
Nom inal Co oling Ca pacity (kW)
095
-
Separator
-
C000Single Circuit CW
Cooling Configuration
C0C0Dual Circuit CW
-
Separator
-
0400V / 3Ph +N / 50Hz
Power Supply
1380V / 3Ph +N / 60Hz
684 m m
Downflow
Introduction
SR12D0 55 --C000-0
SD Nomenclature
SProduct NameSmartCool
DProduct VariantDedicated Chil led Water
181800 mm
222200 mm
25Case Width2500 mm
313100 mm
353500 mm
D
Flow Configura on
085-255 Nomi nal Cooling Capacity (kW)
-Separator
CChilled Water
HCoil Streamed For High Flow
Coil Type
LCoil Streamed For Low Flow
CChil led Water Circuit
Second Circuit
0No Chi lled Water Circuit
HCoil Streamed For High Flow
Coil Type Second Circuit
LCoil Streamed For Low Flow
-Separator
0400V / 3Ph + N / 50Hz
1Power Supply380V
Downflow
/ 3Ph +N / 60Hz
SD31D215-CH00-0
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
11
Page 12
SmartCool™ 6 - 200kW
Unit Overview
SN, SR Range
Cooling Coil
Introduction
Electric Heat
Precision Air Conditioning
Hinged Control Panel
Humidication
Chilled Water ValvesFans
SD Range
Air Filters
Humidier
Chilled Water
Pipework
Floor Height
Floorstand
Fixed Control Panel
12
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 13
SmartCool™ 6 - 200kW
Chilled Water Components
SN, SR Range
Cooling Coil
Chilled Water Valves
Introduction
SD Range
Pipework
Connections
Cooling Coil
Valves
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
13
Page 14
SmartCool™ 6 - 200kW
Chilled Water Components
Precision Air Conditioning
System Conguration
Range
Number of Circuits
SNSRSD
SingleSingleDualSingleDual
Introduction
Hydrophilic Epoxy Coated RTPF Chilled Water Coil
0-10 Volts Chilled Water Regulating Valve (2 Way)
0-10 Volts Chilled Water Regulating Valve (3 Way)
0-10 Volts Chilled Water Regulating Valve
(2 x 2-Way) Auto Commission
Pressure Independant Control Valve (PICV)
Chilled Water
Brazed Connections
Threaded Connections
Grooved Connections
Flanged Connections
Standard Features ○ Optional Features – Feature Not Available
●
Chilled Water Coil
Chilled water coils shall be ideally positioned to optimise airow and heat transfer, they shall be manufactured from plain
copper tubes with mechanically bonded aluminium ns. Fins shall be coated with a non-stick acrylic lm (hydrophilic) to
provide additional corrosion protection and efcient surface water removal for improved performance. Plain aluminium
shall not be acceptable. The cooling coil shall be mounted over a full width stainless steel condensate tray. A 22mm
condensate drain hose connection shall be available. For control of water ow, various valve options shall be tted.
The factory test pressure shall not be less than 20 Barg and the maximum operating pressure shall be less than 10.
Sweat copper pipe for brazed connection shall be standard. Optional threaded and Grooved connections shall be
available.
●●●●●
●● ● ●●
○○ ○ ––
–––○○
○○○○○
●●●●●
○○○○○
–––○○
–––○○
14
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Grooved water connections shall be avaliable enabling easy pipework termination.
Flanged Connections
For spool and unit termination, two types of ange shall be available.
For the spool termination, a bespoke ange design shall incorporate a ange prole and gasket conguration.
For the unit termination, a PN16 round bi-metallic ange shall be used. The unit termination end shall require staggering
by 100mm to allow tting of the anges as shown.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
2 Port Chilled Water
Valves with 2 Port
Commissioning Valve
3 Port Chilled Water Valves
3 Port Chilled Water
Valves with Bypass
Standard Features ○ Optional Features – Feature Not Available
●
0-10 Volts DC 3 Port Chilled Water Regulating Valve (SN, SR Units)
●●●●●●●●●●●●
–––––––○○○○○
○○○○○○○–––––
○○○○○○○–––––
Precision Air Conditioning
BL
BI
WTS
BI
Inlet
Coil(s)
DR
BI
M
BI
Outlet
0-10V DC 3 Port
Regulating Valve
0-10 Volts DC 3 Port Chilled Water Regulating Valve with Bypass (SN, SR Units)
Coil(s)
BL
DR
BI
BI
0-10V DC 3 Port
Regulating Valve
WTS
Bypass Valve
M
BI
Inlet
BI
Outlet
16
M
2 Port Regulating Valve
0-10V DC 3 Port
Regulating Valve
M
BI
BL
Binder Point
Bleed Valve
Drain Valve
DR
Water Temperature Sensor
WTS
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
0-10V DC 2 Port
Regulating Valve
Page 17
SmartCool™ 6 - 200kW
0-10 Volts DC 2 Port Chilled Water Regulating Valve (SN, SR, SD Units)
For systems with variable speed pumps and water ow, a 2 port control valve can be tted. The two port valve has a shut
off pressure of 13.6 Barg.
BL
BI
2 Port Valve
M
WTS
BI
Inlet
Coil(s)
DR
BI
Outlet
0-10 Volts DC 2 Port Chilled Water Regulating Valve with bypass for auto commissioning (SD Units)
For systems with variable speed pumps and water ow, a 2 port control valve can be tted The two port valve has a shut
off pressure of 13.6 Barg.
A bypass leg tted with a further 2 port valve enables auto commissioning.
The auto commissioning shall be enabled by using a differential pressure transducer to maintain balanced water ow
through the bypass. The controller maintains the same pressure drop through the coil and the bypass. A xed owrate is
required for this initial commissioning to occure.
BL
BI
2 Port Valve
WTS
BI
Introduction
Coil(s)
BI
BL
Binder Point
Bleed Valve
M
Inlet
Bypass Valve
DR
Outlet
M
2 Port Regulating Valve
0-10V DC 3 Port
Regulating Valve
M
0-10V DC 2 Port
Regulating Valve
Drain Valve
DR
Water Temperature Sensor
WTS
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
17
Page 18
SmartCool™ 6 - 200kW
Precision Air Conditioning
Pressure Independant Control Valve (PICV)
Pressure Independant Control Vales (PICV) tted to the SmartCool ensure that constant waterow is achieved. The PICV
valves maintain the design owrate based upon the valve setup.
SN / SR Units
Introduction
DN20DN25DN32DN40
SN06D-C000
SN09D-C000
SN12D-C000–
SR09D-C000–
SR12D-C000––
SR15D-C000––
SR18D-C000––
● Standard Features Optional Features – Feature Not Available
● Standard Features Optional Features – Feature Not Available
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 19
SmartCool™ 6 - 200kW
Airow Components
System Conguration
RangeSNSRSD
Number of CircuitsSingleSingleDualSingleDual
EC Backward Curved Centrifugal Fans in Unit
EC Backward Curved Centrifugal Fans in Floorstand
G4 Air Filtration
High Grade F7 Filtration
Airow Monitoring
Chilled Water
Airow Switch
Constant Air Volume
Constant Pressure Control
●
Standard Features ○ Optional Features – Feature Not Available
Fan & Motor Assembly
Backward curved impellers, direct drive centrifugal fan assemblies shall be used with integral EC motors. They shall be
dynamically balanced for quiet operation.
Fan speed, air ow and external static pressure shall be controlled by the use of a voltage controller which shall maintain
optimised performance and reduce energy consumption.
Designed for high corrosion resistance, the impellers shall be composite plastic with a galvanised rotor.
●●●––
–––●●
●●●●●
○○○○○
○○○○○
●●●●●
○○○○○
○○○○○
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
19
Page 20
SmartCool™ 6 - 200kW
Electronically Commutated (EC) Fan Motor
EC motors incorporate integrated electronics to convert AC power to DC for efcient and accurate speed control and are
adjustable via the microprocessor display keypad.
The fans offer maximum air ow performance while keeping sound levels to a minimum.
It gives the exibility of connecting to AC mains with the efciency and simple speed control of a DC motor. The EC fan
offers signicant power reduction in comparison with an equivalent AC fan at modulated fan speeds. The inbuilt EC fan
Introduction
control module allows for fan speed modulation from 15-100%.
A standard AC fans modulating range is typically 40 -100% of full fan speed.
Standard voltage regulated (VR) fan speed controllers offer a linear response. The illustration on the right shows a
comparison of the typical power input required by each method.
Precision Air Conditioning
Input Power
Airflow
Key
EC (Electronically Commutated) Fan Speed Control
Regulated (VR) Fan Speed Control
Standard Filtration
Pleated disposable panel lters in a rigid frame. Conform to ISO16890:2016 with ltration classes of ISO-C-85 (SN)
ISO-C-75 (SR) and ISO-C-80 (SD)
Access and removal from unit front. As standard the microprocessor provides an alarm following a pre set run time limit
being exceeded.
High Grade ISO-1-60 Filtration
Pleated disposable panel lters conforming to ISO 16890:2016 with ltration class of ISO-C-60 shall be provided.
Air Flow Switch
An adjustable differential pressure switch shall activate a visual alarm at the status panel and break the power supply in
the event of a fan or motor failure.
20
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 21
SmartCool™ 6 - 200kW
Electrical Components
RangeSNSRSD
Number of Circuits SingleSingleDualSingleDual
Door Interlocked Mains Isolator
Electrical Switch Gear
Customer Connection Terminals
Power Monitoring
Phase Monitoring Relay
Electrical
●
Standard Features ○ Optional Features – Feature Not Available
* Fitted as standard when dual power supply is tted.
Ultra Capacitive Module (Controller Power Backup)*
Dual Power Supply
Variable Humidication
Electric Heating
Modulating Electric Heating
Introduction
System Conguration
●●●●●
●●●●●
●●●●●
○○○○○
○○○○○
○○○○○
○○○○○
○○○○○
○○○○○
○○○○○
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
21
Page 22
SmartCool™ 6 - 200kW
Electrical Panels
The control panel contains the necessary contactors, transformer, sub circuit protection, volt free contacts for a common
alarm and mains and inter-connecting terminals. The panel is situated within the cabinet and is hinged to allow for
essential maintenance of other components within the unit (SN, SR Units only). The electrical control panels are wired to
the latest European standards and codes of practice.
Control Panel Closed (SN, SR Units)
Introduction
Precision Air Conditioning
Control Panel Closed
Control Panel Open (SN,SR Units)
SD Units
Optional Control Panel
Control Panel Open
Standard Control Panel
22
Optional control panels are tted
dependant on which optional
features are tted
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Optional Control Panel
Page 23
SmartCool™ 6 - 200kW
Electric Heating
SN, SR Units
These shall be multi-stage nned electric heating elements complete with auto and manual reset overheat cut-out
protection, element shall be phase balanced for increased efciency.
The electric heating elements are designed to be located between coil blocks, prior to fans. This enables the unit to
effectively re-heat the air and evenly distribute the temperature within the oor void. All sizes of electric heating are
congurable based upon customer requirements.
A maximum bank of 7.5kW is allocated per coil block. The avaliable heating shall be 3kW, 6kW or 7.5kW. Consequently
the level of conguration is dependent on the number of coils in the unit.
SD Units
These shall be multi-stage nned electric heating elements complete with auto and manual reset overheat cut-out
protection, element shall be phase balanced for increased efciency.
The electric heating elements are designed to be located within the unit’s fan module. This enables the unit to effectively
re-heat the air and evenly distribute the temperature within the oor void. All sizes of electric heating are congurable
based upon customer requirements.
A bank of 7.5kW is allocated per fan and as standard each can be downsized in banks of 7.5kW. Consequently the level
of conguration is dependent on the number of fans in the unit.
Electric Heating Thyristor Control
In addition to the electric heat option a 0 – 100% Thyristor shall be provided to deliver accurate heating control.
●Standard Features ○ Optional Features – Feature Not Available
Inlet and Drain Connections
The humidiers have a 3/4” BSPF Braided Flexible Hose inlet connection and a 22mm drain hose connection.
The humidier drain pump has a owrate of 7.0l/m.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
○○○○○○○○○○○○
–○○○○○○○○○○○
––––––○–○○○○
––––––––○○○○
Page 25
SmartCool™ 6 - 200kW
Humidication
Control Principles
In a humidier with electrodes, steam shall be produced by passing a current between electrode plates to generate heat.
The higher the current being passed between the electrodes, the greater the quantity of steam that is produced.
To modulate the rate of steam production, this system shall vary the level of water within the cylinder, thereby increasing
the immersion level of the electrodes and the current being passed between them. The more conducting area that is
available to pass current between the electrodes, the larger the amount of steam that shall be produced.
Modulated by the controller, the water level is varied so that the level of steam being produced ensures that the room
humidity set-point is continually maintained within a tight tolerance.
Optimised Lifetime
The life span of the Airedale humidication system shall be optimised by the inclusion of a water conductivity sensor
into the bottle feed. This sensor shall determine the conductivity level of the supply water and by using an algorithm
embedded in the software, determines the frequency that the bottle should be drained.
Example: (Optimised Lifetime with High Water Conductivity Supply)
As liquid water is boiled off into steam, mineral deposits are left in solution increasing the conductivity of the water.
To counter this, the intelligent software increases the frequency of drain meaning that the replenishing supply water
keeps the concentration of minerals diluted. By maintaining an acceptable mineral concentration, the bottle lifespan is
maximised.
De-humidication
(With Electric Heating and Humidication only)
Controlled by the microprocessor the de-humidication feature reduces fan speeds by 20% (adjustable). The reduction of
fan speed increases de-humidication which means that the time taken to reduce the room humidity to the required level
is drastically decreased, along with the energy required to do so.
The return temperature is monitored during de-humidication to ensure that the temperature does not fall to a critical
level. If the temperature reaches the low limit de-humidication is cancelled until the return air temperature increases.
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
25
Page 26
SmartCool™ 6 - 200kW
Precision Air Conditioning
Humidier - Intelligent Modulation
Humidication shall be provided by an electrode boiler. The sealed humidier design shall ensure that only clean sterile
steam is supplied to the conditioned area and corrosive salts and minerals are held in the disposable bottle. The steam
shall be distributed through a sparge pipe tted to the coil assembly.
Featuring modulating capacity output control as standard, the system shall provide continuous modulation of steam
output in response to a proportional control signal. The output control shall range from 20%-100% of the humidier rated
Introduction
value and be designed to give an approximate steam output of +/- 5% at 25°C (at the sensor), thus ensuring precise
control of the conditioned space.
The cylinder operating life time shall be automatically optimised via the integrated water conductivity sensor, which
combined with the controls shall monitor and regulate the water rell cycle to reduce excessive salt deposits and the
progressive wear of the cylinder.
All humidier parameters and alarms shall be accessible and adjustable via the microprocessor display keypad unit,
main features shall include not less than:
● Supply water conductivity (µS/cm)
● Actual steam output (kg/h)
● Required steam output (kg/h)
● Actual current rating (A)
● Required current rating (A)
● Status mode (Start Up, Running, Filling, Draining)
Water Conductivity & Cylinder Type
Three different cylinders shall be available which correspond to the supply water conductivity.
The cylinder type shall be matched with the standard conductivity of the supply water to ensure optimum performance
and to increase the life span of the cylinder.
1 Low Conductivity (Soft Water) 100 to 350 µS/cm
2 Standard Conductivity (Moderate / Hard Water) 350 to 750 µS/cm
3 High Conductivity (Very Hard Water) 750 to 1250 µS/cm
Conductivity is a measure of the ability of water to pass an electric current, measured in micro Siemens / centimetre (µS/
cm).
As standard the humidier shall be tted with the standard conductivity cylinder which shall cover the majority of water
supplies.
Where the water conductivity is known, please specify at order. For further details please contact Airedale.
26
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 27
SmartCool™ 6 - 200kW
Dual Power Supply
The SmartCool range shall be designed with dual power supply capability, so that in the event of a power failure the
supply can be switched from utility to an alternative power supply (such as second utility or generator).
A dual power supply changeover switch shall be provided to enable continuous power to the SmartCool in order to
reduce unit downtime and therefore loss of cooling to a minimum.
For the dual power supply feature to operate effectively the two incoming power supplies must have the same voltage
and frequency.
During changeover of power there is an interval of ≈180ms with no power. For critical applications a power backup
module can be added to maintain power to the unit controls, allowing for immediate reinstatement of cooling following
changeover.
The option as standard offers switch position status and supply priority set, both of which are congurable via the unit’s
display.
Supply priority set is fully congurable via the unit’s display and is used to set which of the two power supplies power will
be drawn from when both power supplies are active.
Switch position status indicates to the end user which position the switch is currently in i.e. A or B and is shown via the
unit’s display.
When the dual power supply is tted the UltraCap UPS is tted as standard.
Ultracap UPS
The Ultracap module is an external backup device for the controller. The module guarantees temporary power to the
controller in the event of power failures and allows for enough time to keep the controller running with time to change
power supplies.
The module is made using Ultracap storage capacitors (EDLC = Electric Double Layer Capacitor), which are recharged
independently by the module.
These ensure reliability in terms of much longer component life than a module made with lead batteries: the life of the
Ultracap module is at least 10 years.
When the dual power supply is tted the Ultracap UPS is tted as standard.
Energy Manager
Analysis of system energy consumption can be monitored via a dedicated LCD display. Unit parameters can be adjusted
via the unit microprocessor control to affect energy usage in line with the system need.
Introduction
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
27
Page 28
SmartCool™ 6 - 200kW
Controls
Introduction
Precision Air Conditioning
Display for illustration only
System Conguration
Number of Circuits SingleSingleDualSingleDual
PCO5 Microprocessor
Airetronix Controls
Vu™ Touch Screen Display
PGD1 Display (Door Mounted)
PGD1 Display with Audible Alarm (Door Mounted)
PDG Touch Display
Constant Air Volume
Constant Pressure Control
Temperature Control
Temperature & Humidity Control
Controls
Supply Air Temp Control
NTC Water Temperature Sensor / Probe
Filter Change Switch
BMS and SNMP Compatibility
Drip Tray Level Detection
Fire Detection
Smoke Detection
Water Detection
RangeSNSRSD
●●●●●
●●●●●
●●●●●
○○○○○
○○○○○
○○○○○
○○○○○
○○○○○
●●●●●
○○○○○
○○○○○
●●●●●
○○○○○
○○○○○
○○○○○
○○○○○
○○○○○
○○○○○
28
●
Standard Features ○ Optional Features – Feature Not Available
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 29
SmartCool™ 6 - 200kW
Vu™
The units shall be supplied with a European ROHS Directive 2002/95/EC compatible microprocessor controller
connected to a 4.3” colour resistive TFT LCD touch screen display.
The microprocessor controller offers powerful analogue and digital control to meet a wide range of monitoring and control
features including a real time clock and industry standard communication port and network connections.
All the SmartCool products feature a 32 bit microprocessor, offering signicant calculation power and operation
processing speed.
Also featured is the facility to adjust and display control settings by local operator, for information and control.
Display / Keypad
The 4.3” touchscreen Vu™ display provides important unit status and allows page navigation with a swipe. The default
screen shows the unit status and room condition (°C/RH %). Further screens offer adjustment to parameters, ne-tuning
of setpoints (via a rotating control wheel) and scrollable data tables.
Trends of system information can be analysed and managed via the Vu™ allowing for easy system optimisation.
The operating status of the unit can also be easily be determined “at a glance” with a colour coded LED bar.
Introduction
Home
Main Menu
Current Alarms (and no. of alarms)
Help Screen
Unit Status
Network Address
Temperature
Humidity
Setpoint
Fan
Cooling
Heang
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
29
Page 30
SD - 4 Stages
SmartCool™ 6 - 200kW
Precision Air Conditioning
PGD1
The units shall be supplied with a European ROHS Directive 2002/95/EC compatible microprocessor controller
connected to an 8 x 22 back-lit LCD keypad display. LEDs shall not be acceptable.
The microprocessor controller offers powerful analogue and digital control to meet a wide range of monitoring and control
features including a real time clock and Industry standard communication port and network connections.
All the boards feature a 16 bit microprocessor, and consequently the calculation power and operation processing speed
Introduction
have been signicantly increased.
Also featured are a visual alarm and the facility to adjust and display control settings by local operator for information and
control.
Display / Keypad
The display keypad features a simple array of keys to navigate through the in built menus.
With an 8 x 22 character (132 x 64 pixel) screen size, back lit in white for improved contrast, the larger screen shall
provide for user friendly viewing and easy status recognition by displaying a combination of text and icons.
The default screen shall show the unit status and room condition (°C/RH %) without the need for interrogation and an
easy to navigate menu structure for further interrogation and adjustment shall be provided.
Fan Operating
Cooling - Variable
Heating - Various Stages
SN - 2 Stages
SR - 3 Stages
De-humidication
Humidication - Variable
30
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 31
SmartCool™ 6 - 200kW
Controls
Password Protection
The control system integrity shall be maintained by restricting access with a password PIN number.
IMPORTANT
To change the PIN , please contact Airedale at time of order with the preferred 4 digit number.
Remote On/Off
Terminals for interlocking shall be provided to enable or disable the unit remotely.
Fire Shut Down
Terminals for interlocking shall be provided to shut down the unit in the event of re.
Evaporator Fan Hours Run Log & Reset
Shall allow the user to monitor the running times of the evaporator fans and reset after maintenance.
Hours run log or visual service indicator shall be provided.
Evaporator Fan Speed Control
Evaporator fan speed control shall be easily set via the display keypad and can be incrementally increased or decreased
to meet on site airow and external static pressure requirements.
Filter Change Alarm
Filter change shall be managed by the software, and shall be based on fan(s) hours run with an alarm being generated
when the pre-set run time limit has been exceeded. The set-point value shall be adjusted to suit each application and is
factory set to 4000 hours.
Standard Network Features
As standard the controller shall be capable of providing a platform for the following and shall be enabled on request for 2
to 8 units, please specify at order:
Networking
A Local Area Network (pLAN ) shall be used to connect up to 8 units to offer intercommunication and Run / Standby
control. This also allows the connection of computers, printers and modems on the same communications ring.
For further details, please contact Airedale Controls.
Introduction
CAUTION
When adding to an existing network, please consult Airedale to ensure strategy compatibility.
Run / Standby Operation
The controller shall enable units to operate in run/standby mode, with up to 8 units networked together, without the need
for additional hardware or controllers. Standby units shall be congured to start when the run unit has a critical alarm.
Smart Key
A smart key shall be supplied to offer software back-up of the control strategy. The key shall feature simple plug in
operation and allow transfer of software programs from the key to the microprocessor and vice versa. The use of a
service laptop shall not be necessary.
Audible Alarm
The display keypad shall be upgraded to include audible alerts.
Water Detector
Three methods shall be available:
1. A solid state (probe) sensor shall be supplied loose for remote mounting on site.
2. Tape suitable for sensing water droplets shall be supplied loose for remote mounting on site. Standard tape
length 10m.
3. Condensate drain tray level detection.
Fire Detection
Shall be supplied loose for installation in the return air stream to shut down the unit in the event of an unusually high
return air temperature.
Smoke Detector
Shall be supplied loose for remote mounting to shut down the unit and activate the alarm upon sensing the presence of
smoke.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
31
Page 32
SmartCool™ 6 - 200kW
Precision Air Conditioning
Controls
Temperature Control
A temperature sensor shall be mounted in the return air side of the unit to sense the return dry bulb condition (cooling
only variants). A combined temperature and humidity sensor shall be supplied on full function units.
The temperature sensor shall be an NTC type thermistor with an accuracy of not less than +/ - 5% at 25°C at the sensor.
The microprocessor shall sense the return air conditions and maintain the return air temperature and humidity by
Introduction
controlling cooling, heating, humidication and dehumidication outputs accordingly.
The microprocessor shall monitor and display the following values as a minimum:
● Return Air Temperature
● Return Air Humidity (Optional on Full Function units)
● Fan run hours
● Coil Temperature Sensor (Indoor)
The maintenance of key components such as air lters shall be monitored via a service indicator which visually
demonstrates the status relative to the component service intervals.
Alarm Log
The controller shall log and allow viewing of not less than the last 100 conditions recorded in descending chronological
order through the keypad display.
The standard display keypad shall visually display operating alarms, however, as an optional extra, a display keypad with
audible alarms is available.
Supply Air Temperature Control
Modulation of unit capacity to ensure that user dened supply air set points shall be maintained and / or a high / low
return air temperature alarm.
During peak demand, the standby units shall temperature assist.
Duty Rotation
Networked units shall be congured to duty rotate, providing equal hours run of fans.
BMS Interface Cards
BMS Interface Card controlled units shall be interfaced with most BMS, factory tted, please contact Airedale.
A wide range of protocols shall be accommodated through the use of interface devices. Available as a standard option
are: ModBus / Jbus, and Carel.
For interfaces such as SNMP, LonWorks, Metasys and BACnet, please contact Airedale.
Also available shall be Airedale’s own supervisory plug-in BMS card pCOWEB.
Based on Ethernet TCP/IP secure technology with SNMP features.
It shall require no proprietary cabling or monitoring software and be supplied pre - programmed with an IP address for
ease of set up. Cables to the BMS to be supplied by others.
32
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 33
SmartCool™ 6 - 200kW
Controls
Constant Pressure Control
Constant pressure control is a method of controlling air pressure within a space, such as a oor void or a duct. The air
pressure is controlled using a variable speed fan that is modulated to maintain a given set point.
Constant pressure control monitors the air pressure differential between two points. In a typical application (shown
below) the pressure under the raised oor (red) is compared to the room pressure (blue).
Introduction
The two pressure points, positive and negative, are routed back to an air differential pressure sensor inside the CRAC
unit. The value from the air pressure sensor is compared to the set point and a fan speed demand is generated, to
maintain the required pressure differential.
It is the responsibility of the installer to t the air pressure sensor(s). The sensor shall be be located under the false
oor with the 6mm amtronix tubing routed back into the control panel of the unit (the tubing must not be obstructed /
damaged to ensure accurate pressure control).
The contant pressure system shall be commissioned by Airedale following routing of tubing from the pressure diffuser
and the unit.
A maximum of 8m/s air velocity is allowed at the diffuser so consideration must be made to its location.
Constant Air Volume
Constant air volume is a method of automatically adjusting the unit fan speed to deliver a specic air volume.
When faced with a change in system resistance, the fan speed modulates to obtain the air volume set point.
Constant air volume monitors the air pressure differential between two points.
These two pressure points, positive and negative, are routed back to an air differential pressure sensor inside the unit.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
33
Page 34
SmartCool™ 6 - 200kW
General Features
Introduction
Precision Air Conditioning
System Conguration
RangeSNSRSD
CircuitsSingleSingleDualSingleDual
Condensate Pump (Hot or Cold Water)*
Condensate Drain Tray Monitoring
Straight and “L” Shaped Ceiling Duct Extensions
Open Floorstand
General
Front and Rear Floorstands (enclosed)
UPS Floorstand
Sterling Board LAT (Wooden Case) Packing
●
Standard Features ○ Optional Features – Feature Not Available
○○○○○
○○○○○
○○○○○
○○○○○
○○○○○
○○○––
○○○○○
*Condensate pump type depends if humidication is selected.
Open & Enclosed Floorstand
Open or enclosed oor stands shall be available, complete with adjustable feet and oor tile lip. Enclosed oor stands
shall incorporate an air turning vane (SN,SR only). The height of the oor stand shall be specied at order.
Discharge Air Conguration
Standard conguration shall be downow “draw through” design.
Straight and L shaped Ceiling Duct Extension
Straight and ‘L’ shaped duct extensions up to a height of 1350mm shall be constructed and nished to match the unit.
For extensions greater than 1350mm, please contact Airedale.
Height shall be specied at order.
Sterling Board LAT (Wooden Case) Packing
Units shall be supplied complete with additional LAT corner protection and cross braces to afford extra transit protection.
Sterling board heat treated man made material shall be used (including pallet) to comply with phytosanity import
regulations, please contact Airedale for this option.
34
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 35
SmartCool™ 6 - 200kW
Condensate Pumps
The SmartCool condensate pump shall be either hot water (full function units when a humidier is tted) or cold water
type (cooling only).
Performance
The following graphs illustrate the TOTAL static (head) pressure available. The system horizontal pipe losses and vertical
lift should be factored in when calculating the condensate pump performance.
Cold Water (Cooling only units)
SN, SR Units
6
The cold water condensate pump has
10mm quarter turn plastic “barbed”
connection.
The discharge line from the pump
should rise no more than 4 metres
before being interrupted with a swan
neck air break and tundish.
SD Units
5
4
3
Head (m)
2
1
0
0.00.51.01.52.02.53.0
Flow Rate (l/min)
9
8
7
6
5
4
Head (m)
3
2
1
0
2.02.53.03.54 .04.55.05.56.0
Flowrate l/min
Introduction
Hot Water (Full function units, SN,SR,SD type units)
The hot water condensate pump
12
uses 10mm (3/8”) copper tube when
connecting to the discharge stub of the
10
8
6
Head (m)
4
pump.
The discharge line from the pump
should rise no more than 6 metres
vertically and no more than 8 metres
in total length before being interrupted
2
0
5.0
9.07.013.015.011.0
Flow Rate (l/min)
with a swan neck air break and tundish.
Condensate Drain Tray Monitoring
A oat level switch shall be incorporated into the unit drain tray for indication of a high water alarm.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
35
Page 36
SmartCool™ 6 - 200kW
Installation Data
Dimensions
SN/SR
Installation
Precision Air Conditioning
Height
Depth
Detail of the doors and return air ducting centres is available from the general arrangement drawings upon request.
Length
LengthHeightDepth
SN06Dmm6841980600
SN09Dmm9631980600
SN12Dmm12421980600
SR09Dmm9631980890
SR12Dmm12421980890
SR15Dmm15211980890
SR18Dmm18001980890
36SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 37
Installation Data
Dimensions
SD
SmartCool™ 6 - 200kW
Installation
Depth
Length
Height
C
LengthHeightDepth
SD18Dmm18001980890
SD22Dmm22001980890
SD25Dmm25001980890
SD31Dmm31001980890
SD35Dmm35001980890
Detail of the doors and return air ducting centres is available from the general arrangement drawings upon request.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
37
Page 38
SmartCool™ 6 - 200kW
Precision Air Conditioning
Installation Data
Lifting
Whenever a unit is lifted, it should be from the base and, where possible, with all packing and protection in position. If
any type of slinging is used, due care should be taken to ensure that the slings do not crush the casework.
IMPORTANT
If the unit is dropped, it should immediately be checked for damage and reported to Airedale.
Positioning & Levelling
The unit should be positioned on a stable and even base. With the use of a spirit level the base should be levelled to
ensure good condensate removal and prevent door misalignment.
Positioning the unit should be achieved by the use of rollers or skids. Crowbars must not be used as they impose a point
load on the unit frame which may cause damage and distortion.
● Check the unit is as ordered. Discrepancies or transit damage should be reported to Airedale immediately.
Installation
● This small footprint unit is relatively tall and heavy. Care should be taken during handling and lifting, that the unit is
well supported and properly balanced.
● Observe airow and maintenance clearances
● Check all services are present and accessible
CAUTION
Airedale will accept no responsibility for mishandling during the positioning of the equipment.
Unpacking
The unit is to be carefully unpacked. Inspected and any damage reported to Airedale immediately.
All packaging is to be recycled accordingly.
38SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 39
Positioning
Minimum Unit Clearance SN, SR
Open and Enclosed Floorstand Option
SmartCool™ 6 - 200kW
D
Installation
ABC - Floorstand
(3)
SN06Dmm684600
SN09D / SR09Dmm963880
SN12D / SR12Dmm1242880
SR15D
mm1521880
Min 350 – Max 750
(+ 50mm Feet Adjustable
+/-20mm)
(4)
SR18Dmm1800 880
Minimum Ceiling Clearance- (D)
Forward Only
Forward and
1 Side
Forward and
2 Sides
All Faces
SN06Dmm720500380250
SN09D / SR09Dmm720500380250
SN12D / SR12Dmm720500380250
SR15Dmm740550440280
SR18Dmm750590480300
(1) Shown with optional open oor stand.
(2) Shaded area indicates minimum service and maintenance requirements. The unit must be installed with allowance for carpet tile clearance.
(3) Dimension C denotes recommended minimum/maximum oor stand height, refer to Airedale for special applications, please specify at order.
(4) Min = Threaded foot at minimum extension (additional to “C” dimension).
Max = Threaded foot at maximum extension (additional to “C” dimension).
Packed Dimensions
For specic markets units shall be shipped, mounted on wooden pallet and covered with polythene. The pallet shall be
mechanically xed to the unit for transportation only (Please contact Airedale for this option). Add 50mm to length and
width and 160mm to height.
WIDTH + 50mm
DEPTH + 50mm
HEIGHT + 160mm
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
39
Page 40
SmartCool™ 6 - 200kW
Positioning
Installation
Minimum Unit Clearance SD
Open and Enclosed Floorstand Option
Precision Air Conditioning
ABC - Floorstand
SD18Dmm1800880
SD22Dmm2200880
SD25Dmm2500880
SD31Dmm3100880
SD35Dmm3500880
Minimum Ceiling Clearance- (D)
SD18Dmm720500380250
SD22Dmm720500380250
SD25Dmm720500380250
SD31Dmm740550440280
SD35Dmm750590480300
(1) Shown with standard open oor stand.
(2) Shaded area indicates minimum service and maintenance requirements. The unit must be installed with allowance for carpet tile clearance.
(3) Dimension C denotes recommended minimum/maximum oor stand height, refer to Airedale for special applications, please specify at order.
Forward Only
Forward and
1 Side
Min 600 – Max 750
Forward and
2 Sides
(3)
All Faces
40SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 41
Pipework Schematics
SN/SR Single Circuit
SmartCool™ 6 - 200kW
WTS
BI
OPTIONAL
BLBL
BI
M
or
DR
BI
Internal Pipework
BLBLBLBL
Installation
SN06
2 COILS
M
SN/SR09
3 COILS
SN/SR12
4 COILS
SR15
5 COILS
SR18
6 COILS
OPTIONAL
BI
BINDER POINT
BI
BL
BLEED VALVE
DR
DRAIN VALVE
2-WAY REGULATING BALL VALVE
OPTIONAL
Floor
Customer Connections
BI
External Pipework
WTS
M
WATER TEMPERATURE SENSOR
3-WAY REGULATING BALL VALVE
(ACTUATOR DRIVEN)
THREADED CONNECTION (BSPT MALE)
Ensure binder points are installed on
both inlet/outlet pipes post unit.
2-WAY REGULATING BALL VALVE
(ACTUATOR DRIVEN)
M
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
41
Page 42
SmartCool™ 6 - 200kW
Pipework Schematics
SR Dual Circuit
Precision Air Conditioning
OPTIONAL
BI
WTS
OPTIONAL
OPTIONAL
BI
DR
M
or
BI
M
Installation
BL
BL
BI
BL
BL
BL
BL
BL
BL
BL
BL
BL
BL
M
WTS
BI
DR
BI
OPTIONALOPTIONAL
BI
BINDER POINT
BI
BL
BLEED VALVE
DR
DRAIN VALVE
2-WAY REGULATING BALL VALVE
BI
M
or
Internal Pipework
Floor
Customer Connections
External Pipework
WATER TEMPERATURE SENSOR
WTS
3-WAY REGULATING BALL VALVE
(ACTUATOR DRIVEN)
M
THREADED CONNECTION (BSPT MALE)
SR09
3 COILS
SR12
4 COILS
SR15
5 COILS
SR18
6 COILS
Ensure binder points are installed on
both inlet/outlet pipes post unit.
2-WAY REGULATING BALL VALVE
(ACTUATOR DRIVEN)
M
42SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 43
Pipework Schematics
SD Single Circuit
SmartCool™ 6 - 200kW
BL
CHILLED WATER
COIL
OUTLET LEG
DR
OPTIONAL BYPASS
LEG
M
PDZAL
M
BI
BL
Installation
DR
WTS
BI
INLET LEG
SD Dual Circuit
Dual circuit units have two single circuits duplicated.
BI
BL
BINDER POINT
BLEED VALVE
DR
WTS
DRAIN VALVE
WATER
TEMPERATURE
SENSOR
M
2 WAY
REGULATING
BALL VALVE
(ACTUATOR
DRIVEN)
PDZAL
DIFFERENTIAL
PRESSURE TRANDUCER
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
43
Page 44
SmartCool™ 6 - 200kW
Incoming Services
SN Single Circuit
VIEW FROM ABOVE
Precision Air Conditioning
79
G
E
92
Installation
SR Single Circuit
F
B
179
105
A DIA 22mm WATER INLET
B DIA 22mm WATER OUTLET
E POWER (CONNECT VIA EXTERNAL CONNECTION BOX)
F CONTROLS (CONNECT VIA CONNECTORS)
G CONDENSATE DRAIN (TEE TO HUMIDIFIER DRAIN - IF USED)
H HUMIDIFIER DRAIN (TEE TO CONDENSATE DRAIN)
J HUMIDIFIER FILL
A
93
FRONT OF UNIT
186
72
684
H
J
70
163.8
G
600
80
79
521
451
272
E
VIEW FROM ABOVE
F
B
105
A
FRONT OF UNIT
963
199
75
254
129
A DIA 35mm WATER INLET
B DIA 35mm WATER OUTLET
E POWER (CONNECT VIA EXTERNAL CONNECTION BOX)
F CONTROLS (CONNECT VIA CONNECTORS)
G CONDENSATE DRAIN (TEE TO HUMIDIFIER DRAIN - IF USED)
H HUMIDIFIER DRAIN (TEE TO CONDENSATE DRAIN)
J HUMIDIFIER FILL
H
J
98
216
80
92
343
632.5
890
811
44SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 45
Incoming Services
SR Dual Circuit
SmartCool™ 6 - 200kW
E
D
VIEW FROM ABOVE
C
556
408
259
111
A DIA 42mm CIRCUIT 1 WATER INLET
B DIA 42mm CIRCUIT 1 WATER OUTLET
C DIA 42mm CIRCUIT 2 WATER INLET
D DIA 42mm CIRCUIT 2 WATER OUTLET
E POWER (CONNECT VIA EXTERNAL CONNECTION BOX)
F CONTROLS (CONNECT VIA CONNECTORS)
G CONDENSATE DRAIN (TEE TO HUMIDIFIER DRAIN - IF USED)
H HUMIDIFIER DRAIN (TEE TO CONDENSATE DRAIN)
J HUMIDIFIER FILL
105
B
A
FRONT OF UNIT
1800
199
J
75
G
92
79
Installation
890
811
F
80
H
98
216
632.5
343
SN, SR Electrical Power Connections
FRONT OF
UNIT
HUMIDIFIER
DRAIN
FLOOR
LEVEL
HUMIDIFIER
FILL
CUSTOMER POWER
CONNECTIONS
HUMIDIFIER
(OPTIONAL)
CONTROLS
IN
CONDENSATE
DRAIN
POWER IN
CONDENSATE PUMP
(OPTIONAL)
VIEW ON RIGHT HAND SIDE
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
45
Page 46
SmartCool™ 6 - 200kW
Incoming Services
SD Single Circuit
1980
Installation
Precision Air Conditioning
SD Dual Circuit
FLOOR LEVEL
H
H VARIES
CLIENT SPECIFIED FLOOR VOID
1980H
170
247
WATER INLET
WATER OUTLET
L
FLOOR LEVEL
29890
2ND GLAND POINT FOR
DUAL POWER OPTION
106
POWER CABLE AND
GLAND POINT
FLOOR LEVEL
H VARIES
CLIENT SPECIFIED FLOOR VOID
170
115
236
WATER INLET
CIRCUIT 2
WATER OUTLET
CIRCUIT 2
WATER INLET
CIRCUIT 1
WATER OUTLET
CIRCUIT 1
L
238
115
108
170
FLOOR LEVEL
36890
2ND GLAND POINT FOR
DUAL POWER OPTION
POWER CABLE AND
GLAND POINT
46SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
47
Page 48
SmartCool™ 6 - 200kW
Water Detector Tape Installation
Water Detection Tape Installation
Monitored by a sensing relay, the water detection tape will provide an alarm when in contact with several drops of
conductive liquid. High humidity should normally not cause an alarm unless it results in condensation dripping on the
tape surface or condensation present on the surface to which the tape is applied.
The recommended installation process is as follows:
● When applying to a surface such as concrete, the most popular method is to press the tape fi rmly onto a
continuous fi lm of approved adhesive or glue. When properly glued to the fl oor the tape lies fl at on the fl oor
avoiding “bridging” (where the detector lifts off the fl oor allowing water to run under the detector without detection)
and avoids damage to the detector
● When applying the tape directly to the piping, the tape is simply strapped to the pipe
● Care should be taken to prevent the wire detectors in the tape from coming into contact with any electrically
conductive material causing a “fault” condition. Anything used in applying the tape which interferes with the
capability of the fl eece substrate may adversely affect the detector’s function
● The tape should not be installed under piping or equipment that can condense liquid as the condensation could
drip on the tape causing an alarm
● The tape should not be installed directly under an air handling unit, but around the unit
● In the sub-fl oor of a computer room the tape should be installed after the raised fl oor, conduit and piping are
installed and the sub-fl oor cleaned and sealed
Any adhesive which alters the chemical composition of the tape must be avoided and any use
thereof voids any warranty, expressed or implied. 3M Scotch-Weld™ 77 adhesive is strongly
recommended to ensure the warranty will be maintained. When adhesive is used, adhesive with an
IMPORTANT
oily or greasy base MUST be avoided as this will affect the tape’s ability to detect moisture.
When the use of an adhesive is not desirable or practical, staples, clips or other devices may be
used. When applying the tape to piping a combination of glue and plastic or nylon straps or wire
ties may be used. The straps or ties help to cut down installation time and secures the tape to the
pipe while the adhesive cures and dries.
Precision Air Conditioning
Any electrically conductive attachment devices used must not touch the wires that are within the
tape fabric. The maximum length of a detector loop, including wire and detector tape is 50 metres.
However, this tape length is not practical for most applications. Where the tape is concealed or not
easily accessible, tape runs should be limited to no more than 30 metres, and 10 to 15 metres per
zone is generally used. If the water detector tape is to be attached to or covered by a metallic or
CAUTION
For further information, please refer to Airedale’s Technical Bulletin and Loose Part Instruction Manual.
conductive surface, care should be taken not to short the conductors.
When installing tape to any surface, be careful not to short circuit or ground out the conductors
(such as over/under conduit or sharp edges of cable trays etc.). This also applies to any covering
which may be applied over the tape. Before installing the tape, be sure to inspect areas where the
tape is to be applied for presence of chemical materials that could create problems. If in doubt, it is
recommended to clean the fl oor with a mild detergent.
48SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 49
pLAN Termination
Customer Side
SmartCool™ 6 - 200kW
Technic a lC0C0
RxTx -
RxTx +
CAUTION
RxTx -
RxTx +
GND
The plugged termination ensures that the connections are made simultaniously.
Failure to attached the cables this way may cause damage to the controller.
GND
Panel Side
C000SN
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
49
Page 50
SmartCool™ 6 - 200kW
Technical Data SN C000 Units
Mechanical and Electrical Data
Precision Air Conditioning
Mechanical
Capacity
Nom Cooling (Gross) (1)kW12.816.821.726.931.336.3
Fan Power Input (Fan Gain)(2) kW0.250.620.651.320.991.75
Water volumel131319192525
Water ow ratel/s0.610.81.031.281.491.73Pressure dropkPa18.731.823.235.424.832.9
Fan & Motor
Quantity x Motor Size(4)kW1 x 0.781 x 0.781 x 2.51 x 2.51 x 2.41 x 2.4
Speed @25Pa ESPrpm195425902120247419852361
Speed @maximum ESPrpm268026802970297024002400
Maximum ESPPa55287112661858985
Nominal Airowm³/s0.700.951.201.551.752.10
Connections
Water Inlet / Outletmm22.022.028.028.035.035.0
Filtration
Quantity66991212
Electric Heating
RatingkW3.03.06.06.06.06.0
Stage of Reheat112222
Humidier
Capacitykg/hr338888
SN06D010-C000
SN06D015-C000
SN09D020-C000
SN09D025-C000
SN12D030-C000
SN12D035-C000
Electrical
Unit Data - Full Function(5)
C0C0Technic a lC000SN
Nominal Run AmpsA10.310.322.422.422.322.3
Recommended Mains Fuse SizeA161632323232
Unit Data - Cooling Only
Nominal Run AmpsA2.552.55554.94.9
Recommended Mains Fuse SizeA101010101010
Max Mains Incoming Cable Sizemm²161616161616
Fan and motor
Full Load AmpsA1.61.6443.93.9
Electric Heat
Current Per PhaseA4.44.48.78.78.78.7
Humidier
RatingkW2.252.256666
Full Load AmpsA3.33.38.78.78.78.7
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5)
Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
50SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
51
Page 52
(3)
(1)
SmartCool™ 6 - 200kW
Precision Air Conditioning
Measurement of Sound Data
All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated
sound intensity meter in accordance with BS EN ISO9614 Part 1: 2009.
All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO9614 Part 1:
2009.
Semi Hemispherical
Sound Pressure Levels are calculated from sound power using the semi-hemispherical method where the noise source
is in junction with 2 boundaries i.e. the oor and 1 wall.
Free Field
For comparison, the semi hemispherical gures can typically be reduced by 6dB to provide free eld conditions.
IMPORTANT
The sound data quoted is based on the unit having a ducted return air and standard backwards curved EC motors tted,
refer to illustration below.
Case breakout sound data is therefore independent of the discharge air and return air sound data.
For non-ducted return air applications, the overall case breakout sound levels may increase, due to the return air sound
being predominant.
Within the conditioned space, sound from in-room ducted discharge air grilles and other equipment will contribute to the
overall sound level and should therefore be considered as part of sound calculations.
Specialist acoustic advice is recommended for noise critical applications.
(2)
(1) Return Air
(2) Case Breakout
(3) Discharge Air
52SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air686466696863585026
Case Breakout706871726964585130
Sound Pressure @ 3m565357585450443715
Discharge Air817576818075696238
Return Air797576797973686137
Case Breakout817982838075696241
Sound Pressure @ 3m666467686561544826
Discharge Air696870746960575134
Return Air686870726858565034
Case Breakout707275766860565237
Sound Pressure @ 3m565761615445423723
Discharge Air767372827567635740
Return Air757372807465625639
Case Breakout777777837467635743
Sound Pressure @ 3m626263696052484329
Discharge Air696572736760575637
Return Air686572716658565536
Case Breakout706978756760575740
Sound Pressure @ 3m555563605245424226
Discharge Air736474787164625844
Return Air726473767062615743
Case Breakout746879797164615847
Sound Pressure @ 3m595364655649474432
dB(A)
SmartCool™ 6 - 200kW
Frequency (Hz) dB
Technic a lC0C0
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
C000SN
53
Page 54
N1
Neutral (Supply 1)
301
L1 (Supply 1)
302
L2 (Supply 1)
303
L3 (Supply 1)
N2
Neutral (Supply 2)
304
L1 (Supply 2)
305
L2 (Supply 2)
306
L3 (Supply 2)
PE
Protective Earth
502
Fire Detector
583
Fire Detector
583
Smoke Detector
584
Smoke Detector
502
Remote On/Off
522
Remote On/Off
2
Condensate Pump Supply (230V)
N (3*)
Condensate Pump Supply (230V)
534
Condensate Pump High Level Alarm
535
Condensate Pump High Level Alarm
609
Flood Detection Tape / Probe
610
Flood Detection Tape / Probe
810
Supply Air Temperature Sensor
811
Supply Air Temperature Sensor
560
Non-Critical Alarm N/O
561
Non-Critical Alarm Common
563
Critical Alarm N/O
564
Critical Alarm Common
565
Critical Alarm N/C
881
BMS Connection
882
BMS Connection
883
BMS Connection
Conn 15
Conn 16
Conn 17
Conn 14
Conn 14
PIN 1
SmartCool™ 6 - 200kW
Technical Data SN C000 Units
Interconnecting Wiring
Precision Air Conditioning
CONN17
CONN14
CONN16
CONN15
PIN 1
PIN 1
Pin No.Wire
1502
2583 or 584
32
4N or 3
PIN 1
Pin No.Wire
1502
2522
3560
4561
5563
6564
7565
Pin No.Wire
12
2N or 3
3PE
4534
5535
6609
7610
8810
9811
C0C0Technic a lC000SN
Pin No.Wire
1881
2882
3883
54SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 55
Technical Data SR C000 Units
Mechanical and Electrical Data
SmartCool™ 6 - 200kW
Mechanical
Capacity
Nom Cooling (Gross) (1)kW34.742.350.360.170.076.384.698.3
Fan Power Input (Fan Gain)(2) kW0.81.451.252.342.122.792.223.8
Water volumel3030404051516565
Water ow ratel/s1.652.012.42.863.333.634.034.68
Pressure dropkPa25.937.430.841.946.854.435.346.3
Fan & Motor
Quantity x Motor Size(4)kW 1 x 1.96 1 x 1.96 1 x 2.9 1 x 2.9 2 x 1.96 2 x 1.96 2 x 2.9 2 x 2.9
Speed @25Pa ESPrpm11741440131315921276140012271455
Speed @maximum ESPrpm15601560166016601560156016601660
Maximum ESPPa463202508129354227557325
Nominal Airowm³/s1.852.302.703.303.804.204.605.50
Connections
Water Inlet / Outletmm35.035.042.042.042.042.05454
Filtration
Quantity99121215151818
Electric Heating
RatingkW7.57.51515151522.522.5
Stage of Reheat11222233
Humidier
Capacitykg/hr888815151515
SR09D030-C000
SR09D040-C000
SR12D045-C000
SR12D055-C000
SR15D065-C000
SR15D075-C000
SR18D080-C000
SR18D095-C000
Technic a lC0C0C000SR
Electrical
Unit Data - Full Function
Nominal Run AmpsA26.426.435.835.850.650.658.758.7
Recommended Mains Fuse SizeA3232505063638080
Unit Data - Cooling Only
Nominal Run AmpsA445.435.43779.869.86
Recommended Mains Fuse SizeA1010101010101616
Max Mains Incoming Cable Sizemm²1616353535357070
Fan and motor
Full Load AmpsA334.54.5334.54.5
Electric heat
Current Per PhaseA10.910.921.721.721.721.732.532.5
Humidier
RatingkW666611.2511.2511.2511.25
Full Load AmpsA8.78.78.78.716.316.316.316.3
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
(5)
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air737371717169645525
Case Breakout757676747271645629
Sound Pressure @ 3m606262605856504214
Discharge Air807877787876706131
Return Air787877767774696031
Case Breakout808282807876706234
Sound Pressure @ 3m656767656362554720
Discharge Air767376757473676137
Return Air757376737371666036
Case Breakout777681777473666140
Sound Pressure @ 3m626267625958524725
Discharge Air827881807979736743
Return Air817881797877726642
Case Breakout828287827979726746
Sound Pressure @ 3m686772686464585331
Discharge Air797876777876706131
Return Air787876767774696030
Case Breakout808182797776696134
Sound Pressure @ 3m656767656361554719
Discharge Air828079808078726334
Return Air818079787977726233
Case Breakout828484828078726437
Sound Pressure @ 3m686970676564574922
Discharge Air787477767574686238
Return Air767477747472676137
Case Breakout787882787574686241
Sound Pressure @ 3m646368646060534827
Discharge Air827882818079736743
Return Air817982797977726642
Case Breakout838287837979726746
Sound Pressure @ 3m686872686564585331
dB(A)
SmartCool™ 6 - 200kW
Frequency (Hz) dB
Technic a lC0C0C000SR
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
57
Page 58
PIN 1
SmartCool™ 6 - 200kW
Technical Data SR C000 Units
Interconnecting Wiring
Precision Air Conditioning
SR
C0C0Technic a lC000
N1
301
302
303
N2
304
305
306
PE
502
583
583
584
502
522
2
N (3*)
534
535
609
610
810
811
560
561
563
564
565
881
882
883
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
Conn 17
Conn 14
Conn 16
Conn 14
Conn 15
CONN17
CONN14
CONN16
CONN15
PIN 1
PIN 1
Pin No.Wire
1502
2583 or 584
32
4N or 3
PIN 1
Pin No.Wire
1502
2522
3560
4561
5563
6564
7565
Pin No.Wire
12
2N or 3
3PE
4534
5535
6609
7610
8810
9811
Pin No.Wire
1881
2882
3883
58SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 59
Technical Data SR C0C0 Units
Mechanical and Electrical Data
SmartCool™ 6 - 200kW
Mechanical
Capacity
Nom Cooling (Gross) (1)kW25.330.536.543.150.554.761.070.1
Fan Power Input (Fan Gain)(2) kW0.811.471.262.362.152.822.253.86
Water volumel1616222227273535
Water ow ratel/s1.21.451.742.052.42.62.93.34
Pressure dropkPa18.726.621.529.030.535.326.233.1
Fan & Motor
Quantity x Motor Size(4)kW 1 x 1.96 1 x 1.96 1 x 2.9 1 x 2.9 2 x 1.96 2 x 1.96 2 x 2.9 2 x 2.9
Speed @25Pa ESPrpm11781444131615951281140412311460
Speed @maximum ESPrpm15601560166016601560156016601660
Maximum ESPPa459197504124349221551318
Nominal Airowm³/s1.852.302.703.303.804.204.605.50
Connections
Water Inlet / Outletmm35.035.042.042.042.042.05454
Filtration
Quantity99121215151818
Electric Heating
RatingkW7.57.57.57.515.015.01515
Stage of Reheat11112222
Humidier
Capacitykg/hr33338888
SR09D020-C0C0
SR09D025-C0C0
SR12D030-C0C0
SR12D035-C0C0
SR15D040-C0C0
SR15D045-C0C0
SR18D050-C0C0
SR18D060-C0C0
Technic a lC0C0C0C0SR
Electrical
Unit Data - Full Function(5)
Nominal Run AmpsA21.021.019.6319.63434340.340.3
Recommended Mains Fuse SizeA2525252550505050
Unit Data - Cooling Only
Nominal Run AmpsA445.435.43779.869.86
Recommended Mains Fuse SizeA1010101010101616
Max Mains Incoming Cable Sizemm²1616161635353535
Fan and motor
Full Load AmpsA334.54.5334.54.5
Electric heat
Current Per PhaseA10.910.910.910.921.721.721.721.7
Humidier
RatingkW2.252.252.252.256666
Full Load AmpsA3.33.33.33.38.78.78.78.7
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air737371717269645525
Case Breakout757777747271645629
Sound Pressure @ 3m606262605856504214
Discharge Air807877787876706131
Return Air797877767774696031
Case Breakout808282807876706234
Sound Pressure @ 3m666767656362554720
Discharge Air777376757473676137
Return Air757376737371666036
Case Breakout777681777473666140
Sound Pressure @ 3m626267625959524726
Discharge Air827881817979736743
Return Air817881797877726642
Case Breakout828287827979726746
Sound Pressure @ 3m686872686464585331
Discharge Air807876787876706131
Return Air787876767774696030
Case Breakout808282797776706134
Sound Pressure @ 3m656767656361554720
Discharge Air828079808078726334
Return Air818079787977726333
Case Breakout828484828078726437
Sound Pressure @ 3m687070676564584922
Discharge Air787477767674686238
Return Air767477757472676138
Case Breakout787882787574686341
Sound Pressure @ 3m646368646060534827
Discharge Air827982818079736743
Return Air817982797977726642
Case Breakout838287837979726746
Sound Pressure @ 3m686872686564585332
dB(A)
SmartCool™ 6 - 200kW
Frequency (Hz) dB
Technic a lC0C0C0C0SR
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
61
Page 62
PIN 1
SmartCool™ 6 - 200kW
Technical Data SR C0C0 Units
Interconnecting Wiring
Precision Air Conditioning
SR
N1
301
302
303
N2
304
305
306
PE
502
583
583
584
502
522
2
N (3*)
534
535
609
610
810
811
560
561
563
564
565
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
Conn 17
Conn 14
Conn 16
Conn 14
CONN17
CONN14
CONN16
CONN15
PIN 1
PIN 1
Pin No.Wire
1502
2583 or 584
32
4N or 3
PIN 1
Pin No.Wire
1502
2522
3560
4561
5563
6564
7565
Pin No.Wire
12
2N or 3
3PE
4534
5535
6609
7610
8810
9811
Pin No.Wire
1881
2882
3883
C0C0Technic a lC0C0
881
882
883
BMS Connection
BMS Connection
BMS Connection
Conn 15
62SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 63
Technical Data SD CH00 Units
Mechanical and Electrical Data
Mechanical
SmartCool™ 6 - 200kW
SD18D110-CH00
Capacity
Nom Cooling (Gross) (1) kW105.3132.4174.7216.5255.2
Fan Power Input (Fan Gain)(2) kW2.63.54.75.97.8
Dimensions - W x D(890) x H(1980)mm18002200250031003500
Weight - Machine Case(3)kg463525588690745
- Fan Modulekg175189244305326
- Operatingkg69978791911011190
Cooling Coil
Water Volumel627388107120
Water Flow Ratel/s5.06.38.310.312.1
Pressure DropkPa35.755.677.276.3106.5
Fan & Motor
Quantity x Motor Size(4) kW2 x 2.92 x 2.93 x 2.94 x 2.94 x 2.9
Speed @ 25Pa ESPrpm13301503140913741532
Speed @ Maximum ESPrpm16571657165716571657
Maximum ESPPa485266392428225
Nominal Airowm³/s5.76.78.811.313.0
Connections
Water Inlet / Outlet mm5454676767
Filtration
Quantity66699
Electric Heating
RatingkW15.015.022.530.030.0
Stage of Reheat22344
Humidier
Capacitykg/hr830303030
RatingkW6.022.522.522.522.5
Full Load AmpsA8.732.632.632.632.6
SD22D140-CH00
SD25D175-CH00
SD31D215-CH00
SD35D255-CH00
Technic a lCH00SD
Electrical
Unit Data - Full Function(5)
Nominal Run AmpsA40.364.279.494.794.7
Recommended Mains Fuse SizeA5080100125125
Unit Data - Cooling Only
Nominal Run AmpsA9.99.914.318.718.7
Recommended Mains Fuse SizeA1616202525
Max Mains Incoming Cable Sizemm²3570707070
Fan and Motor
Full Load AmpsA4.54.54.54.54.5
Electric heat
Current Per PhaseA21.721.732.543.443.4
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
64SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 65
Technical Data SD CH00 Units
2
M
Q
36
Kv
4
Waterside Pressure Drop Data
180.0
160.0
140.0
SmartCool™ 6 - 200kW
120.0
100.0
80.0
60.0
Pressure Drop (kPa)
40.0
20.0
0.0
0.002.004.006.008.0010.0012.0014.0016.00
4 SD31D215 - CH00 - 0
5 SD35D255 - CH00 - 0
Includes coil, port valve and pipework.
To calculate 3 port valve pressure drop:
∆P valve =
5
Technic a lCH00SD
Flow Rate (l/s)
SD31D215-CH00-0SD35D225-CH00-0
where ∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
Fluid 100% water.
Kv Cooling Kv Bypass
SD31D215-CH006363
SD35D255-CH006363
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
65
Page 66
SmartCool™ 6 - 200kW
Technical Data SD CH00 Units
Sound Data
Precision Air Conditioning
Overall
Sound Measurement631252505001000200040008000
Discharge Air636677645650474032
SD18D110-CH00
SD22D140-
CH00
SD25D175-
CH00
Technic a l
SD31D215-
CH00
SD35D255-
CH00
(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air586471595347474032
Case Breakout647276676054514638
Sound Pressure @ 3m505762524639363223
Discharge Air666980675953514336
Return Air616774625550514335
Case Breakout677579706357545041
Sound Pressure @ 3m536065554943393527
Discharge Air666980675953514335
Return Air616774625650504335
Case Breakout677579706357545041
Sound Pressure @ 3m536065554943393526
Discharge Air677081686054514436
Return Air626875635650514336
Case Breakout687580706458545042
Sound Pressure @ 3m536166564943403627
Discharge Air707384706257544739
Return Air657178665954544739
Case Breakout717883736761585445
Sound Pressure @ 3m566468595246433930
dB(A)
Frequency (Hz) dB
CH00SD
66SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 67
Technical Data SD CH00 Units
Interconnecting Wiring
SmartCool™ 6 - 200kW
N1
301
302
303
N2
304
305
306
PE
502
583
583
584
502
522
2
N (3*)
534
535
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
Technic a lCH00SD
609
610
810
811
560
561
563
564
565
881
882
883
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
67
Page 68
SmartCool™ 6 - 200kW
Technical Data SD CL00 Units
Mechanical and Electrical Data
Mechanical
Precision Air Conditioning
Technic a lSD
SD18D115-CL00
Capacity
Nom Cooling (Gross) (1)kW91.6110.2144.3186.4215.4
Fan Power Input (Fan Gain)(2)kW2.63.54.75.97.8
Dimensions - W x D(890) x H(1980)mm18002200250031003500
Weight - Machine Case(3)kg463525588690745
- Fan Modulekg175189244305326
- Operatingkg69978791911011190
Cooling Coil
Water Volumel627388107120
Water Flow Ratel/s3.64.45.77.48.6
Pressure DropkPa25.939.562.467.195.1
Fan & Motor
Quantity x Motor Size(4)kW2 x 2.92 x 2.93 x 2.94 x 2.94 x 2.9
Speed @ 25Pa ESPrpm13341503140913741532
Speed @ Maximum ESPrpm16571657165716571657
Maximum ESPPa485266392428225
Nominal Airowm³/s5.76.78.811.313.0
Connections
Water Inlet / Outletmm5454676767
Filtration
Quantity66699
Electric Heating
RatingkW15.015.022.530.030.0
Stage of Reheat22344
Humidier
Capacitykg/hr830303030
RatingkW6.022.522.522.522.5
Full Load AmpsA8.732.632.632.632.6
SD22D145-CL00
SD25D180-CL00
SD31D235-CL00
SD35D270-CL00
CL00
Electrical
Unit Data - Full Function(5)
Nominal Run AmpsA40.364.279.494.794.7
Recommended Mains Fuse SizeA5080100125125
Unit Data - Cooling Only
Nominal Run AmpsA9.99.914.318.718.7
Recommended Mains Fuse SizeA1616202525
Max Mains Incoming Cable Sizemm²3570707070
Fan and Motor
Full Load AmpsA4.54.54.54.54.5
Electric heat
Current Per PhaseA21.721.732.543.443.4
(1) Entering air 35°C / 24% RH water 18°C / 24°C
(2) Fan gain/ fan power input is shown for a unit delivering nominal air volume with 25Pa ESP. The fan gain / fan power values will change when selected with alternative airow or
ESP values.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other Fans are available, please contact airedale.
68SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
69
Page 70
2
M
Q
36
Kv
SmartCool™ 6 - 200kW
Technical Data SD CL00 Units
Waterside Pressure Drop Data
300.00
250.00
Precision Air Conditioning
200.00
150.00
100.00
Pressure Drop (kPa)
50.00
Technic a lSD
0.00
0.002.004.006.008.0010.0012.0014.0016.00
4 SD31D235-CL00-0
5 SD35D270-CL00-0
Includes coil, 2 port valve and pipework.
To calculate 2 port valve pressure drop:
5
4
Flow Rate (l/s)
SD31D235-CL00-0SD35D270-CL00-0
∆P valve =
where ∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
Fluid 100% water.
CL00
Kv Cooling Kv Bypass
SD31D235-CL006363
SD35D270-CL006363
70SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 71
Technical Data SD CL00 Units
Sound Data
SmartCool™ 6 - 200kW
Overall
Sound Measurement631252505001000200040008000
Discharge Air636677645650474032
SD18D115-CL00
SD22D145-CL00
SD25D180-CL00
SD31D235-CL00
SD35D270-CL00
(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air586471595347474032
Case Breakout647276676054514638
Sound Pressure @ 3m505762524639363223
Discharge Air666980675953514336
Return Air616774625550514335
Case Breakout677579706357545041
Sound Pressure @ 3m536065554943393527
Discharge Air666980675953514335
Return Air616774625650504335
Case Breakout677579706357545041
Sound Pressure @ 3m536065554943393526
Discharge Air677081686054514436
Return Air626875635650514336
Case Breakout687580706458545042
Sound Pressure @ 3m536166564943403627
Discharge Air707384706257544739
Return Air657178665954544739
Case Breakout717883736761585445
Sound Pressure @ 3m566468595246433930
dB(A)
Frequency (Hz) dB
Technic a lSDCL00
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
71
Page 72
SmartCool™ 6 - 200kW
Technical Data SD CL00 Units
Interconnecting Wiring
Precision Air Conditioning
N1
301
302
303
N2
304
305
306
PE
502
583
583
Technic a l
584
502
522
2
N (3*)
534
535
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
609
610
810
811
560
561
563
564
565
881
882
883
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
72SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 73
Technical Data SD CHCH Units
Mechanical and Electrical Data
Mechanical
SmartCool™ 6 - 200kW
SD18D085-CHCH
Capacity
Nom Cooling (Gross) (1) kW75.298.3128.4155.0183.6
Fan Power Input (Fan Gain)(2) kW2.33.54.15.47.2
Dimensions - W x D(890) x H(1980)mm18002200250031003500
Weight - Machine Case(3) kg477547618727788
- Fan Modulekg175189244305325
- Operatingkg70279894011271221
Cooling Coil
Water Volumel50627996108
Water Flow Ratel/s3.64.76.17.48.7
Pressure DropkPa23.039.543.537.151.3
Fan & Motor
Quantity x Motor Size(4) kW2 x 2.92 x 2.93 x 2.94 x 2.94 x 2.9
Speed @ 25Pa ESPrpm12661491133713221479
Speed @ Maximum ESPrpm16571657165716571657
Maximum ESPPa538287463473302
Nominal Airowm³/s5.36.58.210.712.4
Connections
Water Inlet / Outletmm5454676767
Filtration
Quantity66699
Electric Heating
RatingkW15.015.022.530.030.0
Stage of Reheat22344
Humidier
Capacitykg/hr830303030
RatingkW6.022.522.522.522.5
Full Load AmpsA8.732.632.632.632.6
SD22D105-CHCH
SD25D135-CHCH
SD31D165-CHCH
SD35D195-CHCH
Technic a lCHCHSD
Electrical
Unit Data - Full Function(5)
Nominal Run AmpsA40.364.279.494.794.7
Recommended Mains Fuse SizeA5080100125125
Unit Data - Cooling Only
Nominal Run AmpsA9.99.914.318.718.7
Recommended Mains Fuse SizeA1616202525
Max Mains Incoming Cable Sizemm²3570707070
Fan and Motor
Full Load AmpsA4.54.54.54.54.5
Electric heat
Current Per PhaseA21.721.732.543.443.4
(1) Entering air 24°C /45% RH water 7°C/ 12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airow at 25Pa ESP, these values may change with different ESP.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other fans are available, please contact Airedale.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
76SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 77
Technical Data SD CHCH Units
Interconnecting Wiring
SmartCool™ 6 - 200kW
N1
301
302
303
N2
304
305
306
PE
502
583
583
584
502
522
2
N (3*)
534
535
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
Technic a lCHCHSD
609
610
810
811
560
561
563
564
565
881
882
883
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
77
Page 78
SmartCool™ 6 - 200kW
Technical Data SD CLCL Units
Mechanical and Electrical Data
Mechanical
Precision Air Conditioning
SD18D090-CLCL
Capacity
Nom Cooling (Gross) (1) kW75.396.7117.6158.8185.4
Fan Power Input (Fan Gain)(2) kW2.33.54.15.47.2
Dimensions - W x D(890) x H(1980)mm18002200250031003500
Weight - Machine Case(3) kg477547618727788
- Fan Modulekg175189244305326
- Operatingkg70279894011271221
Cooling Coil
Water Volumel50627996108
Water Flow Ratel/s3.03.84.76.37.4
Technic a l
Pressure DropkPa23.141.025.549.772.1
Fan & Motor
Quantity x Motor Size(4) kW2 x 2.92 x 2.93 x 2.94 x 2.94 x 2.9
Speed @ 25Pa ESPrpm12661491133713221479
Speed @ Maximum ESPrpm16571657165716571657
Maximum ESPPa538287463473302
Nominal Airowm³/s5.36.58.210.712.4
Connections
Water Inlet / Outletmm5454676767
Filtration
Quantity66699
Electric Heating
RatingkW15.015.022.530.030.0
Stage of Reheat22344
Humidier
Capacitykg/hr830303030
RatingkW6.022.522.522.522.5
Full Load AmpsA8.732.632.632.632.6
SD22D120-CLCL
SD25D140-CLCL
SD31D190-CLCL
SD35D225-CLCL
Electrical
CLCLSD
Unit Data - Full Function(5)
Nominal Run AmpsA40.364.279.494.794.7
Recommended Mains Fuse SizeA5080100125125
Unit Data - Cooling Only
Nominal Run AmpsA9.99.914.318.718.7
Recommended Mains Fuse SizeA1616202525
Max Mains Incoming Cable Sizemm²3570707070
Fan and Motor
Full Load AmpsA4.54.54.54.54.5
Electric heat
Current Per PhaseA21.721.732.543.443.4
(1) Entering air 35°C / 24% RH water 18°C / 24°C
(2) Fan gain/ fan power input is shown for a unit delivering nominal air volume with 25Pa ESP. The fan gain / fan power values will change when selected with alternative airow or
ESP values.
(3) Machine weight excludes water charge.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Values given for full function units with standard selections for heating, humidication, supply air fans.
Other Fans are available, please contact airedale.
78SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
79
Page 80
2
M
Q
36
Kv
SmartCool™ 6 - 200kW
Technical Data SD CLCL Units
Waterside Pressure Drop Data
250.00
Precision Air Conditioning
200.00
150.00
100.00
Pressure Drop (kPa)
Technic a l
50.00
0.00
4 SD31D190-CLCL-0
5 SD35D225-CLCL-0
5
4
0.002.004.006.008.0010.0012.0014.00
Flow Rate (l/s)
SD31D190-CLCL-0SD35D225-CLCL-0
Includes coil, 2 port valve and pipework.
To calculate 3 port valve pressure drop:
∆P valve =
where
∆P = Pressure Drop in kPa,
Q = Water Flow Rate in l/s and M =
CLCLSD
Fluid 100% water.
SD31D190-CLCL6363
SD35D225-CLCL6363
Kv Cooling Kv Bypass
80SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 81
Technical Data SD CLCL Units
Sound Data
SmartCool™ 6 - 200kW
Overall
Sound Measurement631252505001000200040008000
Discharge Air626576635549463931
SD18D090-CLCL
SD22D120-CLCL
SD25D135-CLCL
SD31D190-CLCL
SD35D225-CLCL
(1) dB(A) is the overall sound level, measured on the A scale
(2) All sound data measured at nominal conditions, Discharge Air, Return air and case breakout is sound power.
Return Air576370585246463831
Case Breakout637075665953494537
Sound Pressure @ 3m495661514538353122
Discharge Air666980675953504335
Return Air616774625550504335
Case Breakout677579696357545041
Sound Pressure @ 3m536065554842393526
Discharge Air656879665852494234
Return Air606673615449494134
Case Breakout667378686256524840
Sound Pressure @ 3m525964544841383425
Discharge Air666980675953504335
Return Air616774625550504235
Case Breakout677479696357534941
Sound Pressure @ 3m536065554942393526
Discharge Air697283696156534638
Return Air647077655852534638
Case Breakout707782726660565244
Sound Pressure @ 3m556367585145423829
dB(A)
Frequency (Hz) dB
Technic a lCLCLSD
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
81
Page 82
SmartCool™ 6 - 200kW
Technical Data SD CLCL Units
Interconnecting Wiring
Precision Air Conditioning
N1
301
302
303
N2
304
305
306
PE
502
583
Technic a l
583
584
502
522
2
N (3*)
534
535
Neutral (Supply 1)
L1 (Supply 1)
L2 (Supply 1)
L3 (Supply 1)
Neutral (Supply 2)
L1 (Supply 2)
L2 (Supply 2)
L3 (Supply 2)
Protective Earth
Fire Detector
Fire Detector
Smoke Detector
Smoke Detector
Remote On/Off
Remote On/Off
Condensate Pump Supply (230V)
Condensate Pump Supply (230V)
Condensate Pump High Level Alarm
Condensate Pump High Level Alarm
CLCLSD
609
610
810
811
560
561
563
564
565
881
882
883
Flood Detection Tape / Probe
Flood Detection Tape / Probe
Supply Air Temperature Sensor
Supply Air Temperature Sensor
Non-Critical Alarm N/O
Non-Critical Alarm Common
Critical Alarm N/O
Critical Alarm Common
Critical Alarm N/C
BMS Connection
BMS Connection
BMS Connection
82SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018
Page 83
SmartCool™ 6 - 200kW
After Sales
After Sales
Warranty
All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by
an Airedale engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or
18 months from the date of despatch, whichever is the sooner.
Parts or Equipment supplied by Airedale for installation within the UK or for Export that are properly commissioned in
accordance with Airedale standards and specifi cation, not commissioned by an Airedale engineer; carry a 12 month
warranty on non consumable Parts only from the date of commissioning or 18 months from the date of despatch,
whichever is the sooner.
Parts or equipment installed or commissioned not to acceptable Airedale standards or specifi cation invalidate all
warranty.
Warranty is only valid in the event that
In the period between delivery and commissioning the equipment:
• is properly protected & serviced as per the Airedale installation & maintenance manual provided
• where applicable the glycol content is maintained to the correct level.
In the event of a problem being reported and once warranty is confi rmed* as valid under the given installation and
operating conditions, the Company will provide the appropriate warranty coverage (as detailed above) attributable to the
rectifi cation of any affected Airedale equipment supplied (excluding costs for any specialist access or lifting equipment
that must be ordered by the customer).
*Once warranty is confi rmed, maintenance must be continued to validate the warranty period.
Any spare part supplied by Airedale under warranty shall be warranted for the unexpired period of the warranty or 3
months from delivery, whichever period is the longer.
To be read in conjunction with the Airedale Conditions of Sale - Warranty and Warranty Procedure, available upon
request.
Procedure
When a component part fails, a replacement part should be obtained through our Spares department. If the part is
considered to be under warranty, the following details are required to process this requirement. Full description of part
required, including Airedale’s part number, if known. The original equipment serial number. An appropriate purchase
order number.
A spares order will be raised under our warranty system and the replacement part will be despatched, usually within 24
hours should they be in stock. When replaced, the faulty part must be returned to Airedale with a suitably completed and
securely attached “Faulty Component Return” (FCR) tag. FCR tags are available from Airedale and supplied with each
Warranty order.
On receipt of the faulty part, suitably tagged, Airedale will pass to its Warranty department, where it will be fully
inspected and tested in order to identify the reason for failure, identifying at the same time whether warranty is justifi ed
or not.
On completion of the investigation of the returned part, a full “Report on Goods Returned” will be issued. On occasion
the release of this complete report may be delayed as component manufacturers become involved in the investigation.
When warranty is allowed, a credit against the Warranty invoice will be raised. Should warranty be refused the Warranty
invoice becomes payable on normal terms.
Exclusions
Warranty may be refused for the following reasons.
• Misapplication of product or component
• Incorrect site installation
• Incomplete commissioning documentation
• Inadequate site installation
• Inadequate site maintenance
• Damage caused by mishandling
• Replaced part being returned damaged without explanation
• Unnecessary delays incurred in return of defective component
Returns analysis
All faulty components returned under warranty are analysed on a monthly basis as a means of verifying component and
product reliability as well as supplier performance. It is important that all component failures are reported correctly.
SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_09_2018
83
Page 84
Head Offi ce
Airedale International Air Conditioning Ltd
Leeds Road
Rawdon
Leeds LS19 6JY
Tel: +44 (0) 113 2391000
Fax:+44 (0) 113 2507219
E-mail enquiries@airedale.com
Web www.airedale.com
TM_SMARTCOOL_6_200kW_7674716_1.10.0_10_2018