30
Supplemental Characteristics
for all model numbers
dc Floating Voltage: Output terminals
can be floated up to ±240 Vdc from
chassis ground
Remote Sensing: Up to half the rated
output voltage can be dropped in each
load lead. The drop in the load leads
subtracts from the voltage available
for the load.
Command Processing Time: Average time
required for the output voltage to begin to
change following receipt of digital data is
20 ms for the power supplies connected
directly to the GPIB
Output Programming Response Time: The
rise and fall time (10/90% and 90/10%) of
the output voltage is less than 15 ms. The
output voltage change settles within
1 LSB (0.025% x rated voltage) of final
value in less than 60 ms.
Down Programming: An active down
programmer sinks approximately
20% of the rated output current
Modulation: (Analog programming of
output voltage and current)
Input Signal: 0 to –5 V
Input Impedance: 10 k Ohm nominal
ac Input: (ac input frequency 47 to 63 Hz)
Voltage 100 Vac 120 Vac 220 Vac 240 Vac
Current 4.4 A 3.8 A 2.2 A 2.0 A
Input Power 480 VA, 400 W at full load;
60 W at no load
GPIB Interface Capabilities SH1, AH1, T6,
L4, SR1, RL1, PP0, DC1, DT1, E1, and C0.
IEEE-488.2 and SCPI-compatible command set
Regulatory Compliance: Complies
with UL 3111-1, IEC 61010-1.
Size: 425.5 mm W x 88.1 mm H x
439 mm D (16.75 in x 3.5 in x 17.3 in)
See page 101 for more details.
Weight: Net, 14.2 kg (31.4 lb); shipping,
16.3 kg (36 lb)
Warranty Period: Three years
Single-Output: 200 W GPIB (Continued)
Specifications
(at 0˚to 55˚C unless
otherwise specified)
6641A- 6643A- 6644A- 6645A- 6645AJ04 J11 J09 J05 J06
Special Order Special Order Special Order Special Order Special Order
Option Option Option Option Option
Number of Outputs 11111
GPIB Yes Yes Yes Yes Yes
Output ratings
Output voltage 13 V 40 V 70 V 150 V 170 V
Output current (40˚C) 15.3 A 5 A 3 A 1.2 A 1 A
Maximum current (50˚C/55˚C) 13.77 A/13 A 4.5 A/4.25 A 2.7 A/2.55 A 1.08 A/1.02 A 0.9 A/0.85 A
Programming accuracy
at 25˚C ±5˚C
Voltage 0.06% + 8.5 mV 17.5 mV 31 mV 65 mV 74 mV
Current 0.15% + 21 mA 6.7 mA 4.1 mA 1.7 mA 1.7 mA
Ripple and noise
from 20 Hz to 20 MHz
Voltage rms 300 µV 450 µV 600 µV 900 µV 1 mV
peak-peak 3 mV 3.5 mV 6 mV 9 mV 10 mV
Current rms 8 mA 3 mA 1.5 mA 1 mA 1 mA
Readback accuracy at 25˚C ±5˚C
(percent of reading plus fixed)
Voltage 0.07% + 10 mV 30 mV 47 mV 100 mV 140 mV
+Current 0.15% + 15 mA 5 mA 3 mA 1.3 mA 1.3 mA
–Current 0.35% + 40 mA 12 mA 6.8 mA 2.9 mA 2.9 mA
Load regulation
Voltage 1 mV 3 mV 4.5 mV 7 mV 8 mV
Current 1 mA 0.25 mA 0.25 mA 0.25 mA 0.25 mA
Line regulation
Voltage 0.5 mV 1 mV 1.5 mV 2.5 mV 3 mV
Current 1 mA 0.25 mA 0.25 mA 0.25 mA 0.25 mA
Transient response time Less than 100 µs for the output voltage to recover to its previous level (within 0.1% of
the voltage rating of the supply or 20 mV, whichever is greater) following any step change in load current of up to
50% of rated current
Supplemental Characteristics (Non-warranted characteristics determined by design and
useful in applying the product)
Average resolution
Voltage 3.5 mV 12 mV 1.4 mV 37.5 mV 42.5 mV
Current 5 mA 2 mA 1.2 mA 0.5 mA 0.5 mA
OVP 23 mV 62 mV 110 mV 250 mV 285 mV
OVP accuracy 260 mV 800 mV 1.5 mV 3 V 3.4 V
Power Products Catalog 2002-2003
For more detailed specifications see the product manual at
www.agilent.com/find/power
Agilent Performance dc Power Supplies speed and accuracy for test optimization
Ordering Information
Opt 100 87 to 106 Vac, 47 to 63 Hz
Opt 120 104 to 127 Vac, 47 to 63 Hz
Opt 220 191 to 233 Vac, 47 to 63 Hz
Opt 240 209 to 250 Vac, 47 to 63 Hz
* Opt 908 Rack-mount Kit (p/n 5063-9212)
* Opt 909 Rack-mount Kit w/ Handles
(p/n 5063-9219)
Opt 0L2 Extra Standard Documentation
Package
Opt 0B3 Service Manual
Opt 0B0 No Documentation Package
* Support rails required
Accessories
p/n 1494-0060 Accessory Slide Kit
p/n 1252-3698 7-pin Analog Plug
p/n 1252-1488 4-pin Digital Plug
p/n 5080-2148 Serial Link Cable
2 m (6.6 ft)
E3663AC Support rails for Agilent
rack cabinets