Aerovent IM-172 User Manual

IM-172
August 2014
General Installation, Operation and Maintenance Instructions For Aerovent Products
Propeller Wall Fans
Models: BSBP, BSDDP
Aerovent Catalog 172 provides additional information on this equipment. This catalog
can be found at www.aerovent.com or by contacting your local Aerovent sales representative.
BSBP BSDDP
Model Nomenclature
Model BSDDP = Wall Propeller Fan, Direct Drive
BSBP = Wall Propeller Fan, Belt Driven
Fan Size
Propeller Type
B = Backswept
Hub Designation
Blade Count
Blade Angle
BSDDP - 24 - B - 1 - 05 - 25
©2014 Aerovent
Receiving, Unpacking & Inspection
When the equipment is received all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Before accepting delivery, carefully inspect each carton or crate for visible shipping damage. If any damage is noticed, the carrier should make the proper notation on the delivery receipt acknowledging the damage. Make notations of all damage on all copies of the bill of lading and have all copies countersigned by the delivering carrier. The carrier should also fill out a Carrier Inspection Report. The factory Traffic Department should then be contacted. File claim for damage with the carrier. Physical damage to the unit after acceptance is not the responsibility of Aerovent.
Unpack each carton or crate and verify that all required parts and proper quantities of each item have been received. Refer to drawings for part descriptions. Report shortages or missing items to your local representative to arrange for replacement parts.
Storage
If fans are stored for any length of time, they should be stored in a clean, dry location to prevent rust and corrosion. Outdoor storage is not recommended. When outdoor storage is necessary, fans should be protected from the elements as completely as possible. Cover the fan inlet and outlet and keep motors dry and clean.
For extended storage (more than 3 months) motor shafts and bearings should be rotated monthly. If stored longer
Due to availability of carriers and truck space, it is not possible to guarantee that all items will be shipped together. Verification of shipments must be limited to only those items on the bill of lading.
The unit nameplate must be checked to make sure the voltage agrees with the power supply available. CAUTION: Sheet metal parts, screws, clips and simiar items inherently have sharp edges, and it is necessary that the installer and service personnel excercise caution.
The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes. This equipment is to be installed by an experienced installation company and fully trained personnel. The mechanical installation of the exhaust ventilator consists of making final connections between the unit and building services, duct connections.
than 6 months, bearing grease in motor and fan should be purged and replaced with compatible grease. Belts should be rechecked for proper tension. Storage records should be kept to assure proper maintenance. The factory can advise warranty centers to provide motor and bearing service if needed.
Limitation of Warranties and Claims
Seller warrants to the original purchaser that the goods sold hereunder shall be free from defects in workmanship and material under normal use and service (except in those cases where the materials are supplied by the buyer) for a period of one year from the date of original installation or eighteen (18) months from the date of shipment, whichever occurs first. The liability of seller under this warranty is limited to replacing, repairing, or issuing credit (at cost, F.O.B. factory and at seller’s discretion) for any part or parts which are returned by buyer during such period provided that:
a. seller is notified in writing within ten (10) days
following discovery of such defects by buyer, or within ten (10) days after such defects should reasonably have been discovered, whichever is less;
b. the defective unit is returned to seller, transportation
charges prepaid by buyer;
c. payment in full has been received by seller or said
products;
d. seller’s examination of such unit shall disclose to its
satisfaction that such defects have not been caused by misuse, neglect, improper installation, repair, alteration, act of God, or accident.
No warranty made hereunder shall extend to any seller product whose serial number is altered, effaced or removed. Seller makes no warranty, express or implied, with respect to motors, switches, controls, or other components of seller’s product, where such components are warranted separately by their respective manufacturers. THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHETHER STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. In no event shall seller be liable to buyer for indirect, incidental collateral, or consequential damages of any kind. (BUYER’S FAILURE TO PAY THE FULL AMOUNT DUE WITHIN SIXTY (60) DAYS OF DATE OF INVOICE SHALL OPERATE TO RELEASE SELLER FROM ANY AND ALL LIABILITY OR OBLIGATION ARISING PURSUANT TO ANY WARRANTY, EXPRESS OR IMPLIED, WHETHER STATUTORY OR OTHERWISE, INCLUDING ANY IMPLIED WARRANTY OR MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, MADE IN CONNECTION WITH ANY CONTRACT FORMED HEREUNDER. BUYER AGREES THAT SUCH FAILURE TO PAY SHALL CONSTITUTE A VOLUNTARY WAIVER OF ANY AND ALL SUCH WARRANTIES ARISING PURSUANT TO SUCH CONTACT.)
2 Aerovent IM-172
Electrical Connection
1. Connect supply wiring to a disconnect switch. Check the wiring diagrams on the motor for con­nections.
2. The motor is factory set at the voltage marked on the fan nameplate. Check the line voltage with the nameplate voltage and wiring diagrams.
3. The main power wiring should be sized for the ampacity shown on the dataplate. Size wires in accordance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be necessary to increase wire size to prevent excessive voltage drop. Wires should be sized for a maximum of 3% voltage drop.
CAUTION: Use copper conductors only.
CAUTION: Protect wiring from sharp edges. Leave
some slack in the line to prevent damage.
4. (Optional) Disconnect switches are not fused. The power leads must be protected at the point of dis­tribution in accordance with the fan dataplate.
Check, Test & Start Procedure
5. On fans without a thermal protector integral to the motor (refer to unit or motor dataplate to determine if protector is present) a separate overload device is required. Refer to Sections 430-32 of the N.E.C. for sizing.
6. All units must be electrically grounded in accordance with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code (ANSI/NFPA 70). A ground lug is provided as standard in the unit terminal box. Size grounding conductor in accordance with Table 250-95 of the National Electrical Code. DO NOT use the ground lug for connecting a neutral conductor.
7. Supply voltage to the power ventilator should not vary by more than 10% of the value indicated on the unit dataplate. Phase unbalance must not exceed 2%.
WARNING: Failure of motor due to operation on
improper line voltage or with excessive phase unbal­ance constitutes product abuse and may cause severe damage to the unit’s electrical components.
WARNING
Electric shock hazard. Could cause severe injury or death. Failure to bond the frame of this equipment to the building electrical ground by use of the grounding terminal provided or other acceptable means may result in electrical shock. Disconnect electric power before servicing equipment. Service to be performed only by qualified personnel.
BEFORE START-UP: Disconnect power to this unit before servicing the unit.
1. Check to verify that the propeller is free to rotate.
2. Verify that supply voltage on the line side of discon­nect agrees with voltage on fan data plate and is within the 10% utilization voltage.
3. Apply power to unit and check rotation of propeller with the directional arrow on the unit.
WARNING: Rotation is critical. If allowed to operate
in the wrong direction, the motor will overload and burn out.
WARNING: Especially check three-phase units for
rotation. For three-phase, rotation can be changed by interchanging any two of the three line leads. If unit is checked on temporary wiring, it should be rechecked when permanently installed. Motor burn-out or tripped overload protection devices are usually the result of wrong rotation.
4. Electrical Input Check: Perform check of fan ampere draw and verify that motor nameplate amps are not exceeded. Take into account the service factor range if motor is nameplated above a 1.0 service factor.
5. Fan RPM should be checked and verified with a tachometer.
Aerovent IM-172 3
Speed Control Installation
The controller is designed to start the motor at high speed and will then slow down. This gives the motor good starting characteristics.
Speed control is available using 115/60/1 open type PSC or shaded pole motors.
Installation
Connect control in series with motor and line voltage (115V only). Never connect across line. See Figure 1.
Minimum Speed Setpoint
All controls are factory set to 65V±3V output as stan­dard with an input voltage of 120V. If different minimum speed is desired, the control may be adjusted by turn­ing minimum speed pot clockwise to decrease minimum speed and counterclockwise to increase minimum speed. Refer to Figure 2.
Warning: If minimum speed is readjusted, verify unit ampere draw does not exceed motor nameplate amps. Do not operate unit in range where amp draw exceeds motor nameplate.
Caution: These motors operate more efficiently in the ranges set from the factory. Operating motor outside these ranges (see Table 2) may cause motor to run hotter and substantially shorten motor life.
Note: Lowering the minimum speed setpoint may adversely affect motor start-up characteristics.
Warning: Certain failure modes of solid-state controls such as half-waving can cause high levels of DC, motor overheating and motor burn-out. Therefore, a thermal overload protection (integral with motor) is required to limit the maximum motor temperature under such a failure.
Note: Do not allow any sleeve bearing motor to operate below 500 RPM. Operation below 500 RPM will substantially shorten bearing life.
Figure 1. Connection Diagram, Speed Control
SPEED CONTROLLER
AC
LINE
(115V)
SWITCH TRI-AC
MOTOR
Table 2. Speed Controller RPM Range
HP RPM MAX. RPM MIN. RPM
1/8
1/8 1/6 1/4 1/2 1/6 1/4 1/2
1/3 1/2 3/4
NOTES:
1. Speed control available only with 115/60/1 open motors (thermally
2. Three-speed motor (multiple tap winding).
3. Speed control should not be connected to low speed tap on motor
4. Speed control connected to high speed tap on motor.
5. Speed control connected to medium speed tap on motor.
1650/1500/1350
1140 1140 900
1
1725 1725 1200
protected).
because of starting characteristics.
2,3
860 860 500
1650 1500
4
5
1300
950
4
5
Table 1. Speed Controller Size
MOTOR
HP RPM VOLTAGE
1650/1500/
1/8
1350
1/8 860 115V X 1/6 860 115V X 1/4 860 115V X 1/2 860 115V X 1/6 1140 115V X 1/4 1140 115V X 1/2 1140 115V X
1 1140 115V X 1/3 1725 115V X 1/2 1725 115V X 3/4 1725 115V X
115V X
SPEED CONTROLLER
DESIGNATION / FLA
KBWC-15K
5 AMP
KBWC-110
10 AMP
KBWC-115
15 AMP
Figure 2. Low End Setpoint Adjustment
SETPOINT ADJUSTMENT SCREW
NOTE: 5 amp model shown. On 10 and 15 amp models, adjustment is made through clearance hole in heat sink.
4 Aerovent IM-172
Panel Installation (without accessories) — BSBP & BSDDP
WALL OPENING REQUIREMENTS
Wall opening size and the distance between propeller and damper are two important dimensions for fan installation. Fans mounted to the wall require a different wall opening size than those mounted in collars or wall boxes. Propeller­to-damper distance (M) is important to reduce turbulance at the damper which may lead to premature failure, and to prevent the propeller blades from hitting the actuator on motorized damper units. Use general installation procedure from page 4.
To achieve the minimum 'M' dimension, this installation requires a spacer (by others)
SPACER
(BY OTHERS)
between the fan and the wall.
If the wall is equal to or greater than the minimum 'M' dimension, the fan can be mounted directly to the wall.
PROP
SIZE
14 -- 17.00 -- 14.50 -- 17.50 -- 14 x 14
18 -- 22.00 -- 19.50 -- 22.50 -- 19 x 19 21 25.00 25.00 22.50 22.50 25.50 25.50 22 x 22 22 x 22
30 36.00 36.00 33.50 33.50 36.50 36.50 33 x 33 33 x 33 36 42.00 42.00 39.50 39.50 42.50 42.50 39 x 39 39 x 39
48 54.00 54.00 51.50 51.50 54.50 54.50 51 x 51 51 x 51 54 60.00 -- 57.50 -- 60.50 -- 57 x 57 -­60 66.00 -- 63.50 -- 66.50 -- 63 x 63 --
PANEL SQ.
BSBP BSDDP BSBP BSDDP BSBP BSDDP BSBP BSDDP
SURFACE MOUNT RECESS (IN WALL)
WALL OPENING (MIN.)
AIR
FLOW
FAN
MIN
DAMPER SIZE
BACKDRAFT DAMPER
'M'
(MIN.)
16.0016 -- 20.00 -- 17.50 -- 20.50 -- 17 x 17
16.0024 28.00 28.00 25.50 25.50 28.50 28.50 25 x 25 25 x 25
16.0042 48.00 48.00 45.50 45.50 48.50 48.50 45 x 45 45 x 45
19.00
Aerovent IM-172 5
Loading...
+ 11 hidden pages