Aerovent IM-167 User Manual

®
IM-167
August 2014
General Installation, Operation and Maintenance Instructions For Aerovent Products
Aerovent Catalog 340 provides additional information on this equipment. This catalog can be found at www.aerovent. com or by contacting your local Aerovent sales representative.
Centrifugal Square Inline Fans
Models SCBD – 080A through 402A Models SCDD – 080A through 165A
Nomenclature
SCBD - 120 A HP
SCBD = Belt Driven Centrifugal Inline
SCDD = Direct Drive Centrifugal Inline
Size
High Pressure
Design Vintage
Receiving, Inspection, & Unpacking
When the equipment is received all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Before accept­ing delivery, carefully inspect each carton or crate for visible shipping damage. If any damage is noticed, the carrier should make the proper notation on the delivery receipt acknowledging the damage. Make notations of all damage on all copies of the bill of lading and have all copies countersigned by the delivering carrier. The car­rier should also fill out a Carrier Inspection Report. The factory Traffic Department should then be contacted. File claim for damage with the carrier. Physical damage to the unit after acceptance is not the responsibility of Aerovent.
©2014 Aerovent
Unpack each carton or crate and verify that all required parts and proper quantities of each item have been received. Refer to drawings for part descriptions. Report shortages or missing items to your local representative to arrange for replacement parts.
Due to availability of carriers and truck space, it is not possible to guarantee that all items will be shipped together. Verification of shipments must be limited to only those items on the bill of lading.
General Installation
The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and with all applicable codes.
Electrical Connection
This equipment is to be installed by an experienced installation company and fully trained personnel.
The mechanical installation of the inline centrifugal fan consists of making final connections between the unit, building services, and duct connections.
1. Connect supply wiring to the disconnect switch (non-fused standard). Check the wiring diagrams on the motor for connections.
2. The motor is factory set at the voltage marked on the fan nameplate. Check the line voltage with the nameplate voltage and wiring diagrams.
3. The main power wiring should be sized for the ampacity shown on the dataplate. Size wires in accordance with the ampacity tables in Article 310 of the National Electrical Code. If long wires are required, it may be necessary to increase wire size to prevent excessive voltage drop. Wires should be sized for a maximum of 3% voltage drop.
CAUTION: Use copper conductors only.
CAUTION: Protect wiring from sharp edges. Leave
some slack in the line to prevent damage.
4. Disconnect switches are not fused. The power leads must be protected at the point of distribution in accordance with the fan dataplate.
5. On fans without a thermal protector integral to the motor (refer to unit or motor dataplate to determine if protector is present) a separate overload device is required. Refer to Sections 430-32 of the N.E.C. for sizing.
6. All units must be electrically grounded in accordance with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code (ANSI/NFPA 70). A ground lug is provided as standard in the unit terminal box. Size grounding conductor in accordance with Table 250-95 of the National Electrical Code. DO NOT use the ground lug for connecting a neutral conductor.
7. Supply voltage to the inline fan should not vary by more than 10% of the value indicated on the unit dataplate. Phase unbalance must not exceed 2%.
WARNING: Failure of motor due to operation on
improper line voltage or with excessive phase unbal­ance constitutes product abuse and may cause severe damage to the unit’s electrical components.
2 Aerovent IM-167
Check, Test & Start Procedure
W
H
E
E
L
R
O
T
A
T
I
O
N
FAN WHEEL
WARNING
Electric shock hazard. Could cause severe injury or death. Failure to bond the frame of this equipment to the building electrical ground by use of the grounding terminal provided or other acceptable means may result in electrical shock. Disconnect electric power before servicing equipment. Service to be performed only by qualified personnel.
BEFORE START-UP: Disconnect power to this unit before servicing the unit.
1. Check to verify that the wheel is free to rotate.
2. For optimum fan performance make sure that the wheel to inlet venturi overlap is maintainted. See Table 1.
3. Verify that supply voltage on the line side of discon­nect agrees with voltage on fan data plate and is within the 10% utilization voltage.
4. Apply power to unit and check rotation of wheel with the directional arrow on the unit. See Table 2.
WARNING: Rotation is critical. If allowed to operate
in the wrong direction, the motor will overload and burn out.
WARNING: Check units for rotation. For three-phase,
rotation can be changed by interchanging any two of the three line leads. If unit is checked on temporary wiring, it should be rechecked when permanently installed. Motor burn-out or tripped overload protec­tion devices are usually the result of wrong rotation.
5. Electrical Input Check: Perform check of fan ampere draw and verify that motor nameplate amps are not exceeded. Take into account the service factor range if motor is nameplated above a 1.0 service factor.
6. Fan RPM should be checked and verified with a tachometer.
7. Units with Speed Control (Direct Drive): Verify that speed controller gives desired operating range of RPM. If minimum speed value is not desired, it may be adjusted. See page 4.
NOTE: The fan was balanced at the factory to be
within stringent vibration levels before shipment. However, there are several things that may cause vibration, such as rough handling in shipment and installation, weak foundations and alignments.
Table 1. Wheel to Inlet Venturi
MODEL OVERLAP
SCBD SCDD
0.50
0.50
Table 2. Wheel Rotation*
MODEL CW CCW
SCBD SCDD
* Wheel rotation is determined when viewed from discharge. Note: On fans with three phase motors the wheel rotation can be changed by reversing any two power leads.
all ---
--- all
Figure 1. Fan Wheel Rotation - View from Discharge
Note: CW rotation shown, CCW rotation is similar but opposite.
Aerovent IM-167 3
Speed Control Installation
(Model SCDD - optional)
Speed control is available for SCDD models using
115/60/1 open type PSC or shaded pole motors.
Installation
Connect control in series with motor and line voltage (115V only). Never connect across line. See Figure 2.
Minimum Speed Setpoint
All controls are factory set to 65V±3V output as stan­dard with an input voltage of 120V. If different minimum speed is desired, the control may be adjusted by turn­ing minimum speed pot clockwise to decrease minimum speed and counterclockwise to increase minimum speed. Refer to Figure 3.
Warning: If minimum speed is readjusted, verify unit ampere draw does not exceed motor nameplate amps. Do not operate unit in range where amp draw exceeds motor nameplate.
Caution: These motors operate more efficiently in the ranges set from the factory. Operating motor outside these ranges (see Table 3) may cause motor to run hotter and substantially shorten motor life.
Note: Lowering the minimum speed setpoint may adversely affect motor start-up characteristics.
Warning: Certain failure modes of solid-state controls such as half-waving can cause high levels of DC, motor overheating and motor burn-out. Therefore, a thermal overload protection (integral with motor) is required to limit the maximum motor temperature under such a failure.
Note: Do not allow any sleeve bearing motor to operate below 500 RPM. Operation below 500 RPM will sub­stantially shorten bearing life.
Figure 2. Connection Diagram, Speed Control
SPEED CONTROLLER
AC
LINE
(115V)
SWITCH TRI-AC
MOTOR
Table 3. Speed Controller RPM Range
HP RPM MAX. RPM MIN. RPM
1/30
1/8
1/15
1/8 1/6 1/4 1/2 1/8 1/6 1/4 1/2
1/3 1/2 3/4
NOTES:
Speed control available only with 115/60/1 open motors (thermally
protected).
Three-speed motor (multiple tap winding). Speed control should not be connected to low speed tap on motor
because of starting characteristics.
Speed control connected to high speed tap on motor. Speed control connected to medium speed tap on motor.
1650/1500/1350
1140 1140 900
1
1725 1725 1200
2,3
860 860 500
1650 1500
4
5
1300
950
4
5
Figure 3. Low End Setpoint Adjustment
Table 4. Speed Controller Size
MOTOR
PART
NUMBER
66801400 Open 115V 1/30
66543600 Open 115V 1/8
66804500 Open 115V 1/15 860 X 66543700 Open 115V 1/8 860 X 67123100 Open 115V 1/6 860 X 66543800 Open 115V 1/4 860 X 66543900 Open 115V 1/2 860 X 66804600 Open 115V 1/8 1140 X 67125100 Open 115V 1/6 1140 X 66544000 Open 115V 1/4 1140 X 66544100 Open 115V 1/2 1140 X 66544200 Open 115V 1 1140 X 66544300 Open 115V 1/3 1725 X 66544400 Open 115V 1/2 1725 X 67122500 Open 115V 3/4 1725 X
ENCLO-
SURE
VOLT-
AGE
HP RPM
1650/1500/
1350
1650/1500/
1350
SPEED CONTROLLER
DESIGNATION / FLA"
KBWC-15K
5 AMP
X
X
KBWC-110
10 AMP
KBWC-115
15 AMP
NOTE: 5 amp model shown. On 10 and 15
amp models, adjustment is made through clear­ance hole in heat sink.
SETPOINT ADJUSTMENT SCREW
4 Aerovent IM-167
Loading...
+ 8 hidden pages