AERCO Motorized Valves Installation Instructions

AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
TID-0028_0C
TECHNICAL INSTRUCTIONS
Valve Description:
AERCO P/N:
24-240VAC/24-125VDC, Spring Return Open Valve, 3”
92084-1
24-240VAC/24-125VDC, Dual-actuator, Spring Return Open Valve, 4”
92084-2
24V, Power Open/Power Close Valve, Fail-in-Place, 3”
92084-3
24V, Power Open/Power Close Valve, Fail-in-Place, 4”
92084-4
24V, Power Open/Power Close Valve, w/Electronic Fail-Safe, 3”
92084-5
24V, Power Open/Power Close Valve, w/Electronic Fail-Safe, 4”
92084-6
24V, Power Open/Power Close Valve, w/Electronic Fail-Safe, 6”
92084-7
Revised: 08/02/2012
Belimo
Installation
Applies to:
load conditions.
Belimo Motorized Valves
Belimo Motorized Control Valves and AERCO Part Numbers
Motorized Valve
All Benchmark Boilers
All KC1000 Boilers
Description of Document: This TID provides instructions
for installing and wiring Belimo motorized valves as used to isolate an AERCO Benchmark or KC1000 Boiler from the system during low
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Installing Belimo Motorized Valves on AERCO Benchmark Boilers
Technical instruction Document
TID-0028_0C
Technical Support:
1-800-526-0288
www.aerco.com
(Mon–Fri, 8am-5pm EST)
Disclaimer
The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
PR2: 08/02/12 Page 2 of 20
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Installing Belimo Motorized Valves on AERCO Benchmark Boilers
Technical instruction Document
TID-0028_0C
Table of Contents
1. Valve Application ..................................................................................................... 4
2. Valve Installation Location ....................................................................................... 4
3. Valve Orientation ...................................................................................................... 5
4. Valve Wiring .............................................................................................................. 5
5. Identifying BMK Pump Relay Option 69102 ............................................................ 7
6. Sequencing of Motorized Valve Through Building Automation System ............ 18
6.1 Prerequisites for Automation ........................................................................................ 18
6.2 Wiring/Programming for Automation ........................................................................... 18
6.3 Sequence of Automation Functions ............................................................................ 19
Belimo Motorized Control Valve Warranty ................................................................ 20
PR2: 08/02/12 Page 3 of 20
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Installing Belimo Motorized Valves on AERCO Benchmark Boilers
Technical instruction Document
TID-0028_0C

1. Valve Application

These valves are only used to isolate a boiler from the system during low load conditions. A separate service valve MUST be installed for each boiler. See Figure 1 and Figure 2, which show typical installation diagrams – local codes and authorities should be consulted for compliance. The primary purpose of these diagrams is to illustrate the motorized valve location – see specific piping diagram provided with the AERCO boiler for the rest of the piping details.
These valves do NOT qualify as service valves.

2. Valve Installation Location

a. Benchmark Boilers: Do NOT install the Motorized Control Valve directly against the outlet of the
boiler. The actuator will interfere with venting and boiler sheet metal.
b. Provide ample clearance from venting, water piping, gas piping, electrical, controls, and other system
components. The valve should be installed with a reasonable amount of “working space” around it to allow room to be able to service the valve and use the manual lever.
Figure 1: Multiple Boiler Piping Schematic Showing Motorized Valve Locations for
AERCO Benchmark Boilers
PR2: 08/02/12 Page 4 of 20
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Installing Belimo Motorized Valves on AERCO Benchmark Boilers
Technical instruction Document
TID-0028_0C
Figure 2: Multiple Boiler Piping Schematic Showing Motorized Valve Locations for
AERCO KC1000 Boilers

3. Valve Orientation

The valve can be oriented in any position as long as the actuator does not go below the horizontal plane. See orientation guide from Belimo that is attached to the valve.

4. Valve Wiring

See Table 1 on the next page to determine which of the included diagrams to use.
IMPORTANT NOTE!
The valves are supplied with 3 feet of power cable (exception: Valve PN 92084-7 is supplied with Screw Terminal for electrical connection) and 3 feet of auxiliary switch cable. If the cables are not long enough, we recommend that a distribution box be connected. The power and auxiliary cables are permanently connected to the valve and cannot be removed.
PR2: 08/02/12 Page 5 of 20
AERCO International, Inc. 100 Oritani Dr. Blauvelt, New York 10913 Phone: 800-526-0288
Installing Belimo Motorized Valves on AERCO Benchmark Boilers
Technical instruction Document
TID-0028_0C
Boiler Series
Motorized Valve
Controller (BVC)
Wiring
Use
Belimo 24-240VAC/24-
92084-2 (Dual Actuator)
24V, Power open/power
92084-7
120V 4-Boiler BVC
P/N 64095
120V 12-Boiler BVC
P/N 64096
24V 4-Boiler BVC
P/N 64097
24V 12-Boiler BVC
P/N 64098
24V, Power open/power
92084-7
24V 4-Boiler BVC
P/N 64097
Wiring Diagram Selection Guide for AERCO Boiler Valve Controller and AERCO supplied Belimo Valves
How to use the below chart:
1. From the first column, identify the AERCO Boiler Series to which the Belimo valve will be applied. If the Belimo valve is being installed on a BMK boiler that is already in the field, to determine if the boiler is equipped with BMK Pump Relay Option 69102, see Figure 1 on next page.
2. From the second column, identify the AERCO part number of the Belimo valve being used.
3. From the third column, identify which AERCO Boiler Valve Controller is being used in the application.
4. Use the resulting wiring diagram from the last column.
Benchmark Boilers equipped
with BMK Pump Relay Option
69102
Benchmark Boilers NOT
equipped with BMK Pump
Relay Option 69102;
KC1000 Boilers
125VDC, Spring Return
Open Valves. AERCO Part
Numbers
92084-1
close Valves. Part Numbers
92084-3 92084-4 92084-5 92084-6
Belimo 24-240VAC/24-
125VDC, Spring Return
Open Valves. AERCO Part
Numbers
92084-1
92084-2 (Dual Actuator)
close Valves. Part Numbers
92084-3 92084-4 92084-5 92084-6
AERCO Boiler Valve
None SD-A-904
None SD-A-863
None SD-A-905
None SD-A-864
24V 12-Boiler BVC
P/N 64098
Diagram to
SD-A-906
SD-A-907
SD-A-909
SD-A-911
SD-A-908
SD-A-910
PR2: 08/02/12 Page 6 of 20
Loading...
+ 14 hidden pages