Applies to Modulex EXT
Natural Gas Modulating &
Condensing Hot Water
Boilers, including Models:
• EXT 481
• EXT 641
• EXT 802
• EXT 962
• EXT 1123
• EXT 1530
• EXT 1912
• EXT 2295
• EXT 2677
• EXT 3060
GF-136-C
(and BCM)
Installation, Operation and Maintenance
Latest Update: 06/24/2013
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 1 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
Boiler Communications Module (BCM)
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
Technical Support
(Mon-Fri, 8am-5pm EST)
1-800-526-0288
www.aerco.com
Disclaimer
The information contained in this manual is subject to change without notice from AERCO
International, Inc. AERCO makes no warranty of any kind with respect to this material, including
but not limited to implied warranties of merchantability and fitness for a particular application.
AERCO International is not liable for errors appearing in this manual. Nor for incidental or
consequential damages occurring in connection with the furnishing, performance, or use of this
material.
Page 2 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
4.2.1 Setting Maximum and Minimum Flow Temperature ................................................................... 20
4.2.2 Setting Room Temperature and Outdoor Compensation ........................................................... 21
4.2.3 Setting Heating Programs and Pumps ....................................................................................... 22
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS .............................................................. 23
5.1 DISPLAY Menu ................................................................................................................................. 24
5.2 USER Menu ....................................................................................................................................... 28
5.3 TIME PROGRAM Menu and Sun-Menus .......................................................................................... 32
5.4 EXPERT Menu and Sub-Menus ........................................................................................................ 37
5.4.1 Available V-Curve Preset Voltage Curves for 0 – 10 Volt Input ................................................. 45
5.5 EXPERT HS Menu ............................................................................................................................ 46
5.6 GENERAL Menu ............................................................................................................................... 46
5.6.1 DATE / TIME Menu ..................................................................................................................... 46
5.6.2 SERVICE Menu .......................................................................................................................... 49
5.7 Installation Menu & E8 Controller Initial Startup ................................................................................ 53
5.7.1 CAP/MODULE Function (Maximum Kilowatts per Burner) ........................................................ 54
5.7.2 Available Settings for Relay Functions 1 – 4 .............................................................................. 55
CHAPTER 6: E8 SETUP AND PROGRAMMING .................................................................................. 57
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 5 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
(This Page Is Intentionally Blank)
Page 6 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
CAUTION
!
!
Installation, Operation & Maintenance Manual
CHAPTER 1: INTRODUCTION
CHAPTER 1: INTRODUCTION
The information in this manual provides a guide to the operation of the Modulex Boiler using
the E8 Controller and the Boiler Communications Module (BCM) mounted on the front of the
unit.
It is imperative that the initial startup procedures be performed by factory trained personnel.
Operation by untrained personnel, prior to the initial startup, will void the equipment warranty.
In addition, CAUTIONS and WARNINGS in this manual must be observed at all times.
It is of utmost importance to observe all CAUTIONS and WARNINGS presented in this manual to avoid injury, death, and
damage to the equipment. Failure to properly heed safety
warnings and cautions may result in the voiding of applicable
warranties.
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 7 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
E8 Controller and BCM for Modulex EXT Installation, Operation &
Maintenance Manual
CHAPTER 1: INTRODUCTION
(This page intentionally blank)
Page 8 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
Rotary Knob
LCD Display
Hinged Cover
Installation, Operation & Maintenance Manual
CHAPTER 2: E8 CONTROLLER AND BCM DESCRIPTION
CHAPTER 2: E8 CONTROLLER AND BCM DESCRIPTION
Modulex boilers contain advanced and reliable electronic controls, which includes the E8
Controller and the BCM (Boiler Communications Module), providing comprehensive
programming and monitoring of the Modulex boiler and its functions. Features and functions of
the E8 Controller are described in the following sections.
2.1 E8 Controller Features and Functions
A standard component included in Modulex units, the E8 Controller is responsible for the
staging and modulation of individual thermal heating modules in a Modulex boiler and also
monitors supply and return water temperatures and domestic hot water zones.
The E8 Controller is housed in a compact enclosure measuring 5.7” (145 mm) x 3.9” (100 mm).
The Controller is mounted on the front of the Modulex Boiler and contains all of the controls,
indicators and displays necessary to adjust, operate and troubleshoot the Modulex Boiler. The
E8 features the following functions for Modulex boilers:
• Shares the heating load among as many of the boiler's thermal heating modules as
possible, maximizing the overall operating efficiency of the boiler.
• Provides access to all testing/programming parameters of each individual heating module:
operation test, operation time, boiler freeze protection and the pump's anti seize program.
• Drives lead-lag burner operation based on operating hours. The boiler module with the least
burner operating hours is the first to start and the burner with the most operating hours is the
first to stop.
• Supports DHW (Domestic Hot Water) production using a dedicated sensor to control a
dedicated pump or 3-way diverting valve for storage tank temperature control.
• Supports a manual operation service mode to control individual modules during
troubleshooting or combustion calibration procedures.
• Drives diagnostics such as relay and senor testing.
• Supports Modbus integration with AERCO BMS II and AERCO Control System (ACS) or
Building Automation Systems. AERCO also offers a Communication Gateway to support
BACnet, Lonworks and N2 system integration.
Window
(in closed
position)
Figure 2-1: Modulex E8 Controller Front Panel
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 9 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 2: E8 CONTROLLER AND BCM DESCRIPTION
2.2 BCM Features and Functions
The BCM (Boiler Communications Module) is an electronic module in Modulex boilers (one per
burner), which supports full interoperability to BAS (Building Automation Systems) via Modbus
protocol to make remote communications and control possible. In addition, it provides
customers with a remote alarm contact to notify customers of faults detected within any of the
boiler's multiple thermal modules. Finally, in the event the boiler's master controller stops
working, the BCM also takes over operations of the boiler.
As a back-up controller, the BCM further increases the reliability of a product line already known
for its uniquely redundant design. Each Modulex boiler combines between two and seven
independent, pre-assembled thermal modules housed in a common enclosure. Each module
has its own dedicated controller with a combustion safeguard, variable-speed fan, modulating
gas valve, electronic ignition, modulating burner, flow temperature sensor, thermostat and heat
exchanger. The independent operation of these thermal modules increases each boiler's overall
reliability. If a single module requires maintenance or repair, the other module(s) in the boiler
can maintain the system load requirements -- thereby providing a level of redundancy that was
previously only realized in multi-boiler installations.
A photo of the module is shown in Figure 2-2 below. Additional information for the BCM
component can be found in Chapter 7, 9, and 10.
Figure 2-2: BCM (Boiler Control Module)
NOTE
Before operating any menus and functions in the E8, one MUST
perform a one-time entry of items into the initial INSTALLATION
menu. See Section 4.1 for more information about initial setup and
configuration of the E8 Controller.
Page 10 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
display symbols apply to all internal heating
circuits for which a separate heating mode has been selected. Note that each
A B C D E I H
G
F
Installation, Operation & Maintenance Manual
CHAPTER 3: E8 CONTROLLER OPERATION
CHAPTER 3: E8 CONTROLLER OPERATION
The E8 Controller operates in NORMAL Mode when the controller door is closed, which allows
for monitoring the boiler status through the display window and setting the HEATING Mode.
When the door is opened, the unit enters MENU Mode, and in this mode the boiler may be
initialized, configured, and adjusted. The controls and display for the E8 controller are described
in the following sections.
3.1 NORMAL Mode Operation (Door Closed)
When the hinged door is closed on the E8, the unit is in NORMAL Mode.
3.1.1 NORMAL Mode Display Functions
Figure 3-1 describes the types of information provided on the LCD display when in NORMAL
Mode (door closed). Note that the display in the illustration is only an example, and that an E8
Controller in service will show information appropriate for its configuration.
Figure 3-1: E8 Display (NORMAL Mode)
ITEM FUNCTIONS
A
B
C
D
E
Current time (24 hour format)
DCF reception OK (only if receiver is connected via eBUS)
Display of the active heating program for the first heating circuit (here: 6:00 to 08:00
a.m. and 4:00 to 10:00 p.m.)
Bus icon (if this icon does not appear, check data line to connected CAN controllers
=> check eBUS via DISPLAY level)
Status display: Shows symbols for Internal Burner 1 Relay ON; Heating Mode; Hot Water Preparation.
Heating Mode display symbol. The
F
symbol occupies a different space across the display bottom. See Figure 3-2.
G
H
Display of current temperature of HS 1 or header temperature when cascading.
Display of number of active burners (only applies when cascading).
Selectable display and Error Codes ("DISPLAY SEL" parameter in USER menu).
I
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 11 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
E8 Controller and BCM for Modulex EXT
Turn the Rotary Knob to select the heating mode
symbol at
the bottom of the display. It takes effect when the setting
is not changed for 5 seconds.
HEATING Mode
Installation, Operation & Maintenance Manual
CHAPTER 3: E8 CONTROLLER OPERATION
3.1.2 HEATING Mode Selection (in NORMAL Mode)
Heating modes may be selected using the Rotary Knob on the controller when the hinged door
is in the closed position (NORMAL Mode). As the Rotary Knob is turned, each appropriate
heating mode symbol is displayed, in turn, along the lower edge of the display.
Mode changes take effect when the setting is not changed for 5 seconds. The symbols and
description for the available heating modes are shown in Figure 3-2.
Figure 3-2: E8 Display (HEATING Modes)
Symbols:
Only the
currently
selected mode
will be
displayed.
SYMBOL MODE NAME DESCRIPTION
Heating Mode
Selection
Standby / OFF
Automatic
Mode 1
Automatic
Mode 2
Summer
Mode
Day
Mode
required. The heating mode is indicated by a
Heat OFF and hot water (HW) preparation OFF, only
frost protection mode.
Heat according to timer program 1; HW according to HW
program.
Heat according to timer program 2; HW according to HW
program.
Heating OFF, HW according to HW program.
24 Hour heating with comfort temperature 1; HW
according to HW program.
Night
Mode
Service
Mode
24 Hour heating with reduced temperature; HW according
to program.
Automatic reset after 15 minutes. Boiler regulated at
max boiler temperature.
Page 12 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
Insert narrow screwdriver deep into holes and lift up
When lit, this LED indicates that the value shown in the display can be
are switched on. Pumps for Heating Circuit 2 (HC2) and Domestic Hot Water (DHW)
CIRCUIT 1 menu). The first burner stage will cut off when the boiler temperature
d to navigate through menus and parameters or adjust
A
B C D
E
G
F
Installation, Operation & Maintenance Manual
CHAPTER 3: E8 CONTROLLER OPERATION
3.1.3 MENU Mode Operation (Door Open)
Opening the E8 controller hinged door reveals the E8 controls (below) and initiates MENU
Mode, which enables access to an extensive set of software menus.
E8 FRONT PANEL: Controls and Indicators
INSTALLATION
Figure 3-3: E8 Display Controls and Indicators
ITEM FUNCTION
A
B
C
D
E
LCD display: Selected Menu/Sub-menus, parameter names/values, and selected
busses are indicated in the LCD display when in MENU Mode.
Mounting Key Access Holes:
controller to remove.
Change LED:
changed using the Rotary Knob (G).
Optical Adaptor: For PC connection
Program Key: Used to select a sub-menu level, select a parameter value to change, or save a new parameter value.
Manual/Automatic Switch: A 2-position (10/2 o’clock) screwdriver adjustable switch.
Normally, this switch is set to the Automatic (2 o’clock) position to allow program control
of the boiler. When set to the Manual (10 o’clock) position, a flashing “EMERG –
MODE” message is displayed. Heating Circuit 1 (HC1) pump and the first burner stage
F
will also be switched on if sensors are installed and enabled. The pump(s) will turn off
when the flow temperature reaches the value set for MAX T-FLOW (in EXPERT/HEAT
reaches the value set for MAX T-MODUL (in EXPERT/INSTALLATION menu).
G
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 13 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
Rotary Knob: Use
parameters.
E8 Controller and BCM for Modulex EXT
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
CIRCL TIME
HOTW-PROG
HTG-PROG 1
HTG-PROG 2
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
SERVICE
DATE/TIME
HOLIDAY
CLOCK CHANGE
Installation, Operation & Maintenance Manual
CHAPTER 3: E8 CONTROLLER OPERATION
3.2 Software Menus
Software menus are divided into five main menus, each with a set of sub-menus (Table 3-1).
The rotary knob on the front of the E8 Controller is used to sequentially cycle through the
menus and the sub-menus. Two small arrows at the bottom of the display point to the selected
menu and sub-menu name, respectively. Note that some menus and sub-menus are read-only
or not available, according to the boiler used and the initial startup configuration.
NOTE
Before operating any menus and functions in the E8, one MUST
perform a one-time entry of items into the initial INSTALLATION
menu. See Section 4.1, E8 Controller Initial Startup for more
information about initial setup and configuration of the E8
Controller.
Note that whenever the unit is powered down and then powered
up again, the INSTALLATION menu will reappear. When this
occurs, the INSTALLATION menu items DO NOT need to be
reentered. Normally, after entry of the required initial
INSTALLATION menu entries, turning the Rotary Knob clockwise
will automatically advance the Controller to the DISPLAY menu
group. All items in this group are “Read Only” and cannot be
changed.
Table 3-1: Main Menus and Sub-Menus
MAIN MENUS SUB-MENUS
DISPLAY
USER
TIME PROGRAMS
EXPERT
Page 14 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
EXPERT HS
GENERAL
INSTALLATION
Points down to
Points right to
Points left to
Selected Bus(es)
Points down to
Sub-MENU
MENU
Sub-MENU Name
Selected
MENU Name
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 3: E8 CONTROLLER OPERATION
Selected
Buss(es)
Selected
Sub-MENU
Name
Names
Names
Figure 3-4: E8 Display in MENU Mode
3.2.1 Basic Menu/Sub-Menu Navigation and Selection
Selected Menu and Sub-menu are indicated by two black arrows at display bottom pointing to
the Menu and Sub-menu names silk-screened below the display (see Figure 3-4).
Following initial startup and one-time entry of the required INSTALLATION menu items (see
E8 Controller Initial Startup, Section 4.1), to access, view and/or change menu items follow
these instructions:
Menu/Sub-Menu Navigation and Selection
1. When the ON/OFF switch on the front of the boiler is turned ON and the swing-down hinged
panel is opened, the controller will enter MENU Mode and INSTALLATION will be displayed
(Figure 3-4) in the LCD. This is the initial INSTALLATION menu and it is assumed that all
entries have already been made. See Section 4.1 for INSTALLATION menu initial entry
information.
2. Turn the Rotary Knob clockwise until the display advances to the DISPLAY menu. The dial
on the clock face will rotate one revolution counterclockwise and then go off. The display will
then show INSTALLATION, which is the first sub-menu in the DISPLAY menu group (Figure
3-4). The two small black arrows at bottom of the display will point down to the menu and
submenu names, in this case DISPLAY and INSTALLATION, respectively.
3. To view functions included in the INSTALLATION sub-menu, press the Program Key (Item
E, Figure 3-3). If desired, turn the Rotary Knob to scroll through the functions in the
INSTALLATION sub-menu. As previously mentioned, these display functions are read-only
and cannot be changed. Once you reach the end of the sub-menu, RETURN will appear in
the display.
4. To exit this sub-menu and advance to the next sub-menu in the DISPLAY menu, press the
Program Key. INSTALLATION will again be displayed. Turn the Rotary Knob clockwise until
the next sub-menu is displayed.
5. Repeat steps 2, 3 and 4 to view the remaining main menus and their associated sub-menus.
The remaining main menus are: USER, TIME PROGRAM, EXPERT, EXPERT HS, and
GENERAL.
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 15 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
E8 Controller and BCM for Modulex EXT
PARAMETER CHANGE PROCEDURE
Use Rotary Knob to navigate to desired Menu/Sub-
Press Program Key to access parameters in the
selected (displayed) sub-menu.
Turn the Rotary Knob to sequence through the
available parameters.
To change a parameter value, press the Program Key
To change the displayed parameter value, turn the
To save the displayed parameter value to the controller
will turn off indicating the new value has been saved.
-
T-DHW
displayed
sub-menu
displayed
values
displayed
value
Displayed
Example: User Menu & Hot Water Sub-menu
parameters
Cycle thru
cycle thru
push!
push!
push!
Display Detail
DESCRIPTION
EXAMPLES
Displayed
Sub-menu
Installation, Operation & Maintenance Manual
CHAPTER 3: E8 CONTROLLER OPERATION
3.2.2 Basic Parameter Navigation, Selection, and Revision
When in the USER, TIME PROGRAM, EXPERT, or GENERAL Main Menu, virtually all sub-
menu items can be changed if the desired. Perform the following steps to access, view, and/or
change menu item parameters:
menu. Menu and sub-menu are indicated by two small
black arrows at bottom of LCD display pointing down to
menu/sub-menu names below display (see Figure 3-4).
HOT
WATER
HOT-WATER
accessed
when the desired parameter is displayed. The Change
LED will light up indicating the displayed parameter may
now be changed.
Rotary Knob; clockwise to increase value and counterclockwise to decrease the value.
memory, press the Program Key. The Change LED
parameters
T-DHW
parameter
values
142.0
T-DHW
140.0
accessed
141.0
142.0
Value Saved!
Page 16 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 4: E8 INITIALIZATION AND QUICK START GUIDE
CHAPTER 4: E8 INITIALIZATION AND QUICK START GUIDE
4.1 Initializing the E8 in the Installation Menu
When power is first applied to the boiler and then the E8 controller cover is opened, the
INSTALLATION
These values MUST be entered in order to initialize the boiler for operation. Once the
LANGUAGE, TIME
controller is initiated and operatable and may be configured for your boiler installation. To reenter the
To initialize the E8 Controller, follow the instructions below and refer to Figure 4-1 and Table 4-1
on the following pages:
1. Set the POWER rocker switch, located to the left of the Controller, to the ON (I) position.
2. Open the panel cover on the Controller. The LCD display will read INSTALLATION. All
INSTALLATION
values in this level must be entered, in sequence, without interruption.
Menu is displayed once (only). See Figure 4-1 for a diagram of this menu.
and
values grouped here have been entered and accepted, the
DATE
menu, cycle the boiler power and open the cover again.
Initial Startup INSTALLATION Entry
3. The first function that appears is LANGUAGE. By default, the display should show
ENGLISH. If ENGLISH is not displayed, turn the Rotary Knob until ENGLISH appears.
4. Press the Program Key to store this setting.
5. Next, TIME will be displayed. Enter the current time (minutes, hours) using the Rotary
Knob. Press the Program Key to store each value.
6. The next items displayed are the YEAR, MONTH and DAY. Enter each item using the
Rotary Knob and press the Program Key as previously described to store the entry.
7. Following entry of all LANGUAGE, TIME and DATE entries, continue entering the
remaining items shown in Figure 4-1 and Table 4-1 until all required items have been
entered. Use the Program Key and Rotary Knob to select, adjust and store all entries as
previously described.
NOTE
Leave the BUS – ID HS parameter blank. Remaining parameters
are already set and do not require any entry.
8. Continue step 7 until RETURN appears in the display, indicating that you are at the end
of the INSTALLATION menu.
9. Press the Program Key to exit the INSTALLATION menu.
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 17 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 4: E8 INITIALIZATION AND QUICK START GUIDE
WARNING
Menu selections shown
are the factory default
settings.
Figure 4-1: INSTALLATION Menu
Page 18 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
ENTRY
RANGE
LANGUAGE
Set Language
ENGLISH
TIME
Set current time (min., hrs)
00:00 – 24:00
digits)
MONTH
Set current month
00-12
DAY
Set current day of month
00-31
CONF DEVICE
Confirm Device
- - - -, 01 – 06
- - - -
HEATSOURCE 1
Heat Source 1
00 – 06
06
HS1 BUS
Heat Source 1 Bus
00 – 04
02
HEATSOURCE 2
Heat Source 2
00 – 05
00
STORAGE HS2
Storage Heat Source 2
00 – 03
00
BUFFER
Buffer
00, 01, 02
00
HC FUNCTION 1
Heating Circuit Function 1
00, 01, 03
00
HC FUNCTION 2
Heating Circuit Function 2
00 – 04
00
CAP/MODULE
See Section 5.7.1 for instructions.
00 – 1000 Kw
40 Kw
RELAY FUNC 1
Relay Function 1 (See Section 5.7.2)
00 – 26
00
T-MF1 SETP
Temperature – Multifunction Relay 1 Setpoint
86°F – 194°F
86°F
MF1 HYST
Multifunction Relay 1 Hysteresis
4°F – 18°F
9°F
RELAY FUNC 2
Relay Function 2 (See Section 5.7.2)
00 – 26
00
T-MF2 SETP
Temperature – Multifunction Relay 2 Setpoint
86°F – 194°F
86°F
MF2 HYST
Multifunction Relay 2 Hysteresis
4°Ra – 18°Ra
9°F
RELAY FUNC 3
Relay Function 3
00 – 26
01
T-MF3 SETP
Temperature – Multifunction Relay 3 Setpoint
86°F – 194°F
86°F
MF3 HYST
Multifunction Relay 3 Hysteresis
4°F – 18°F
9°F
RELAY FUNC 4
Relay Function 4
00 – 26
02
T-MF4 SETP
Temperature – Multifunction Relay 4 Setpoint
86°F – 194°F
86°F
MF4 HYST
Multifunction Relay 4 Hysteresis
4°F – 18°F
9°F
BUS ID 1
Bus Identification No. 1
00 – 15
01
BUS ID 2
Bus Identification 2
00 – 15
02
01=1K
Installation, Operation & Maintenance Manual
CHAPTER 4: E8 INITIALIZATION AND QUICK START GUIDE
Table 4-1: INSTALLATION Menu Listing
PARAMETERS DESCRIPTION
INSTALLATION Sub-Menu
YEAR
Set current year
XXXX (4
DEFAULT
5K SENSOR 5,000 Ohm Sensor
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 19 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
00=5K,
00 = 5 K
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 4: E8 INITIALIZATION AND QUICK START GUIDE
4.2 QUICK START INSTRUCTIONS
Below are instructions for setting the most basic settings in the E8 controller, including
maximum and minimum flow temperature, room temperature settings, heat slope, and initiation
of heating programs.
IMPORTANT NOTE!
Before the boiler may be used, the E8 controller MUST be first
intitialized by entering language, year, month, day, and hour in the
Installation Menu as described in Section 4.1.
4.2.1 Setting Maximum and Minimum Flow Temperature
Figure 4-2: E8 Quick Start, Max. & Min. Flow Temperature Settings
Page 20 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 4: E8 INITIALIZATION AND QUICK START GUIDE
4.2.2 Setting Room Temperature and Outdoor Compensation
Figure 4-3: E8 Quick Start, Room Temperature and Outdoor Compensation
Settings with Outdoor Temperature (Slope) Chart
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 21 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 4: E8 INITIALIZATION AND QUICK START GUIDE
4.2.3 Setting Heating Programs and Pumps
Figure 4-4: E8 Quick Start, Heating and Pump Program Settings
Page 22 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
CIRCL TIME
HOTW-PROG
HTG-PROG 1
HTG-PROG 2
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
SERVICE
DATE/TIME
HOLIDAY
CLOCK CHANGE
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
This chapter provides flow-chart illustrations and tabular listings of all Menu and Sub-Menu
functions. Overall menu hierarchy is shown below:
MAIN MENUS SUB-MENUS
DISPLAY
USER
TIME PROGRAMS
EXPERT
EXPERT HS
INSTALLATION
GENERAL
IMPORTANT!
In the following flow-chart illustrations and tabular listings, descriptions, entry
ranges, and default values are provided for only the commonly used functions
which are referenced in Chapter 6, titled E8 Set-Up & Programming. These
commonly used functions are shown in Bold Italics in the illustrations and
tables which follow.
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 23 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
DISPLAY
INSTALLATION
T-OUTSIDE
T-EXT DES
T-COLL DES
T-COLLECTOR
T-BOIL
T-SOLID FUEL
T-RETURN 1
T-RETURN 2
T-BUFFER T
T-BUFFER M
T-BUFFER L
T-STORAGE 3
MODGRAD
RETURN
HOT WATER
T-DHW RATED
T-DHW
T-DHW L
RETURN
HTG CIRCUIT 2
T-ROOM DES A
T-ROOM
HUMIDITY
T-FLOW RATED
T-FLOW
N-OPT-TIME
RETURN
SOLAR M/F
T-MF1
T-MF2
T-MF3
T-MF4
T-COLLECTOR
T-DHW
T-DHW L
RETURN
HTG CIRCUIT 1
T-ROOM DES A
T-ROOM
HUMIDITY
T-FLOW RATED
T-FLOW
N-OPT-TIME
RETURN
DISPLAY
E8 Controller and BCM for Modulex EXT
DISPLAY
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
5.1 DISPLAY Menu
The DISPLAY Menu contains the INSTALLATION, HOT WATER, HEATING (HTG) CIRCUIT
1 & 2 and a SOLAR M/F Sub-Menu as shown in Figures 5-1 & 5.2, and in Table 5-1.
Figure 5-1: DISPLAY Menu Flow Chart
Page 24 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
DISPLAY
DISPLAY
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
Figure 5-2: DISPLAY Menu
NOTE
Some menus are visible only if the relevant sensor is wired (e.g.
HOT WATER is displayed only if the DHW storage sensor is
wired).
NOTE
All DISPLAY Menu and Sub-Menu functions are READ ONLY and
cannot be changed. Temperature readings shown are in °F.
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 25 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
E8 Controller and BCM for Modulex EXT
A 0 to 10 volt external input
Reset and Constant Set Point modes.
T-COLLECTOR
sequence between Heat Modules.
T-RETURN 1
Not Applicable
T-BUFFER T
Not Applicable
T-BUFFER L
Not Applicable
Knob to sequence between Heat Modules.
Sub-Menu.
Based on heating prog and
USER/HOT WATER menu.
T-DHW L
Not Applicable
WATER Sub-Menu.
DISPLAY
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
FUNCTION DESCRIPTION REMARKS
INSTALLATION Sub-Menu
DISPLAY
Table 5-1: DISPLAY Menu Listing46
T-EXT DES
T-COLL DES
T-BOIL
T-SOLID FUEL Not Applicable
T-RETURN 2 Not Applicable
T-BUFFER M Not Applicable
T-STORAGE 3 Not Applicable
MODGRAD
Boiler Set Point setting in 0 to 10 volt input
mode
Boiler Set Point temperature in Indoor/ Outdoor
Header Set Point temperature (cascade)
Press Program Key to display temperature
and ON/OFF status of individual Heat
Modules (HS) which range from 2 (EXT
321) to 8 (EXT 3060). Turn Rotary Knob to
Press Prog Key to display Modulation % for
individual Heat Modules (HS). Turn Rotary
signal can be used to change the
Boiler set point.
The Burner symbol ( )
is displayed when the
respective Heat Module is
ON.
RETURN
Press Program Key to exit INSTALLATION
HOT WATER Sub-Menu
T-DHW RATED
T-DHW Actual hot water temperature
T-CIRCL Not Applicable
RETURN
DHW set point temperature
Press Program Key to exit the HOT
Page 26 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
operating mode. Actual
DHW set point as set in
Only if tank sensor is
installed
E8 Controller and BCM for Modulex EXT
T-ROOM DES A
Not Applicable
heating circuit.
as hot water circuit
T-DHW
Current hot water temperature
T-FLOW RATED
FLOW
Current flow temperature
N-OPT-TIME
Not Applicable
CIRCUIT 1 Sub-Menu.
T-MF1
Not Applicable
T-MF2
Not Applicable
T-MF3
Not Applicable
Currently not used
T-MF4
Not Applicable
1
T-DHW
Not Applicable
M/F Sub-Menu.
DISPLAY
DISPLAY
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
Table 5-1: DISPLAY Menu Listing (Continued)
FUNCTION DESCRIPTION REMARKS
HTG CIRCUIT 1 Sub-Menu
T-ROOM Current room air temperature.
HUMIDITY Room humidity (%).
T-DHW RATED Hot water set point temperature
Current flow set point temperature
RETURN
HTG CIRCUIT 2 Sub-Menu
Functions for HTG (Heating) Circuit 2 are identical to HTG Circuit 1 Functions
above.
SOLAR M/F Sub-Menu
Press Program Key to exit HTG
Only if indoor sensor is
connected
Only if humidity sensor
is installed and
parameters set for
Appears only if heating
circuit is programmed
Same as above
Not applicable
T-COLLECTOR
T-DHW L Not Applicable
RETURN
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 27 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
Not Applicable
Press Program Key to exit SOLAR
Currently not used
Currently not used
Currently not used
Currently not used
Currently not used
Currently not used
USER
INSTALLATION
LANGUAGE
CONTRAST
DISPLAY SEL
RETURN
HOT WATER
1X DHW
T-DHW 1
T-DHW 2
T-DHW 3
BOB VALUE
CIRCL-P-DHW
ANTILEGION
RETURN
SOLAR M/F
RETURN
HTG CIRCUIT 1
MODE
T-ROOM DES 1
T-ROOM DES 2
T-ROOM DES 3
T-REDUCED
T-ABSENCE
T-LIMIT DAY
T-LIMIT N
HEATSLOPE
OPTIM HEAT
MAX OPT-TIME
ECONO OPTI
PC ENABLE
RETURN
HTG CIRCUIT 1
MODE
T-ROOM DES 1
T-ROOM DES 2
T-ROOM DES 3
T-REDUCED
T-ABSENCE
T-LIMIT DAY
T-LIMIT N
HEATSLOPE
OPTIM HEAT
MAX OPT-TIME
ECONO OPTI
PC ENABLE
RETURN
USER
USER
E8 Controller and BCM for Modulex EXT
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
5.2 USER Menu
The USER Menu (Figures 5-3 & 5-4) contains the same Sub-Menus as the DISPLAY Menu.
However, the USER Menu items are not “Read Only” and therefore can be changed. The SubMenu functions in the USER Menu also differ from those contained in the DISPLAY Menu.
Tabular listings for the USER Menu items are provided in Table 5-2.
Figure 5-3: USER Menu Flow Chart
Page 28 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
E8 Controller and BCM for Modulex EXT
USER
USER
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
Figure 5-4: USER Menu Diagram
OMM-0093_0A AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 29 of 108
GF-136-C Ph.: 800-526-0288 PRI: 06/24/2013
E8 Controller and BCM for Modulex EXT
CONTRAST
Domestic Hot Water
connected).
Sub-Menu.
1X DHW
Not Applicable
T-DHW 1
Hot Water set point
50°F - 158°F
140°F
T-DHW 2
Not Applicable
T-DHW 3
Not Applicable
BOB-VALUE
Not Applicable
DHW
Menu.
USER
USER
Installation, Operation & Maintenance Manual
CHAPTER 5: E8 CONTROLLER MENUS AND SUB-MENUS
Table 5-2: USER Menu Listing
FUNCTION DESCRIPTION ENTRY RANGE DEFAULT
INSTALLATION Sub-Menu
LANGUAGE Selects display language.
Adjusts display contrast
Sets the day of the week or the sensor
temperature (°F) to appear in the display when
the swing-down panel is closed.
Day: SUN – SAT
T-OUTSIDE: Outside Temperature
FLOW TEMP (1/2): Flow Temp. For Heating
Circuit 1 or 2 supply
DISPLAY
SEL
water temperature. (Only
if sensor is installed)
T-DHW:
Temperature.
T-BOILER; Boiler Outlet Temperature.
T-ROOM (1 / 2): Room Temp, Heating
Circuit 1 or 2 (ONLY if
Remote Control is
12 languages are
available.
-20 to 20
See
DESCRIPTION
Column
ENGLISH
00
- - - -
RETURN
HOT WATER Sub-Menu
CIRCL-P-
RETURN
Page 30 of 108 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0093_0A
PRI: 06/24/2013 Phone: 800-526-0288 GF-136-C
Press Program Key to exit INSTALLATION
Not Applicable
Press Program Key exit HOT WATER Sub-
Loading...
+ 78 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.