AERCO Modulex E8 Controls Guide

GF-115-C
OMM-0084_0D
USER MANUAL
Other manuals for this product include:
Gas Fired Boiler Systems
Modulex E8 Controller
MLX-303
E8 Controller for MLX Series Boilers
Boiler Communications Module (BCM)
for MLX Series Boilers
Installation, Operation, and Maintenance
Modulating, Condensing, Hot Water Boiler Models:
MLX-454
MLX-606
MLX-757
MLX-909
MLX-1060
And BC Module (BCM)
.
GF-115-H MLX Series Boiler Manual
GF-115-G MLX Gas Design Guide
GF-115-P-H MLX Piping Guide
GF-115-V MLX Venting Guide
GF-115-E MLX Electrical Power Guide
Revised: 11/30/2012
PR1: 11/30/12 Page 1 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
Technical Support:
1-800-526-0288
www.aerco.com
(Mon–Fri, 8am-5pm EST)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Disclaimer
The information contained in this manual is subject to change without notice from AERCO International, Inc. AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
PR1: 11/30/12 Page 2 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
OMM-0084_0D

Table of Contents

Table of Contents .......................................................................................... 3
1. INTRODUCTION ..................................................................................... 7
1.1 Safety and Warnings ........................................................................................ 7
2. E8 CONTROLLER AND BCM DESCRIPTION .......................................... 9
2.1 E8 Controller Features And Functions ........................................................... 9
2.2 BCM Features And Functions ....................................................................... 10
3. E8 CONTROLLER OPERATION ............................................................ 11
3.1 NORMAL Mode Operation (Door Closed)..................................................... 11
3.1.1 NORMAL Mode Display Functions ................................................................... 11
3.1.2 HEATING Mode Selection (in NORMAL Mode) ............................................. 12
3.1.3 MENU Mode Operation (Door Open) ................................................................ 13
3.2 Software Menus .............................................................................................. 14
3.2.1 Basic Menu/Sub-Menu Navigation and Selection .............................................. 15
3.2.2 Basic Parameter Navigation, Selection, and Revision ........................................ 16
4. E8 CONTROLLER MENUS AND SUB-MENUS ...................................... 17
4.1 DISPLAY Menu ............................................................................................... 18
4.2 USER Menu ..................................................................................................... 21
4.3 TIME PROGRAM Menu and Sun-Menus ....................................................... 24
4.4 EXPERT Menu and Sub-Menus ..................................................................... 25
4.4.1 Available V-Curve Preset Voltage Curves for 0 – 10 Volt Input ....................... 31
4.5 EXPERT HS Menu (Not Used) ...................................................................... 32
4.6 GENERAL Menu ............................................................................................. 32
4.6.1 DATE / TIME Menu ........................................................................................... 32
4.6.2 SERVICE Menu .................................................................................................. 34
4.7 E8 Controller Initial Startup ........................................................................... 37
4.7.1 CAP/MODULE Function (Maximum Kilowatts per Burner) ............................ 39
4.7.1 Available Settings for Relay Functions 1 – 4 ...................................................... 40
5. E8 OPERATING MODE: Set-up and Programming .................................. 41
5.1 Indoor/Outdoor Reset Mode .......................................................................... 41
5.1.1 Wiring Connections............................................................................................. 41
5.1.2 Indoor/Outdoor Reset Operation Configuration ................................................. 41
5.1.3 Viewing the Boiler Setpoint ................................................................................ 43
5.2 Constant Set Point Mode ............................................................................... 43
5.2.1 Wiring Connections............................................................................................. 44
5.2.2 Constant Setpoint Mode Configuration............................................................... 44
5.2.3 Viewing Constant Set Point ................................................................................ 44
PR1: 11/30/12 Page 3 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
5.2.4 Configuring Set Point High and Low Limits Per Outside Temperature Sensor . 44
5.3 0 to 10 Volt Remote Set Point Mode ............................................................. 47
5.3.1 Remote Signal Source Wiring Connections ........................................................ 47
5.3.2 Configuring Remote Signal Source..................................................................... 48
5.3.3 Setting the Voltage and Set Point Limits for U1/U2 and T1/T2 ......................... 49
5.3.4 Setting the Curve 11-UO Voltage ....................................................................... 50
5.3.5 Viewing the Set Point .......................................................................................... 51
5.4 Domestic Hot Water Operation Using A Tank Sensor ................................ 51
5.4.1 Sensor Wiring Connections ................................................................................. 51
5.4.2 Configuring the Controller for DHW With a Tank Sensor ................................. 52
5.4.3 Setting the DHW Set Point ................................................................................. 53
5.4.4 Displaying Temperatures Associated With DHW .............................................. 54
5.5 DHW Operation Using an Aquastat .............................................................. 55
5.5.1 Sensor Wiring Connections ................................................................................. 55
5.5.2 Configuring the Controller for DHW With an Aquastat ..................................... 55
5.5.3 Setting the DHW Set Point ................................................................................. 55
5.5.4 Displaying Temperatures Associated With DHW .............................................. 55
5.6 Boiler & Pump Enable/Disable ...................................................................... 55
6. CONNECTION DIAGRAMS .................................................................... 57
6.1 Power Terminal Assignments ....................................................................... 58
6.2 Sensor Terminal Assignments ...................................................................... 59
7. BOILER COMMUNICATIONS MODULE (BCM) ..................................... 61
7.1 Boiler Communications Module (BCM) Description ................................... 61
7.2 BCM Fault Relay ............................................................................................. 63
7.2.1 BCM Fault Relay Wiring .................................................................................... 63
7.2.2 Clearing Faults .................................................................................................... 63
7.3 BCM Configured as Back-Up Controller ...................................................... 64
7.3.1 BCM Back-Up Controller Wiring ....................................................................... 64
7.4 BCM Configured as Primary Controller Utilizing Modbus .......................... 65
7.4.1 Operating Scenario .............................................................................................. 65
7.4.2 Physical Modbus RS485 Wiring ......................................................................... 66
7.4.3 Disconnecting the E8 from the E-Bus on the BCM Board. ................................ 67
7.4.4 AERCO BMS II/ACS Master to BCM Slave Wiring Connections. ................... 68
7.4.5 EMS or BAS Master to BCM Slave Wiring Connections .................................. 68
7.5 RS485 Loop Termination Resistors and Bias .............................................. 68
7.5.1 Master AERCO BMS II/ACS or EMS/BAS Terminating Resistor and Bias ..... 68
7.5.2 BCM Controller Terminating Resistor and Bias ................................................. 69
7.6 Modbus Network Wiring Diagram ................................................................. 70
7.7 Modbus Software Set-Up ............................................................................... 73
7.7.1 BCM Set-Up for Modbus Operation ................................................................... 73
PR1: 11/30/12 Page 4 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
7.7.2 Monitoring and Configuration Only ................................................................... 74
7.7.3 AERCO BMS II/ACS Modbus Control and Monitoring .................................... 74
7.7.4 Modbus Remote Setpoint Control and Monitoring ............................................. 74
7.7.5 EMS or BAS Set-Up As Master to BCM Controller Slaves ............................... 74
7.8 Multiple Modulex Boiler Heating Mode – Utilizing a BMS II or ACS ........... 74
7.8.1 Sequence of Operation (Example: Four-Modulex boiler installation) ................ 75
8. E8 CONTROLLER MENU LISTINGS ..................................................... 77
8.1 DISPLAY Menu ............................................................................................... 77
8.2 USER Menu ..................................................................................................... 79
8.3 TIME PROGRAM Menu .................................................................................. 81
8.4 EXPERT Menu ................................................................................................ 84
8.5 GENERAL Menu ............................................................................................. 89
8.5.1 DATE / TIME Sub-Menu ................................................................................... 89
8.5.2 SERVICE Sub-Menu .......................................................................................... 90
9. BCM MODBUS AND ADDRESS ASSIGNMENTS ................................... 93
9.1 BCM Modbus Communication & Support Requirements ........................... 93
9.1.1 Function Codes .................................................................................................... 93
9.1.2 Modbus Support Requirements ........................................................................... 93
9.2 BCM Controller Standard Holding Register Assignments ......................... 94
9.2.1 BCM Controller Standard Input Register Assignments ...................................... 94
9.2.2 BCM Controller Standard Holding Register Assignments ................................. 94
10. E8, BCM, AND BMM FAULT CODES ................................................. 101
10.1 Processing and Clearing Fault Codes ........................................................ 102
10.2 Fault Codes and Descriptions ..................................................................... 103
10.2.1 E8 Controller Fault Codes ............................................................................. 104
10.2.2 BCM (Boiler Communications Module) Fault Codes ................................... 106
10.2.3 BMM (Burner Management Module) Fault Codes ....................................... 108
PR1: 11/30/12 Page 5 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
(This page left intentionally blank)
PR1: 11/30/12 Page 6 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
OMM-0084_0D
WARNING
!
!
CAUTION
!
!
DANGER
!
!
DANGER
!
!

1. INTRODUCTION

The information in this manual provides a guide to the operation of the Modulex Boiler using the E8 Controller and the Boiler Communications Module (BCM) mounted on the front of the unit. Sections 3, 4, 5, 6, and 8 provide descriptions and procedures for the E8 Controller. Sections 7, 9, and 10 provide similar information for the BCM.
It is imperative that the initial startup procedures be performed by factory trained personnel. Operation by untrained personnel, prior to the initial startup, will void the equipment warranty. In addition, CAUTIONS and WARNINGS in this manual must be observed at all times.

1.1 Safety and Warnings

The following defined symbols are used throughout this manual to notify the reader of potential hazards of varying risk levels.
Indicates an imminently hazardous situation, which if not avoided, WILL result in death or serious injury.
Indicates a potentially hazardous situation, which if not avoided, MAY result in death or serious injury.
Indicates a potential hazardous situation, which if not avoided, COULD result in minor or moderate injury. Also may caution against unsafe practices.
Note that all hazard notifications and notes are presented enclosed in a rectangle with filleted (round) corners, as shown below, in order to differentiate them from the main text.
It is of utmost importance to observe all CAUTIONS and WARNINGS presented in this manual to avoid injury, death, and damage to the equipment. Failure to properly heed safety warnings and cautions may result in the voiding of applicable warranties.
PR1: 11/30/12 Page 7 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
(This page left intentionally blank)
PR1: 11/30/12 Page 8 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
OMM-0084_0D
Rotary Knob
LCD Display
Hinged Cover

2. E8 CONTROLLER AND BCM DESCRIPTION

Modulex boilers contain advanced and reliable electronic controls, which includes the E8 Controller and the BCM (Boiler Communications Module), providing comprehensive programming and monitoring of the Modulex boiler and its functions. Features and functions of the E8 Controller are described in the following sections.

2.1 E8 Controller Features And Functions

A standard component included in Modulex units, the E8 Controller is responsible for the staging and modulation of individual thermal heating modules in a Modulex boiler and also monitors supply and return water temperatures and domestic hot water zones.
The E8 Controller is housed in a compact enclosure measuring 5.7” (145 mm) x 3.9” (100 mm). The Controller is mounted on the front of the Modulex Boiler and contains all of the controls, indicators and displays necessary to adjust, operate and troubleshoot the Modulex Boiler. The E8 features the following functions for Modulex boilers:
Shares the heating load among as many of the boiler's thermal heating modules as possible. maximizing the overall operating efficiency of the boiler.
Provides access to all testing/programming parameters of each individual heating module: operation test, operation time, boiler freeze protection and pump's anti seize program.
Drives lead-lag burner operation based on operating hours. The boiler module with the least burner operating hours is the first to start and the burner with the most operating hours is the first to stop.
Supports DHW (Domestic Hot Water) production using a dedicated sensor to control a dedicated pump or 3-way diverting valve for storage tank temperature control.
Supports a manual operation service mode to control individual modules during troubleshooting or combustion calibration procedures.
Drives diagnostics such as relay and senor testing.
Supports Modbus integration with AERCO BMS II and AERCO Control System (ACS) or
Building Automation Systems. AERCO also offers a Communication Gateway to support BACnet, Lonworks and N2 system integration.
Window
(in closed
position)
Figure 2-1: Modulex E8 Controller Front Panel
PR1: 02/23/12 Page 9 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D

2.2 BCM Features And Functions

The BCM (Boiler Communications Module) is an electronic module in Modulex boilers (one per burner), which supports full interoperability to BAS (Building Automation Systems) via Modbus protocol to make remote communications and control possible. In addition, it provides customers with a remote alarm contact to notify customers of faults detected within any of boiler's multiple thermal modules. Finally, in the event the boiler's master controller stops working, the BCM also takes over operations of the boiler.
As a back-up controller, the BCM further increases the reliability of a product line already known for its uniquely redundant design. Each Modulex boiler combines between two and seven independent, 151,500 BTU/hr., pre-assembled thermal modules housed in a common enclosure. Each module has its own dedicated controller with a combustion safeguard, variable­speed fan, modulating gas valve, electronic ignition, modulating burner, flow temperature sensor, thermostat and heat exchanger. The independent operation of these thermal modules increases each boiler's overall reliability. If a single module requires maintenance or repair, the other module(s) in the boiler can maintain the system load requirements -- thereby providing a level of redundancy that was previously only realized in multi-boiler installations.
A photo of the module is shown in Figure 2-2 below. Additional information for the BCM component can be found in Section 7, 9, and 10.
Figure 2-2: Modulex BCM (Boiler Communications Module)
PR1: 11/30/12 Page 10 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
OMM-0084_0D
Heating Mode display symbol. The display symbols apply to all internal heating circuits for which a separate heating mode has been selected. Note that each
H B E
D
I G F C A

3. E8 CONTROLLER OPERATION

The E8 Controller operates in NORMAL Mode when the controller door is closed, which allows for monitoring the boiler status through the display window and setting the HEATING Mode. When the door is opened, the unit enters MENU Mode, and in this mode the boiler may be initialized, configured, and adjusted. The controls and display for the E8 controller are described in the following sub-sections.

3.1 NORMAL Mode Operation (Door Closed)

When the hinged door is closed on the E8, the unit is in NORMAL Mode.

3.1.1 NORMAL Mode Display Functions

Figure 3-1 describes the types of information provided on the LCD display when in NORMAL
Mode (door closed). Note that the display in the illustration is only an example, and that an E8 Controller in service will show information appropriate for its configuration.
Figure 3-1: E8 LCD Display in NORMAL Mode (Door Closed)
E8 Controller Display in NORMAL Mode
Item Functions
A
Current time (24 hour format)
B
DCF reception OK (only if receiver is connected via eBUS)
Display of the active heating program for the first heating circuit (here: 6:00 to 08:00
C
a.m. and 4:00 to 10:00 p.m.)
Bus icon (if this icon does not appear, check data line to connected CAN controllers
D
=> check eBUS via DISPLAY level)
E
Status display: Shows symbols for Internal Burner 1 Relay ON; Heating Mode; Hot Water Preparation.
F
symbol occupies a different space across the display bottom. See Figure 3-2.
G
Display of current temperature of HS 1 or header temperature when cascading.
H
Display of number of active heat generators (only applies when cascading).
Selectable display and Error Codes (refer to "DISPLAY SEL" parameter in the USER
I
menu).
PR1: 02/23/12 Page 11 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
SYMBOL
MODE NAME
DESCRIPTION
Turn the Rotary Knob to select the heating mode
heating mode is indicated by a symbol at the bottom of the display. It takes effect when the setting is not changed for 5 seconds.
HEATING Mode Symbols:

3.1.2 HEATING Mode Selection (in NORMAL Mode)

Heating modes may be selected using the Rotary Knob on the controller when the hinged door is in the closed position (NORMAL Mode). As the Rotary Knob is turned, each appropriate heating mode symbol is displayed, in turn, along the lower edge of the display.
Mode changes take effect when the setting is not changed for 5 seconds. The symbols and description for the available heating modes are shown in Figure 3-2.
Only currently selected mode will be displayed.
Figure 3-2: Heating Mode Display Symbols and Description
E8 Controller HEATING Modes
Heating Mode
Selection
Standby / OFF
Automatic Mode 1
Automatic Mode 2
Summer Mode
Day
Mode
Night Mode
required. The
(Heat OFF and hot water (HW) preparation OFF, only frost protection mode)
(Heat according to timer program 1; HW according to HW program)
(Heat according to timer program 2; HW according to HW program)
(Heating OFF, HW according to HW program)
(24 Hour heating with comfort temperature 1; HW according to HW program)
(24 Hour heating with reduced temperature; HW according to program)
Service Mode
PR1: 11/30/12 Page 12 of 112
(Automatic reset after 15 minutes. Boiler regulated at max boiler temperature)
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
Insert narrow screwdriver deep into holes and lift up
When lit, this LED indicates that the value shown in the display can be
D
position (10/2 o’clock) screwdriver adjustable switch.
FLOW (in EXPERT/HEAT
F
E
D
C B A
G

3.1.3 MENU Mode Operation (Door Open)

Opening the E8 controller hinged door reveals the E8 controls (Figure 3-3) and initiates the MENU Mode, which enables access to an extensive set of software menus.
INSTALLATION
Figure 3-3: E8 Controller Controls (cover open in MENU Mode)
E8 Controller Controls and Indicators
ITEM FUNCTION
A
B
C
E
F
LCD display: Selected Menu/Sub-menus, parameter names/values, and selected
busses are indicated in the LCD display when in MENU Mode.
Mounting Key Access Holes: controller to remove.
Change LED: changed using the Rotary Knob (A).
Optical Adaptor: For PC connection
Program Key: Used to select a sub-menu level, select a parameter value to change, or save a new parameter value.
Manual/Automatic Switch: A 2-
Normally, this switch is set to the Automatic (2 o’clock) position to allow program control of the boiler. When set to the Manual (10 o’clock) position, a flashing “EMERG – MODE” message is displayed. Heating Circuit 1 (HC1) pump and the first burner stage are switched on. Pumps for Heating Circuit 2 (HC2) and Domestic Hot Water (DHW) will also be switched on if sensors are installed and enabled. The pump(s) will turn off when the flow temperature reaches the value set for MAX T­CIRCUIT 1 menu). The first burner stage will cut off when the boiler temperature reaches the value set for MAX T-MODUL (in EXPERT/INSTALLATION menu).
G Rotary Knob: Used to navigate through menus and parameters or adjust parameters.
PR1: 11/30/12 Page 13 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
CIRCL TIME
HOTW-PROG
HTG-PROG 1
HTG-PROG 2
INSTALLATION
HOT WATER
HEAT CIRCUIT I
HEAT CIRCUIT II
SOLAR/MF
SERVICE
DATE/TIME
HOLIDAY
CLOCK CHANGE

3.2 Software Menus

Software menus are divided into five main menus, each with a set of sub-menus (Table 3-1). The rotary knob on the front of the E8 Controller is used to sequentially cycle through the menus and the sub-menus. Two small arrows at the bottom of the display point to the selected menu and sub-menu name, respectively. Note that some menus and sub-menus are read-only or not available, according to the boiler used and the initial startup configuration.
NOTE
The menu processing steps presented in this manual assume that all required (one-time) INSTALLATION menu items have already been entered at setup. It should be noted that whenever the unit is powered down and then powered up again, the INSTALLATION menu will reappear. When this occurs, the INSTALLATION menu items DO NOT need to be reentered. Normally, after entry of the required initial INSTALLATION menu entries, turning the Rotary Knob clockwise will automatically advance the Controller to the DISPLAY menu group. All items in this group are “Read Only” and cannot be changed.
See Sub-section 4.7, E8 Controller Initial Startup for more information about initial setup and configuration of the E8 Controller.
Table 3-1: Main Menus and Sub-Menus
MAIN MENUS SUB-MENUS
DISPLAY
USER
TIME
PROGRAMS
EXPERT
EXPERT HS
INSTALLATION
GENERAL
PR1: 11/30/12 Page 14 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
Points down to Points right to
Points left to
Points down to
Sub-MENU
MENU
Sub-MENU Name
Selected Buss(es)
Selected Bus(es)
Selected
Selected
MENU Name
Names
Sub-MENU Name
Names
Figure 3-4: E8 Display in MENU Mode (after first opening hinged door)

3.2.1 Basic Menu/Sub-Menu Navigation and Selection

Selected Menu and Sub-menu are indicated by two black arrows at display bottom pointing to the Menu and Sub-menu names silk-screened below the display (see Figure 3-4).
Following initial startup and one-time entry of the required INSTALLATION menu items (see E8 Controller Initial Startup, sub-section 4.7), to access, view and/or change menu items follow these instructions:
Menu/Sub-Menu Navigation and Selection
1. When the ON/OFF switch on the front of the boiler is turned ON and the swing-down hinged panel is opened, the controller will enter MENU Mode and INSTALLATION will be displayed (Figure 3-4) in the LCD. This is the initial INSTALLATION menu and it is assumed that all entries have already been made. See sub-section 4.8 for INSTALLATION menu initial entry information.
2. Turn the Rotary Knob clockwise until the display advances to the DISPLAY menu. The dial on the clock face will rotate one revolution counterclockwise and then go off. The display will then show INSTALLATION, which is the first sub-menu in the DISPLAY menu group (Figure 3-4). The two small black arrows at bottom of the display will point down to the menu and submenu names, in this case DISPLAY and INSTALLATION, respectively.
3. To view functions included in the INSTALLATION sub-menu, press the Program Key (Item E, Figure 3-3). If desired, turn the Rotary Knob to scroll through the functions in the INSTALLATION sub-menu. As previously mentioned, these display functions are read-only and cannot be changed. Once you reach the end of the sub-menu, RETURN will appear in the display.
4. To exit this sub-menu and advance to the next sub-menu in the DISPLAY menu, press the Program Key. INSTALLATION will again be displayed. Turn the Rotary Knob clockwise until the next sub-menu is displayed.
5. Repeat steps 2, 3 and 4 to view the remaining main menus and their associated sub-menus. The remaining main menus are: USER, TIME PROGRAM, EXPERT, EXPERT HS (Not Applicable to Modulex), and GENERAL.
PR1: 11/30/12 Page 15 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
Parameter Change Procedure
Use Rotary Knob to navigate to desired Menu/Sub-
Press Program Key to access parameters in the selected (displayed) sub-menu.
Turn Rotary Knob to sequence through the available parameters.
To change a parameter value, press the Program Key To change the displayed parameter value, turn Rotary
To save the displayed parameter value to the controller
will turn off indicating the new value has been saved.
-
-
T-DHW
displayed
sub-menu
displayed
values
accessed
displayed
value
Displayed
Example: User Menu & Hot Water Sub-menu
parameters
accessed
Cycle thru
cycle thru
push!
push!
push!
Display Detail
Description
Examples
Displayed
Sub-menu

3.2.2 Basic Parameter Navigation, Selection, and Revision

When in the USER, TIME PROGRAM, EXPERT, or GENERAL Main Menu, virtually all sub- menu items can be changed if the desired. Perform the following steps to access, view, and/or change menu item parameters:
menu. Menu and sub-menu are indicated by two small black arrows at bottom of LCD display pointing down to menu/sub-menu names below display (see Figure 3-
HOT
WATER
HOT-WATER
when desired parameter is displayed. The Change LED will light up indicating the displayed parameter may now be changed.
Knob; clockwise to increase value and counter­clockwise to decrease the value.
memory, press the Program Key. The Change LED
parameters
T-DHW
parameter
values
142.0
DHW
T
140.0
141.0
142.0
Value Saved!
PR1: 11/30/12 Page 16 of 112
GF-115-C
OMM-0084_0D

4. E8 CONTROLLER MENUS AND SUB-MENUS

This section provides flow-chart illustrations and tabular listings of all Menu and Sub-Menu functions. Overall menu hierarchy is shown below:
1. DISPLAY
a. INSTALLATION b. HOT WATER c. HEAT CIRCUIT I d. HEAT CIRCUIT II e. SOLAR/MF
2. USER
a. INSTALLATION b. HOT WATER c. HEAT CIRCUIT I d. HEAT CIRCUIT II
e. SOLAR/MF
3. TIME PROGRAMS
a. CIRCL TIME b. HOTW-PROG c. HTG-PROG 1 d. HTG-PROG 2
4. EXPERT
a. INSTALLATION b. HOT WATER c. HEAT CIRCUIT I d. HEAT CIRCUIT II e. SOLAR/MF
5. EXPERT HS
a. INSTALLATION
6. GENERAL
a. SERVICE b. DATE/TIME c. HOLIDAY d. CLOCK CHANGE
IMPORTANT!
In the following flow-chart illustrations and tabular listings, descriptions, entry ranges, and default values are provided for only the commonly used functions which are referenced in Section 5, titled E8 Operating Mode: Set-Up & Programming. These commonly used functions are shown in Bold Italics in the illustrations and tables which follow. Refer to Section 8 for additional information on functions marked “Not Applicable” in the illustrations and tables provided.
PR1: 02/23/12 Page 17 of 112
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
DISPLAY
INSTALLATION
T-OUTSIDE T-EXT DES T-COLL DES T-COLLECTOR T-BOIL T-SOLID FUEL T-RETURN 1 T-RETURN 2 T-BUFFER T T-BUFFER M T-BUFFER L T-STORAGE 3 MODGRAD RETURN
HOT WATER
T-DHW RATED T-DHW T-DHW L
RETURN
HTG CIRCUIT 2
T-ROOM DES A T-ROOM HUMIDITY T-FLOW RATED T-FLOW N-OPT-TIME RETURN
SOLAR M/F
T-MF1 T-MF2 T-MF3 T-MF4 T-COLLECTOR T-DHW T-DHW L RETURN
HTG CIRCUIT 1
T-ROOM DES A T-ROOM HUMIDITY T-FLOW RATED T-FLOW N-OPT-TIME RETURN

4.1 DISPLAY Menu

The DISPLAY Menu contains an INSTALLATION, HOT WATER, HEATING (HTG) CIRCUIT 1 & 2 and a SOLAR M/F Sub-Menu as shown in Figure 4-1 and in Table 4-1.
Figure 4-1: DISPLAY Menu Flow Chart
PR1: 11/30/12 Page 18 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
Boiler Set Point temperature in Indoor/ Outdoor
T-COLLECTOR
sequence between Heat Modules.
Knob to sequence between Heat Modules.
Sub-Menu.
Based on heating prog and
USER/HOT WATER menu.
T-DHW L
Not Applicable
T-CIRCL
Not Applicable
WATER Sub-Menu.
All DISPLAY Menu & Sub-Menu functions are READ ONLY and cannot be changed. Temperature readings shown are in °F.
FUNCTION DESCRIPTION REMARKS
INSTALLATION Sub-Menu
NOTE
Table 4-1: DISPLAY Menu Listing
T-OUTSIDE Outside air temperature
T-EXT DES
T-COLL DES
T-BOIL
T-SOLID FUEL Not Applicable
T-RETURN 1 Not Applicable
T-RETURN 2 Not Applicable
T-BUFFER T Not Applicable
T-BUFFER M Not Applicable
T-BUFFER L Not Applicable
T-STORAGE 3 Not Applicable
MODGRAD
Boiler Set Point setting in 0 to 10 volt input mode
Reset and Constant Set Point modes.
Header Set Point temperature (cascade)
Press Program Key to display temperature and ON/OFF status of individual Heat Modules (HS) which range from 2 (MLX-
303) to 7 (MLX-1060). Turn Rotary Knob to
Press Prog Key to display Modulation % for individual Heat Modules (HS). Turn Rotary
Displayed only if outside air sensor is installed.
A 0 to 10 volt external input signal can be used to change the Boiler set point.
The Burner symbol ( ) is displayed when the respective Heat Module is ON.
RETURN
Press Program Key to exit INSTALLATION
HOT WATER Sub-Menu
T-DHW RATED
T-DHW Actual hot water temperature
RETURN
PR1: 11/30/12 Page 19 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
DHW set point temperature
Press Program Key to exit the HOT
operating mode. Actual DHW set point as set in
Only if tank sensor is installed
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
FUNCTION
DESCRIPTION
REMARKS
T-DHW
T-FLOW RATED
FLOW
N-OPT-TIME
Not Applicable
CIRCUIT 1 Sub-Menu.
T-MF3
Not Applicable
T-MF4
Not Applicable
1
T-DHW
Not Applicable
T-DHW L
Not Applicable
M/F Sub-Menu.
Table 4-1: DISPLAY Menu Listing (Continued)
HTG CIRCUIT 1 Sub-Menu
T-ROOM DES A Not Applicable
T-ROOM Current room air temperature.
HUMIDITY Room humidity (%).
T-DHW RATED Hot water set point temperature
Current hot water temperature
Current flow set point temperature
Current flow temperature
RETURN
HTG CIRCUIT 2 Sub-Menu
Functions for HTG (Heating) Circuit 2 are identical to HTG Circuit 1 Functions above.
Press Program Key to exit HTG
Only if indoor sensor is
connected
Only if humidity sensor
is installed and
parameters set for
heating circuit.
Appears only if heating
circuit is programmed
as hot water circuit
Same as above
Not applicable
SOLAR M/F Sub-Menu
T-MF1
T-MF2
T-COLLECTOR
RETURN
PR1: 11/30/12 Page 20 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
Not Applicable
Not Applicable
Not Applicable
Press Program Key to exit SOLAR
Currently not used
Currently not used
Currently not used
Currently not used
Currently not used
Currently not used
Currently not used
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
USER
INSTALLATION
LANGUAGE CONTRAST DISPLAY SEL RETURN
HOT WATER
1X DHW
T-DHW 1
T-DHW 2 T-DHW 3 BOB VALUE CIRCL-P-DHW ANTILEGION
RETURN
SOLAR M/F
RETURN
HTG CIRCUIT 1
MODE
T-ROOM DES 1 T-ROOM DES 2 T-ROOM DES 3 T-REDUCED T-ABSENCE
T-LIMIT DAY T-LIMIT N HEATSLOPE
OPTIM HEAT MAX OPT-TIME ECONO OPTI PC ENABLE
RETURN
HTG CIRCUIT 1
MODE
T-ROOM DES 1 T-ROOM DES 2 T-ROOM DES 3 T-REDUCED T-ABSENCE
T-LIMIT DAY T-LIMIT N HEATSLOPE
OPTIM HEAT MAX OPT-TIME ECONO OPTI PC ENABLE
RETURN

4.2 USER Menu

The USER Menu (Figure 4-2) contains the same Sub-Menus as the DISPLAY Menu. However, the USER Menu items are not “Read Only” and therefore can be changed. The Sub­Menu functions in the USER Menu also differ from those contained in the DISPLAY Menu. Tabular listings for the USER Menu items are provided in Table 4-2.
Figure 4-2: USER Menu Flow Chart
PR1: 11/30/12 Page 21 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
CONTRAST
00
Domestic Hot Water
connected).
Menu.
T-DHW 1
Hot Water set point
50°F - 158°F
140°F
T-DHW 2
Not Applicable
T-DHW 3
Not Applicable
DHW
Menu.
Table 4-2: USER Menu Listing
FUNCTION DESCRIPTION ENTRY RANGE DEFAULT
INSTALLATION Sub-Menu
LANGUAGE Selects display language.
Adjusts display contrast
Sets the day of the week or the sensor temperature (°F) to appear in the display when the swing-down panel is closed.
Day: SUN – SAT
T-OUTSIDE: Outside Temperature
FLOW TEMP (1/2): Flow Temp. For Heating
Circuit 1 or 2 supply
DISPLAY SEL
water temperature. (Only if sensor is installed)
T-DHW: Temperature.
T-BOILER; Boiler Outlet Temperature.
T-ROOM (1 / 2): Room Temp, Heating
Circuit 1 or 2 (ONLY if Remote Control is
12 languages are
available.
-20 to 20
ENGLISH
See
DESCRIPTION
Column
- - - -
RETURN
HOT WATER Sub-Menu
1X DHW Not Applicable
BOB-VALUE Not Applicable
CIRCL-P-
RETURN
PR1: 11/30/12 Page 22 of 112
Press Program Key to exit INSTALLATION Sub-
Not Applicable
Press Program Key exit HOT WATER Sub-
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
Night
T-ROOM DES 1
Not Applicable
T-ROOM DES 2
Not Applicable
T-REDUCED
Not Applicable
T-ABSENCE
Not Applicable
-23.0°F–104.0°F
periods.
-23.0°F–104.0°F
1°F.
OPTIM HEAT
Not Applicable
ECONO OPTI
Not Applicable
PC-ENABLE
Not Applicable
CIRCUIT 1 (or 2) sub-menu.
display to the TIME PROGRAM Menu.
Table 4-2: USER Menu Listing (Continued)
FUNCTION DESCRIPTION ENTRY RANGE DEFAULT
HTG CIRCUIT 1 Sub-Menu
- - - -, Standby,
MODE Displays Timer Mode for Boiler
Auto 1, Auto 2, Day,
- - - -
T-ROOM DES 3
T-LIMIT DAY Applies during day-time heating periods
T-LIMIT N
HEATSLOPE
MAX OPT-TIME
RETURN
HTG CIRCUIT 2 Sub-Menu
Functions for HTG Circuit 2 are identical to HTG Circuit 1 Functions listed above.
Not Applicable
Applies during reduced night-time
Indicate number of degrees that the flow temperature changes if the outside temperature increases or decreases by
Not Applicable
Press Program Key to exit HTG
- - - -,
- - - -,
0.00 – 3.00 1.20
66.0°F
50.0°F
SOLAR M / F Sub-Menu (No Functions Currently In This Sub-Menu)
Pressing the Program Key with SOLAR M/F displayed will change display to
RETURN
PR1: 11/30/12 Page 23 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
RETURN. Press Program Key again to redisplay SOLAR M/F. Turning the Rotary Knob clockwise will advance thd
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
TIME PROGRAM
CIRCL TIME
MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY SUNDAY MO-FR SA-SU MO-SU RETURN
HOTW-PROG
MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY SUNDAY MO-FR SA-SU MO-SU RETURN
HTG-PROG 1
MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY SUNDAY MO-FR SA-SU MO-SU RETURN
HTG-PROG 2
MONDAY TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY SUNDAY MO-FR SA-SU MO-SU RETURN

4.3 TIME PROGRAM Menu and Sun-Menus

Day and Time-related functions can be set using the TIME PROGRAM Menu and its associated Sub-Menus. However, at the present time, none of the Sub-Menus and functions in the TIME PROGRAM Menu are being utilized. This menu is shown in Figure 4-3.
Refer to Section 8 for additional information on these Menu and Sub-Menu functions.
Figure 4-3: TIME PROGRAM Menu Flow Chart
PR1: 11/30/12 Page 24 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
EXPERT
INSTALLATION
CODE-NO BUS ID HS BUS ID 1 BUS ID 2 AF SUPPLY BUS TERM EBUS SUPPLY TIME MASTER MAX T COLL MIN T COLL MAX T-HS2 MIN T-HS2 V-CURVE CURVE 11-U1 CURVE 11-U2 CURVE 11-T1 CURVE 11-T2 CURVE 11-UA HYSTERESIS FOUND MODULS CAP/MODULE NEW CONFIG MIN MOD CASC HW-BOILER CONTR DEVIAT DES OUTPUT BLOCK TIME MAX T-MODUL DYN UPWARD DYN DOWNWARD RESET TIME MODULAT MAX MODULAT MIN MIN MOD HS SEQUENCE 1 SEQUENCE 2 SEQU CHANGE SEQ SW TIME LOCK TIME HYST BURNER 2 HS COOL FUNC T-HS COOL HEATSOURCE 1 HS1 BUS HEATSOURCE 2 STORAGE HS 2 BUFFER RETURN
CONTINUED ON SHEET 2

4.4 EXPERT Menu and Sub-Menus

The EXPERT Menu contains the following Sub-Menus: INSTALLATION, HOT WATER, HEAT CIRCUIT 1, HEAT CIRCUIT 2 and SOLAR M/F as shown in Figure 4-4. As this figure shows, the EXPERT Menu includes an extensive list of Sub-Menu functions, particularly in the INSTALLATION Sub-Menu. Tabular listings for the EXPERT Menu and Sub-Menu items are provided in Table 4-3.
Whenever “CODE NO.” is displayed, it indicates that the valid password must be entered. This is accomplished by entering code 0000 (four zeros) by pressing the Program Key four (4) times.
PR1: 11/30/12 Page 25 of 112
Figure 4-4: EXPERT Menu Flow Chart (Sheet 1 of 2)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
EXPERT
HTG CIRCUIT 1
HC FUNCTION PUMP MODE
MIXER OPEN MIXER CLOSE
MAX T-FLOW MIN T-FLOW T-FROST PROT
OUT-TEMP-DEL SLOPE OFFSET B-HEAT SINK
RETURN
HOT-WATER
DHW RELIEF
PARALLEL T-BOILER DHW
HYST DHW DHW FOLLOWUP
THERM INPUT
WALL HUNG LOAD THROUGH
RETURN
HTG CIRCUIT 2
HC FUNCTION PUMP MODE MAX T-FLOW MIN T-FLOW T-FROST PROT
OUT-TEMP-DEL B-HEAT SINK RETURN
SOLAR M/F
RELAY FUNC 1 T-MF 1 SETP MF1 HYST RELAY FUNC 2 T-MF 2 SETP MF2 HYST RELAY FUNC 3 T-MF 3 SETP MF3 HYST RELAY FUNC 4 T-MF 4 SETP MF4 HYST
F15 FUNCTION RETURN
CONTINUED FROM SHEET 1
Figure 4-4: EXPERT Menu Flow Chart (Sheet 2 of 2)
PR1: 11/30/12 Page 26 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
INSTALLATION Sub-Menu
CODE-NO
Permits entry of valid Code No.(0000)
0000 - 9999
0000
the boiler
CHANGE
numbers must not be assigned twice.
be assigned twice.
AF SUPPLY
Outdoor sensor power supply
00, 01 (OFF/ON)
01 (ON)
BUS TERM
Bus terminating resistor (Must be set to 01)
00, 01 (OFF/ON)
01 (ON)
SUPPLY
MASTER
point temperature.
temperature.
0 to 10 Volt input Voltage curves. Choose
customize a curve.
CURVE 11-U1
Low voltage setting
0.00V – 10.00V
0.000
CURVE 11-U2
High voltage setting
0.00V – 10.00V
10.00
CURVE 11-T1
Minimum set point temperature
32.0°F – 248.0°F
59.0°F
CURVE 11-T2
Maximum set point temperature
32.0°F – 248.0°F
185.0°F
this setting will stop/start the Boiler.
NOTE
Whenever “CODE NO.” is displayed, it indicates that the valid password must be entered. This is accomplished by entering code
0000 (four zeros) by pressing the Program Key four (4) times.
Table 4-3: EXPERT Menu Listing
FUNCTION DESCRIPTION ENTRY RANGE DEFAULT
BUS ID HS
BUS ID 1
BUS ID 2
EBUS
TIME
MAX T-COLL
MIN T-COLL
MAX T-HS2
MIN T-HS2
BUS ID HS MUST be set to - - - - to operate
The heating circuits are sequentially numbered starting with „01“, heating circuit
Heating circuits are sequentially numbered starting with “01“, heating circuit numbers must not
Switches the Ebus supply ON/OFF 00, 01 (OFF/ON) 01 (ON)
Not Applicable
Sets the maximum allowable header set
Sets the minimum allowable header set point
Not Applicable
Not Applicable
01 - 08
(00), 01 – 15 01
(00), 01 – 15 - - - -
86.0°F – 230.0°F 185.0°F
50.0°F – 176.0°F 50.0°F
DO NOT
V-CURVE
CURVE 11-UO
from preset curves (see para. 3.5.1) or
Stop/Start voltage level. Going below/above
PR1: 11/30/12 Page 27 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
00 – 11 11
0.00V – 10.00V 1.00
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
(Continued)
HYSTERESIS
Not Applicable
MODULS
for service.
module.
NEW CONFIG
Not Applicable
CASC
HW-BOILER
Not Applicable
00 – 08
00
actual water temperature.
DES OUPUT
Required system output [in %]
0 – 100%
00
SWITCH TIME
Not Applicable
(N/A)––
(N/A)
BLOCK TIME
Not Applicable
(N/A)
(N/A)
MODUL
UPWARD
DOWNWARD
RESET TIME
Not Applicable
5 – 500
50
after the delay time elapses.
off
MIN MOD HS
Not Applicable
0% - 60%
35%
HW
SEQUENCE 1
SEQUENCE 2
Boiler sequence 2
87654321
Table 4-3: EXPERT Menu Listing (Continued)
FUNCTION DESCRIPTION ENTRY RANGE DEFAULT
INSTALLATION Sub-Menu
FOUND
CAP/MODULE
MIN MOD
CONTR DEVIAT
MAX T-
DYN
DYN
Displays the number of heat modules available
Displays the maximum Kw output of each heat
Not Applicable 01 – 08 01
Control Deviation indicates the temperature difference between the Boiler set point and the
Maximum temperature of Heat Module 122.0°F to 230.0°F 194.0°F
Not Applicable (N/A) (N/A)
Not Applicable (N/A) (N/A)
Display
00 – 1000 Kw 40 Kw
Display °F
MODULAT MAX
MODULAT MIN
MOD LEVEL
PR1: 11/30/12 Page 28 of 112
Start Level. If this modulation percentage is exceeded, the next heat module is connected
Stop Level. If value drops below this modulation percentage, the last heat generator (module) of the current sequence is switched
Not Applicable
Boiler sequence 1 12345678
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
50% - 100% 30%
10% - 60% 35%
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
ENTRY
RANGE
SEQU CHANGE
Sequence change mode
01 – 06
06
SEQ SW TIME
Time to sequence change (hours)
10 – 800
200
LOCK TIME
Not Applicable
00 min – 30 min
00
HYST BURNER2
Not Applicable
T-HS COOL
Not Applicable
Identification of Boiler Type being used:
06 = Multi-Stage, modulating (cascade via BUS)
Heat Source
HEATSOURCE 2
Not Applicable
N/A–
N/A
STORAGE HS2
Not Applicable
N/A–
N/A
BUFFER
Not Applicable
N/A
N/A
SCREED
Not Applicable
N/A
N/A
SCREED PROGR
Not Applicable
N/A
N/A
RETURN
Press Program Key to exit INSTALLATION Sub-Menu.
HOT WATER Sub-Menu
DHW RELIEF
Not Applicable
N/A
N/A
02 = Pump Parallel Running
DHW)
HYST DHW
Hot Water Hysteresis
48°F – 129°F
48°F
min.
Storage Tank With Thermostat = 01
WALL HUNG
Not Applicable
LOAD THROUGH
Not Applicable
RETURN
Press Program Key to exit HOT WATER Sub-Menu.
Table 4-3: EXPERT Menu Listing (Continued)
FUNCTION DESCRIPTION
DEFAULT
INSTALLATION Sub-Menu (Continued)
HS COOL-FCT Not Applicable
00 = No Boiler
HEATSOURCE 1
HS 1 BUS
01 = Single-Stage, switching 02 = Single-Stage, modulating 03 = 2-Stage, switching 04 = 2 individual, switching 05 = Multi-Stage, switching
Communication connection between Controller and
See
DESCRIPTION
00 – 04 02
06
(Multi-Stage
Modulating)
Parallel pump operation.
PARALLEL
T-BOILER DHW
DHW FOLLOWUP Pump Run-Down Time
THERM INPUT
PR1: 11/30/12 Page 29 of 112
00 = Hot Water Priority 01 = Hot Water Partial Priority
Boiler temperature increase during Hot Water operation.
Boiler Temp = (DHW Temp Setting) + (T-BOILER
Storage Tank With Sensor = 00
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
00, 01, 02
32°F – 194°F 97°F
00 min. – 30
00, 01
01
00 min.
00
GF-115-C
Modulex E8 Controller and BCM
Operations and Maintenance Manual
OMM-0084_0D
ENTRY
RANGE
mixing valve.
Circulation pump mode control for
03 = Continuous pump operation
MIXER CLOSE
Maximum allowable water temperature setting for the heating circuit.
Minimum allowable water temperature setting for the heat circuit.
Specifies the minimum allowable outside
INSTALLATION Mode)
DEL
OFFSET
B-HEAT SINK
Not Applicable
N/A
N/A
Press Program Key to exit HEAT CIRCUIT 1 (or 2) Sub-Menu.
Table 4-3: EXPERT Menu Listing (Continued)
FUNCTION DESCRIPTION
HEAT CIRCUIT 1 & 2 Sub-Menus
The Sub-Menu Functions for HEAT CIRCUIT 1 & HEAT CIRCUIT 2 are identical, except for the MIXER OPEN & MIXER CLOSE Functions which apply only to HEAT CIRCUIT 1. The Function values in this Sub-Menu level will change, depending on the Heat Circuit Function (HC FUNCTION) selected.
Heat Circuit Function defines type of circuit:
00 = Standard Heat Circuit 01 = Control to fixed flow temperature
HC FUNCTION
PUMP MODE
02 = Swimming pool control (HC 2 ONLY) 03 = Hot Water Circuit 04 = Return flow temp. Increase via
ON/OFF switching of pumps. 00 = Standard pump control 01 = Pump switching per heating limits 02 = Pump switching per heating program
00 – 04
00 – 03 00
DEFAULT
00
(Standard
Heat
Circuit)
MIXER OPEN
MAX T-FLOW
MIN T-FLOW
T-FROST PROT
OUT-TEMP-
SLOPE
RETURN
Not Applicable
Not Applicable
air temperature setting for the Frost Protection Mode. If temperature drops below this value, the system switches to the Frost Protect Mode and the pumps are switched ON. (This Function should be set to 0°F in the
Not Applicable N/A N/A
Not Applicable N/A N/A
68°F – 230°F 176°F
50°F – 230°F 50°F
-5°F – 41°F 32°F
PR1: 11/30/12 Page 30 of 112
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288
Loading...
+ 82 hidden pages