AERCO INTERNATIONAL, Inc., Northvale, New Jersey 07647 USA
AC-106
®
MODBUS
Communication Manual
for
ELECTRONIC CONTROL SYSTEM
(ECS)
Used to Interface AERCO Equipment
to Building Automation Systems
Modbus® is a registered trademark of AEG Modicon
REVISED 7/28/10
Page 2
THIS PAGE INTENTIONALLY BLANK
ii
Page 3
ELECTRONIC CONTROL SYSTEM COMMUNICATION INTERFACE
TABLE OF CONTENTS
Title Page
1. INTRODUCTION 1
2. COMMUNICATION BOARD 1
3. MODBUS COMMUNICATION SIGNAL CONNECTIONS 1
4. MODBUS COMMUNICATION INFORMATION 2
5 CHANGING COMMUNICATION ADDRESSES ON THE AERCO EUROTHERM
TEMPERATURE CONTROLLER 4
6. REFERENCED DOCUMENTS 6
7. INTERFACING THE ECS WITH A BUILDING’S BAS/EMS 6
8. ALARMS 7
9. CLEARING HARDWARE ERROR (HW.ER) DISPLAY 8
LIST OF FIGURES
1. Temperature Controller (Eurotherm 2408) Terminal Connection Diagram 2
LIST OF TABLES
1 MODBUS Communication Signal Connections 2
2. Eurotherm Series 2400 Controller MODBUS Points 3
3 AERCO Electronic Control System (ECS) Point Definitions 6
4. Process Alarms 7
5. Diagnostic Alarms 7
iii
Page 4
THIS PAGE INTENTIONALLY BLANK
iv
Page 5
AC-106 INSTRUCTIONS - ECS COMMUNICATIONS
ELECTRONIC CONTROL SYSTEM COMMUNICATION INTERFACE
1. INTRODUCTION
The Electronic Control System (ECS), used on AERCO indirect fired water heaters, can be ordered with a
MODBUS® Communication Option, which will permit it to be controlled by an external Energy
Management System (EMS), Building Automation System (BAS), or a computer supplied by others.
2. COMMUNICATION BOARD
The Communication Board provides the MODBUS interface between any of the possible external control
systems and the ECS. The Temperature Controller (Eurotherm 2408) used in the ECS can be optionally
equipped with a Communication Board which can be connected to external control systems utilizing either
an RS232 or RS485 MODBUS communication interface. The corresponding part numbers for the
alternative MODBUS Communication Boards are as follows:
PART NUMBER DESCRIPTION
64009-1 RS232 COMMUNICATION BOARD
64009-2 RS485 COMMUNICATION BOARD
3. MODBUS COMMUNICATION SIGNAL CONNECTIONS
CAUTION
DO NOT route MODBUS communication wiring in the same conduit as power wiring.
Attempting to do so may result in excessive noise on the signal lines. Also, ensure that
the RS232 or RS485 signal cable connections do not exceed the following lengths:
CABLE TYPE
RS232 50 feet
RS485 4,000 feet
To implement ECS MODBUS control, connect the cable leads from the external controller to the
Temperature Controller as instructed in Table 1.
• Refer to the Temperature Controller (Eurotherm 2408) pinouts shown in Figure 1 to locate the
required terminals.
• Refer to Table 2 Eurotherm Series 2400 Controller MODBUS Points for a listing of active
MODBUS data addresses for the 2408 Controller.
• The Eurotherm documents referenced on page 3 provide additional communication information
related to MODBUS.
MAXIMUM LENGTH
NOTE
AERCO recommends that shielded, twisted-pair cable be used for communication wiring.
Examples of suitable wiring are: Belden 9841, 8761, 3105A, or equivalent.
1
Page 6
Table 1. MODBUS Communication Signal Connections
2408 TEMPERATURE
CONTROLLER
SIGNAL
PIN NO.
NAME
RS232/9-PIN RS232/25-PIN RS485
SIGNAL
NAME
COMPUTER CONTROL CABLE
PIN NO. PIN NO. PIN NO.
GROUND HD GROUND 5 7 GROUND
RECEIVE HE TRANSMIT 3 2 A-
TRANSMIT HF RECEIVE 2 3 B+
2408 CONTROLLER
1A
1B
1C
1D
2A
2B
2C
2D
3A
3B
3C
3D
HA
HB
HC
HD
HE
HF
JA
JB
JC
JD
JE
JF
L
N
LA
LB
LC
AA
AB
AC
VI
V+
V-
In1
In2
C
Figure 1. Temperature Controller (Eurotherm 2408) Terminal Connection Diagram
4. MODBUS COMMUNICATION INFORMATION
The Eurotherm 2400 Controller supports the MODBUS RTU mode of transmission. The default settings
are as follows:
• 9600 baud rate
• One start bit
• Eight data bits
• One stop bit
• No parity
2
Page 7
MODBUS
Address
Data
Table 2. Eurotherm Series 2400 Controller MODBUS Points
Menu
Item
Menu Item
Description
Units &
Range
Default/Comments
Register
Type
Ref. 1
Comm.
Guide
5 w.SP Setpoint 40-205°F 140°F, Address to
read value
24 SP 1 Setpoint 40-205°F 140°F, Address to
change value
1 Top
Value
133 LoGH Peak Temp 40-205°F Resets on Power
135 LoGA Average
134 LoGL Low Temp 40-205°F Resets on Power
13 (set)
74 (status,
0 = safe
1 = alarm)
14 (set)
74 (status,
0 = safe
AL 1 Over Temp
AL 2
(FSH)
Outlet Temp 40-205°F Same value as front
display
Loss
40-205°F Resets on Power
Temp
Alarm
Full Scale
High Alarm
40-205°F 20°F above
205°F 205 ° F
Loss
Loss
setpoint; Alarm
Type 17: Deviation
High
Alarm Type 2: Full
Scale High
Read
Only
Write 5-11
Read
Only
Read
Only
Read
Only
Read
Only
Read
Only
Read
Only
5-4
5-3
5-15
5-15
5-15
5-7
5-20
5-7
5-20
1= alarm)
258 Sbr Feedback
Sensor Break
289 Li 1 Feedback
Sensor Temp
290 Li 2 Flow GPM Read
3 OP Control
Output Signal
26 RmSet
pt
Remote
Setpoint
Status:
0: Good
1: Failed
40-180°F Sensor input to
% Correlates to valve
(40 to 180)
°F
Denotes Feedback
Sensor
Failure/Open Circuit
controller, same as
display temp.
position
Holding
Read
Only
Read
Only
Only
Read
Only
3
5-18
5-14
5-14
5-4
Page 8
5. CHANGING COMMUNICATION ADDRESSES ON THE AERCO
EUROTHERM TEMPERATURE CONTROLLER
To change the modbus address:
The address is defaulted to 1 from
the factory. Refer to the Button map
below for all panel navigation
instructions.
1. Page to the ACCS list and
Scroll down the list to codE.
2. Enter 24 using the Up Arrow.
The number will display and flash
PASS.
3. Scroll to Goto (current value is OPEr) and use the
Down Arrow to enter a value of Full
confirmed by the flashing of the lower display
momentarily off and then on.
Button Map
Page
4. Go to the home screen by pressing the Page
and Scroll buttons at the same time.
Scroll
Down
Arrow
. The entry is
Up
Arrow
4
Page 9
5. Page to the cmS list
6. Scroll to the Addr screen
7. Use the Up Arrow to select
the desired address number.
8. Go to the home screen by
pressing the Page and Scroll buttons at the same
time.
9. Page to the ACCS List and
change the code to anything
other than 24 and the codE
number you entered will
flash off and then on to 0 to
confirm that access is now
set to the OPEr level and is
safe to return to use.
10.Confirm that the Addr is set
properly by pressing Page button
until the cmS list is displayed and
Scroll to Addr. If the value is
correct you are done, if not
please repeat the steps again.
5
Page 10
6. REFERENCE DOCUMENTS
1. Eurotherm 2000 Series Communications Handbook, # HA026230
2.Eurotherm 2404/2408 Control Setpoint Programmer Installation and Operation
Handbook, # HA025132
7. INTERFACING THE ECS WITH A BUILDING BAS/EMS
The ECS may be interfaced with a building’s Building Automation System (BAS) or Energy
Management System (EMS). Table 3 below shows the Modbus data addresses both for the
BAS/EMS and the AERCO ECS.
Table 3. AERCO Electronic Control System (ECS) Point Definitions
All Modbus addresses specified in this manual are written generically in
hexadecimal/decimal format. However, many Building Automation Systems utilize
another form of addressing where:
• 40001 is added to the generic address for a Holding Register
address.
• 30001 is added to the generic address for an Input Register
address.
Check the addressing scheme being used by the BAS interfaced to the XPC Gateway.
6
Page 11
8. ALARMS
Table 4. Process Alarms
DISPLAY MEANING
_FSL*
_FSH*
_dEu*
_dHi*
_dLo*
PV Full Scale Low Alarm.
PV Full Scale High Alarm.
PV Deviation Band Alarm
PV Deviation High Alarm
PV Deviation Low Alarm
Table 5. Diagnostic Alarms
DISPLAY MEANING WHAT TO DO`
EE.Er Electrically Erasable Memory Error:
The value of an operator, or
configuration, parameter has been
corrupted.
S.br
Sensor Break
Input sensor is unreliable or the
input signal is out of range.
This fault will automatically take you into
Configuration level. Check all of the
configuration parameters before returning
to Operator level. Once in Operator level,
check all of the operator parameters
before resuming normal operation. If the
fault persists, or occurs frequently,
contact your supplier
Check that the sensor is correctly
connected
L.br
Hw.Er
no.io
rmt.F
LLLL
HHHH
Err1
Err2
Err3
Loop Break
The feedback loop is open circuit
Hardware Error
Indication that a module is of the
wrong type, missing, or faulty.
No I/O
None of the expected I/O items are
installed
Check that the heating and cooling
circuits are working properly
Check to ensure that the correct items
are installed. See page A-4 for procedure
to clear the Hardware Error.
This error message normally occurs
when pre-configuring a controller without
installing any of the required I/O
modules.
Remote input failure.
The remote DC input is open or
Check for open or short circuit wiring on
the remote DC input.
shorted
Out of range low reading Check the value of the input
Out of range high reading Check the value of the input
Error 1: ROM self-test fail Return Controller for repair
Error 2: RAM self-test fail Return Controller for repair
Error 3: Watchdog fail Return Controller for repair
7
Page 12
AC-106 INSTRUCTIONS - ECS COMMUNICATIONS
Err4
Error 4: Keyboard failure. Stuck
button or button was pressed
Switch power off and then on, without
touching any of the controller buttons
during power-up
Err5
Error 5: Faulty internal
communication
Check printed circuit board
interconnections. If the fault cannot be
cleared, return the controller for repair.
Err6
Digital filter chip faulty or loose
Return Controller for repair
board inside controller
Err7
Err8
PV ID failure Return Controller for repair
Module 1 ID failure Faulty or loose module, or isolation
problem
Err9
Module 2 ID failure Faulty or loose module, or isolation
problem
ErrA
Module 3 ID failure Faulty or loose module, or isolation
problem
dCF
DC output failure Return Controller for repair
9. CLEARING HARDWARE ERROR (HW.ER) DISPLAY
To clear a Hardware Error and reset the Temperature Controller, proceed as follows:
1. Simultaneously press the Page (
) and Scroll ( ) buttons on the Temperature Controller.
2. Using the Up (▲) arrow button, change the password to “8”.
3. Simultaneously press the Page (
) and Scroll ( ) buttons again and observe the
Temperature Controller display. The top line will display “8” and the bottom line will display “NO”.
4. Press the Up (▲) arrow button to toggle the display from “NO” to “YES”.
5. Simultaneously press the Page (
) and Scroll ( ) buttons to “Reset” the Temperature
Controller and clear the Hardware Error.
8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.