AERCO AC-106 Communication Manual

Page 1
Instruction No.
AERCO INTERNATIONAL, Inc., Northvale, New Jersey 07647 USA
AC-106
®
Communication Manual
for
ELECTRONIC CONTROL SYSTEM
(ECS)
Used to Interface AERCO Equipment
to Building Automation Systems
Modbus® is a registered trademark of AEG Modicon
REVISED 7/28/10
Page 2
THIS PAGE INTENTIONALLY BLANK
ii
Page 3

ELECTRONIC CONTROL SYSTEM COMMUNICATION INTERFACE

TABLE OF CONTENTS

Title Page
1. INTRODUCTION 1
2. COMMUNICATION BOARD 1
3. MODBUS COMMUNICATION SIGNAL CONNECTIONS 1
4. MODBUS COMMUNICATION INFORMATION 2 5 CHANGING COMMUNICATION ADDRESSES ON THE AERCO EUROTHERM TEMPERATURE CONTROLLER 4
6. REFERENCED DOCUMENTS 6
7. INTERFACING THE ECS WITH A BUILDING’S BAS/EMS 6
8. ALARMS 7
9. CLEARING HARDWARE ERROR (HW.ER) DISPLAY 8

LIST OF FIGURES

1. Temperature Controller (Eurotherm 2408) Terminal Connection Diagram 2

LIST OF TABLES

1 MODBUS Communication Signal Connections 2
2. Eurotherm Series 2400 Controller MODBUS Points 3 3 AERCO Electronic Control System (ECS) Point Definitions 6
4. Process Alarms 7
5. Diagnostic Alarms 7
iii
Page 4
THIS PAGE INTENTIONALLY BLANK
iv
Page 5
AC-106 INSTRUCTIONS - ECS COMMUNICATIONS

ELECTRONIC CONTROL SYSTEM COMMUNICATION INTERFACE

1. INTRODUCTION

The Electronic Control System (ECS), used on AERCO indirect fired water heaters, can be ordered with a MODBUS® Communication Option, which will permit it to be controlled by an external Energy Management System (EMS), Building Automation System (BAS), or a computer supplied by others.

2. COMMUNICATION BOARD

The Communication Board provides the MODBUS interface between any of the possible external control systems and the ECS. The Temperature Controller (Eurotherm 2408) used in the ECS can be optionally equipped with a Communication Board which can be connected to external control systems utilizing either an RS232 or RS485 MODBUS communication interface. The corresponding part numbers for the alternative MODBUS Communication Boards are as follows:
PART NUMBER DESCRIPTION
64009-1 RS232 COMMUNICATION BOARD
64009-2 RS485 COMMUNICATION BOARD

3. MODBUS COMMUNICATION SIGNAL CONNECTIONS

CAUTION
DO NOT route MODBUS communication wiring in the same conduit as power wiring. Attempting to do so may result in excessive noise on the signal lines. Also, ensure that the RS232 or RS485 signal cable connections do not exceed the following lengths:
CABLE TYPE
RS232 50 feet
RS485 4,000 feet
To implement ECS MODBUS control, connect the cable leads from the external controller to the Temperature Controller as instructed in Table 1.
Refer to the Temperature Controller (Eurotherm 2408) pinouts shown in Figure 1 to locate the required terminals.
Refer to Table 2 Eurotherm Series 2400 Controller MODBUS Points for a listing of active MODBUS data addresses for the 2408 Controller.
The Eurotherm documents referenced on page 3 provide additional communication information related to MODBUS.
MAXIMUM LENGTH
NOTE
AERCO recommends that shielded, twisted-pair cable be used for communication wiring. Examples of suitable wiring are: Belden 9841, 8761, 3105A, or equivalent.
1
Page 6
Table 1. MODBUS Communication Signal Connections
2408 TEMPERATURE
CONTROLLER
SIGNAL
PIN NO.
NAME
RS232/9-PIN RS232/25-PIN RS485
SIGNAL
NAME
COMPUTER CONTROL CABLE
PIN NO. PIN NO. PIN NO.
GROUND HD GROUND 5 7 GROUND
RECEIVE HE TRANSMIT 3 2 A-
TRANSMIT HF RECEIVE 2 3 B+
2408 CONTROLLER
1A
1B
1C
1D
2A
2B
2C
2D
3A
3B
3C
3D
HA
HB
HC
HD
HE
HF
JA
JB
JC
JD
JE
JF
L
N
LA
LB
LC
AA
AB
AC
VI
V+
V-
In1
In2
C
Figure 1. Temperature Controller (Eurotherm 2408) Terminal Connection Diagram

4. MODBUS COMMUNICATION INFORMATION

The Eurotherm 2400 Controller supports the MODBUS RTU mode of transmission. The default settings are as follows:
9600 baud rate
One start bit
Eight data bits
One stop bit
No parity
2
Page 7
MODBUS
Address
Data
Table 2. Eurotherm Series 2400 Controller MODBUS Points
Menu
Item
Menu Item
Description
Units &
Range
Default/Comments
Register
Type
Ref. 1
Comm.
Guide
5 w.SP Setpoint 40-205°F 140°F, Address to
read value
24 SP 1 Setpoint 40-205°F 140°F, Address to
change value
1 Top
Value
133 LoGH Peak Temp 40-205°F Resets on Power
135 LoGA Average
134 LoGL Low Temp 40-205°F Resets on Power
13 (set)
74 (status,
0 = safe
1 = alarm)
14 (set)
74 (status,
0 = safe
AL 1 Over Temp
AL 2
(FSH)
Outlet Temp 40-205°F Same value as front
display
Loss
40-205°F Resets on Power
Temp
Alarm
Full Scale High Alarm
40-205°F 20°F above
205°F 205 ° F
Loss
Loss
setpoint; Alarm Type 17: Deviation High
Alarm Type 2: Full Scale High
Read
Only
Write 5-11
Read
Only
Read
Only
Read
Only
Read
Only
Read
Only
Read
Only
5-4
5-3
5-15
5-15
5-15
5-7
5-20
5-7
5-20
1= alarm)
258 Sbr Feedback
Sensor Break
289 Li 1 Feedback
Sensor Temp
290 Li 2 Flow GPM Read
3 OP Control
Output Signal
26 RmSet
pt
Remote Setpoint
Status:
0: Good
1: Failed
40-180°F Sensor input to
% Correlates to valve
(40 to 180) °F
Denotes Feedback Sensor Failure/Open Circuit
controller, same as display temp.
position
Holding
Read
Only
Read
Only
Only
Read
Only
3
5-18
5-14
5-14
5-4
Page 8
5. CHANGING COMMUNICATION ADDRESSES ON THE AERCO EUROTHERM TEMPERATURE CONTROLLER
To change the modbus address:
The address is defaulted to 1 from the factory. Refer to the Button map below for all panel navigation instructions.
1. Page to the ACCS list and Scroll down the list to codE.
2. Enter 24 using the Up Arrow.
The number will display and flash PASS.
3. Scroll to Goto (current value is OPEr) and use the Down Arrow to enter a value of Full
conrmed by the flashing of the lower display momentarily off and then on.
Button Map
Page
4. Go to the home screen by pressing the Page and Scroll buttons at the same time.
Scroll
Down Arrow
. The entry is
Up
Arrow
4
Page 9
5. Page to the cmS list
6. Scroll to the Addr screen
7. Use the Up Arrow to select
the desired address number.
8. Go to the home screen by
pressing the Page and Scroll buttons at the same
time.
9. Page to the ACCS List and
change the code to anything
other than 24 and the codE
number you entered will flash off and then on to 0 to confirm that access is now set to the OPEr level and is safe to return to use.
10.Confirm that the Addr is set properly by pressing Page button
until the cmS list is displayed and
Scroll to Addr. If the value is
correct you are done, if not please repeat the steps again.
5
Page 10
6. REFERENCE DOCUMENTS
1. Eurotherm 2000 Series Communications Handbook, # HA026230
2. Eurotherm 2404/2408 Control Setpoint Programmer Installation and Operation
Handbook, # HA025132
7. INTERFACING THE ECS WITH A BUILDING BAS/EMS
The ECS may be interfaced with a building’s Building Automation System (BAS) or Energy Management System (EMS). Table 3 below shows the Modbus data addresses both for the BAS/EMS and the AERCO ECS.
Table 3. AERCO Electronic Control System (ECS) Point Definitions
Equip. Point Name
Electric Valve (ECS)
01-Cntl Output Signal 30004
02-Setpoint 30006 w.SP (Setpoint) Input 0x0005 / 5 °F (40 to 180)
03-RmSetpt 40027
04-Outlet Temp 30002
05-FBk Sensor Temp 30290
06-Over Temp Alarm 30075
BAS Modbus
Data Addr
AC-106 Point
Name
OP (Control Output Signal) Input 0x0003 / 3 % (0 to 100)
Remote Input Comms Access parameter(Setpoi nt) Holding 0x001A / 26 °F (40 to 180)
Top Value (Outlet Temp) Input 0x0001 / 1 °F (40 to 205)
Li1 (Feedback Sensor Temp) Input 0x0121 / 289 °F (40 to 180)
AL 1 (Over Temp Alarm) Input 0x004A / 74
Reg.
Type
Modbus Data
Addr (Hex/Dec.) Units (Range)
Enum (0,1) 0 = Safe, 1 = Alarm
07-Flow Rate 30291 Li2 (Flow) Input 0x0122 / 290 GPM
IMPORTANT
All Modbus addresses specified in this manual are written generically in hexadecimal/decimal format. However, many Building Automation Systems utilize another form of addressing where:
40001 is added to the generic address for a Holding Register address.
30001 is added to the generic address for an Input Register address.
Check the addressing scheme being used by the BAS interfaced to the XPC Gateway.
6
Page 11

8. ALARMS

Table 4. Process Alarms
DISPLAY MEANING
_FSL* _FSH* _dEu* _dHi* _dLo*
PV Full Scale Low Alarm.
PV Full Scale High Alarm.
PV Deviation Band Alarm
PV Deviation High Alarm
PV Deviation Low Alarm
Table 5. Diagnostic Alarms
DISPLAY MEANING WHAT TO DO`
EE.Er Electrically Erasable Memory Error:
The value of an operator, or configuration, parameter has been corrupted.
S.br
Sensor Break Input sensor is unreliable or the input signal is out of range.
This fault will automatically take you into Configuration level. Check all of the configuration parameters before returning to Operator level. Once in Operator level, check all of the operator parameters before resuming normal operation. If the fault persists, or occurs frequently, contact your supplier
Check that the sensor is correctly connected
L.br
Hw.Er
no.io
rmt.F
LLLL HHHH Err1
Err2 Err3
Loop Break The feedback loop is open circuit
Hardware Error Indication that a module is of the wrong type, missing, or faulty.
No I/O None of the expected I/O items are installed
Check that the heating and cooling circuits are working properly
Check to ensure that the correct items are installed. See page A-4 for procedure to clear the Hardware Error.
This error message normally occurs when pre-configuring a controller without installing any of the required I/O modules.
Remote input failure. The remote DC input is open or
Check for open or short circuit wiring on the remote DC input.
shorted
Out of range low reading Check the value of the input
Out of range high reading Check the value of the input
Error 1: ROM self-test fail Return Controller for repair
Error 2: RAM self-test fail Return Controller for repair
Error 3: Watchdog fail Return Controller for repair
7
Page 12
AC-106 INSTRUCTIONS - ECS COMMUNICATIONS
Err4
Error 4: Keyboard failure. Stuck button or button was pressed
Switch power off and then on, without touching any of the controller buttons
during power-up
Err5
Error 5: Faulty internal communication
Check printed circuit board interconnections. If the fault cannot be cleared, return the controller for repair.
Err6
Digital filter chip faulty or loose
Return Controller for repair
board inside controller
Err7 Err8
PV ID failure Return Controller for repair
Module 1 ID failure Faulty or loose module, or isolation
problem
Err9
Module 2 ID failure Faulty or loose module, or isolation
problem
ErrA
Module 3 ID failure Faulty or loose module, or isolation
problem
dCF
DC output failure Return Controller for repair

9. CLEARING HARDWARE ERROR (HW.ER) DISPLAY

To clear a Hardware Error and reset the Temperature Controller, proceed as follows:
1. Simultaneously press the Page (
) and Scroll ( ) buttons on the Temperature Controller.
2. Using the Up () arrow button, change the password to “8”.
3. Simultaneously press the Page (
) and Scroll ( ) buttons again and observe the
Temperature Controller display. The top line will display “8” and the bottom line will display “NO”.
4. Press the Up () arrow button to toggle the display from “NO” to “YES”.
5. Simultaneously press the Page (
) and Scroll ( ) buttons to “Reset” the Temperature
Controller and clear the Hardware Error.
8
Loading...