AEMC Instruments MN379T User manual

Page 1
AC Current Probe Model MN379T
User Manual
DESCRIPTION
The MN379T (Catalog #2153.02) is th e l atest in compact AC curre nt p ro bes. D esigned to meet the most stringent demands in indus tr y and elec trical contr acti ng, it also mee ts t he lat est s afet y and perf orma nce standards. The pr obe has a measurement ran ge up to 120Arms, a range and resolution capable of displaying 10mV o f output p er amp of measured curre nt, a volt meter acc uracy of 0.5% or b etter to tak e full advantage of the accuracy of the probe and an input impedance of 1MΩ.
WARNING
The safety warnin gs are provided to ensure the safety of personnel and p roper operation o f the instrument. Read the instruction completely.
• Use caution on any circ uit: p ote ntially high voltages a nd currents may be pres ent a nd m a y pose a shock hazard.
• Do not use the probe if damaged. Al ways connect the current probe to the measuring device before it is connected around the conductor
• Do not use on non-i nsulated conductor with a potential to ground greater than 600V CAT III pollution 2. Use extreme caution when clamping around bare conductors or bus bars.
• Before each use, inspect the probe; look for cracks in housing or output cable insulation.
• Do not use clamp in wet environment or in locations that hazardous gases exist.
• Do not use the probe anywhere beyon d the tac til e bar rie r.
INTERNATIONAL ELECTRICAL SYMBOLS
This symbol signifies that the cur rent prob e is protect ed by doubl e or reinfo rced ins ulation. Us e only factory specified replacement parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before using the instrument.
This is a type A current sensor. This symbol signifies that application around and removal from HAZARDOUS LIVE conductors is permitted.
DEFINITION OF MEASUREMENT CATEGORIES CAT IV: For measurem ents performed at the primary electrical supply (<1000V) such as on primary
overcurrent protection devices, ripple control units, or meters.
CAT III: For measurements performed in the building installation at the distribution level such as on
hardwired equipment in fixed installation and circuit breakers.
CAT II: For m easurements performed on circuits directly co nnected to the electri cal distribution system.
Examples are measurements on household appliances or portable tools.
RECEIVING YOUR SHIPMENT
Upon receiving your shipment, m ake sure th at the contents a re consist ent with the pac king list. Notif y your distributor of an y missin g items. If the e quipment appear s to b e dama ged, fil e a claim immedi atel y with the carrier and notify your distributor at once, giving a detailed description of any dama ge
www.GlobalTestSupply.com
Page 2
Ip
0.005A
0.05A
0.5A
5A
1.5 %
+0.02mV
Phase
6.5 °
5 °
4.5 °
4 °
Ip
0.1A
1A
10A
100A
1%
+0.02mV
Phase
3.2 °
2.2°
2.2 °
2.2 °
ELECTRICAL SPECIFICATIONS
Nominal Range: 5A, 100A Measurement Range: 5A: 0.005 to 6A
100A: 0.1 to 120A Transformation Ratio: Voltage output Output Signal: 5A: 200mV/A
100A: 10mV/A
Accuracy and Phase Shift*:
5A Range - Accuracy
Vs %
1.5% 1% 1%
www.GlobalTestSupply.com
100A Range - Accuracy
Vs %
*Reference conditions: 18°C to 28°C, 20 to 75% RH, external magnetic field <40 A/m, 48 to 65Hz sine wave, distortion factor less than 1%, no DC component, no external current carrying conductor, test sample centered. Load impedance > 1MΩ.
1% 1% 1%
Frequency Range: 40 to 10kHz Limit Operating Conditions:
200A MAX to 1kHz; Derating above 1kHz: 200A x (1*F), F in kHz
Working Voltage: 600Vrms
Page 3
Common Mode Voltage: 600Vrms
Influence of Adjacent Conductor:
< 15mA/A at 50Hz
Influence of DC on AC signal:
5A Range: DC Current < 1A, < 3% 100A Range: DC Current < 10A, < 10%
Influence of Conductor Position in Jaw:
0.5% of mV output @ 50/60Hz
Influence of Frequency:
5A Range:
40Hz to 1kHz: <0.7% of mV output 1kHz to 3kHz: <2%% of mV output
150A Range:
40Hz to 1kHz: <0.7% of mV output 1kHz to 3kHz: <0.7% of mV output
Influence of Temperature:
200 ppm/°K, or 0.2% of mV output per 10°K
Influence of Humidity (10 to 90% RH):
0.2% of mV output per 10°K @ 18° to 28°C
MECHANICAL SPECIFICATIONS
Operating Temperature:
14° to 131°F (-10° to +55°C)
Storage Temperature:
-40° to 158°F (-40° to +70°C)
Operating Relative Humidity:
10° to 35°C 85% RH (without roll-off above 35°C)
Maximum Cable Diameter:
One Ø 0.78" (20mm), bus bar 20 x 5 mm
Case Protection:
IP 40 (IEC 529)
Drop Test:
Test per IEC 68-2-32:
1.0 m drop on 38mm of Oak on concrete Test per IEC 68-2-27
Vibration:
Test per IEC 68-2-6
Dimensions:
5.47 x 2.00 x 1.18" (139 x 51 x 30mm)
Weight:
180g (6.5oz)
Polycarbonate Material:
Jaws: Polycarbonate with 10% fiberglass charge, Red UL 94 V0 Case: Polycarbonate 920A Gray
Opening Operations - Life: > 50,000 Output:
10 ft (3m) insulated lead with BNC connector
SAFETY SPECIFICATIONS
Electrical:
Double insulation or reinforced insulation between the primary or secondary and the outer case of the handle conforms to IEC 1010-2-32.
Common Mode Voltage:
600V CAT III, Pollution Degree 2
Electromagnetic Compatibility:
Emissivity: EN61326-1 Class B Electrostatic discharge IEC 1000-4-2 Radiated field IEC 1000-4-3 Fast transients IEC 1000-4-4 Magnetic field at 50/60Hz IEC 1000-4-8
ORDERING INFORMATION
AC Current Probe MN379T .....Cat #2153.02
www.GlobalTestSupply.com
Page 4
OPERATION
Please make sure that you have already read and fully understand the WARNING section on page 1.
Making Measurements with the AC Current Probe Model MN379T
Connect the BNC connector to your voltage-measuring instrument. The AC current p ro be has an o utput of 200mV/A and 10mV/A . This means that wit h the probe in the 10mV/A position, for 100A AC in a conductor around which the probe is clamped, 1V AC will come out of the probe leads to your instrument. Select t he range which corresponds t o the measured current. If the current magnitude is unknown, start wit h the probe in the 10mV/A position and if t he current is < 5 amps the p robe can be switched to the 200mV/A posi tion for the higher resol ution. Clamp the probe a r oun d th e con ductor. With the probe in the 1 0mV/A position tak e the reading on the met er and multiply it b y 100 to obtain the measured current (e.g, 16 0m V reading = 160 x 100 = 16,000mA or 16A).
The 5A range is design t o measure on 5A c urrent transfo rmer. T he outp ut is 1V rms f or 5A me asured. Enter a scale factor in the meter if possible for direct reading.
For best accuracy, avoid if possible, the proximity of other conductors which may create noise.
Tips for Making Precise Measurements
When using a curre nt probe with a meter, it is impo rtant to select the range that p rovides the best resolution. Failure to do this may result in measurement errors.
Make sure that probe ja w mating surfa ces are free of dus t and contaminat ion. Contami nants caus e air gaps between the j aws, i ncrea sing the phase s hift betw een p rimar y and se co ndar y. It is very critical for power measurement.
MAINTENANCE: Warning
For maintenance use only original factory replacement parts.
To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so.
To avoid electrical sh ock and/or damage to t he instrument, do n ot get water or other f oreign agents
into the probe
Cleaning
To ensure optimum p erforma nce, it is i mportant t o keep the probe jaw ma ting surf aces clea n at all time s. Failure to do so m ay result in err or in readings . To clean the p robe jaws, us e very fine sa nd paper (fine
600) to avoid scratching the jaw, then gently clean with a soft oiled cloth.
REPAIR AND CALIBRATION
You must contact our Service Center for a Customer Service Authorization number (CSA#). This will ensure that whe n your instrument arriv es, it will be tracked an d p rocessed promptl y. Ple ase w rit e t h e CS A# on the outside of the shipping container.
Chauvin Arnoux
Faraday Drive • Dover, NH 03820 USA
15
®
, Inc. d.b.a. AEMC® Instruments
(800) 945-2362 (Ext. 360) • (603) 749-6434 (Ext. 360) • repair@aemc.com
(Or contact your authori zed di stributor)
NOTE: All customers must obtain a CSA# before returning any instrument. TECHNICAL AND SALES ASSISTANCE
If you are experiencing any technical problems, or require any assistance with the proper use or application of this instrument, please contact our technical hotline:
(800) 945-2362 (Ext. 351) • (603) 749-6434 (Ext. 351) • techsupport@aemc.com
LIMITED WARRANTY
The cu rrent prob e is warranted to t he owner f or a period of two years from the date o f original purchase against defects in manufacture. This limited warranty is given by AEMC distributor from whom it was pu rchas ed. This warrant y is void if t he unit has been tam pered with, abus ed or if the defect is related to service not performed by AEMC
®