POWER QUALITY ANALYZERS, METERS & LOGGERS
GROUND RESISTANCE TESTER
Simple Logger® II TRMS Current
Three-Phase Power Quality Analyzer
Simple Logger® II TRMS Current & Voltage
DATA LOGGERS
DATA LOGGERS
Multi-Function
4 to 20mAdc Current Model L322 &
DC Voltage Model L432
Two channel logger has the ability to
perform a variety of recording tasks
with easy and intuitive setup
IP 40
Rated
SPECIFICATIONS
Special product
FEATURES
2 independent input channels
-20 to +20mA
DC (Model L322)
User-selectable ranges of ± 100mV;
± 1V and ± 10V
DC per channel
(Model L432)
Programmable storage rates from
8 every second to 1 every day
4 user selectable storage modes
Stores up to 240,000 measurements in
non-volatile memory
Powered by standard Alkaline batteries
Lightweight, compact, fits anywhere
5 LED indicators quickly and clearly
display logger status
Includes FREE DataView
®
software for data storage, real-time display, analysis and report generation
Optically isolated USB 2.0 communication
cable included
EN 61010-1; 50V CAT III
APPLICATIONS (MODEL L322)
Process control monitoring and
troubleshooting
Profile temperature, pressure, flow and other
parameters directly
General purpose DC current monitoring
And many more
APPLICATIONS (MODEL L432)
Circuit design troubleshooting
Sensor monitoring
Battery testing
Power supply profiling
And many more
MODELS L322 L432
ELECTRICAL
Channels
Input Connection Measurement Range
Resolution Accuracy
(DC and 50/60Hz)
Range 1 (0.25% of Reading +0.05mA) ±(0.5% of Reading +1mV)
Range 2 ±(0.5% of Reading +1mV)
Range 3 ±(0.5% of Reading +10mV)
Input Impedance
Sample Rate
Storage Rate
Storage Modes
Recording Length Memory
Communication
Power Source Battery Life
MECHANICAL
Dimensions
Weight (with battery)
Case
Vibration
Shock
Drop
One 4-position removable screw-type terminal block
-20 to +20mA
Programmable from 8 every second to 1 every day
Start/Stop, FIFO, Extended Recording Mode (XRM
15 minutes to 8 weeks, programmable using DataView
The recorded data is stored in non-volatile memory and
will be retained even if the battery is low or removed.
(dependent on sample rate and recording length)
dc
0.01mA 0.1mV - 1mV - 10mV
50Ω
8 samples taken at storage interval
240,000 measurements (512KB)
USB 2.0 optically isolated
2 x 1.5V AA-cell Alkaline batteries (included)
5.45 x 2.75 x 1.28" (136 x 70 x 32mm)
IEC 68-2-6 (1.5mm, 10 to 55Hz)
Two
±100mV/1V/10Vdc (selectable through
DataView
100 hours to >45 days
6.4 oz (181g)
UL94-V0
IEC 68-2-27 (30G)
IEC 68-2-32 (1m)
®
100mV/1V: 80kΩ
10V: 800kΩ
software)
) and Alarm
®
CATALOG NO. DESCRIPTION
2126.06 Simple Logger® II Model L322 (2-Channel, 4 to 20mAdc Current, DataView® software)
2126.07
Simple Logger
Technical Assistance (800) 343-1391
®
II Model L432 (2-Channel, DC ±100mV/1V/10Vdc, DataView® software)
www.aemc.com
DATAVIEW®
Software for Data Loggers
Data Analysis and Reporting Software for Data Loggers
Typical DataView® Functional Displays
Quick and simple configuration of all functions and settings from one dialog box.
Configure all data logger functions of the Simple Logger
Display and analyze real-time data on your PC
Configure all data logger functions and
parameters from your PC including sample rate, recording length, channel configuration and more
Create and store a complete library of configurations that can
be uploaded to the logger as needed
Zoom in and out and pan through sections of the graph to
analyze the data
Download, display and analyze recorded data
Display waveforms, trend graphs, harmonics (AC models)
and text summaries
Create custom views and reports
Print reports using standard or custom templates you design
Free software upgrades are available on
our website www.aemc.com
®
II Models
Configure all alarm functions with straightforward selections.
Real-time view of trend, waveform and status screens.
www.aemc.com
Real-time display of all active inputs on computer through
®
DataView
software.
Technical Assistance (800) 343-1391