AEMC JM840A Data sheet

AC Current Probes Model JM840A (pdf) Rev. 03 10/05
Technical Assistance (800) 343-1391 www.aemc.com1of 4
AC Current Probe Model JM840A
The Model JM840A is a high performance AC current probe for higher currents. Excellent transformation and low phase shift, plus a broad frequency response, permit accurate measurements of current and power. The high quality magnetic core and uniform windings provide for accurate measurements up to 500A
AC/1000AAC/
1800A
AC. The “squared” jaw permits
multiple conductor or bus bar positioning. The Model JM840A provides excellent True RMS capabilities and reliable signal reproduction.
The Model JM840A first works as a traditional current transformer providing current outputs (mA) over a broad range of transformation ratios. The Model JM840A is designed for use on DMMs, power and harmonic meters, recorders or instruments with AC current ranges.

Features

Nominal range: 500AAC, 1000AAC,
1500A
AC (continuous cycle for the
full temperature range)
• Transformation ratio: 500:1, 1000:1, 1500:1
Output: 2mA, 1mA
AC/AAC and
0.66mA
AC/AAC
Designed for use on DMMs, power and harmonic meters, recorders or
instruments with AC current ranges

Applications

Field testing
Electrical utility
HVAC
Industrial maintenance
Laboratory
Plant maintenance
AC Current Probes Model JM840A (pdf) Rev. 03 10/05
Technical Assistance (800) 343-1391 www.aemc.com2of 4

Specifications

MODELS JM840A
ELECTRICAL
Nominal Range 1500A Measurement Range 1 to 1800AAC Transformation Ratio 500:1. 1000:1, 1500:1 Output Signal 2mA
AC/AAC (1A @ 500A)
1mAAC/AAC (1A @ 1000A)
Accuracy (500A Range)
25A 4% of Reading 100A 3% of Reading 500A 3% of Reading
Phase Shift (500A Range)
25A 4° 100A 3.5° 500A
Accuracy (1000A Range)
50A 3% of Reading 200A 2% of Reading
1000A 1% of Reading
Phase Shift (1000A Range)
50A 3° 200A 1.5°
3000A
Accuracy (1500A Range)
75A 1.5% of Reading 300A 0.75% of Reading
1500A 0.5% of Reading
Phase Shift (1500A Range)
75A 1.5° 300A 0.75°
1500A 0.5°
Overload 700A for 10 min (500A);
1400A for 10 min (1000A);
1800A for 10 min (1500A)
Frequency Range 30 to 1500Hz; current
derating above 1500Hz
for continuous use
Load Impedance ≤5Ω
(500A, 1000A, 1500A)
Working/Common Mode Voltage
600V
AC
Output Termination Jack
MECHANICAL
Operating Temperature 14° to 122°F (-10° to 50°C) Storage Temperature -13° to 176°F (-25° to 80°C) Jaw Opening 3.54" (90mm) Maximum Conductor Size Cable: 2.52" Ø max (64mm); Bus bar: 1.97 x 5.31" (50 x 135mm); 2.52 x 3.94" (64 x 100mm) Dimensions 4.72 x 12.40 x 1.89" (120 x 315 x 48mm) Weight 2.65 lbs (1200g) Polycarbonate Material Handles: 10% fiberglass charged polycarbonate UL94 VO; Jaws: ABS UL V2
SAFETY
Electrical EN61010-2-32 Electromagnetic EN 50081-1 Class B; EN 50082-2 Electrostatic discharge IEC 100-4-2;
Compatibility Radiated field IEC 1000-4-3; Fast transients IEC 1000-4-4; Magnetic field at 50/60Hz IEC 1000-4-4
Double Insulation Yes
CE Mark Yes
Note: Reference conditions:
23°C ± 3°K, 20 to 85% RH, 45 to 65Hz, external magnetic field < 40A/m, no DC component, no external current carrying conductor, test sample centered.
AC Current Probes Model JM840A (pdf) Rev. 03 10/05
Technical Assistance (800) 343-1391 www.aemc.com3of 4
Ø=2.52" (64mm)

ORDERING INFORMATION CATALOG NO.

AC Current Probe Model JM840A (Jack – 2mA/A – 500A; 1mA/A – 1000A; .66mA/A – 1500A max) . . . . . . . . Cat. #2110.85
Includes a user manual
Accessories (Optional)
Banana plug adaptor (to nonrecessed plug) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cat. #1017.45
Leads, set of 2, 5 ft safety (1000V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cat. #2111.29
Banana/BNC Connector XF-SS (4mm banana plug) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cat. #2111.32
Jacks:
Two standard safety banana jacks (4mm)
Cable max.
1.97 x 5.31" (50 x 135mm) or
2.52 x 3.94" (64 x 100mm) Bus Bar max.
P1 P2
12.01"
(305mm)
4.72"
(120mm)
1.89"
(48mm)
AC Current Probes Model JM840A (pdf) Rev. 03 10/05
Technical Assistance (800) 343-1391 www.aemc.com4of 4

Contact Us

United States and Canada:
Chauvin Arnoux
®
, Inc.
d.b.a. AEMC
®
Instruments 200 Foxborough Blvd. Foxborough, MA 02035 USA (508) 698-2115 • Fax (508) 698-2118 www.aemc.com
Customer Support – for placing an order, obtaining price and delivery:
customerservice@aemc.com
Sales Department – for general sales information:
sales@aemc.com
Repair and Calibration Service – for information on repair and calibration, obtaining a user manual:
repair@aemc.com
Technical and Product Application Support – for technical and application support:
techinfo@aemc.com
Webmaster – for information regarding www.aemc.com:
webmaster@aemc.com
South America, Central America, Mexico, Caribbean, Australia and New Zealand:
Chauvin Arnoux
®
, Inc.
d.b.a. AEMC
®
Instruments 15 Faraday Drive Dover, NH 03820 USA (978) 526-7667 • Fax (978) 526-7605 export@aemc.com www.aemc.com
All other countries:
Chauvin Arnoux SCA 190, rue Championnet 75876 Paris Cedex 18, France 33 1 44 85 45 28 • Fax 33 1 46 27 73 89 info@chauvin-arnoux.com www.chauvin-arnoux.com
Loading...