Hazmat Grounding & Bonding

Site Considerations

Locate grounding points on the tankers and transfer pump.
Make connections to damaged tanker first to avoid a potential spark.
When possible, grounding systems should be established uphill and outside of the H
ot Zone.
Resistance measurement should be compliant with your local jurisdiction which usually follows NFPA 472 @ 1000Ω or less, or NEC @ 25Ω or less; lower is
always better. Higher resistance means longer static discharge time.

Installing the Grounding System

STEP 1:

WARNING:
Make sure the ground rod is fully screwed tight into the Driver/
Extractor tool before driving it into the ground to avoid thread damage.
Install/establish three separate static grounding systems, one for the distressed tanker
pum
The grounding sites should be uphill and upwind, as well as outside of the
distressed tanker's Hot Zone.
NOTE:
acceptable grounding resistance. Multiple rods should be connected to each other via jumper cables.
(X1),
p is not mounted to the fire truck. They should be at least 10 feet apart.
One or more rods may be needed for each grounding system to obtain an
grounding (to be connected to the tanker)
one for the recovery tanker
be connected to the pump apparatus)
(X2),
and a
third
for the pump
3 to 6 feet apart and
connected to the tanker)
(X3)
when the
99-MAN 100438v3

Testing the Grounding System

STEP 2:

Conduct independent Fall-of-Potential tests on each of the grounding systems.

1.
Insert the auxiliary test electrode
50
to 80
syst
Insert the auxiliary test electrode
2.
distance approximately and in a straight line with the
3
.
Connect the
electrodes, and instrument as shown below.
4
.
Press and hold the green power button for approximately 2 seconds to
turn the instrument on. Next, press and release the blink red. When the reading stabilizes it will stop blinking and turn green. Record the resistance.
ft away at a location that is central to the three X rod grounding
ems.
30
to
Red, Blue
and
Green
H(z) a few inches into the ground and
S(Y)
few inches into the ground at a
45
ft from the first grounding system
H(z) electrode.
test wires to the ground rod(s),
TEST
button. It will
E1(x1)
5
.
Repeat steps 2, 3 and 4 for grounding systems
NOTE:
local authorities.
After achieving the acceptable resistance, disconnect the meter and auxiliary rods
S(Y) and
systems).
Readings should be below
H(z)
before Step 3 (connecting the tankers and pump to their grounding
1000Ω, 750Ω, 100Ω
X2
or
and
X3.
25Ω
as defined by
99-MAN 100438v3
Connect to the Grounding System
STEP 3:

Following the diagram, perform the steps below in the following order:

Connect a grounding cable to the distressed tanker first and then to
X1.
its grounding system
Connect a grounding cable to the recovery tanker first and then to its ground system
Connect a grounding cable to the transfer pump first and then to its grounding system
X2.
X3.
NOTE:
X3
is not needed if the pump is mounted to a fire truck.
Connect a bonding cable to the distressed tanker first and then to
the recovery tanker. Connect the hoses to the pump and tankers.
Begin the transfer process.
99-MAN 100438v3
Static Ground Test System
Ships with:
Cat. #2135.13
Cat. #5000.92
Ground Tester Model 6422
Cat. #2135.55
50’ Bonding Cable
with REB Clamp
Cat. #2155.12
HAZMAT Kit
Cat. #2155.01
PRODUCT PACKAGING
Set of 2, 14.5” T-shaped
Auxiliary Ground Electrodes
Cat. #2135.39
Set of 2, color-coded
Lead, 5’ (Red and Blue) for Reels
Cat. #5000.34
Waterproof Utility Case with inserts
Ground Tester Driver/Extractor Tool
Cat. #2155.11
(2 Sets of) 3 Copper Clad Ground Rods with
2 Ground Rod Couplers
Cat. #2155.10 (3 Rods & 2 Couplers)
(3) 50’ Ground Cable with
REB Clamp on one end and
Mueller Clip on the other
Cat. #2155.14 (1 Reel)
30’ Lead (green)
Cat. #5000.01
Also Includes:
User Manual
6 AA Batteries – Uninstalled
Flathead Screwdriver
H
andles supplied with
Red and Blue Reels
150’ Red Wire on Reel
Cat. #5000.04
Ground Tester
Calibration Checker
For Models 6422/6424
150’ Blue Wire on Reel
Cat. #5000.07
(2 Sets of) 3 10’ Ground Rod
Jumper Cables
Cat. #2155.15 (1 Set of 3)
Extra Handles for Reels
Cat. #5000.64
USB Drive containing
Training Video
Accessories (Sold Separately):
150’ Jumper Cable
Cat. #2155.16
Test Equipment Depot - 800.517.8
431 - 5 Commonwealth Ave, MA 01801