Input Terminals
Inputs
Voltage (TRMS AC+DC)
Voltage Ratio
Current (TRMS AC+DC)
Frequency (Hz)
Distribution Systems
Power Values
Energy Values
Harmonics
Transients
Flicker (Pst)
Unbalance
Recording
Alarm Mode
Peak
Phasor Display
Display
Snapshots
Electrical Safety
Protection
Languages
Communication Interface
Battery Life
Power Supply
Dimensions / Weight
MN93: 500mA to 200A
AmpFlex® or MA193 Clamps: 100mA to 10000Aac
1P 2W, 1P 3W, 2P 2W, 2P 3W, 2P 4W, 3P 3W, 3P 4W,
st
to 50th, Direction, Sequence; THD: 0 to 50, phase
1
Color ¼ VGA TFT screen (320 x 240) diagonal 148mm
IEC 61010, 1000V CAT III / 600V CAT IV
9.6V NiMH rechargeable battery pack (included)
External AC supply: 110/230Vac ±10% (50/60Hz)
9.8 x 7.8 x 2.6" (240 x 180 x 55mm) / 4.3 lbs (1.95kg)
A
*
R
E
Y
W
Y
3
3
A
T
R
N
R
A
4 voltage / 3 current
3 voltage / 3 current
2 to 1000V
up to 500kV
SR193 Clamp: 1A to 1000Aac
ac; MN193: 0.005 to 100Aac
MR193 Clamp: 1A to 1300Aac/dc
SL261 Clamp: 50mA to 100Aac/dc
J93: 50 to 3500Aac/dc
Current Ratio: up to 60kA
40 to 69Hz
Split-Phase 2W & 3W & Aron meters
W, VA, var, VAD, PF, DPF, cos ϕ, tan ϕ
Wh, varh, VAh, VADh
up to 51
Yes
Yes
Yes
10 types; 4000 recorded
Yes
Automatic
12
IP53
more than 27
USB
>13 hrs, 25 hrs in Record Mode
T
A
Y
S
R
IP
53
Rated
G
PRODUCT INCLUDES
8333 Kit
Three current probes, four black 10 ft voltage leads, four black
alligator clips, twelve color-coded input ID markers, NiMH battery,
110/240V power adapter with US power cord, carrying bag, soft
carrying pouch, and USB stick supplied with product user manual
and DataView
®
software.
OPTIONAL ACCESSORIES
AmpFlex® 193 flexible current probe (6500A)
Color-coded, 24" or 36", rated 600V CAT IV
* Registration must take place within 30 days of purchase
www.aemc.com
MN193 current probe (5A/100A)
Color-coded, rated 600V CAT III
Technical Assistance (800) 343-1391
Page 2
PowerPad® III Model 8333
Large Color Functional Displays
FEATURES
• True RMS single-, two- and three-phase
measurements at 256 samples/cycle, plus DC
• Real-time color waveforms
• Easy-to-use on-screen setup
• Automatic current probe recognition
and scaling
• True RMS voltage and current measurement
• Measures DC volts, amps and power
• Displays and captures voltage, current and
power harmonics to 50
direction, in real-time
• Captures transients down to 1/256
• Stores comprehensive data base of
logged data
• Phasor diagram display
• VA, var and W per phase and total
• kVAh, varh and kWh per phase and total
• Neutral current calculated and displayed
for three-phase
• Transformer K-Factor display
• Power Factor, displacement PF display
• Captures up to 51 transients
• Short term flicker display
• Phase unbalance (current and voltage)
• Harmonic Distortion (total and individual)
from 1
st
to 50
th
• Alarms, surges and sags
• Screen snapshot function captures waveforms
or other information on the display
• Includes FREE DataView
configuring data storage, real-time display,
analysis and report generation
th
order, including
th
of a cycle
®
software for
Configuration
Power and Energy Mode
Recording Mode
Transient Mode
Phasor Diagram
Harmonics Mode
CATALOG NO.DESCRIPTION
2136.10PowerPad® III Model 8333 (no probes)
2136.11PowerPad
2136.12PowerPad
Accessories (Optional)
2140.28AC Current Probe Model MR193-BK
2140.32AC Current Probe Model MN93-BK
2140.33AC Current Probe Model SR193-BK
2140.34AmpFlex
2140.35AmpFlex
2140.36AC Current Probe Model MN193-BK
2140.48MiniFlex
2140.49AC/DC Current Probe Model J93-BK
2140.50MiniFlex
®
III Model 8333 w/3 193-24-BK AmpFlex
®
III Model 8333 w/3 MN193-BK Probes
®
Sensor 24" Model 193-24-BK
®
Sensor 36" Model 193-36-BK
®
Sensor 10" Model MA193-10-BK
®
Sensor 14" Model MA193-14-BK
Technical Assistance (800) 343-1391
®
Sensors
www.aemc.com
Page 3
POWER QUALITY ANALYZERS, METERS & LOGGERS
Optional Accessories
SENSOR TYPECURRENT RANGE
MiniFlex® MA193-BK *
10" or 14" sensor
MR193-BK
Battery operated
SR193-BK
100mA to 3000Aac
1 to 1000Aac
1 to 1300Adc
1 to 1200Aac
ACCURACY
(TYPICAL)
±1%0°
±2.5%-0.80°
±0.3%0.2°
TYPICAL
ON Φ AT
50/60HZ
ERROR
MAX
CONDUCTOR
SIZE
2.75"
(70mm)
1.6"
(41mm)
2.05"
(52mm)
USED WITH
MODEL
PEL 102
PEL 103
PEL 105
8333
8336
8220
8230
PEL 102
PEL 103
PEL 105
8333
8336
8435
8220
8230
PEL 102
PEL 103
PEL 105
8333
8336
8435
LIMITED
RANGE IF
USED WITH
MODEL
8220
8230
8435
N/A2140.28
N/A2140.33
CATALOG
NUMBER
2140.48
(10" sensor)
2140.50
(14" sensor)
AmpFlex® 193-BK *
100mA to 12,000Aac
24" or 36" sensor
AmpFlex® A196
10 to 10,000Aac
24" sensor IP67
Maximum current reduced by a factor of 2 for 400Hz fundamental frequency.
*
±1%0°
±2%0°
7.64"
(190mm)
or
11.46"
(290mm)
5.73"
(145mm)
PEL 102
PEL 103
PEL 105
8333
8336
PEL 105
8435
8220
8230
8435
N/A
2140.34
(24" sensor)
2140.35
(36" sensor)
2140.75
(24" sensor)
www.aemc.com
Technical Assistance (800) 343-1391
Page 4
POWER QUALITY ANALYZERS, METERS & LOGGERS
Optional Accessories
MN93-BK
MN193-BK
SL261 **
J93
SENSOR TYPECURRENT RANGE
0.5 to 240Aac
100A
5A
100A
10A
200mA to 120Aac±1%0.75°
5mA to 6Aac±1%1.7°
5 to 100Aac/dc±4%±0.5°
50mA to 10Aac/dc±3%±1°
Battery operated
50 to 3500Aac
50 to 5000Adc
Battery operated
ACCURACY
(TYPICAL)
±1%0.8°
±1%±1°
TYPICAL
ERROR
ON Φ AT
50/60HZ
MAX
CONDUCTOR
SIZE
0.78"
(20mm)
0.78"
(20mm)
0.46"
(11.8mm)
2.83"
(72mm)
Busbar:
5 x 1.69"
(127 x 43mm)
USED WITH
MODEL
PEL 102
PEL 103
PEL 105
8333
8336
8435
8220
8230
PEL 102
PEL 103
PEL 105
8333
8336
8435
8220
8230
PEL 102
PEL 103
PEL 105
8333
8336
8435
PEL 102
PEL 103
PEL 105
8333
8336
8435
LIMITED
RANGE IF
USED WITH
MODEL
8220
8230
N/A2140.36
N/A1201.51
N/A2140.49
CATALOG
NUMBER
2140.32
Note: Refer to the Power Meter’s product user manual for complete specifications.
All current sensors can be used with the Models 8435 and PEL 105.
However, only the A196 flexible sensors are waterproof.
CATALOG NO.DESCRIPTION
1201.51AC/DC Current Probe Model SL261 (BNC)
2140.37Adapter – US 110V Power Adapter (eliminates need for batteries) 8220 & 8230 only
2140.28AC/DC Current Probe Model MR193-BK
2140.32AC Current Probe Model MN93-BK
2140.33AC Current Probe Model SR193-BK
2140.34AmpFlex
2140.35AmpFlex
2140.36AC Current Probe Model MN193-BK
2140.48MiniFlex
2140.49AC/DC Current Probe Model J93-BK
2140.50MiniFlex
2140.75AmpFlex
®
Sensor 24" Model 193-24-BK
®
Sensor 36" Model 193-36-BK
®
Sensor 10" Model MA193-10-BK
®
Sensor 14" Model MA193-14-BK
®
Sensor 24" (waterproof - IP67) Model A196-24-BK
Technical Assistance (800) 343-1391
** AC/DC Current Probe BNC Adapter
for Model SL261 only
Catalog #2140.40
www.aemc.com
Page 5
DATAVIEW®
Software for Power & Energy Loggers
Data Analysis and Reporting Software
Configure all functions of the Power & Energy Loggers
• Display and analyze real-time data on your PC
• Configure functions and parameters from your PC
• Customize views, templates and reports to your exact needs
• Create and store a complete library of configurations that
can be uploaded as needed
• Zoom in and out and pan through sections of the graph to