Ademco W8735ER01 User Manual

66-1202-01
W8735ER Wireless Outdoor Reset
CAUTION
Module
INSTALLATION INSTRUCTIONS

FEATURES

• RedLink™ wireless communication protocol
• Fast wireless connection to outdoor sensor
• Enables Boiler Outdoor Temperature Reset
• Enables Warm Weather Shutdown
• Enables Boost Override
• Simple low-voltage, 3-wire installation to combustion control (3 EnviraCOM)
• EnviraCOM™/RedLink Enabled

INSTALLATION

APPLICATION

The W8735ER Wireless Outdoor Reset Module, when connected to the C7089R1013 Wireless Outdoor Sensor, works with any AquaReset enabled Aquastat® such as the L7224/48 Aquastat, S9360/61/80 Integrated Boiler Control, and R7910 SOLA Control via the EnviraCOM™ 3-wire bus. The Wireless Outdoor Reset Module enables efficiency control functionality, such as Outdoor Temperature Reset, Boost function, and Warm Weather Shutdown function to generate average operational savings of up to 15%.

SPECIFICATIONS

Electrical Ratings: Voltage: 24 Vac, 60 Hz.
Environmental Ratings:
Temperature: -30 °F to +150 °F (-34 °C to +66 °C). Humidity: 0 to 95% relative humidity, non-condensing.
Accessories (Can be ordered separately):
C7089R1013 Wireless Outdoor Temperature Sensor

When Installing this Product...

1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi­tion.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your application.
3. The installer must be a trained, experienced service
technician.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
5. The Outdoor Reset Module can be wall mounted in any
orientation desired or dictated by the surroundings.
6. The holes are sized for the #6 sheet metal screws
(included).
7. Precise leveling of the product is not required.
W8735ER WIRELESS OUTDOOR RESET MODULE
CAUTION
CAUTION
M33912
5-9/16
(141)
5-1/32
(128)
1-1/4
(32)
4-9/16
(116)
4-13/32
(112)
X 3 2 1
W8735ER1000
Wireless
Outdoor Reset Module
POWER
WIRELESS SETUP
CONNECTED
CONNECT
FLASHING: CONNECTING TO REMOTE DEVICE(S)
GREEN: CONNECTED TO REMOTE DEVICES(S)
RED: REMOTE DEVICE(S) NOT COMMUNICATING
EnviraCOM
BUS
3 2 1
EnviraCOM
ENABLED CONTROL
M28849A

WIRING

Do not mount the W8735ER on a metallic surface as this can interfere with reception.
Electrical Interference (Noise) Hazard. Can cause erratic system operation.
Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels. Use shielded cable to reduce interference when rerouting is not possible.
1. Disconnect power.
2. Mount the Wireless Outdoor Temperature Control Mod-
ule with the supplied hardware.
3. Wire the 1, 2, and 3 terminals on the Outdoor Reset
Module to the 1, 2, and 3 terminals on the EnviraCOM™ enabled thermostat (if available), Aquastat, Integrated Burner Control, SOLA, or anywhere on the bus where access to the EnviraCOM bus is available and conve­nient. See Fig. 1.
4. Turn power on.
5. Bind the C7089R Wireless Outdoor Sensor to the Wire-
less Outdoor Reset Module. See “Sensor Binding” on page 3.

C7089R INSTALLATION

Mount Outdoor Sensor

Before installing the C7089 sensor, make sure 2 AA (lithium preferred) batteries are inserted. See Fig. 2.
M32937
Fig. 2. Battery Installation
1. Mount the sensor bracket on a vertical wall. at least 6
inches below any overhang. Choose a location pro­tected from direct sunlight. See Fig. 3.
Fig. 1. W8735ER Wireless Outdoor Reset Module wiring
diagram.
M28491
Fig. 3. Mounting the Sensor Bracket and Sensor
2. Mount the sensor bracket in the selected spot.
3. Once the sensor is bound to the W8735ER (see SEN-
SOR BINDING), place the sensor in the bracket, facing away from the wall.
66-1202—01 2
W8735ER WIRELESS OUTDOOR RESET MODULE

Sensor Binding

The C7089R Outdoor Sensor must be bound with the W8735ER Wireless Outdoor Reset Module in order for communication between the two controls to be established.
When the W8735ER Wireless Outdoor Temperature Module is powered but not bound to a sensor, the POWER LED will be ON (green) and the CONNECTED LED will be OFF.
1. Remove the cover from the C7089R to expose the
CONNECT button.
2. Press the CONNECT button on the W8735ER until the
CONNECTED LED flashes green (1 blink/second) after approximately five seconds of flashing red. If the sensor is not bound within the next 15 minutes the W8735ER times out and the CONNECTED LED will turn OFF.
3. While the CONNECTED LED flashes green on the
W8735ER, press the CONNECT button on the C7089R sensor.
4. The CONNECTED LED will start to blink fast (4 blinks/
second).
NOTE: If flashing doesn’t speed up to 4 blinks/second,
the sensor and the W8735ER have not bound. Repeat step 4. If binding is not successful during a 15 minutes period, the W8735ER will time out. Repeat steps 2 through 4. Make sure the W8735ER and the sensor are positioned at least 3 feet apart during the binding process.
5. Once the flashing rate goes back to 1 blink/second,
press the CONNECT button on the W8735ER to end the binding process.
6. Once the C7089R sensor and the W8735ER bind, the
CONNECTED LED on the W8735ER will be ON solid (green).
7. Place sensor cover back on the sensor and return the
sensor to the bracket. See Fig. 3.
NOTE: Pressing the CONNECT button on either the
W8735ER or wireless sensor for 15 seconds or more will result in the unbinding of the wireless sensor and deactivation of the OTC functionality. To rebind the sensor to the W8735ER follow steps 1-7 in this section.
NOTES:
If the W8735ER is bound to a sensor but the sen-
sor signal is lost, the CONNECTED LED will be ON (red).
Once the sensor is bound to the W8735ER and
the module is connected to the EnviraCOM com­munication bus as described in the WIRING sec­tion of this document, hold the sensor where you intend to install it and check for the outdoor tem­perature to be displayed on the combustion con­trol. If the outdoor temperature is not displayed, change the positioning of the sensor.
If the W8735ER is not successfully bound to
C7089R within five minutes of power up, the W8735ER will generate a missing sensor alarm. See Table 6 for a complete listing of EnviraCOM alarms and trobuleshooting guide.