Before and during installation, keep in mind these sources of potential problems:
• Faulty cabling/connector
• Dirty connectors and ports
• Malfunction of one or more Fusion components
• Antenna, base station, or repeater problem
• External RF interface
• Tripped circuit breaker
• Equipment is not grounded
• Using a crossover Ethernet cable that does not support full hardware handshaking
when using AdminBrowser
InterReach Fusion Installation, Operation, and Reference Manual7-1
CONFIDENTIAL
Installation Requirements
7.1.1Component Location Requirements
7.1.2Cable and Connector Requirements
NOTE: Faulty cabling is the cause of a vast majority of problems. All CATV cable
should be tested to TIA-570-B specifications.
Fusion components are intended to be installed in indoor locations only.
If outdoor installation is desired, such as a parking garage, the Fusion components
must be installed in the appropriate environmental enclosures.
Fusion equipment operates over the following:
• CATV 75 Ohm cable with F connectors
• Single-mode fiber (SMF) or multi-mode (MMF) cable with SC/APC fiber connectors throughout the fiber network, including fiber distribution panels
These cables are widely-used, industry standards for the cable TV industry. The regulations and guidelines for Fusion cable installation are identical to those specified by
the TIA/EIA 568-B standard and the TIA/EIA/570-A standards.
LGC Wireless recommends solid copper center conductor, plenum-rated CATV cable
and connectors for conformity to building codes, standards, and to ensure stated performance of maximum distance and RF specifications.
CommScope 2065V cable or equivalent is required for RG-59.
CommScope 2279V cable or equivalent is required for RG-6.
CommScope 2293K cable may also be used for RG-11.
NOTE: Refer to Appendix A for more information related to 75 Ohm
CATV.
LGC Wireless recommends connectors with fixed centerpins to ensure proper seating
and to eliminate oxidation, which occurs with bare center conductors. Recommended
connectors are as follows:
CANARE Connectors
• FP-C4F for commScope 2065V cable
• FP-C55A for CommScope 2279V cable
• FP-C71A for CommScope 2293K cable
7-2InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
NOTE: The proper crimp tool and die must be matched by the connector
type.
7.1.3Distance Requirements
Table 7-1 shows the distances between Fusion components and related equipment.
Safety Precautions
Table 7-1
Equipment
CombinationCable TypeCable LengthAdditional Information
Repeater/BTS to
Fusion Main Hub
Fusion Expansion
Hub to RAU
Main Hub to Expansion Hub
RAU to passive
antenna
Coaxial; N male
connectors
CATV 75 Ohm;
shielded F male connectors
Multi-mode fiber:
Single-mode fiber:
SC/APC male connectors
Coaxial; N male
connectors
Distance Requirements
3–6 m (10–20 ft) typicalLimited by loss and noise.
Refer to your link budget
calculation.
10 m (33 ft) maximumLimited by CE Mark require-
ments.
• Minimum: 10 meters (33 ft)
• Maximum:
150 meters (492 ft) for RG-59;
170 meters (558 ft) for RG-6;
275 meters (902 ft) for RG-11
Refer to Table 5-1 and Table 5-2.
500 m (1640 ft.) maximum
6 km (19,685 ft.) maximum
1–3.5 m (3–12 ft) typicalLimited by loss and noise.
Refer to “System Gain” on
page 6-11.
Limited by 3 dB optical
attenuation
Refer to your link budget
calculation.
D-620610-0-20 Rev A
7.2Safety Precautions
7.2.1Installation Guidelines
Use the following guidelines when installing LGC Wireless equipment:
1.
Provide sufficient airflow and cooling to the equipment to prevent heat build-up
from exceeding the maximum ambient air temperature specification. Do not compromise the amount of airflow required for safe operation of the equipment.
2.
If you are removing the system, turn it off and remove the power cord first. There
are no user-serviceable parts inside the components.
Help Hot Line (U.S. only): 1-800-530-99607-3
CONFIDENTIAL
Safety Precautions
3.
The internal power supplies have internal fuses that are not user replaceable. Consider the worst-case power consumption shown on the product labels when provisioning the equipment’s AC power source and distribution.
4.
Verify that the Hub is grounded properly using the AC power cord third wire
ground.
NOTE: Be careful with the mechanical loading of the rack mounted hub.
Mount the equipment in the rack in such a way that a hazardous condition,
due to uneven mechanical loading, does not result,.
7.2.2General Safety Precautions
The following precautions apply to LGC Wireless products:
• The units have no user-serviceable parts. Faulty or failed units are fully replaceable
through LGC Wireless. Please contact us at:
• Although modeled after an Ethernet/LAN architecture and connectivity, the units
are not intended to connect to Ethernet data hubs, routers, cards, or other similar
data equipment.
• When you connect the fiber optic cable, take the same precaution as if installing
Ethernet network equipment. All optical fiber SC/APC connectors should be
cleaned according to the cable manufacturer’s instructions.
• When you connect a radiating antenna to an RAU, firmly hand-tighten the N connector – DO NOT over-tighten the connector.
WARNING: To reduce the risk of fire or electric shock, do not
expose this equipment to rain or moisture. The components are
intended for indoor use only. Do not install the RAU outdoors. Do not
connect an RAU to an antenna that is located outdoors where it could
be subject to lightning strikes, power crosses, or wind.
• The Expansion Hub and RAU units are designed for intra-building cabling only.
Outdoor routing of any cabling to these units shall not exceed 140 feet.
NOTE: Outdoor cables farther than 140 feet must be installed with proper
lightning protection.
7-4InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
7.2.3Fiber Port Safety Precautions
This mark appears on the front panel of the
Main Hub and the Expansion Hub.
CLASS1
LASERPRODUCT
CLASS 1
LASER PRODUCT
The following are suggested safety precautions for working with fiber ports. For
information about system compliance with safety standards, refer to Appendix B.
WARNING: Observe the following warning about viewing fiber
ends in ports. Do not stare with unprotected eyes at the connector
ends of the fibers or the ports of the hubs. Invisible infrared radiation is present at the front panel of the Main Hub and the Expansion
Hub. Do not remove the fiber port dust caps unless the port is going
to be used. Do not stare directly into a fiber port.
• Test fiber cables: When you test fiber optic cables, connect the optical power
source last and disconnect it first. Use Class 1 test equipment.
• Fiber ends: Cover any unconnected fiber ends with an approved cap. Do not use
tape.
• Broken fiber cables: Do not stare with unprotected eyes at any broken ends of the
fibers. Laser light emitted from fiber sources can cause eye injury. Avoid contact
with broken fibers; they are sharp and can pierce the skin. Report any broken fiber
cables and have them replaced.
• Cleaning: Be sure the connectors are clean and free of dust or oils. Use only
approved methods for cleaning optical fiber connectors.
• Modifications: Do not make any unauthorized modifications to this fiber optic
system or associated equipment.
• Live work: Live work is permitted because LGC Wireless equipment is a Class 1
hazard.
• Signs: No warning signs are required.
Safety Precautions
D-620610-0-20 Rev A
• Class 1 laser product: The system meets the criteria for a Class 1 laser product
per IEC 60825-1: 1993+A1:+A2:2001 and IEC106825-2.
Complies with 21 CFR 1040.10 and 1040.11 except for deviations pursuant to
Laser Notice No. 50, dated July 26, 2001.
The hazard level at all locations within the equipment is Hazard Level 1.
• CAUTION: Use of controls or adjustments or performance of procedures other
than those specified herein may result in hazardous radiation exposure.
Help Hot Line (U.S. only): 1-800-530-99607-5
CONFIDENTIAL
Preparing for System Installation
7.3Preparing for System Installation
7.3.1Pre-Installation Inspection
7.3.2Installation Checklist
Follow this procedure before installing Fusion equipment:
1.
Verify the number of packages received against the packing list.
2.
Check all packages for external damage; report any external damage to the shipping carrier. If there is damage, a shipping agent should be present before you
unpack and inspect the contents because damage caused during transit is the
responsibility of the shipping agent.
3.
Open and check each package against the packing list. If any items are missing,
contact LGC Wireless customer service (refer to Section 7.2.2 on page 7-4).
4.
If damage is discovered at the time of installation, contact the shipping agent.
Table 7-2
Installation RequirementConsideration
Floor PlansInstallation location of equipment clearly marked
System DesignUsed to verify frequency bands after installation
Power available:
Fusion Main Hub (AC)
Fusion Expansion Hub (AC)
To RAU (DC)
Rack space available
(Main and Expansion Hub)
Wallmount Fusion Main HubHub must be mounted on 3/4” plywood backboard.
Clearance for air circulation:
Fusion Main or Expansion Hub
RAU
Suitable operating environment:
Fusion Main or Expansion Hub
RAUs
Donor Antenna-to-Fusion Configuration (for each Fusion Band)
Donor AntennaInstalled, inspected; N-male to N-male coaxial cable to lightning arrestor/surge
Lightning Arrestor or
Surge Suppressor
RepeaterInstalled between lightning arrestor/surge suppressor and Hub; N-male to N-male
Installation Checklist
Hub’s power cord is 2 m (6.5 ft) long.
115/230V, 2/1A, 50–60 Hz
115/230V, 6/3A, 50-60 Hz
54V (from the Hub)
89 mm (3.5 in.) high (2U)
76 mm (3 in.) front and rear, 51 mm (2 in.) sides
76 mm (3 in.) all around
Indoor location only
0° to +45°C (+32° to +113°F)
5% to 95% non-condensing humidity
–25° to +45°C (–13° to +113°F)
5% to 95% non-condensing humidity
suppressor
Installed between roof-top antenna and repeater; N-male to N-male 50 Ohm coaxial cable and outdoor cables longer than 140 feet.
coaxial cable. The Repeater must be a UL listed product.
7-6InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Preparing for System Installation
Table 7-2
Installation RequirementConsideration
Installation Checklist (continued)
AttenuatorInstalled between the circulator and the Hub downlink port to prevent overload.
Optionally, it may be installed between the uplink port and the circulator.
Circulator or DuplexerInstalled between the repeater and the Hub uplink and downlink ports
Base Station-to-Fusion Configuration (for each Fusion Band)
Base StationInstalled, inspected; verify RF power (see tables in Section 6.3 on page 6-4);
N-male to N-male coaxial cable
AttenuatorAttenuation may be required to achieve the desired RF output at the RAU, and the
desired uplink noise floor level
Circulator or DuplexerWhen using a duplex BTS: Installed between the BTS and the Hub uplink and
downlink ports. Not used with a simplex BTS
Connecting Multiple Fusion Main Hubs Together
5-port Alarm Daisy-Chain Cable
(PN 4024-3)
For contact alarm monitoring of fault and warning alarms. Used to feed the alarms
from multiple Fusion Main Hubs into a BTS or MetroReach Focus. N.C. Operation.
Cabling
Coaxial: repeater, base station,
Coax approved; N-type male connectors.
Smart Source to Fusion Main
Hub
Coaxial: RAU to passive
antennas
Fiber: Main Hub to Expansion
Hubs
Use low-loss cable; N male connector; typical 1 m (3.3 ft) using RG142 coaxial
cable.
SC/APC (angle-polished) male connectors for entire fiber run (can use SC/APC
pigtails, PN 4012SCAPC-10 for MMF or 4013SCAPC-10 for SMF);
Use jumper fiber cables for collocated Main and Expansion Hubs (3 m/10 ft.):
7-8InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
7.3.4Optional Accessories
Preparing for System Installation
Table 7-4
Optional Accessories for Component Installation
Description
Wall-mount bracket (PN 4712)
When using this bracket with an Fusion Main Hub, the Hub’s mounting bracket must
be moved to the alternate mounting position (refer to the procedure on page
page 7-11).
Cable management (Cable manager: PN 4759; Tie wrap bar: PN 4757)
Jumper cable when Main and Expansion Hubs are collocated, 3 m (10 ft.)
Multi-mode fiber SC/APC: PN 4018SCAPC-10
Teltone Line Sharing Switch (M-394-B-01)
When using a single POTS line with multiple Fusion Main Hub/Modems: Connect up
to four modems to a line sharing switch; switches can be cascaded to accommodate up
to 16 modems per POTS line
The following procedures assume that the system is new from the factory and that it
has not been programmed with bands.
If you are replacing components in a pre-installed system with either new units or
units that may already be programmed (for example, re-using units from another system), refer to Section 8.
CAUTION: Install Fusion Main Hubs in indoor locations only.
Installing a Fusion Main Hub in a Rack
The Fusion Main Hub (2U high) mounts in a standard 19 in. (483 mm) equipment
rack. Allow clearance of 76 mm (3 in.) front and rear, and 51 mm (2 in.) on both sides
for air circulation. No top or bottom clearance is required.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-11
CONFIDENTIAL
Fusion Installation Procedures
Figure 7-1
Flush Mounting Bracket Detail
Consideration:
• The Fusion Main Hub is shipped with #10-32 mounting screws. Another common
rack thread is #12-24. Confirm that the mounting screws match the rack’s threads.
To install the Hub in a rack:
1.
Insert spring nuts into rack where needed or use existing threaded holes.
2.
Place the Hub into the rack from the front.
3.
Align the flange holes with the spring nuts installed in Step 1.
4.
Insert the mounting screws in the appropriate positions in the rack.
5.
Tighten the mounting screws.
Installing an Optional Cable Manager in the Rack
• Using the screws provided, fasten the cable manager to the rack, immediately
above or below the Main Hub.
Installing a Main Hub Using the 12” Wall-Mounted Rack (PN 4712)
Considerations:
• The rack-mounting brackets on the Fusion Main Hub must be moved to the
recessed mounting position (shown in Figure 7-2) to allow for the required 76 mm
(3 in.) rear clearance.
7-12InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
• The maximum weight the bracket can hold is 22.5 kg (50 lbs).
• The bracket is designed to accommodate a Fusion Main Hub (12 lbs.) or an Expansion Hub (14.5 lbs.).
• The wall mount bracket should be securely mounted to wall, using the four key slot
mounting holes on the bracket.
Using the Wall Rack-Mounting Option
You can flip the rack mounting brackets, as shown in Figure 7-2, so the hub can be
mounted 76 mm (3 in.) forward in the rack.
Figure 7-2
Bracket Detail For Wall Mount Rack (PN 4712)
To install the Hub to the wall-mounted rack:
1.
Attach the wall bracket (PN 4712) to wall the using #10 Pan Head wood screws,
1-1/2” minimum length for mounting in wood studs or 3/4“thick plywood.
The bracket must be positioned so that the Hub will be in a horizontal position
when it is installed. (Refer to Figure 7-2.)
D-620610-0-20 Rev A
NOTE: If wall stud spacing of 16” is not available, LGC recommends that
3/4” plywood be pre-installed to the wall. You can then attach the bracket to
the plywood using the wood screws.
2.
Remove both of the rack mounting brackets from the Hub.
3.
Reattach each of the rack mounting brackets to the recessed wall mount position.
4.
Install the Hub in the rack using the rack mounting screws.
Help Hot Line (U.S. only): 1-800-530-99607-13
CONFIDENTIAL
Fusion Installation Procedures
Installing a Fusion Main Hub Directly to the Wall
To install the Hub directly to the wall:
1.
Pre-install 3/4” plywood to the wall.
2.
Mount both of the rack mounting brackets using #10-32 machine screws (refer to
illustration Figure 7-4).
3.
Attach the Hub to the wall so the mounting brackets are orientated at the top and
bottom of the wall mounted hub. (Refer to Figure 7-3.)
Figure 7-3
Installing Directly to the Wall
Use two #10 Pan Head wood screws, 1-1/2” length, to secure each bracket to the
plywood. In this orientation the enclosure fans shall face to the left.
7-14InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
Figure 7-4
Using Hub Rack-Mounting Brackets for Direct Wall Installation
Connecting the Fiber Cables to the Main Hub
Considerations:
• Before connecting the fiber cables, confirm that their optical loss does not exceed
the 3 dB optical budget.
• If you are using fiber distribution panels, confirm that the total optical loss of fiber
cable, from the Main Hub through distribution panels and patch cords to the
Expansion Hub, does not exceed the optical budget.
• Make sure the fiber cable’s connectors are SC/APC (angle-polished). Using any
other connector type will result in degraded system performance and may damage
the equipment. (You can use an SC/APC pigtail if the fiber cable’s connectors are
not SC/APC. Refer to“Fusion Splicing of Fiber and Pigtail” on page 7-37. Or, you
can change the fiber’s connector to SC/APC.)
NOTE: Observe all Fiber Port Safety Precautions listed in Section 7.2.3 on page 7-5.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-15
CONFIDENTIAL
Fusion Installation Procedures
To clean the fiber ports:
You can clean the Hub’s fiber ports using canned compressed air or isopropyl alcohol
and foam tipped swabs.
Considerations:
• If using compressed air:
• The air must be free of dust, water, and oil.
• Hold the can level during use.
• If using isopropyl alcohol and foam tipped swabs:
• Use only 98% pure or more alcohol
Procedure using compressed air:
1.
Remove the port’s dust cap.
2.
Spray the compressed air away from the unit for a few seconds to clean out the
nozzle and then blow dust particles out of each fiber port.
Procedure using isopropyl alcohol:
1.
Remove the connector’s dust cap.
2.
Dip a 2.5mm lint-free, foam-tipped swab in isopropyl alcohol and slowly insert
the tip into the connector.
3.
Gently twist the swab to clean the port.
4.
Insert a dry swab into the port to dry it.
Additionally, you can use compressed air after the alcohol has completely evaporated.
To clean the fiber ends:
Be sure that the fiber cable’s SC/APC connectors are clean and free of dust and oils.
You need lint-free cloths, isopropyl alcohol, and compressed air
1.
Moisten a lint-free cloth with isopropyl alcohol.
2.
Gently wipe the fiber end with the moistened cloth.
3.
Using a dry lint-free cloth, gently wipe the fiber end.
4.
Spray the compressed air away from the connector for a few seconds to clean out
the nozzle and then use it to completely dry the connector.
To test the fiber cables:
Perform cable testing and record the results. Test results are required for the final
As-Built Document.
To connect the fiber cables:
The fiber cable is labeled with either 1 or 2, or is color-coded. In addition to these
labels, you should add a code that identifies which port on the Main Hub is being
7-16InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
used and which Expansion Hub the cables are intended for. This differentiates the
connectors for proper connection between the Main Hub and Expansion Hubs.
For example:
First pair to Main Hub port 1: 11 (uplink), 12 (downlink);
Second pair to Main Hub port 2: 21 (uplink), 22 (downlink);
Third pair to Main Hub port 3: 31 (uplink), 32 (downlink); and so on.
If the fiber jumper is labeled with 1 or 2:
1.
Connect 1s to
2.
Connect 2s to
3.
Record which cable number and port number you connected to
DOWNLINK
UPLINK
DOWNLINK
.
ports on the Main Hub.
ports on the Main Hub.
UPLINK
and
This information is needed when connecting the other end of the fiber cable to the
Expansion Hub’s fiber ports.
The fiber port LEDs should be off, indicating that the Expansion Hub(s) are not
connected.
If the fiber jumper is color-coded (for example, “blue” or “red”):
1.
Connect “blue” to
2.
Connect “red” to
3.
Record which color and port number you connected to
UPLINK
ports on the Main Hub.
DOWNLINK
ports on the Main Hub.
UPLINK
and
DOWNLINK
This information is needed when connecting the other end of the fiber cable to the
Expansion Hub’s fiber ports.
The fiber port LEDs should be off, indicating that the Expansion Hub(s) are not
connected.
.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-17
CONFIDENTIAL
Fusion Installation Procedures
Powering On the Main Hub
1.
Connect the AC power cord to the Main Hub.
2.
Plug the power cord into an AC power outlet.
3.
Turn on the power to the Main Hub and check that all the LED lamps are functioning properly.
Upon power-up, the LEDs blinks for five seconds as a visual check that they are
functioning. After the five-second test:
LED states during power on will vary, depending on whether Expansion Hubs are
connected. Refer to Table 7-5 for possible combinations.
Table 7-5
Troubleshooting Main Hub LEDs During Installation
During
Installation
Power OnLEDStateActionImpact
1.
Main Hub
power is
On with no
Expansion
Hubs connected.
POWER
POWER
PORT
OffCheck AC power; check that the Main Hub power-on
switch is on; replace the Main Hub
The Main Hub is not
powering on.
RedReplace the Main HubThe power supply is
out-of-specification.
LEDs are on
but they
didn’t blink
through all
Replace the Main Hub.The micro controller is
not resetting properly;
flash memory corrupted.
states
PORT
RedThe port is unusable; replace the Main Hub when
Off
possible.
Fiber sensor fault, do
not use the port.
7-18InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
Table 7-5
Troubleshooting Main Hub LEDs During Installation (continued)
During
Installation
Power OnLEDStateActionImpact
2.
Main Hub
power is
On with
Expansion
Hubs connected and
powered
on.
PORT
Off• If the port LEDs do not illuminate, check the fiber
uplink for excessive optical loss.
• If Expansion Hub’s
DL STATUS
LED is red:
• Verify that the fiber is connected to the correct
port (that is, uplink/downlink)
• Swap the uplink and downlink cables.
• Connect the fiber pair to another port. If the sec-
No uplink optical
power, the Expansion
Hub is not recognized
as being present.
No communication
with the Expansion
Hub.
ond port’s LEDs do not illuminate Green/Red,
replace the Main Hub.
• If the second port works, flag the first port as
unusable; replace the Main Hub when possible.
PORT
Red (60 ppm)• If the Expansion Hub
check the downlink fiber cable for excessive optical loss.
DL STATUS
LED is red,
No communication
with the Expansion
Hub.
• Connect the fiber pair to another port. If the second port’s LEDs do not illuminate Green/Red,
replace the Main Hub.
• If the second port works, flag the first port as
unusable; replace the Main Hub when possible.
PORT
RedThe Expansion Hub or connected RAU reports a fault
Use AdminManager to determine the problem.
The Expansion Hub or
one or more RAUs are
off-line.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-19
CONFIDENTIAL
Fusion Installation Procedures
7.4.2Installing Expansion Hubs
The Expansion Hub (2U high) can be installed in a standard 19 in. (483 mm) equipment rack or in a wall-mountable equipment rack that is available from LGC Wireless. Allow a clearance of 76 mm (3 in.) front and rear and 51 mm (2 in.) sides for air
circulation. No top and bottom clearance is required.
CAUTION: Install Expansion Hubs in indoor locations only.
Installing an Expansion Hub in a Rack
Consideration:
• The Expansion Hub is shipped with #10-32 mounting screws. Another common
rack thread is #12-24. Confirm that the mounting screws match the rack’s threads.
Figure 7-5
Flush Mounting Bracket Detail
To install the hub in a rack:
1.
Insert spring nuts into the rack where needed or use existing threaded holes.
2.
Place the Expansion Hub into the rack from the front.
3.
Align the flange holes with the spring nuts installed in Step 1.
4.
Insert the mounting screws in the appropriate positions in the rack.
5.
Tighten the mounting screws.
7-20InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
Installing an Expansion Hub Using the 12” Wall-Mounted Rack
Considerations:
• The rack (PN4712) is 305 mm (12 in.) deep. The Expansion Hub is 381 mm (15
in.) deep. You must move the rack mounting brackets on the Expansion Hub, as
shown in Figure 7-6) to the center mounting position to allow for the 76 mm (3 in.)
rear clearance that is required.
• The maximum weight the rack can hold is 22.5 kg (50 lbs).
Figure 7-6
Bracket Detail For Wall Mount Rack (PN 4712)
To install the hub in a wall-mounted rack:
1.
Attach the equipment rack to the wall using the screws that are provided.
The rack must be positioned so that the Expansion Hub will be in a horizontal
position when it is installed.
D-620610-0-20 Rev A
NOTE: If wall stud spacing of 16” is not available, LGC recommends that
3/4” plywood be pre-installed to the wall. You can then attach the bracket to
the plywood using the wood screws.
2.
Remove both of the rack mounting brackets from the Hub.
3.
Reattach each of the rack mounting brackets to the recessed wall mount position
(Figure 7-6).
4.
Install the Hub in the rack using the rack mounting screws.
5.
Tighten the mounting screws.
Help Hot Line (U.S. only): 1-800-530-99607-21
CONFIDENTIAL
Fusion Installation Procedures
Installing a Fusion Expansion Hub Directly to the Wall
To install the Hub directly to the wall:
1.
Pre-install 3/4” plywood to the wall.
2.
Mount both of the rack mounting brackets using #10-32 machine screws (refer to
illustration Figure 7-7).
3.
Attach the Hub to the wall so the mounting brackets are orientated at the top and
bottom of the wall mounted hub. (Refer to Figure 7-8.)
Figure 7-7
Using Hub Rack-Mounting Brackets for Direct Wall Installation
7-22InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
Figure 7-8
Installing Directly to the Wall
D-620610-0-20 Rev A
NOTE: Leave the dust caps on the fiber ports until you are ready to connect the fiber
optic cables.
Installing an Optional Cable Manager in the Rack
• Using the screws provided, fasten the cable manager to the rack, immediately
above or below the Expansion Hub.
Powering On the Expansion Hub
1.
Connect the AC power cord to the Expansion Hub.
2.
Plug the power cord into an AC power outlet.
Help Hot Line (U.S. only): 1-800-530-99607-23
CONFIDENTIAL
Fusion Installation Procedures
3.
Turn on the power to the Expansion Hub and check that all the LED lamps are
functioning properly.
Upon power-up, the LEDs blinks for five seconds as a visual check that they are
functioning. After the five-second test:
• The
POWER
and
UL STATUS
LEDs should be green.
– If the uplink fiber is not connected, the
UL STATUS
LED turns red indicating
that there is no communication with the Main Hub.
• The
E-HUB STATUS
and
DL STATUS
LEDs should be red.
• All port LEDs should be off because no RAUs are connected yet.
Connecting the Fiber Cables to the Expansion Hub
Considerations:
• Before connecting the fiber cables, confirm that their optical loss does not exceed
3 dB optical budget. RL is less than -60dB.
• If fiber distribution panels are used, confirm that the total optical loss of fiber
cable, from the Main Hub through distribution panels and patch cords to the
Expansion Hub, does not exceed the optical budget.
• Make sure the fiber cable’s connectors are SC/APC (angle-polished).Using any
other connector type will result in degraded system performance and may damage
the equipment. (You can use an SC/APC pigtail if the fiber cable’s connectors are
not SC/APC, refer to “Fusion Splicing of Fiber and Pigtail” on page 7-37, or
replace the connectors.)
NOTE: Observe all Fiber Port Safety Precautions listed in Section 7.2.3 on page 7-5.
To connect the fiber cables:
The fiber cable is labeled with either 1 or 2, or is color-coded. For proper connection
between the Main Hub ports and the Expansion Hub ports, refer to the numbering or
color-coded connections you recorded when installing the Main Hub(s).
If the fiber jumper is labeled with 1 or 2:
1.
Connect 2 to
The
DL STATUS
not, there is a downlink problem. Make sure you are connecting the correct cable
to the port.
2.
Connect 1 to
The
UL STATUS
take up to 20 seconds to establish communication.
The Expansion Hub’s
it the frequency band command.
7-24InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
DOWNLINK
on Expansion Hub.
LED should turn green as soon as you connect the fiber. If it does
UPLINK
on Expansion Hub.
LED turns green on the first Main Hub communication. It may
E-HUB STATUS
LED turns green when the Main Hub sends
D-620610-0-20 Rev A
Fusion Installation Procedures
If the
UL STATUS
and
E-HUB STATUS
LEDs do not turn green/green, check the
Main Hub LEDs. Refer to page 7-18, item 2 in Table 7-5.
If the fiber jumper is color-coded (for example, “blue” or “red”):
1.
Connect “red” to
The
DL STATUS
DOWNLINK
on Expansion Hub.
LED should turn green as soon as you connect the fiber. If it does
not, there is a downlink problem. Make sure you are connecting the correct cable
to the port.
2.
Connect “blue” to
The
UL STATUS
UPLINK
on Expansion Hub.
LED turns green on the first Main Hub communication. It may
take up to 20 seconds to establish communication.
The Expansion Hub’s
E-HUB STATUS
LED turns green when the Main Hub sends
it the frequency band command.
If the
UL STATUS
and
E-HUB STATUS
LEDs do not turn green/green, check the
Main Hub LEDs. See page 7-18, item 2 in Table 7-5.
Connecting the 75 Ohm CATV Cables
Considerations:
• Verify that the cable has been tested and the test results are recorded. This information is required for the As-Built Document.
• Verify that only captive centerpin F connectors are used on the solid copper center
conductor CATV cable from CommScope (or equivalent).
• Verify that the CATV cable is labeled with:
• Fusion Expansion Hub port number being used
• RAU identifier
• Carrier (for multiple operator systems)
To connect the CATV cables:
1.
Connect the CATV cables to the F ports according to the labels on the cables.
The
STATUS
LEDs should be off because the RAUs are not connected at the other
end of the CATV cable.
2.
Record which cable you are connecting to which port (that is, from the label on
the cable).
This information is required for the As-Built Document.
3.
Tie-off the cables or use the optional cable manager to avoid damaging the connectors because of cable strain.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-25
CONFIDENTIAL
Fusion Installation Procedures
Troubleshooting Expansion Hub LEDs During Installation
• All Expansion Hub
PORT
LEDs with RAUs connected should indicate Green/Red.
This indicates that the RAU is powered on and communication has been established.
• The Expansion Hub
Table 7-6
During
InstallationLEDStateActionImpact
1.
Expansion
POWER
OffCheck AC power; make sure the
Hub power
is On and no
RAUs are
connected
PORT
LEDs are on but
didn’t blink through
all states.
PORT
Flashing Red
(6 PPM)
UL STATUS
Red, after power-up
blink
2.
Expansion
UL STATUS
DL STATUS
PORT
Red
RedCheck the downlink fiber for opti-
OffCheck the CATV cable.Power is not getting to the
Hub power
is On and
RAUs are
PORT
Flashing Red
(60 PPM)
connected
PORT
RedUse AdminBrowser to determine
Troubleshooting Expansion Hub LEDs During Installation
UL STATUS
LED should be Green.
The Expansion Hub is not
Expansion Hub power-on switch
powering on.
is on; replace the Expansion Hub.
Replace the Expansion Hub.The Microcontroller is not
resetting properly; flash
memory corrupted.
Port unusable; replace the Expansion Hub when possible.
Current sensor fault; do not
use the port.
Replace the Expansion Hub.The Expansion Hub laser is
not operational; no uplink
between the Expansion Hub
and Main Hub.
Check the Main Hub LEDs
Refer to page 7-18, item 2 in
No communication with
Main Hub.
Table 7-5.
Use AdminBrowser to determine
the problem.
No downlink between the
cal power; verify that the cables
are connected to correct ports
Expansion Hub and Main
Hub.
(that is, uplink/downlink)
Check the Main Hub LEDs. Refer
to page 7-18, item 2 in Table 7-5.
RAU.
Test the CATV cable. If the cable
tests OK, try another port. If the
second port’s LEDs are Red/Off,
replace the RAU. If the second
RAU doesn’t work; replace the
Expansion Hub.
Power levels to RAU are not
correct; communications are
not established.
If the second port works, flag
the first port as unusable;
replace EH when possible.
RAU is off-line.
the problem.
7-26InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
7.4.3Installing RAUs
CAUTION: Install RAUs in indoor locations only. Do not con-
nect an antenna that is installed in an outdoor location to an RAU.
For outdoor installations, a protective enclosure is required.
Installing RAUs
Mount all RAUs in the locations marked on the floor plans.
Considerations:
• Install 800 iDEN and 850/1900 MHz RAUs so that their antennas will be separated
by enough space to reduce signal interference between the 800 and 850 bands.
Refer to Section , “800/850 MHz Isolation Requirements,” on page 7-27 for recommended distance between antennas.
• You can place the unit, without its fastening hardware, on a flat surface, such as a
shelf, desk, cabinet, or any other horizontal surface that allows stable placement
with the mounting base facing down to the mounting surface. For mounting to
other locations (that is, walls, ceilings, poles) the RAU must be securely mounted
using the 4 slotted mounting holes provided with #6 diameter fasteners. This
method of mounting must securely hold a minimum of 7 lbs. load.
• Attach the RAU securely to a stationary object (that is, a wall, pole, or ceiling tile).
• For proper ventilation:
• Keep at least
• Do not stack RAUs on top of each other.
• Always mount the RAU with the solid face (containing the mounting holes)
against the mounting surface.
76 mm (3 in.)
Fusion Installation Procedures
clearance around the RAU to ensure proper venting.
D-620610-0-20 Rev A
Installing Passive Antennas
Refer to the manufacturer’s installation instructions to install passive antennas.
Location
Passive antennas are usually installed below the ceiling. If they are installed above
the ceiling, you must consider the additional loss due to the ceiling material when
estimating the antenna coverage area.
800/850 MHz Isolation Requirements
When deploying any RF system, give special attention to preventing receiver blocking or desensitization by out-of-band transmitters. Typically, sharp filters in the
receiver front-end will reduce the interfering transmitters to tolerable levels. In select
cases, the interferers may occupy a frequency band that is directly adjacent to the
receiving band and cannot be adequately rejected by filtering. The only recourse in
Help Hot Line (U.S. only): 1-800-530-99607-27
CONFIDENTIAL
Fusion Installation Procedures
850
850
850
Cellular
MHub
FSN-809019-1 RAU
FSN-8519-1 RAU
850
Cellular
RAU
850
EHub
Cellular
these situations is to provide sufficient isolation by physically separating the interfering transmitters and receivers.
iDEN occupies spectrum at both 800 MHz and 900 MHz (Tx:806–825/Rx:851–870
and Tx:896–901/Rx:935–940), while the Cellular A and B carriers share a single 850
MHz block (Tx:869–894/Rx:824–849). The combination of these frequency bands,
800/900 MHz iDEN and 850 MHz Cellular, result in uplink (BTS receive) bands that
are adjacent to downlink (BTS transmit) bands. Figure 7-9 depicts these nearly contiguous bands, with arrows indicating the interfering downlink and receiving uplink
bands.
Figure 7-9
800/850 MHz Spectrum
Installation of an in-building distributed antenna system (DAS) to provide coverage
for both 800/900 MHz iDEN and 850 MHz Cellular must account for these downlink-to-uplink interference issues and provide adequate isolation.
LGC offers the following guidelines toward achieving the proper amount of isolation
when deploying LGC Wireless Unison DAS products.
Figure 7-10
Guideline for Unison RAU Antenna Placement
800 MHz iDEN Downlink and 850 MHz Cellular Uplink
A 2 MHz frequency gap (851 – 849 MHz) separates the 800 iDEN downlink and 850
Cellular uplink frequency bands. Because of this narrow spacing, 800 iDEN downlink intermodulation products may fall within the 850 Cellular uplink band. In addition, 800 iDEN downlink signals near the lower edge of the band at 851 MHz may
7-28InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
cause the 850 Cellular uplink automatic level control (ALC) circuitry in the RAU to
engage and thereby reduce uplink gain.
To prevent either of these conditions, use the following guidelines:
• Lower frequency 800 iDEN signals < –30dBm for Fusion
Given a typical DAS configuration (4 iDEN carriers, omni-directional antennas, line
of sight), these guidelines translate to an antenna spacing (d1) of 6 – 9 meters.
850 MHz Cellular Downlink and 900 MHz iDEN Uplink
A 2 MHz frequency gap (896 – 894 MHz) separates the 850 Cellular downlink and
900 iDEN uplink frequency bands. Because of this narrow spacing, 850 Cellular
downlink intermodulation products may fall within the 900 iDEN uplink band. In
addition, 850 Cellular downlink signals near the upper edge of the band at 894 MHz
may cause the 900 iDEN uplink ALC to engage and thereby reduce uplink gain.
To prevent either of these conditions, use the following guidelines:
• Upper frequency 850 Cellular signals < –30dBm for Fusion
Given a typical DAS configuration (6 CDMA carriers for Fusion, omni-directional
antennas, line of sight), these guidelines translate to an antenna spacing (d2) of 8-14
meters.
Spacing between RAUs FSN-8519-1 and FSN-809019-1 should be in a range of from
8 to 14 meters.
Connecting the Antenna to the RAU
Connect a passive multi-band antenna to the N connector on the RAU using coaxial
cable with the least amount of loss possible.
CAUTION: Firmly hand-tighten the N connector – DO NOT
over-tighten the connector.
Connecting the CATV Cable
Considerations:
• Verify that the cable has been tested and the test results are recorded. This information is required for the As-Built Document.
• Verify that only captive centerpin 75 Ohm Type-F connectors are used on the solid
copper center conductor CATV 75 Ohm cable.
• Verify that the CATV cable is labeled with:
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-29
CONFIDENTIAL
Fusion Installation Procedures
• Fusion Main Hub port number being used
• RAU identifier
• Carrier (for multiple operator systems)
To connect the CATV cable:
1.
Connect the CATV cables to the F female port on the RAU according to the label
on the cable.
Power is supplied by the Fusion Main Hub over the CATV cable conductors.
Upon power up, the LEDs will blink for two seconds as a visual check that they
are functioning. After the two-second test:
• The
LINK
LED should be green indicating it is receiving power and communi-
cations from the Fusion Main Hub.
• The
ALARM
LED should be red until the Fusion Main Hub issues the band
command, within about 20 seconds, then it should be green.
2.
Record which cable you are connecting to the RAU (from the label on the cable).
This information is required for the As-Built Document.
3.
Tie-off cables or use the optional cable manager to avoid damaging the connectors
because of cable strain.
7.4.3.1Troubleshooting Using RAU LEDs During Installation
• The
LINK
LED should be green and remain green for longer than 90 seconds. The
ALARM
Table 7-7
During
InstallationLEDStateActionImpact
The RAU is connected
to the Fusion Expansion Hub, which is
powered on
LINK
ALARM
LINK
ALARM
LINK
ALARM
LEDs are red when the system band has not been programmed.
Troubleshooting RAU LEDs During Installation
OffCheck CATV cable.No power to the RAU.
Off
Green• Check CATV cable
Red
Red from
green, after
cables are
connected for
60 seconds
Red
• Check Hub LEDs
Refer to page 7-26, item 2 in
Table 7-6.
• Use AdminBrowser to determine the
problem.
• Check CATV cable.
• Check the Hub LEDs.
• Use AdminBrowser to determine the
problem.
The RAU is off-line.
No communications
between the RAU and the
Hub.
7-30InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
7.4.3.2Installing RAUs in a Multiple Operator System
When installing both iDEN and Cellular systems in parallel, either as dual-band or
multiple operator systems, you must take special provision to assure that the individual RAUs do not interfere with each other.
The 850/1900 MHz and 800/900/1900 MHz RAU’s antennas must be separated
by at least 8 meters (26 feet) to assure that the iDEN downlink signals do not
interfere with the Cellular uplink signals.
7.4.4Configuring the System
Before the system can operate properly, use AdminBrowser to program the Fusion
Main Hub with the frequency bands that are to be distributed. The Hub must be programmed with the same frequencies as the RAU used.
NOTE: The frequency bands should automatically be set on power up and
this step should not be required.
Considerations:
• The AdminBrowser software, described in the AdminBrowser User Manual
(PN D-620607-0-20), must be running on a PC/laptop.
• Crossover Ethernet cable with male connectors required.
Connecting the PC to the Fusion Main Hub to Run AdminBrowser
1.
Connect the AC power cord to the Hub.
Make sure the Hub is grounded through the ground lug on the AC power and
the frame ground lug as required. The warranty does not cover damage
caused when an ungrounded Hub is powered on.
2.
Plug the power cord into an AC power outlet.
3.
Verify that all cables are properly connected on the Hub.
4.
Turn on the power to the Hub.
All LEDs blink through the power up sequence. At each port where an RAU is
detected (drawing current), the port LEDs lights green. The Fusion
is orange during system boot and should turn green after about 90 seconds if it
finds no faults. This state indicates the band’s are not programmed and provides
feedback on the status of the RAU connections.
The LEDs blink for 20 seconds as a visual check that they are functioning.
5.
Connect the cross-over Ethernet cable to the PC/laptop and then to the
100-BASE-T
port on the Hub’s front panel.
STATUS
RJ-45
LED
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-31
CONFIDENTIAL
Fusion Installation Procedures
Programming the Fusion Main Hub Using AdminBrowser
• Connect the provided TCP/IP crossover cable to the laptop and then to the
Admin/LAN
RJ-45
port on the Fusion Main Hub’s front panel.
• Turn on the laptop and start the Fusion Main Hub.
Windows 2000
1.
Right-click
2.
Highlight
the Figure 7-11 appears.
My Network Places
Internet Protocol (TCP/IP)
and select
Properties
and click
.
Properties
. A screen similar to
Figure 7-11
Internet Protocol (TCP/IP) Properties Window
3.
Make note of the current IP address, Subnet mask, and Default gateway, if they
are configured. You will need to re-enter them after you have configured the
Fusion Main Hub.
4.
Select
Use the following IP address
5.
Change the
6.
Change the
7.
Change the
8.
Click OK twice. You may be asked if you want to reboot your computer. If so,
click
IP address
Subnet mask
Default gateway
Yes
.
to 192.168.0.101
to 255.255.255.0
to 192.168.0.1
.
7-32InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Windows XP
1.
Click
Start>Settings>Network Connections>Local Area Connection
dow shown in Figure 7-12 appears.
Fusion Installation Procedures
. The win-
Figure 7-12
2.
In the
Internet Protocol (TCP/IP)
3.
Perform steps 3 through 8 in the preceding section.
Local Area Connection Properties Window
This connection uses the following items
and click
Properties
, scroll down to and select
.
D-620610-0-20 Rev A
Using AdminBrowser
1.
Launch your web browser, type
Https://192.168.0.100
in the URL line, and click Go.
2.
When AdminBrowser appears, log in using the default password: password.
Help Hot Line (U.S. only): 1-800-530-99607-33
CONFIDENTIAL
Fusion Installation Procedures
3.
Click System Configuration and then click Set Date/Time. A page similar to
Figure 7-13 appears.
Figure 7-13
4.
Enter the desired time and date in the format indicated on the page and click Set
Set Time and Date Window
Date/Time. A page appears requiring you to reboot the system for the new date
and time to take effect.
5.
Select the Fusion Main Hub and click Install/Configure System. A screen similar
to the Figure 7-14 appears.
Figure 7-14
AdminBrowser Configuration Window
6.
If desired, type in a label.
7-34InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
The label is the system name displayed next to the icons and used in messages.It
can be up to 32 characters long depending upon the firmware version.
The default system label is “Fusion” and will be used if you enter nothing.
7.
Type in a Date and Time or leave the current system date and time unchanged.
Enter time is a 24-hour format.
8.
Use the next section to schedule a System Test.
This section allows you to do the following:
• Click the check box to enable this feature.
• Click the check box to cause system test on power up.
• Enter values to schedule the date and time of the next system test.
• Enter values to specify the recurrence of the test by day or by week.
Schedule System Test allows periodic, automatic execution of the system
end-to-end test. Just like Perform System Test, a Schedule System Test suspends
normal service for the duration of the test; calls are dropped, and no new calls can
be established during the test. Test duration depends on the configuration (number
of RAUs) and requires one or two minutes to complete.
After completion of the system test, the scheduled system test time is updated to
the next test time, and an event log entry is made.
9.
Use the scroll bar on the left side of the page to scroll down to view the rest of the
page as shown in Figure 7-15.
Figure 7-15
10.
In the Band area, do the following:
AdminBrowser Configuration Window (continued)
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-35
CONFIDENTIAL
Fusion Installation Procedures
• You should not have to select the bands. The system self configures the band
by validating that all the RAUs connected are the same type.
• Use the pull-down to specify the Uplink and Downlink gain for each band. You
can set system gain within the specified range in 1 dB increments.
• Use the pull-down to set the Uplink Automatic Level Control to either “Single”
or “Multiple” for each band in the system. (The default is “Multiple.”
11.
In the Input/Output Alarms area, do the following for each Alarm Sense:
• Enable each Alarm Sense by using the check box.
• Use the pull-down to set the Normal State to Closed or Opened. (The default is
“Closed.”
• Assign a label to each alarm sense.
12.
When you have completed inputting the desired information, click
Install System
to configure the system.
During configuration all disconnect statuses are cleared for attached RAUs; the
frequency band, gain, and system label are set; logs are cleared; the system test is
performed; and finally the system tree is refreshed. The icons should be:
Indicating that the band is correctly set.
Indicating that communications are OK.
If there are problems, the icons will be different and a message is displayed in the
Messages pane.
13.
Connect the Main Hub to the RF source (for example, BTS or BDA).
Do not exceed the maximum input RF power (1 Watt) to the Fusion Main
Hub. Exceeding the limit could cause permanent damage to the Hub.
CAUTION:Only carriers and their approved installers or LGC-authorized
installers are allowed to connect to the RF source. Serious damage to the
equipment can occur if it is over-driven.
The Fusion system should now be operational. Using a mobile phone, walk your
site and test the signal strength.
14.
Make sure to change the TCP/IP setting in your laptop back to their original values.
NOTE: NOTE: LGC Wireless’ equipment is designed to operate in the
licensed frequency bands of mobile, cellular, and PCS operators. In the
USA, the EU, and most countries this equipment may only be used by the
licensee, his authorized agents or those with written authorization to do so.
Similarly, unauthorized use is illegal, and subjects the owner to the corre-
7-36InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
sponding legal sanctions of the national jurisdiction involved. Ownership of
LGC Wireless equipment carries no automatic right of use.
7.5Splicing Fiber Optic Cable
The fiber cable must have SC/APC connectors for the entire run. If it does not, you
can splice a pigtail, which has SC/APC connectors, to the fiber cable.
LGC offers two pigtails: one for single-mode fiber (PN 4013SCAPC-3) and one for
multi-mode fiber (PN 4012SCAPC-3).
LGC Wireless recommends fusion splices because they have the lowest splice loss
and return loss. Mechanical splices have higher losses and higher back reflection than
fusion splices and are not recommended.
Using a fusion splicer involves fusing together two butted and cleaved ends of fiber.
The fusion splicer aligns the fibers and maintains alignment during the fusion process. Fusion splices have very low loss (typically less than 0.05 dB) and very low
back reflection (return loss). Fusion splices should be organized in a splice tray
designed to store and protect the splices.
Splicing Fiber Optic Cable
Fusion Splicing of Fiber and Pigtail
Before you begin, make sure the fusion splicer is set to the proper mode (that is, single- or multi-mode).
To fusion splice the fiber optic cable to the SC/APC pigtail: Option A
1.
Secure both the fiber cable and the SC/APC pigtail in a splice tray that is installed
immediately adjacent to the Hub.
2.
Prepare the fiber end by cutting back the polyethylene jacket, the kevlar or fiberglass strength members, the extruded coating, and the buffer coating in order to
expose the “bare fiber” – cladding plus core.
Ensure that sufficient slack is maintained in order to be able to reach the fusion
splicer.
3.
Clean the unclad fiber core using isopropyl alcohol and lint-free wipes.
4.
Cleave the unclad fiber to the length prescribed by the fusion splicer’s specification sheets.
5.
Repeat steps 2 through 4 for the SC/APC pigtail.
6.
Pass the splice sleeve onto the fiber strand.
7.
Position both fiber ends in the fusion splicer and complete splice in accordance
with the fusion splicer’s operation instructions.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-37
CONFIDENTIAL
Splicing Fiber Optic Cable
8.
Ensure that the estimated loss for the splice as measured by the fusion splicer is
0.10 dB or better.
9.
Slide the fusion splicing sleeve over the point of the fusion splice.
10.
Place the sleeve and fused fiber into the fusion splicer’s heater.
11.
Allow time for the splice sleeve to cure.
12.
Return fiber splice to the splice tray, store the sleeve in a splice holder within the
tray, and store excess cable length in accordance with the tray manufacture’s
directions.
After successfully testing the fiber, plug the SC/APC pigtail into the proper optical port on the Hub.
To fusion splice the fiber optic cable to the SC/APC pigtail: Option B
1.
Secure both the fiber cable and the SC/APC pigtail in a splice tray portion of a
fiber distribution panel.
2.
Prepare the fiber end by cutting back the polyethylene jacket, the kevlar or fiberglass strength members, the extruded coating, and the buffer coating in order to
expose the “bare fiber” – cladding plus core.
Ensure that sufficient slack is maintained in order to be able to reach the fusion
splicer.
3.
Clean the unclad fiber core using isopropyl alcohol and lint-free wipes.
4.
Cleave the unclad fiber to the length prescribed by the fusion splicer’s specification sheets.
5.
Repeat steps 2 through 4 for the SC/APC pigtail.
6.
Pass the splice sleeve onto the fiber strand.
7.
Position both fiber ends in the fusion splicer and complete splice in accordance
with the fusion splicer’s operation instructions.
8.
Ensure that the estimated loss for the splice as measured by the fusion splicer is
0.10 dB or better.
9.
Slide the fusion splicing sleeve over the point of the fusion splice.
10.
Place the sleeve and fused fiber into the fusion splicer’s heater.
11.
Allow time for the splice sleeve to cure.
12.
Return fiber splice to the splice tray, store the sleeve in a splice holder within the
tray, and store excess cable length in accordance with the tray manufacture’s
directions.
13.
After successfully testing the fiber cable, plug the SC/APC pigtail into the back
side of the SC/APC bulkhead in the Fiber Distribution Panel.
Install a SC/APC patch cord between the front side of the SC/APC bulkhead and
the proper optical port on the Hub.
NOTE: Refer to Section 9 for troubleshooting.
7-38InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Interfacing the Fusion Main Hub to an RF Source
7.6Interfacing the Fusion Main Hub to an RF Source
WARNING: Only LGC personnel or LGC-authorized installation per-
sonnel should connect the Fusion Main Hub to its Band associated base
station or repeater. Exceeding the maximum input power could cause
failure of the Fusion Main Hub (refer to Section 5.2 on page 5-4 for maximum
power specifications). If the maximum composite power is too high, attenuation
is required.
7.6.1Connecting a Single Fusion Main Hub to an RF Source
The Fusion system supports three RF sources, one for Band 1, Band 2, and Band 3.
This section explains how each Band can be connected to its associated RF source.
Connecting a Fusion Main Hub to an In-Building BTS
WARNING: Only LGC personnel or LGC-authorized installation per-
sonnel should connect the Fusion Main Hub to a base station or
repeater. Exceeding the maximum input power could cause failure of
the Fusion Main Hub (refer to Section 5.2 on page 5-4 for maximum power specifications). If the maximum composite power is too high, attenuation is required.
CAUTION:The
UPLINK
and
DOWNLINK
ports cannot handle a DC power
feed from the base station. If DC power is present, a DC block must be used
or the hub may be damaged.
Connecting a Simplex Base Station to a Fusion Main Hub RF Band:
1.
Connect an N-male to N-male coaxial cable to the transmit simplex connector on
the base station.
2.
Connect the other end of the N-male to N-male coaxial cable to the
DOWNLINK
connector on the Hub for the corresponding Band 1, Band 2, or Band 3.
3.
Connect an N-male to N-male coaxial cable to the receive simplex connector on
the base station.
4.
Connect the other end of the N-male to N-male coaxial cable to the
UPLINK
con-
nector on the Hub for the corresponding Band 1, Band 2, or Band 3.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-39
CONFIDENTIAL
Interfacing the Fusion Main Hub to an RF Source
N-male to N-male
Coaxial Cable
Base Station
Simplex
T1/E1 to
Mobile
Switching
Center
Insert attenuator, if needed
Note: This applies to either Band 1, Band 2, and Band 3.
Band 1
Band 2
Band 3
UL1UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Band 3
Figure 7-16
Simplex Base Station to a Fusion Main Hub
Connecting a Duplex Base Station to a Fusion Main Hub:
When connecting to a duplex base station, use a circulator or duplexer between it and
the Fusion Main Hub.
You can insert attenuators between the circulator or duplexer and Hub as needed.
1.
Connect an N-male to N-male coaxial cable to the duplex connector on the base
station.
2.
Connect the other N-male connector or duplexer to a circulator.
3.
Connect an N-male to N-male coaxial cable to the
DOWNLINK
connector on the
Hub for Band 1, Band 2, and Band 3.
4.
Connect the other end of the N-male coaxial cable to the transmit connector on the
circulator.
5.
Connect an N-male to N-male coaxial cable to the
UPLINK
connector on the Hub
for Band 1, Band 2, and Band 3.
6.
Connect the other end of the N-male coaxial cable to the receive connector on the
circulator.
7-40InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Interfacing the Fusion Main Hub to an RF Source
N-male to N-male
Coaxial Cable
Base Station
Duplex
T1/E1 to
Mobile
Switching
Center
Insert attenuator, if needed
N-male to N-male
Coaxial Cable
Note: This applies to either Band 1, Band 2, Band 3.
Band 1
Band 2
Band 3
UL1UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Circulator
Figure 7-17
Duplex Base Station to a Fusion Main Hub
Help Hot Line (U.S. only): 1-800-530-99607-41
D-620610-0-20 Rev A
CONFIDENTIAL
Interfacing the Fusion Main Hub to an RF Source
N-male to N-male
Coaxial Jumper Cables
N-male to N-male
Coaxial Jumper Cable
to Repeater or
Base Station
between Combiner/Splitter and
N-male to N-male
Coaxial Jumper Cables
between Combiner/Splitter and
Fusion Main Hub’s Uplink PortFusion Main Hub’s Downlink Port for
2 x 1 Power
Combiner/Splitter
2 x 1 Power
Combiner/Splitter
BTS 1
ULDL
BTS 2
ULDL
Insert attenuators, if needed
for each on Band 1, Band 2, or Band 3either Band 1, Band 2, or Band 3
Band 1
Band 2
Band 3
UL1UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Connecting a Fusion Main Hub RF Band to Multiple BTSs
WARNING: Only LGC personnel or LGC-authorized installation per-
sonnel should connect the Fusion Main Hub to a base station or
repeater. Exceeding the maximum input power could cause failure of
the Fusion Main Hub (refer to Section 5.2 on page 5-4 for maximum power specifications). If the maximum composite power is too high, attenuation is required.
You can use power combiner/splitters to connect a Fusion Main Hub RF Band to multiple base stations, as shown in Figure 7-18.
Figure 7-18
Connecting a Fusion Main Hub to Multiple Base Stations
7-42InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Interfacing the Fusion Main Hub to an RF Source
Roof-top
Antenna
Grounded
Surge Suppressor
Repeater
N-male to N-male
Coaxial Cables
N-male to N-male
Coaxial Cable
N-male to N-male
Coaxial Cable
Circulator
Attenuator
(optional)
Note: This applies to either Band 1, Band 2, or Band 3.
Band 1
Band 2
Band 3
UL1UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
1
2
3
Connecting a Fusion Main Hub to a Roof-top Antenna
LGC Wireless recommends that you use a lightning arrestor or surge protector in a
roof-top antenna configuration. Insert the lightning arrestor or surge protector
between the roof-top antenna and the repeater connected to the Fusion Main Hub RF
Band.
1.
Connect an N-male to N-male coaxial cable to the roof-top antenna.
2.
Connect the other end of the N-male to N-male coaxial cable to the grounded
surge suppressor.
3.
Connect an N-male to N-male coaxial cable to the grounded surge suppressor.
4.
Connect the other end of the N-male to N-male coaxial cable to the repeater.
5.
Connect an N-male to N-male coaxial cable to the repeater.
6.
Connect the other end of the N-male to N-male coaxial cable to the circulator
1
connector.
7.
Connect an N-male to N-male coaxial cable to the circulator 2connector.
8.
Connect the other end of the N-male to N-male coaxial cable to the
connector on the Hub for either Band 1, Band 2, or Band 3.
Attenuation may be required to achieve the desired RF output at the RAU.
9.
Connect an N-male to N-male coaxial cable to the circulator 3connector.
10.
Connect the other end of the N-male to N-male coaxial cable to the
nector on the Hub for either Band 1, Band 2, or Band 3.
DOWNLINK
UPLINK
con-
D-620610-0-20 Rev A
Figure 7-19
Help Hot Line (U.S. only): 1-800-530-99607-43
Connecting a Fusion Main Hub to a Roof-top Antenna
CONFIDENTIAL
Interfacing the Fusion Main Hub to an RF Source
Connecting a Fusion Main Hub to MetroReach Focus
Refer to the MetroReach Focus manual for information.
7.6.2Connecting Multiple Fusion Main Hubs to an RF Source
You can use power combiner/splitters as splitters to connect multiple Fusion Main
Hubs in order to increase the total number of RAUs in a system. You can also use
power combiner/splitters to combine base station channels in order to increase the
number of RF carriers the system transports.
Connecting Multiple Fusion Main Hubs to a Simplex Repeater or
BTS
WARNING: Only LGC personnel or LGC-authorized installation per-
sonnel should connect the Fusion Main Hub to a base station or
repeater. Exceeding the maximum input power could cause failure of
the Fusion Main Hub (refer to Section 5.2 on page 5-4 for maximum power specifications). If the maximum composite power is too high, attenuation is required.
Considerations:
• 2 hybrid power combiner/splitters; one for uplink and one for downlink (2x1 for
two Fusion Main Hubs, 3x1 for three, 4x1 for four, and so on.)
• 1 N-male to N-male coaxial jumper cable between each power combiner/splitter
and the base station
• 2 N-male to N-male coaxial jumper cables between each power combiner/splitter
and each Fusion Main Hub RF Band (either Band 1 or Band 2)
Procedure:
1.
Connect the power combiner/splitters to the repeater or base station using N-male
to N-male coaxial jumper cables:
a.
From the first power combiner/splitter to the repeater or base station
b.
From the second power combiner/splitter to the repeater or base station
DOWNLINK
2.
Connect the power combiner/splitters to the Hubs:
a.
From the first Hub’s
UPLINK
port (Band 1, Band 2, or Band 3) to the first
UPLINK
power combiner/splitter
b.
From the first Hub’s
DOWNLINK
port (Band 1, Band 2, or Band 3) to the sec-
ond power combiner/splitter
c.
From the second Hub’s
UPLINK
port (Band 1, Band 2, or Band 3) to the first
power combiner/splitter
d.
From the second Hub’s
DOWNLINK
port (Band 1, Band 2, or Band 3) to the
second power combiner/splitter
7-44InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Interfacing the Fusion Main Hub to an RF Source
NOTE: Connections should not cross Bands. For example, all Band 1 connections
should be made to the same hybrid power combiner/splitter connected to the repeater
BTS that matches the Band 1 frequency.
3.
Check Hub LEDs.
After connecting and powering on the Hub, check all LEDs to ensure that the system is operating properly.
Make sure the Hub is grounded. The warranty does not cover damage caused
when an ungrounded Hub is powered on.
NOTE: Use a 50 ohm terminator on any unused power combiner/splitter ports.
Figure 7-20 shows how to connect two Main Hubs to a simplex repeater or base station. Connecting two Hubs increases the total number of supportable RAUs from 8 to
16.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-45
CONFIDENTIAL
Interfacing the Fusion Main Hub to an RF Source
N-male to N-male
Coaxial Jumper Cables
N-male to N-male
Coaxial Jumper Cable
to Repeater or
Base Station
2 x 1 Power
Combiner/Splitter
N-male to N-male
Coaxial Jumper Cable
to Repeater or
Base Station
between Combiner/Splitter and
N-male to N-male
Coaxial Jumper Cables
between Combiner/Splitter and
Fusion Main Hub’s Uplink Port for
Fusion Main Hub’s Downlink Port for
2 x 1 Power
Combiner/Splitter
either Band, Band 2, Band 3
either Band 1, Band 2, Band 3
Band 1
Band 2
Band 3
UL1UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Band 1
Band 2
Band 3
UL1UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Figure 7-20
Connecting Two Fusion Main Hub’s RF Band Ports to a Simplex
Repeater or Base Station
7-46InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Interfacing the Fusion Main Hub to an RF Source
Connecting Multiple Fusion Main Hubs to a Duplex Repeater or
BTS
WARNING: Only LGC personnel or LGC-authorized installation per-
sonnel should connect the Fusion Main Hub to a base station or
repeater. Exceeding the maximum input power could cause failure of
the Fusion Main Hub (refer to Section 5.2 on page 5-4 for maximum power specifications). If the maximum composite power is too high, attenuation is required.
Considerations:
• 2 hybrid power combiner/splitters; one for uplink and one for downlink (2x1 for
two Fusion Main Hubs, 3x1 for three, 4x1 for four, and so.)
• 2 N-male to N-male coaxial jumper cables to connect each Fusion Main Hub’s RF
Band to the power combiner/splitters
• 1 circulator
• 1 N-male to N-male coaxial jumper cable between each circulator and the repeater
or base station
• 1 N-male to N-male coaxial jumper cable between each circulator and power com-
biner/splitter
Procedure:
1.
Connect the circulator to the repeater or base station using one N-male to N-male
coaxial jumper cable.
2.
Connect each power combiner/splitter to the circulator using one N-male to
N-male coaxial jumper cable per combiner/splitter.
3.
Connect the power combiner/splitter to the Hubs using N-male to N-male coaxial
jumper cable:
a.
From the first Hub’s
UPLINK
(Band 1, Band 2, or Band 3) port to the first
power combiner/splitter
b.
From the first Hub’s
DOWNLINK
(Band 1, Band 2, or Band 3) port to the sec-
ond power combiner/splitter
c.
From the second Hub’s
UPLINK
(Band 1, Band 2, or Band 3) port to the first
power combiner/splitter
d.
From the second Hub’s
DOWNLINK
(Band 1, Band 2, or Band 3) port to the
second power combiner/splitter
NOTE: Connections should not cross Bands. For example, all Band 1 connections
should be made to the same hybrid power combiner/splitter connected to the repeater
BTS that matches the Band 1 frequency.
D-620610-0-20 Rev A
4.
Check Hub LEDs.
Help Hot Line (U.S. only): 1-800-530-99607-47
CONFIDENTIAL
Interfacing the Fusion Main Hub to an RF Source
N-male to N-male
Coaxial Jumper Cables
2 x 1 Power
Combiner/Splitter
between Combiner/Splitter and
N-male to N-male
Coaxial Jumper Cables
between Combiner/Splitter and
Fusion Main Hub’s Uplink Port
Fusion Main Hub’s Downlink Port for
2 x 1 Power
Combiner/Splitter
N-male to N-male
Coaxial Jumper Cable
N-male to N-male
Coaxial Jumper Cable
Circulator
N-male to N-male
Coaxial Jumper Cable
to Repeater or
Base Station
Insert attenuator, if needed
for either Band 1, Band 2,
either Band 1, Band 2, or Band 3
or Band 3
Band 1
Band 2
Band 3
UL1UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Band 1
Band 2
Band 3
UL1UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
After connecting and powering on the Hub, check all LEDs to ensure that the system is operating properly.
Make sure the Main Hub is grounded. The warranty does not cover damage
caused when an ungrounded Hub is powered on.
NOTE: Use a 50 ohm terminator on any unused power combiner/splitter ports.
Figure 7-21 shows how to connect two Hubs to a duplex repeater or base station. You
need to use one circulator and one more coaxial jumper cable, as shown.
Figure 7-21
Connecting Two Fusion Main Hub’s RF Band Ports to a Duplex
Repeater or Base Station
7-48InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Connecting Contact Alarms to a Fusion System
7.7Connecting Contact Alarms to a Fusion System
The Fusion Main Hub can generate (source) two contact alarms as well as sense three
external contact alarm.
• Alarm Source (refer to Section 7.7.1 on page 7-50)
The Fusion Main Hub has two alarm contacts, fault (major) and warning (minor).
These contacts are normally-closed (NC) and will open when an internal alarm is
detected.
NOTE: The contact can be changed to normally-open (NO) with AdminBrowser. This is not recommended since no alarm would be sent if power to
the Fusion Main Hub fails.
• Fault is activated when any faults or disconnects are detected.
• Warning is activated when any warning conditions are detected except lockout
or when the end-to-end system test is not valid.
• Alarm Sense (refer to Section 7.7.2 on page 7-53)
The Fusion Main Hub can monitor 3 external alarm contacts. Each port can be configured for normally-open (NO) or normally-closed (NC) contacts. The interface
expects a set of floating contacts, and an external voltage source is not required for
this interface. Use AdminBrowser to monitor the port status.
Table 7-8 lists the alarm types, equipment to which the Fusion Main Hub is connected, cable(s) used, and the faults and warnings that are detected.
SourceBTS5-port Alarm Daisy-Chain CableFaults and Warnings
SenseUnison5-port Alarm Daisy-Chain Cable
Alarm Types
Fusion
Connected toCable(s) UsedErrors Detected
In addition, a custom daisy-chain cable-to-BTS interface
cable is required. Make this interface cable to the desired
length and with the appropriate pin placement.
Faults
and the Alarm Sense Adapter
Cable
Note that Unison and MetroReach Focus support only faults (major errors).
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-49
CONFIDENTIAL
Connecting Contact Alarms to a Fusion System
RF OUT
DOWNLINK
RF IN
UPLINK
FIBER
UPLINK
DOWNLINK
ALARM
RS-232C
MetroReach
Focus
RFM
Alarm
Sense
Alarm
Source
Alarm
Source
5-port Alarm Daisy-Chain Cable
May need
9-pin Adapter,
which ships
with the cable
Fusion Main Hub
Band 1
Band 2
Band 3
UL1 UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Band 1
Band 2
Band 3
UL1 UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Do not mix Unison and Fusion Main Hubs in the same daisy-chain. You can
daisy-chain multiple Unison Hubs together and use the Alarm Sense Adapter Cable to
connect the chain to a Fusion Main Hub, which will act as an alarm sensor.
7.7.1Alarm Source
Fusion always acts as an alarm source, no matter what type of equipment you are connecting to. Refer to Section 7.7.2 on page 7-53 if you want Fusion to sense Unison
contact closures or other external alarms.
Using MetroReach Focus to Monitor Fusion
When you connect MetroReach Focus to the Fusion, the Fusion Main Hub is the output of the alarms (alarm source) and Focus is the input (alarm sense), as shown in
Figure 7-22. Focus supports only faults (major errors).
Figure 7-22
Connecting MetroReach to Fusion
7-50InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Connecting Contact Alarms to a Fusion System
BTS
Interface
Cable
Alarm
Sense
Alarm
Source
Alarm
Source
5-port Alarm Daisy-Chain Cable
Fusion Main Hub
(custom made, on-site)
Band 1
Band 2
Band 3
UL1 UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Band 1
Band 2
Band 3
UL1 UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Using a Base Station to Monitor Fusion
NOTE: The BTS must be configured, by the carrier, for contact closure monitoring
prior to connecting a Fusion Main Hub to it.
When you connect a BTS to Fusion, the Fusion Main Hub is the output of the alarms
(alarm source) and the BTS is the input (alarm sense), as shown in Figure 7-23. An
interface cable is required between the daisy-chain cable and the BTS. Because BTS
alarm interface pinouts and Fusion-to-BTS distances vary, this cable is often custom
and wired on-site. Refer to Section 3.2.1 for Alarm Contact details (Normally
Closed).
Figure 7-23
Using a BTS to Monitor Fusion
NOTE: For normally open contacts, the fault and warning contacts need to
be wired in parallel with other Main Hubs.
D-620610-0-20 Rev A
NOTE: LGC Wireless does not recommend using normally open contacts.
Help Hot Line (U.S. only): 1-800-530-99607-51
CONFIDENTIAL
Connecting Contact Alarms to a Fusion System
Line Switch
Straight-through modem cable connected
to Fusion Main Hub’s front panel serial port
PSTN
Modem
PC running
Standard Browser
Software
BTS
Interface
Cable
Alarm
Sense
Alarm
Source
Alarm
Source
5-port Alarm Daisy-Chain Cable
Fusion Main Hub
Modem
Modem
Band 1
Band 2
Band 3
UL1 UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Band 1
Band 2
Band 3
UL1 UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Using a Base Station and AdminBrowser to Monitor Fusion
NOTE: The BTS must be configured, by the carrier, for contact closure monitoring
prior to connecting a Fusion Main Hub to it.
In order to take full advantage of Fusion’s OA&M capabilities you can use LGC
Wireless’ AdminBrowser software in addition to a BTS to monitor the system, as
shown in Figure 7-24. Refer to Section 7.8.6 for SNMP optional feature capabilities.
Figure 7-24
Using a BTS and AdminBrowser to Monitor Fusion
7-52InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
7.7.2Alarm Sense
Up to 5 Unison Main Hubs
Fusion Main Hub
Alarm
Sense
Alarm
Source
Alarm
Source
Alarm Sense
Adapter Cable
5-port Alarm Daisy-Chain Cable
Band 1
Band 2
Band 3
UL1UL2
UL3
DL1
DL2
DL3
AC Power
Alarms
Use AdminBrowser to enable the Fusion system for “alarm sense” when connecting
to the contact closure of Unison Main Hubs or other external alarms (refer to Set
Contact Sense Properties in the AdminBrowser User Manual).
Using Fusion to Monitor Unison
When you connect Unison to Fusion, the Fusion Main Hub is the input of the alarms
(alarm sense) and the Unison is the output (alarm source), as shown in Figure 7-25.
The input alarm sense needs to be set to normally closed (NC).
Connecting Contact Alarms to a Fusion System
Figure 7-25
Using Fusion to Monitor Unison
Unison supports only faults. You must use the Alarm Sense Adapter Cable (refer to
page 7-56) to interface the daisy-chain cable to Fusion. The adapter cable is required
because it translates the Unison fault pinout to the sense input pins on the Fusion
Main Hub.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-53
CONFIDENTIAL
Connecting Contact Alarms to a Fusion System
8
1
Diagnostic I
External
Equipment
Contacts
+5V
Figure 7-26
Alarm Sense Contacts
7-54InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
7.7.3Alarm Cables
DB-9 female to
Base Station,
MetroReach Focus,
or
J1
Female
J2
Male
J3
Male
J4
Male
J5
Male
J6
Male
J7
Female
Terminator
Splice
Splice
Splice
Splice
Splice
Splice
Splice
Splice
7
9
4
5
7
9
4
5
7
9
4
5
7
9
4
5
7
9
4
5
7
4
1.2 meters (4 feet)
.5 meter
(1.5 feet)
DB-9 male to Fusion,
Unison, MetroReach
Focus, Alarm Port
DB-9 male to Fusion,
Unison, MetroReach
Focus Alarm Port
DB-9 male to Fusion,
Unison, MetroReach
Focus Alarm Port
DB-9 male to Fusion,
Unison, MetroReach
Focus Alarm Port
Option 1: DB-9 to Fusion,
Unison, MetroReach
Focus
Alarm Port.
J7 not used
Option 2: Use J2-J5
for alarm ports. J6 is used
to connect to an additional
Alarm Daisy-Chain Cable.
J7 is not used.
Option 3: Connect
fewer than 5 ports and
terminate the daisy chain
by connecting J7 to the
lowest unused port.
Connector
Hood
.5 meter
(1.5 feet)
.5 meter
(1.5 feet)
.5 meter
(1.5 feet)
.25 meter
(.75 feet)
the Alarm Sense
Adapter Cable when
connecting Unison
NOTE: Do not daisy-chain Fusion
Main Hubs with Unison or
MetroReach Focus if you want both
faults and warnings from Fusion. Only
faults are reported if you combine
Fusion with Unison or MetroReach in
the same daisy chain.
7
9
4
5
5-port Alarm Daisy-Chain Cable
Figure 7-27 shows the 5-port Alarm Daisy-Chain Cable (PN 4024-3), which supports
fault and warning conditions.
Connecting Contact Alarms to a Fusion System
Figure 7-27
5-port Alarm Daisy-Chain Cable
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-55
CONFIDENTIAL
Connecting Contact Alarms to a Fusion System
J8
1
8
J9
7
9
To FusionTo Daisy-Chain Cable
3 feet
Alarm Sense Adapter Cable
The alarm sense adapter cable (PN 4025-1) translates the Unison fault pinout to the
sense input pins on the Fusion Main Hub. You must use this adapter cable, illustrated
in Figure 7-28, with the 5-port Alarm Daisy-Chain Cable when connecting Unison to
Fusion.
Figure 7-28
Alarm Sense Adapter Cable
7-56InterReach Fusion Installation, Operation, and Reference Manual
Note that the only accessory available through LGC Wireless is the Ethernet
cross-over 100 BASE-T cable, which is provided with AdminBrowser.
7.8.1Direct Connection
In this configuration, the PC connects directly to the
RJ-45 100 BASE-T
port on the
Fusion Main Hub’s front panel using a cross-over cable.
Figure 7-29
OA&M Direct Connection
NOTE: The cross-over cable provided with the Fusion Main Hub supports
full hardware handshaking, which is required. Refer to Appendix A.4 on
page A-8 for cable wiring information.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-57
CONFIDENTIAL
Alarm Monitoring Connectivity Options
Straight-through
modem cable
PC running
Software
Standard Browser
Modem
Straight-through modem cable
PSTN
Modem
7.8.2Modem Connection
In this configuration, the PC and the Fusion Main Hub connect to modems and communicate using a standard dial-up telephone connection.
Figure 7-30
OA&M Modem Connection
NOTE: Refer to Appendix A.3 on page A-7 for the modem cable wiring information.
7-58InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
Modem switch settings are as follows for US Robotics modem:
• PC-side: 3, 4 and 8 Down (“ON” position)
• Fusion Hub-side: 1, 4 , 5 and 8 Down (“ON” position)
7.8.2.1Setting Up Fusion Modem Using AdminBrowser
Use the following steps to set up a PPP Dial-In on Fusion:
1.
Start AdminBrowser as explained in the AdminBrowser manual.
2.
Select System Configuration.
3.
Select Setup Modem Connection. The window shown in Figure 7-31 appears.
D-620610-0-20 Rev A
Alarm Monitoring Connectivity Options
Figure 7-31
4.
Make the desired changes.
5.
Click Setup Connection.
Default Dial-in Settings (Fusion Hub)
7.8.2.2Setting Up a PC Modem Using Windows
Use the following sets to set up a dial-up connection on your PC:
1.
Click Start, Settings, Network Connections. The window shown in Figure 7-32
appears.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-59
CONFIDENTIAL
Alarm Monitoring Connectivity Options
Figure 7-32
2.
Click Create a new connection. The window shown in Figure 7-33 appears.
Network Connections Window
Figure 7-33
3.
Click Next. The window shown in Figure 7-34 appears.
New Connection Wizard - Welcome Window
7-60InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Alarm Monitoring Connectivity Options
Figure 7-34
4.
Select Connect to the network at my workplace and click Next. The window
New Connection Wizard - Network Connection Type Window
shown in Figure 7-35 appears.
Figure 7-35
New Connection Wizard - Network Connection Window
D-620610-0-20 Rev A
5.
Select Dial-up connection and click Next. The window shown in Figure 7-36
appears.
Help Hot Line (U.S. only): 1-800-530-99607-61
CONFIDENTIAL
Alarm Monitoring Connectivity Options
Figure 7-36
6.
Type a name for this connection and click Next. The window shown in
New Connection Wizard - Connection Name Window
Figure 7-37 appears.
Figure 7-37
New Connection Wizard - Phone Number to Dial Window
7.
Type the desired dial in phone number and click Next. The window shown in
Figure 7-38 appears.
7-62InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Alarm Monitoring Connectivity Options
Figure 7-38
8.
Select Anyone’s use and click Next. The window shown in Figure 7-39 appears.
Figure 7-39
New Connection Wizard - Connection Availability Window
New Connection Wizard - Completing New Connection Window
D-620610-0-20 Rev A
9.
Click Finish. The window shown in Figure 7-40 appears.
Help Hot Line (U.S. only): 1-800-530-99607-63
CONFIDENTIAL
Alarm Monitoring Connectivity Options
Figure 7-40
10.
Type a password as indicated and click Properties. The window shown in
Connect Fusion Hub Window
Figure 7-41 appears.
The default parameters are as follows:
• User name: pppuser
• Password (one word, all lower case): password
Figure 7-41
11.
Click Configure... The window shown in Figure 7-42 appears.
Fusion Hub Properties Window
7-64InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Alarm Monitoring Connectivity Options
Figure 7-42
12.
Select the modem speed and other parameters for your modem as desired and
Modem Configuration Window
click OK.
13.
Select the Security tab. The window shown in Figure 7-43 appears.
Figure 7-43
Fusion Hub Properties - Security Tab Window
D-620610-0-20 Rev A
14.
Select Typical and then click the Networking tab. The window shown in
Figure 7-44 appears.
Help Hot Line (U.S. only): 1-800-530-99607-65
CONFIDENTIAL
Alarm Monitoring Connectivity Options
Figure 7-44
15.
Select Internet Protocol (TCP/IP) as shown and click Properties. The window
Fusion Hub Properties - Networking Tab Window
shown in Figure 7-45 appears.
Figure 7-45
Internet Protocol Properties Window
16.
Select Obtain an IP address automatically and Obtain DNS server address
automatically and click OK.
17.
To connect to the Fusion Hub over the Dial-up connection, start you web browser
and type the server IP address configured in Section 7.8.2.1 in the address bar.
7-66InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Alarm Monitoring Connectivity Options
LAN switch
100 BASE-T Ethernet connection
RJ-45 male to RJ-45 male
100 BASE-T Cable
PC running
Software
Standard Browser
AdminBrowser software is resident
in Fusion.
7.8.3100 BASE-T Port Expander Connection
In this configuration a LAN switch is used to allow the connection of multiple
devices to a single PC with a 100 BASE-T port. Testing was performed with a Linksys 4-port switch. A standard RJ-45 Ethernet cable must be made to connect the LAN
switch to the Fusion Main Hub.
Figure 7-46
OA&M Connection using a 232 Port Expander
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-67
CONFIDENTIAL
Alarm Monitoring Connectivity Options
Modem
PSTN
Line Sharing Switch
Up to 4 modems
per Switch
Modem
Modem
Straight-through
modem cable
Straight-through
modem cable
PC running
Software
Standard Browser
Standard phone cable
7.8.4POTS Line Sharing Switch Connection
Using a line sharing switch, you can connect up to four modems to a single telephone
line. Testing was performed with a Teltone Line Sharing Switch, model number
M-394-B-01.
Figure 7-47
OA&M Connection Using a POTS Line Sharing Switch
Up to 16 modems can be monitored using a single telephone line by cascading line
sharing switches, as shown in Figure 7-48.
7-68InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Alarm Monitoring Connectivity Options
Modem
PSTN
Line Sharing Switch
Line Sharing SwitchLine Sharing SwitchLine Sharing SwitchLine Sharing Switch
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
M
o
d
e
m
Straight-through
modem cable
Straight-
through
modem
cables
PC running
Software
Standard Browser
Standard phone cable
Figure 7-48
Cascading Line Sharing Switches
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-69
CONFIDENTIAL
Alarm Monitoring Connectivity Options
LAN
Switch
TCP/IP
Ethernet
100 BASE-T Cable
RJ-45 to RJ-45 male
Ethernet
PC running
Software
Standard Browser
7.8.5Ethernet LAN Connection
An Ethernet LAN connection can be used to communicate between the PC and
Fusion. Testing was performed with an Linksys 4-port LAN switch.
Figure 7-49
OA&M Connection Using Ethernet and ENET/232 Serial Hub
7-70InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
7.8.6SNMP Interface
Faults and warnings can also be diagnosed with SNMP using a standard (NMS) network management system (optional). SNMP resident software in Fusion provides
SNMP interactions for Traps and Notification.
The Fusion SNMP includes a MIB for integrating into the Network Management System (NMS) and supports SNMPv1 and SNMPv2c.
Alarm Monitoring Connectivity Options
Figure 7-50
Fusion SNMP Configuration Options
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99607-71
CONFIDENTIAL
Alarm Monitoring Connectivity Options
7-72InterReach Fusion Installation, Operation, and Reference Manual
Be aware that the new RAU must support the same bands as the one you are replacing. If the RAU is of the wrong band combination, it will not operate properly in the
system.
Replacing an RAU
1.
Using AdminBrowser, log in and click
2.
Click
S
MATION
HOW SYSTEM TREE
.
, select Fusion Main Hub, and click
All system settings for Hubs and RAUs will be displayed. Write down or save the
Uplink and Downlink Attenuation setting so you can set the new RAU with the
same settings.
3.
Click
C
ANCEL
to close the window.
4.
Verify that the new RAU is of the same frequency bands as the one replaced.
5.
Disconnect the CATV cable and antenna cable from the unit to be replaced.
6.
Install the new RAU.
7.
Connect the antenna cable and then the CATV cable to the new RAU.
8.
Click
S
YSTEM CONFIGURATION
9.
Click
S
HOW SYSTEM TREE
10.
Select the Fusion RAU replaced and click
.
.
S
YSTEM INFORMATION
E
DIT UNIT PROPERTIES
.
GET S
YSTEM INFOR
.
-
D-x620610-0-20 Rev A
InterReach Fusion Installation, Operation, and Reference Manual8-1
CONFIDENTIAL
Replacing an RAU
11.
Set the attenuation of each band as the old RAU was programmed and click
P
ROPERTIES
.
Perform System Test
When convenient, perform System Test to optimize performance.
During System Test, the entire system is temporarily off-line and no RF is
being transmitted.
Checking the RAU’s LEDs
1.
The RAU’s
• If the LEDs do not blink on power up, replace the RAU.
2.
After several seconds both LEDs should change to green, which indicates that the
unit has been successfully replaced, there is communication with the Hub, and the
RAU band is correct.
a.
If the
the RAU model is correct for the intended frequency band.
LINK
and
ALARM
LEDs should blink (green/red) on power up.
LINK
LED remains green and the
ALARM
LED remains red, verify that
S
AVE
– Disconnect the cable and then reconnect it once; doing this more than once
will not change the result.
b.
If both LEDs still don’t change to green, use AdminBrowser to determine the
exact nature of the fault and see a recommendation of how to correct it.
c.
If both LEDs turn red (after 90 seconds), the Hub has terminated communications.
8-2InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-x620610-0-20 Rev A
Replacing a Fusion Expansion Hub
8.2Replacing a Fusion Expansion Hub
Replacing a Fusion Expansion Hub
1.
Turn off the power to the Expansion Hub.
2.
Disconnect all CATV cables, both fiber cables, and the AC power cord.
3.
Replace the Expansion Hub with a new one.
4.
Connect the AC power cord, all CATV cables, and both fiber cables – remembering to clean and correctly connect the uplink and downlink fiber.
5.
Turn on the power to the Expansion Hub.
AdminBrowser Tasks
• The Main Hub automatically issues the band setting.
• When convenient, use AdminBrowser to perform System Test in order to optimize
performance.
During System Test, the entire system is temporarily off-line and no RF is
being transmitted. For a fully loaded system (one Main Hub, four Expansion
Hubs, and 32 RAUs), it can take up to 1.5 minutes to complete the test.
Checking the Expansion Hub’s LEDs
• The LEDs should blink through all states on power up.
• If the LEDs do not blink on power up, replace the Expansion Hub.
• If the LEDs do not illuminate at all, make sure the AC power cable is connected.
• The
UL STATUS
• The
E-HUB STATUS
• For each CATV port that has an RAU connected the LEDs should be green.
It can take several seconds for each CATV connection for the LEDs to display
properly.
NOTE: Refer to Section 9 for troubleshooting using the LEDs.
and
and
DL STATUS
POWER
LEDs should be green.
LEDs should be green.
D-x620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99608-3
CONFIDENTIAL
Replacing a Fusion Main Hub
8.3Replacing a Fusion Main Hub
You must record the system configuration settings from the old Fusion Main Hub’s
memory before replacing the unit. You will program the new Main Hub with this
information. If the Main Hub is programmed incorrectly, the system will not work. If
the Hub to be replaced is not functioning and you cannot use AdminBrowser, get the
configuration settings from the As-Built Document that was created as part of the
original installation.
Replacing a Fusion Main Hub
1.
Using AdminBrowser, log in, click
T
REE
, select Fusion Hub, click
2.
Turn off the power to the Fusion Main Hub.
3.
Disconnect all cables and the AC power cord.
4.
Replace the Main Hub with a new one.
5.
Connect the AC power cord and all cables.
6.
Connect the crossover Ethernet cable to the PC and then to the Main Hub’s front
panel 100Base-T connector. ADMIN/LAN port)
7.
Start the standard browser on the PC to communicate with AdminBrowser software.
8.
Turn on the power to the Main Hub.
9.
Observe the LEDs after turning on the power.
All the LEDs blink during the initial power up sequence. All LEDs should turn
green after the power on sequence is complete. Power up sequence takes between
1 and 2 minutes depending on the number of RAUs.
S
YSTEM INFORMATION
GET S
YSTEM INFORMATION
, click
.
S
HOW SYSTEM
Configure the New Fusion Main Hub
1.
Using AdminBrowser and log in to the Main Hub.
2.
Click
S
YSTEM CONFIGURATION
3.
Click
SET D
ATE/TIME
4.
Click
SET D
ATE/TIME
5.
Follow the instructions to eventually reboot the system to set the date and time.
6.
Using AdminBrowser, log in and click
7.
Click
I
NSTALL SYSTEM
8.
Set the new Main Hub parameters from the old Main Hub and click
TEM
(that is, uplink and downlink gain, system labels, and so on).
9.
Follow the instructions to perform a System Test.
and enter the current date and time.
.
.
8-4InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
.
S
YSTEM CONFIGURATION
.
I
NSTALL SYS
D-x620610-0-20 Rev A
-
Replacing a Fusion Main Hub
10.
Click
S
YSTEM CONFIGURATION
M
ODEM CONNECTION
if the Main Hub has Network or Modem equipment con-
and click on
S
ETUP NETWORK CONNECTION OR
nected to it.
During System Test, the entire system is temporarily off-line and no RF is
being transmitted.
Checking the Main Hub’s LEDs
• The LEDs should blink through a 5-second test on power up.
• If the LEDs do not blink on power up, replace the Main Hub.
• If the LEDs do not illuminate at all, make sure the AC power cable is connected.
• For each fiber optic port that has a connected Expansion Hub, which has been programmed with a band, the
• Refer to Section 9.3, “Troubleshooting,” on page 9-3 for more LED states.
NOTE: If there is no communication between the Main Hub and the Expansion
Hubs, use the AdminBrowser to isolate system problems.
PORT
LED should be green.
D-x620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99608-5
CONFIDENTIAL
Replacing a Fusion Main Hub
8-6InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-x620610-0-20 Rev A
SECTION 9
Maintenance, Troubleshooting,
and Technical Assistance
There are no user-serviceable parts in any of the Fusion components. Faulty or failed
components are fully replaceable through LGC Wireless. All units should be replaced
and returned to the factory for service if needed.
Address2540 Junction Avenue
Phone1-408-952-2400
Fax1-408-952-2410
Help Hot Line1-800-530-9960 (U.S. only)
Web Addresshttp://www.lgcwireless.com
e-maillgccustomersupport@lgcwireless.com
San Jose, California
95134-1902 USA
+1-408-952-2400 (International)
D-620610-0-20 Rev A
InterReach Fusion Installation, Operation, and Reference Manual9-1
CONFIDENTIAL
Maintenance
9.2Maintenance
Keep the fiber ports clean and free of dust. No other periodic maintenance of the
Fusion equipment is required.
To clean the fiber ports:
You can clean the Hub’s fiber ports using canned compressed air or isopropyl alcohol
and cotton swabs.
Considerations:
• If you use compressed air:
• The air must be free of dust, water, and oil.
• Hold the can level during use.
• If using isopropyl alcohol and foam-tipped swab:
• Use only 98% pure or more alcohol.
Procedure using compressed air:
1.
Remove the connector’s dust cap.
2.
Spray the compressed air away from the unit for a few seconds to clean out the
nozzle and then blow dust particles out of each fiber port.
Procedure using isopropyl alcohol:
1.
Remove the connector’s dust cap.
2.
Dip a 2.5mm lint-free, foam-tipped swab in isopropyl alcohol and slowly insert
the tip into the connector.
3.
Gently twist the swab to clean the connector.
4.
Insert a dry swab to dry the connector.
Additionally, you can use compressed air after the alcohol has completely evaporated.
9-2InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
9.3Troubleshooting
NOTE: Fusion has no user-serviceable parts. Faulty or failed units are fully
replaceable through LGC Wireless.
Sources of potential problems include:
• Faulty cabling/connector
• Malfunction of one or more Fusion components
• Antenna, base station, or repeater problem
• External RF interface
• Tripped circuit breaker
• Equipment is not grounded
• Using an Ethernet crossover cable that does not support full hardware handshaking
when using AdminBrowser
NOTE: Faulty cabling is the cause of a vast majority of problems. All CATV 75
Ohm cable should be tested to TIA-570-B specifications. The RAU will be damaged if the cable connector is not installed properly.
Troubleshooting
You must use AdminBrowser for troubleshooting the system, use the LEDs only as
backup or for confirmation.
If you cannot determine the cause of a problem after following the recommended procedures, call LGC Wireless customer help hot line:
Or, email us at lgccustomersupport@lgcwireless.com.
Please provide the following information:
• Serial number of the unit
• Description of the problem
• Using AdminBrowser 1.00, access Special Features, then the Get Service
Information window. Save and email this file to LGC Wireless.
• What is the length of the CATV cable? What type is it (for example RG-6)?
• Status of the LEDs on the unit
• Was the unit power cycled?
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99609-3
CONFIDENTIAL
Troubleshooting
9.3.1Troubleshooting Using AdminBrowser
Use AdminBrowser software to determine the current faults and warnings for all of
the units in the system. To troubleshoot, start with the Fusion Main Hub’s faults AND
warnings, then proceed to each of the Expansion Hubs, finishing with each of the
RAUs.
NOTE: AdminBrowser v1.00 displays events (faults, warnings, or status
messages) depending on your view preference. To change your view preference, refer to Section 3.3.2, “View Preference,” on page 3-10.
System Troubleshooting
Using AdminBrowser, click
AND STATUSES
. This gives the present status of the system, depending upon View
S
YSTEM INFORMATION
Preferences for all components.
Faults usually impact service; warnings may impact service; status messages contain
information that should not be ignored, but indicate conditions that do not generally
impact service.
NOTE: System commands can take longer to execute compared to component commands.
NOTE: This RAU icon indicates there is fault on the RAU. This icon
indicates a disconnected device. You cannot request status on a discon-
nected device.
9.3.1.1Troubleshooting Recommendations
Some actions that you can take, depending on the device fault or warning include, are
as follows:
, then click
GET F
AULTS
, W
ARNINGS
a.
Hardware faults on Expansion Hub.
– Try swapping fiber with another Expansion Hub at the Main Hub.
– Try cleaning the fiber and the fiber ports with alcohol foam tip swab and
compressed air. See Section , “To clean the fiber ports:,” on page -2.
– Power cycle the Expansion Hub.
b.
Under Alarms, click
C
LEAR ALL DISCONNECTS
at the Fusion Main Hub.
9-4InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
c.
Power cycle the Fusion Main Hub.
d.
RAU hardware faults. Try moving a working CATV to the suspect port and
verifying that the RAU comes up OK.
e.
Try isolating the system components:
– Check to see if the whole system is effected or a portion of the system.
– If the whole system is effected, disconnect the DAS system from the RF
source and see if the RF source is working.
– Continue to isolate by disabling portions of the system. Under System Con-
figuration, click
OUT OF S
S
HOW SYSTEM TREE
ERVICE/SET IN SERVICE
9.3.1.2Fault/Warning/Status Indications
Once all of the units are powered on and the cable connections are made, the faults
from each unit can be requested using AdminBrowser. Start with the Fusion Main
Hub and work downstream.
Resolve all faults first and then check the warnings. Take appropriate action to
resolve the faults, as indicated in the following tables. In cases where there is more
than one possible cause, they are listed from the “most likely” to the “least likely”
cause. Actions are listed in the order that they should be performed; not all actions
may need to be done.
Troubleshooting
and select a component. Then click
.
SET
NOTE: If you have a red
STATUS
LED without a fault message, it probably
indicates that the unit is locked out.
Refer to Appendix C for tables containing Fault, Warning, and Status messages and
their meanings.
9.3.2Troubleshooting Using LEDs
The following troubleshooting guide is from the perspective that all Fusion equipment is installed, their cables are connected, and they are powered on; it is assumed
that the system was operating normally before the problem to be diagnosed occurred.
Always use AdminBrowser, if possible, to troubleshoot the system. The Fusion Main
Hub and Expansion Hub LEDs are for backup troubleshooting. The RAU LEDs probably will not provide additional information for troubleshooting.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99609-5
CONFIDENTIAL
Troubleshooting
9.3.2.1Troubleshooting Main Hub LEDs During Normal Operation
All of the Main Hub’s LEDs should be green during normal operation. If any LEDs
are red, get status using AdminBrowser to determine the exact cause and recommendations.
During
Normal
Operation
Expansion
Hub Not
Connected
Expansion
Hub
Connected
Table 9-1
Troubleshooting Main Hub Port LEDs During Normal Operation
Main Hub
Port LEDsStateActionImpact
PORT
PORT
RedIf the Expansion Hub was discon-
nected accidentally, re-connect the
cables. The LEDs should change to
Green/Red (then Green/Green, after
20 seconds, if the Main Hub band
has been programmed).
When the Expansion Hub is to be
removed from service permanently,
use AdminBrowser’s ‘Clear All Disconnect Status’ command to clear all
disconnect states to no connect
states.
Red 60
ppm)
Use AdminBrowser to determine the
exact cause of the Main Hub’s faults.
The Expansion Hub was previously
connected, but it is not currently connected; the Expansion Hub uplink
cable disconnected.
AdminBrowser clears all disconnects
caused by installation as part of the
clean-up process. After installation,
power cycle the Main Hub or use
AdminBrowser’s “Clear All Disconnect Status” command.
Changes the Main Hub’s port LEDs to
Off/Off.
Lost communication with Expansion
Hub; could be Expansion Hub problem
or fiber cable problem.
The Expansion Hub communication
problems delay MH responses to
AdminBrowser commands, resulting in
command time-outs. You can disconnect the offending Expansion Hub initially to obtain status from the rest of
the system, then connect the Expansion
Hub and resolve the communication
problem.
PORT
RedThe Expansion Hub or connected
RAU reports a fault condition; use
AdminBrowser to determine the
exact cause of the Expansion Hub
Degraded performance or unit may be
off-line.
Depends on fault condition.
and RAU’s faults.
9-6InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Troubleshooting
During
Normal
Operation
At Any
Time
At Any
Time
Table 9-2
Troubleshooting Main Hub Status LEDs During Normal Operation
Main Hub
Status
LEDsStateActionImpact
MAIN HUB
STATUS
RedUse AdminBrowser to determine the
exact cause of the fault.
Internal Main Hub fault.
Power cycle one time. If the fault
remains, replace the Main Hub.
Use AdminBrowser to check if the
Main Hub is commanded
The Main Hub and all downstream
units are off-line.
Out-of-Service (every Expansion
Hub port status LED will be red as
well).
A power cycle will not clear a commanded Out-of-Service, you must
use AdminBrowser to clear this
state.
MAIN HUB
STATUS
Flashing
Red
Reduce input signal power.Signal compression.
(60ppm(
POWER
RedReplace the Main Hub.One or more power supplies are out of
specification.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99609-7
CONFIDENTIAL
Troubleshooting
9.3.2.2Troubleshooting Expansion Hub LEDs During Normal Operation
During
Normal
Operation
RAU is not
connected
RAU is
connected
• All of the Expansion Hub
LINK
and
E-HUB/RAU
LEDs that have RAUs connected
should be Green/Green, indicating that the RAU is powered on, communication is
established, and operation is normal.
• The
POWER, EHUB STATUS, DL STATUS
Table 9-3
Troubleshooting Expansion Hub Port LEDs During Normal
, and
UL STATUS
Operation
Expansion
Hub Port
LEDsStateActionImpact
PORT
PORT
PORT
PORT
OffIf the RAU was disconnected acci-
dentally, re-connect the CATV
cable. The Expansion Hub’s port
LEDs should change to Green/Red
(then Green/Green, after 20 seconds, if the Main Hub is connected,
powered on, and has band programmed).
Use AdminBrowser’s “Clear All
Disconnect Status” command if
you are permanently removing the
RAU from service. The Expansion
Hub’s port LEDs should change to
Off/Off.
RedDisconnect/reconnect the CATV
cable to force power-on reset to the
RAU. If the port LEDs remain Red
check for the exact cause of Expansion Hub faults using AdminBrowser.
Flashing
Red (60
ppm)
The RAU reports a fault condition;
check for the exact cause of Expansion Hub and RAU faults using
AdminBrowser.
Flashing
Red (60
ppm)
The Expansion Hub reports no connection, cable shorts, or a current
port trap condition.
The RAU was previously connected,
but it is not currently connected; the
RAU cable is disconnected.
Lost communications with the RAU.
The RAU could have powered down
due to over current; cable could have
been damaged.
Depends on the fault condition.
Expansion Hub communications with
the RAU. The Expansion Hub is at
fault. The cable could have been damaged. The cable leads may be shorted.
LEDs should all be Green.
9-8InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Troubleshooting
During
Normal
Operation
At Any Time
Table 9-4
Troubleshooting Expansion Hub Status LEDs During Normal
Operation
Expansion
Hub
Status
LEDsStateActionImpact
UL STATUS
DL STATUS
E-H
STATUS
RedCheck uplink fiber for optical loss.
Power cycle Expansion Hub one
time to check uplink laser.
RedCheck the downlink fiber for opti-
cal loss
RedIf either the
STATUS
UL STATUS
or the
are also red, see above.
DL
Cycle power on the Expansion
Hub. If fault remains, replace the
Expansion Hub.
No communications between the Main
Hub and the Expansion Hub.
Uplink laser failure.
No communications with the Main Hub.
Internal Expansion Hub fault (including
either of the above
STATUS
states).
UL STATUS
or
DL
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-99609-9
CONFIDENTIAL
Troubleshooting CATV
9.4Troubleshooting CATV
The following table summarizes CATV problems, as reported by AdminBrowser if a
cable is cut or miswired.
NOTE: Recommended minimum and maximum CATV cable lengths vary
depending upon the type of CATV cable used. Refer to Section 6.1.2, “Cable
and Connector Requirements,” on page 6-2.
Table 9-5
Problem TypeMessageIconImpact
Loose connector, shorted conductor or
improper connection to the
shield.
None
• No communication with RAUn
• Portn UL RF path loss is too high
• The DL RF path loss is too high
• RAUn over current or port short
Summary of CATV Cable Wiring Problems
High phase noise, degraded signal on both
Downlink and Uplink (high bit error rate)
RAU unable to communicate with Hub,
degraded performance or RAU off-line
Increased ripple in the uplink path, decreased
UL gain, or no UL gain
Increased ripple in the downlink path, RAU
off-line
Leave your name and phone number and an LGC Wireless customer service representative will return your call within an hour. Be prepared to provide the following
information when you receive the return call:
• Company name
• End user name
• Type of system, model number, frequency
• Approximate time in service (warranty), sales order number
• Description of problem
• LED status
• AdminBrowser faults, warnings, and status messages
9-10InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
APPENDIX A
Cables and Connectors
A.175 Ohm CATV Cable
• Connects the Expansion Hub to the RAU(s)
• Transmits multiband (downlink) and receives (uplink) IF signals
• Delivers DC electrical power to the RAUs. The Fusion Hub’s DC voltage output is
54V DC nominal. A current limiting circuit is used to protect the Hub if it reaches
its current limit
• Carries configuration and status information
• Use 75 Ohm type-F connectors with captive centerpins
• Lengths:
RG-59:
• Minimum: 0 meters (0 ft.)
• Maximum: 150 meters (492 ft.)
RG-6:
• Minimum: 0 meters (0 ft.)
• Maximum: 170 meters (558 ft.)
RG-11:
• Minimum: 0 meters (0 ft.)
• Maximum: 275 meters (902 ft.)
Recommended minimum and maximum CATV cable lengths vary depending upon
which CATV cable you use.
Be sure to test cable termination before installing the cable.
CommScope CATV cable or equivalent is required:
CommScope 20655V for RG-59. This cable is illustrated in Figure A-1.
CommScope 2279V for RG-6. This cable is illustrated in Figure A-2.
CommScope 2293K for RG-11.This cable is illustrated in Figure A-3.
D-620610-0-20 Rev A
InterReach Fusion Installation, Operation, and Reference ManualA-1
CONFIDENTIAL
Figure A-1
CommScope 2065V for RG-59
A-2InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Figure A-2
CommScope 2279V for RG-6
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960A-3
CONFIDENTIAL
Figure A-3
CommScope 2293K for RG-11
NOTE: LGC Wireless requires solid copper center conductor CATV cable for
proper DC voltage to the RAU and maximum distances.
A-4InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Use the following connectors and tools to prepare the cable ends:
CommScope cable part number: 2065V
Canare part number: F connector FP-C4F
Crimp Tool TC-1, Crimp Die TCD-4C, Cable Strip preparation tool TS100E
CommScope cable part number: 2279V
Canare part number: F connector FP-C55A
Crimp Tool TC-1, Crimp Die TCD-35CA, Cable Strip preparation tool TS100E
CommScope cable part number: 2293V
Canare part number: F connector FP-C71A
Crimp Tool TC-1, Crimp Die TCD-7CA, Cable Strip preparation tool TS100E
If the maximum distance is not required, then copper-clad over steel-center conductor
cable may be used to reduce cable costs.
Table A-2 shows CommScope cable choices of plenum, non-plenum, solid copper
conductor, and copper-clad over-steel conductor cable with their part numbers and
maximum distances.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960A-5
CONFIDENTIAL
Table A-1
System Gain (Loss) Relative to CATV Cable Length (All RAUs except
800/900/1900)
Comm-
Cable
Type
RG-59
RG-6
RG-11
Scope
Part
Number
2065VYesX150210
2022VYesX120120*
5572RNoX110110*
5565NoX150210
2279VYesX170230
2275VYesX170175*
5726NoX170170*
5765NoX170230
2293KYesX275375
2285KYesX275370*
5913NoX275370*
Plenum
Rated
Solid
Copper
Conductor
Copper
Clad
Conductor
Zero-loss
RF
Maximum
Length
(meters)
Distance
Where
RF is
10dB
Below
Input RF
(meters)
* Exceeding the distance of copper-clad cable will result in the attached RAU becoming
non-functional. If the distance of a cable run is at its maximum and is of concern, LGC recommends the use of solid copper cable to ensure successful operation.
A-6InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Table A-2
RAUs
Cable
Type
RG-59
RG-6
RG-11
System Gain (Loss) Relative to CATV Cable Length for 800/900/1900
Distance
Where
CommScope
Part
Number
Plenum
Rated
Solid
Copper
Conductor
Copper
Clad
Conductor
RF
Maximum
Length
(meters)
2065VYesX150210
2022VYesX8080*
5572RNoX7070*
5565NoX150210
2279VYesX170230
2275VYesX115115*
5726NoX110110*
5765NoX170230
2293KYesX275375
2285KYesX240240*
5913NoX240240*
Zero-loss
RF is
10dB
Below
Input RF
(meters)
D-620610-0-20 Rev A
* Exceeding the distance of copper-clad cable will result in the attached RAU becoming non-functional. If
the distance of a cable run is at its maximum and is of concern, LGC recommends the use of solid copper
cable to ensure successful operation.
Help Hot Line (U.S. only): 1-800-530-9960A-7
CONFIDENTIAL
A.2Fiber Optical Cables
• Connects the Main Hub to Expansion Hub(s)
• Transmits (downlink) and receives (uplink) optical signals
• Carries configuration and status information
• Use industry-standard 62.5µm/125µm MMF or Corning SMF-28 fiber, or equivalent.
• SC/APC (angle-polished) connectors are required throughout the fiber network
(port-to-port), including fiber distribution panels
• Distances:
• Multi-mode Fiber: up to 500 m (1,640 ft) – 3 dB optical loss maximum
• Single-mode Fiber: up to
A.3Coaxial Cable
• Connects a Fusion Hub to a repeater or base station (N-type connectors)
• Connects an RAU to a passive antenna (N-type connectors)
6 km (19,685 ft)
– 3 dB optical loss maximum
A-8InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
A.4Standard Modem Cable
DB-9 Connector
Pin
DB-25 Connector
Pin
1
2
3
4
5
6
7
8
9
8
3
2
20
7
6
4
5
22
This cable (PN 4028-10) connects a modem to the Fusion Hub’s front panel serial
port.
Figure A-1
Standard Modem Cable Pinout
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960A-9
CONFIDENTIAL
A.5TCP/IP Cross-over Cable
1 234567 8
Brown
Brown/
White
Blue
Blue/
White
Green/
White
GreenOrange
Orange/
White
Top View of the Wiring Map for Category 5 (CAT 5) UTP Cable
(TIA/EIA 568-A Standard)
Straight Connect
RJ-45 Port
1 2 3 4 5 6 7 8
W-GGW-O
BL
W-BL
O
W-BR
BR
RJ-45 Port
1 2 3 4 5 6 7 8
W-OOW-G
BL
W-BL
G
W-BR
BR
3
61
4
52
7
8
Connector 1
Connector 2
(586A)
(586B)
A TCP/IP cross-over cable (PN 4069-ADB) is used to connect a standard browser PC
to the AdminBrowser with a Fusion Hub. A cable is included with the Fusion Hub.
The pinouts for this cable are illustrated in Figure A-2.
Figure A-2
Wiring Map for TCP/IP Cable
A-10InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
A.6DB-25 to DB-9 Null Modem Cable
Note that for each DB-9 connector, pins 1 and 6 are tied together and sent to pin 4
of the opposite connector, providing the required handshake signals.
DB-9
Connector
Pin
DB-9
Connector
Pin
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
Use a DB-9 female to DB-9 female null modem cable to connect the craft person’s
PC/Laptop to the RS-232 port on the front of the Fusion Hub for IP address configuration. Table A-3 lists the cable pinout and Figure A-3 shows a diagram of its wiring.
Table A-3
FromSignalToSignal
P1-4DTRP2-6, P2-1DSR, DCD
P1-6DSRP1-1, P2-4DCD, DTR
P1-3TXDP2-2RXD
P1-2RXDP2-3TXD
P1-5GNDP2-5GND
P1-7RTSP2-8CTS
P1-8CTSP2-7RTS
P1-9N/CN/CN/C
Figure A-3
DB-9 Female to DB-9 Female Null Modem Cable Pinout
DB-9 Female to DB-9 Female Null Modem Cable Diagram
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960A-11
CONFIDENTIAL
A-12InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.