ADC FSN-809019-2 User Manual

SECTION 7
Installing Fusion
This section contains the following subsections:
• Section 7.1 Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
• Section 7.2 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
• Section 7.4 Fusion Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
• Section 7.5 Splicing Fiber Optic Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-37
• Section 7.6 Interfacing the Fusion Main Hub to an RF Source . . . . . . . . . . 7-39
• Section 7.7 Connecting Contact Alarms to a Fusion System . . . . . . . . . . . . 7-49
• Section 7.8 Alarm Monitoring Connectivity Options . . . . . . . . . . . . . . . . . . 7-57
D-620610-0-20 Rev A
7.1 Installation Requirements
Before and during installation, keep in mind these sources of potential problems:
• Faulty cabling/connector
• Dirty connectors and ports
• Malfunction of one or more Fusion components
• Antenna, base station, or repeater problem
• External RF interface
• Tripped circuit breaker
• Equipment is not grounded
• Using a crossover Ethernet cable that does not support full hardware handshaking when using AdminBrowser
InterReach Fusion Installation, Operation, and Reference Manual 7-1
CONFIDENTIAL
Installation Requirements
7.1.1 Component Location Requirements
7.1.2 Cable and Connector Requirements
NOTE: Faulty cabling is the cause of a vast majority of problems. All CATV cable
should be tested to TIA-570-B specifications.
Fusion components are intended to be installed in indoor locations only.
If outdoor installation is desired, such as a parking garage, the Fusion components must be installed in the appropriate environmental enclosures.
Fusion equipment operates over the following:
• CATV 75 Ohm cable with F connectors
• Single-mode fiber (SMF) or multi-mode (MMF) cable with SC/APC fiber connec­tors throughout the fiber network, including fiber distribution panels
These cables are widely-used, industry standards for the cable TV industry. The regu­lations and guidelines for Fusion cable installation are identical to those specified by the TIA/EIA 568-B standard and the TIA/EIA/570-A standards.
LGC Wireless recommends solid copper center conductor, plenum-rated CATV cable and connectors for conformity to building codes, standards, and to ensure stated per­formance of maximum distance and RF specifications.
CommScope 2065V cable or equivalent is required for RG-59.
CommScope 2279V cable or equivalent is required for RG-6.
CommScope 2293K cable may also be used for RG-11.
NOTE: Refer to Appendix A for more information related to 75 Ohm CATV.
LGC Wireless recommends connectors with fixed centerpins to ensure proper seating and to eliminate oxidation, which occurs with bare center conductors. Recommended connectors are as follows:
CANARE Connectors
• FP-C4F for commScope 2065V cable
• FP-C55A for CommScope 2279V cable
• FP-C71A for CommScope 2293K cable
7-2 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
NOTE: The proper crimp tool and die must be matched by the connector type.
7.1.3 Distance Requirements
Table 7-1 shows the distances between Fusion components and related equipment.
Safety Precautions
Table 7-1
Equipment Combination Cable Type Cable Length Additional Information
Repeater/BTS to Fusion Main Hub
Fusion Expansion Hub to RAU
Main Hub to Expan­sion Hub
RAU to passive antenna
Coaxial; N male connectors
CATV 75 Ohm; shielded F male con­nectors
Multi-mode fiber: Single-mode fiber: SC/APC male con­nectors
Coaxial; N male connectors
Distance Requirements
3–6 m (10–20 ft) typical Limited by loss and noise.
Refer to your link budget calculation.
10 m (33 ft) maximum Limited by CE Mark require-
ments.
• Minimum: 10 meters (33 ft)
• Maximum: 150 meters (492 ft) for RG-59; 170 meters (558 ft) for RG-6; 275 meters (902 ft) for RG-11
Refer to Table 5-1 and Table 5-2.
500 m (1640 ft.) maximum
6 km (19,685 ft.) maximum
1–3.5 m (3–12 ft) typical Limited by loss and noise.
Refer to “System Gain” on page 6-11.
Limited by 3 dB optical attenuation
Refer to your link budget calculation.
D-620610-0-20 Rev A
7.2 Safety Precautions
7.2.1 Installation Guidelines
Use the following guidelines when installing LGC Wireless equipment:
1.
Provide sufficient airflow and cooling to the equipment to prevent heat build-up from exceeding the maximum ambient air temperature specification. Do not com­promise the amount of airflow required for safe operation of the equipment.
2.
If you are removing the system, turn it off and remove the power cord first. There are no user-serviceable parts inside the components.
Help Hot Line (U.S. only): 1-800-530-9960 7-3
CONFIDENTIAL
Safety Precautions
3.
The internal power supplies have internal fuses that are not user replaceable. Con­sider the worst-case power consumption shown on the product labels when provi­sioning the equipment’s AC power source and distribution.
4.
Verify that the Hub is grounded properly using the AC power cord third wire ground.
NOTE: Be careful with the mechanical loading of the rack mounted hub. Mount the equipment in the rack in such a way that a hazardous condition, due to uneven mechanical loading, does not result,.
7.2.2 General Safety Precautions
The following precautions apply to LGC Wireless products:
• The units have no user-serviceable parts. Faulty or failed units are fully replaceable through LGC Wireless. Please contact us at:
1-800-530-9960 (U.S. only) +1-408-952-2400 (International)
• Although modeled after an Ethernet/LAN architecture and connectivity, the units are not intended to connect to Ethernet data hubs, routers, cards, or other similar data equipment.
• When you connect the fiber optic cable, take the same precaution as if installing Ethernet network equipment. All optical fiber SC/APC connectors should be cleaned according to the cable manufacturer’s instructions.
• When you connect a radiating antenna to an RAU, firmly hand-tighten the N con­nector – DO NOT over-tighten the connector.
WARNING: To reduce the risk of fire or electric shock, do not expose this equipment to rain or moisture. The components are intended for indoor use only. Do not install the RAU outdoors. Do not connect an RAU to an antenna that is located outdoors where it could be subject to lightning strikes, power crosses, or wind.
• The Expansion Hub and RAU units are designed for intra-building cabling only. Outdoor routing of any cabling to these units shall not exceed 140 feet.
NOTE: Outdoor cables farther than 140 feet must be installed with proper lightning protection.
7-4 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
7.2.3 Fiber Port Safety Precautions
This mark appears on the front panel of the Main Hub and the Expansion Hub.
CLASS 1
LASER PRODUCT
CLASS 1
LASER PRODUCT
The following are suggested safety precautions for working with fiber ports. For information about system compliance with safety standards, refer to Appendix B.
WARNING: Observe the following warning about viewing fiber ends in ports. Do not stare with unprotected eyes at the connector ends of the fibers or the ports of the hubs. Invisible infrared radia­tion is present at the front panel of the Main Hub and the Expansion Hub. Do not remove the fiber port dust caps unless the port is going to be used. Do not stare directly into a fiber port.
Test fiber cables: When you test fiber optic cables, connect the optical power source last and disconnect it first. Use Class 1 test equipment.
Fiber ends: Cover any unconnected fiber ends with an approved cap. Do not use tape.
Broken fiber cables: Do not stare with unprotected eyes at any broken ends of the fibers. Laser light emitted from fiber sources can cause eye injury. Avoid contact with broken fibers; they are sharp and can pierce the skin. Report any broken fiber cables and have them replaced.
Cleaning: Be sure the connectors are clean and free of dust or oils. Use only approved methods for cleaning optical fiber connectors.
Modifications: Do not make any unauthorized modifications to this fiber optic system or associated equipment.
Live work: Live work is permitted because LGC Wireless equipment is a Class 1 hazard.
Signs: No warning signs are required.
Safety Precautions
D-620610-0-20 Rev A
Class 1 laser product: The system meets the criteria for a Class 1 laser product per IEC 60825-1: 1993+A1:+A2:2001 and IEC106825-2.
Complies with 21 CFR 1040.10 and 1040.11 except for deviations pursuant to Laser Notice No. 50, dated July 26, 2001.
The hazard level at all locations within the equipment is Hazard Level 1.
CAUTION: Use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure.
Help Hot Line (U.S. only): 1-800-530-9960 7-5
CONFIDENTIAL
Preparing for System Installation
7.3 Preparing for System Installation
7.3.1 Pre-Installation Inspection
7.3.2 Installation Checklist
Follow this procedure before installing Fusion equipment:
1.
Verify the number of packages received against the packing list.
2.
Check all packages for external damage; report any external damage to the ship­ping carrier. If there is damage, a shipping agent should be present before you unpack and inspect the contents because damage caused during transit is the responsibility of the shipping agent.
3.
Open and check each package against the packing list. If any items are missing, contact LGC Wireless customer service (refer to Section 7.2.2 on page 7-4).
4.
If damage is discovered at the time of installation, contact the shipping agent.
Table 7-2
Installation Requirement Consideration
Floor Plans Installation location of equipment clearly marked
System Design Used to verify frequency bands after installation
Power available:
Fusion Main Hub (AC) Fusion Expansion Hub (AC) To RAU (DC)
Rack space available (Main and Expansion Hub)
Wallmount Fusion Main Hub Hub must be mounted on 3/4” plywood backboard.
Clearance for air circulation:
Fusion Main or Expansion Hub RAU
Suitable operating environment:
Fusion Main or Expansion Hub RAUs
Donor Antenna-to-Fusion Configuration (for each Fusion Band)
Donor Antenna Installed, inspected; N-male to N-male coaxial cable to lightning arrestor/surge
Lightning Arrestor or Surge Suppressor
Repeater Installed between lightning arrestor/surge suppressor and Hub; N-male to N-male
Installation Checklist
Hub’s power cord is 2 m (6.5 ft) long. 115/230V, 2/1A, 50–60 Hz 115/230V, 6/3A, 50-60 Hz 54V (from the Hub)
89 mm (3.5 in.) high (2U)
76 mm (3 in.) front and rear, 51 mm (2 in.) sides 76 mm (3 in.) all around
Indoor location only 0° to +45°C (+32° to +113°F) 5% to 95% non-condensing humidity
–25° to +45°C (–13° to +113°F) 5% to 95% non-condensing humidity
suppressor
Installed between roof-top antenna and repeater; N-male to N-male 50 Ohm coax­ial cable and outdoor cables longer than 140 feet.
coaxial cable. The Repeater must be a UL listed product.
7-6 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Preparing for System Installation
Table 7-2
Installation Requirement Consideration
Installation Checklist (continued)
Attenuator Installed between the circulator and the Hub downlink port to prevent overload.
Optionally, it may be installed between the uplink port and the circulator.
Circulator or Duplexer Installed between the repeater and the Hub uplink and downlink ports
Base Station-to-Fusion Configuration (for each Fusion Band)
Base Station Installed, inspected; verify RF power (see tables in Section 6.3 on page 6-4);
N-male to N-male coaxial cable
Attenuator Attenuation may be required to achieve the desired RF output at the RAU, and the
desired uplink noise floor level
Circulator or Duplexer When using a duplex BTS: Installed between the BTS and the Hub uplink and
downlink ports. Not used with a simplex BTS
Connecting Multiple Fusion Main Hubs Together
5-port Alarm Daisy-Chain Cable (PN 4024-3)
For contact alarm monitoring of fault and warning alarms. Used to feed the alarms from multiple Fusion Main Hubs into a BTS or MetroReach Focus. N.C. Opera­tion.
Cabling
Coaxial: repeater, base station,
Coax approved; N-type male connectors. Smart Source to Fusion Main Hub
Coaxial: RAU to passive antennas
Fiber: Main Hub to Expansion Hubs
Use low-loss cable; N male connector; typical 1 m (3.3 ft) using RG142 coaxial
cable.
SC/APC (angle-polished) male connectors for entire fiber run (can use SC/APC
pigtails, PN 4012SCAPC-10 for MMF or 4013SCAPC-10 for SMF);
Use jumper fiber cables for collocated Main and Expansion Hubs (3 m/10 ft.):
Multi-mode: PN 401SCAPC-10 Single-mode: PN 4018SCAPC-10
Distance limited by optical loss of 3 dB
Multi-mode up to 500 m (1640 ft.) Single-mode up to 6 km (19,685 ft.)
CATV TIA-570-B approved; centerpin F male connectors. CATV cable must be screened
and it must be grounded at both connector ends. The RAU will be damaged if it is
mis-wired.
Tie-off cables to avoid damaging the connectors because of cable strain.
Fusion Expansion Hub to RAUs • Minimum: 0 meters (0 ft)
• Maximum: RG-59: 150 meters (472 ft) *
RG-8: 170 meters (558 ft)
RG-11: 275 meters (902 ft)
* Refer to Appendix A for CATV cable requirements.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960 7-7
CONFIDENTIAL
Preparing for System Installation
Table 7-2
Installation Requirement Consideration
Installation Checklist (continued)
Configuring the System
PC/laptop running
Refer to the AdminBrowser User Manual (PN D-620607-0020) standard browser software
Miscellaneous
Cross-over Ethernet cable Male connectors; Fusion Main Hub to a PC/laptop running a standard browser to
the Fusion AdminBrowser software; local connection or LAN switch connector
for remote connections.
Straight-through cable Female/male connectors; Fusion Main Hub to a modem for a remote connection.
Distances
Fusion Main Hub is within 3–6m (10–20 ft) of connecting repeater/BTS/MetroReach
If longer distance, determine the loss of the cable used for this connection and
adjust the RF signal for each Band into the Fusion Main Hub accordingly. This can
be done by readjusting the power from the base station, or by changing the attenu-
ation value between the base station/repeater and the Hub Bands (1 and 2).
7.3.3 Tools and Materials Required
Table 7-3
Tools and Materials Required for Component Installation
Description
Cable ties
Screwdriver
Mounting screws and spring nuts
Screws, anchors (for mounting RAUs)
Drill
Fiber connector cleaning kit
Fusion splicer
Splicing tool kit (including snips, cladding strippers, fiber cleaver, isopropyl alcohol, lint-free wipes)
Fusion splicing sleeves
7-8 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
7.3.4 Optional Accessories
Preparing for System Installation
Table 7-4
Optional Accessories for Component Installation
Description
Wall-mount bracket (PN 4712)
When using this bracket with an Fusion Main Hub, the Hub’s mounting bracket must be moved to the alternate mounting position (refer to the procedure on page page 7-11).
Cable management (Cable manager: PN 4759; Tie wrap bar: PN 4757)
Splice trays
Pigtails with SC/APC connectors, 3 m (10 ft.)
Multi-mode fiber SC/APC pigtail: PN 402SCAPC-10 Single-mode fiber SC/APC pigtail: PN 4013SCAPC-10
Jumper cable when Main and Expansion Hubs are collocated, 3 m (10 ft.)
Multi-mode fiber SC/APC: PN 4018SCAPC-10
Teltone Line Sharing Switch (M-394-B-01)
When using a single POTS line with multiple Fusion Main Hub/Modems: Connect up to four modems to a line sharing switch; switches can be cascaded to accommodate up to 16 modems per POTS line
Alarm Cables:
5-port Alarm Daisy-Chain Cable (PN 4024-3) Alarm Sense Adapter Cable (PN 4025-1)
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960 7-9
CONFIDENTIAL
Fusion Installation Procedures
7.4 Fusion Installation Procedures
The following procedures assume that the system is new from the factory and that it has not been programmed with bands.
If you are replacing components in a pre-installed system with either new units or units that may already be programmed (for example, re-using units from another sys­tem), refer to Section 8.
• Installing a Fusion Main Hub . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
• Installing a Fusion Main Hub in a Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
• Using the Wall Rack-Mounting Option . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-13
• Installing an Optional Cable Manager in the Rack . . . . . . . . . . . . . . . . . . 7-12
• Installing a Main Hub Using the 12” Wall-Mounted Rack (PN 4712) . . . 7-12
• Installing a Fusion Main Hub Directly to the Wall . . . . . . . . . . . . . . . . . . 7-14
• Connecting the Fiber Cables to the Main Hub . . . . . . . . . . . . . . . . . . . . . . 7-15
• Powering On the Main Hub . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18
• Installing Expansion Hubs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20
• Installing an Expansion Hub in a Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-20
• Installing an Expansion Hub Using the 12” Wall-Mounted Rack . . . . . . . 7-21
• Installing a Fusion Expansion Hub Directly to the Wall . . . . . . . . . . . . . . 7-22
• Installing an Optional Cable Manager in the Rack . . . . . . . . . . . . . . . . . . 7-23
• Powering On the Expansion Hub . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23
• Connecting the Fiber Cables to the Expansion Hub . . . . . . . . . . . . . . . . . . 7-24
• Connecting the 75 Ohm CATV Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-25
• Troubleshooting Expansion Hub LEDs During Installation . . . . . . . . . . . 7-26
• Installing RAUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27
• Installing RAUs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27
• Installing Passive Antennas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27
• Connecting the Antenna to the RAU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-29
• Connecting the CATV Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-29
• Troubleshooting Using RAU LEDs During Installation . . . . . . . . . . . . . . 7-30
• Installing RAUs in a Multiple Operator System . . . . . . . . . . . . . . . . . . . . 7-31
• Configuring the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-31
• Connecting the PC to the Fusion Main Hub to Run AdminBrowser . . . . . 7-31
• Programming the Fusion Main Hub Using AdminBrowser . . . . . . . . . . . . 7-32
• Fusion Splicing of Fiber and Pigtail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-37
7-10 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
The following procedures assume that the system is installed and programmed.
• Interfacing the Fusion Main Hub to an RF Source . . . . . . . . . . . . . . . . . . . . . 7-39
• Connecting a Single Fusion Main Hub to an RF Source . . . . . . . . . . . . . . 7-39
• Connecting a Fusion Main Hub to a Roof-top Antenna . . . . . . . . . . . . . . . 7-43
• Connecting Multiple Fusion Main Hubs to an RF Source . . . . . . . . . . . . . 7-44
• Connecting Multiple Fusion Main Hubs to a Duplex Repeater or BTS . . 7-47
• Connecting Contact Alarms to a Fusion System . . . . . . . . . . . . . . . . . . . . . . . 7-49
• Alarm Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-50
• Alarm Sense . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-53
• Alarm Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-55
• Alarm Monitoring Connectivity Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-57
• Direct Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-57
• Modem Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-58
• 100 BASE-T Port Expander Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 7-67
• POTS Line Sharing Switch Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-68
• Ethernet LAN Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-70
• SNMP Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-71
7.4.1 Installing a Fusion Main Hub
CAUTION: Install Fusion Main Hubs in indoor locations only.
Installing a Fusion Main Hub in a Rack
The Fusion Main Hub (2U high) mounts in a standard 19 in. (483 mm) equipment rack. Allow clearance of 76 mm (3 in.) front and rear, and 51 mm (2 in.) on both sides for air circulation. No top or bottom clearance is required.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960 7-11
CONFIDENTIAL
Fusion Installation Procedures
Figure 7-1
Flush Mounting Bracket Detail
Consideration:
• The Fusion Main Hub is shipped with #10-32 mounting screws. Another common rack thread is #12-24. Confirm that the mounting screws match the rack’s threads.
To install the Hub in a rack:
1.
Insert spring nuts into rack where needed or use existing threaded holes.
2.
Place the Hub into the rack from the front.
3.
Align the flange holes with the spring nuts installed in Step 1.
4.
Insert the mounting screws in the appropriate positions in the rack.
5.
Tighten the mounting screws.
Installing an Optional Cable Manager in the Rack
• Using the screws provided, fasten the cable manager to the rack, immediately above or below the Main Hub.
Installing a Main Hub Using the 12” Wall-Mounted Rack (PN 4712)
Considerations:
• The rack-mounting brackets on the Fusion Main Hub must be moved to the recessed mounting position (shown in Figure 7-2) to allow for the required 76 mm (3 in.) rear clearance.
7-12 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
• The maximum weight the bracket can hold is 22.5 kg (50 lbs).
• The bracket is designed to accommodate a Fusion Main Hub (12 lbs.) or an Expan­sion Hub (14.5 lbs.).
• The wall mount bracket should be securely mounted to wall, using the four key slot mounting holes on the bracket.
Using the Wall Rack-Mounting Option
You can flip the rack mounting brackets, as shown in Figure 7-2, so the hub can be mounted 76 mm (3 in.) forward in the rack.
Figure 7-2
Bracket Detail For Wall Mount Rack (PN 4712)
To install the Hub to the wall-mounted rack:
1.
Attach the wall bracket (PN 4712) to wall the using #10 Pan Head wood screws, 1-1/2” minimum length for mounting in wood studs or 3/4“thick plywood.
The bracket must be positioned so that the Hub will be in a horizontal position when it is installed. (Refer to Figure 7-2.)
D-620610-0-20 Rev A
NOTE: If wall stud spacing of 16” is not available, LGC recommends that 3/4” plywood be pre-installed to the wall. You can then attach the bracket to the plywood using the wood screws.
2.
Remove both of the rack mounting brackets from the Hub.
3.
Reattach each of the rack mounting brackets to the recessed wall mount position.
4.
Install the Hub in the rack using the rack mounting screws.
Help Hot Line (U.S. only): 1-800-530-9960 7-13
CONFIDENTIAL
Fusion Installation Procedures
Installing a Fusion Main Hub Directly to the Wall
To install the Hub directly to the wall:
1.
Pre-install 3/4” plywood to the wall.
2.
Mount both of the rack mounting brackets using #10-32 machine screws (refer to illustration Figure 7-4).
3.
Attach the Hub to the wall so the mounting brackets are orientated at the top and bottom of the wall mounted hub. (Refer to Figure 7-3.)
Figure 7-3
Installing Directly to the Wall
Use two #10 Pan Head wood screws, 1-1/2” length, to secure each bracket to the plywood. In this orientation the enclosure fans shall face to the left.
7-14 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
Figure 7-4
Using Hub Rack-Mounting Brackets for Direct Wall Installation
Connecting the Fiber Cables to the Main Hub
Considerations:
• Before connecting the fiber cables, confirm that their optical loss does not exceed the 3 dB optical budget.
• If you are using fiber distribution panels, confirm that the total optical loss of fiber cable, from the Main Hub through distribution panels and patch cords to the Expansion Hub, does not exceed the optical budget.
• Make sure the fiber cable’s connectors are SC/APC (angle-polished). Using any other connector type will result in degraded system performance and may damage the equipment. (You can use an SC/APC pigtail if the fiber cable’s connectors are not SC/APC. Refer to“Fusion Splicing of Fiber and Pigtail” on page 7-37. Or, you can change the fiber’s connector to SC/APC.)
NOTE: Observe all Fiber Port Safety Precautions listed in Section 7.2.3 on page 7-5.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960 7-15
CONFIDENTIAL
Fusion Installation Procedures
To clean the fiber ports:
You can clean the Hub’s fiber ports using canned compressed air or isopropyl alcohol and foam tipped swabs.
Considerations:
• If using compressed air:
• The air must be free of dust, water, and oil.
• Hold the can level during use.
• If using isopropyl alcohol and foam tipped swabs:
• Use only 98% pure or more alcohol
Procedure using compressed air:
1.
Remove the port’s dust cap.
2.
Spray the compressed air away from the unit for a few seconds to clean out the nozzle and then blow dust particles out of each fiber port.
Procedure using isopropyl alcohol:
1.
Remove the connector’s dust cap.
2.
Dip a 2.5mm lint-free, foam-tipped swab in isopropyl alcohol and slowly insert the tip into the connector.
3.
Gently twist the swab to clean the port.
4.
Insert a dry swab into the port to dry it.
Additionally, you can use compressed air after the alcohol has completely evapo­rated.
To clean the fiber ends:
Be sure that the fiber cable’s SC/APC connectors are clean and free of dust and oils. You need lint-free cloths, isopropyl alcohol, and compressed air
1.
Moisten a lint-free cloth with isopropyl alcohol.
2.
Gently wipe the fiber end with the moistened cloth.
3.
Using a dry lint-free cloth, gently wipe the fiber end.
4.
Spray the compressed air away from the connector for a few seconds to clean out the nozzle and then use it to completely dry the connector.
To test the fiber cables:
Perform cable testing and record the results. Test results are required for the final As-Built Document.
To connect the fiber cables:
The fiber cable is labeled with either 1 or 2, or is color-coded. In addition to these labels, you should add a code that identifies which port on the Main Hub is being
7-16 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
used and which Expansion Hub the cables are intended for. This differentiates the connectors for proper connection between the Main Hub and Expansion Hubs.
For example: First pair to Main Hub port 1: 11 (uplink), 12 (downlink); Second pair to Main Hub port 2: 21 (uplink), 22 (downlink); Third pair to Main Hub port 3: 31 (uplink), 32 (downlink); and so on.
If the fiber jumper is labeled with 1 or 2:
1.
Connect 1s to
2.
Connect 2s to
3.
Record which cable number and port number you connected to
DOWNLINK
UPLINK
DOWNLINK
.
ports on the Main Hub.
ports on the Main Hub.
UPLINK
and
This information is needed when connecting the other end of the fiber cable to the Expansion Hub’s fiber ports.
The fiber port LEDs should be off, indicating that the Expansion Hub(s) are not connected.
If the fiber jumper is color-coded (for example, “blue” or “red”):
1.
Connect “blue” to
2.
Connect “red” to
3.
Record which color and port number you connected to
UPLINK
ports on the Main Hub.
DOWNLINK
ports on the Main Hub.
UPLINK
and
DOWNLINK
This information is needed when connecting the other end of the fiber cable to the Expansion Hub’s fiber ports.
The fiber port LEDs should be off, indicating that the Expansion Hub(s) are not connected.
.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960 7-17
CONFIDENTIAL
Fusion Installation Procedures
Powering On the Main Hub
1.
Connect the AC power cord to the Main Hub.
2.
Plug the power cord into an AC power outlet.
3.
Turn on the power to the Main Hub and check that all the LED lamps are func­tioning properly.
Upon power-up, the LEDs blinks for five seconds as a visual check that they are functioning. After the five-second test:
LED states during power on will vary, depending on whether Expansion Hubs are connected. Refer to Table 7-5 for possible combinations.
Table 7-5
Troubleshooting Main Hub LEDs During Installation
During Installation Power On LED State Action Impact
1.
Main Hub power is On with no Expansion Hubs con­nected.
POWER
POWER
PORT
Off Check AC power; check that the Main Hub power-on
switch is on; replace the Main Hub
The Main Hub is not powering on.
Red Replace the Main Hub The power supply is
out-of-specification.
LEDs are on but they didn’t blink through all
Replace the Main Hub. The micro controller is
not resetting properly; flash memory cor­rupted.
states
PORT
Red The port is unusable; replace the Main Hub when
Off
possible.
Fiber sensor fault, do not use the port.
7-18 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
Table 7-5
Troubleshooting Main Hub LEDs During Installation (continued)
During Installation Power On LED State Action Impact
2.
Main Hub power is On with Expansion Hubs con­nected and powered on.
PORT
Off • If the port LEDs do not illuminate, check the fiber
uplink for excessive optical loss.
• If Expansion Hub’s
DL STATUS
LED is red:
• Verify that the fiber is connected to the correct port (that is, uplink/downlink)
• Swap the uplink and downlink cables.
• Connect the fiber pair to another port. If the sec-
No uplink optical power, the Expansion Hub is not recognized as being present.
No communication with the Expansion Hub.
ond port’s LEDs do not illuminate Green/Red, replace the Main Hub.
• If the second port works, flag the first port as unusable; replace the Main Hub when possible.
PORT
Red (60 ppm) • If the Expansion Hub
check the downlink fiber cable for excessive opti­cal loss.
DL STATUS
LED is red,
No communication with the Expansion Hub.
• Connect the fiber pair to another port. If the sec­ond port’s LEDs do not illuminate Green/Red, replace the Main Hub.
• If the second port works, flag the first port as
unusable; replace the Main Hub when possible.
PORT
Red The Expansion Hub or connected RAU reports a fault
Use AdminManager to determine the problem.
The Expansion Hub or one or more RAUs are off-line.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960 7-19
CONFIDENTIAL
Fusion Installation Procedures
7.4.2 Installing Expansion Hubs
The Expansion Hub (2U high) can be installed in a standard 19 in. (483 mm) equip­ment rack or in a wall-mountable equipment rack that is available from LGC Wire­less. Allow a clearance of 76 mm (3 in.) front and rear and 51 mm (2 in.) sides for air circulation. No top and bottom clearance is required.
CAUTION: Install Expansion Hubs in indoor locations only.
Installing an Expansion Hub in a Rack
Consideration:
• The Expansion Hub is shipped with #10-32 mounting screws. Another common rack thread is #12-24. Confirm that the mounting screws match the rack’s threads.
Figure 7-5
Flush Mounting Bracket Detail
To install the hub in a rack:
1.
Insert spring nuts into the rack where needed or use existing threaded holes.
2.
Place the Expansion Hub into the rack from the front.
3.
Align the flange holes with the spring nuts installed in Step 1.
4.
Insert the mounting screws in the appropriate positions in the rack.
5.
Tighten the mounting screws.
7-20 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
Installing an Expansion Hub Using the 12” Wall-Mounted Rack
Considerations:
• The rack (PN4712) is 305 mm (12 in.) deep. The Expansion Hub is 381 mm (15 in.) deep. You must move the rack mounting brackets on the Expansion Hub, as shown in Figure 7-6) to the center mounting position to allow for the 76 mm (3 in.) rear clearance that is required.
• The maximum weight the rack can hold is 22.5 kg (50 lbs).
Figure 7-6
Bracket Detail For Wall Mount Rack (PN 4712)
To install the hub in a wall-mounted rack:
1.
Attach the equipment rack to the wall using the screws that are provided.
The rack must be positioned so that the Expansion Hub will be in a horizontal position when it is installed.
D-620610-0-20 Rev A
NOTE: If wall stud spacing of 16” is not available, LGC recommends that 3/4” plywood be pre-installed to the wall. You can then attach the bracket to the plywood using the wood screws.
2.
Remove both of the rack mounting brackets from the Hub.
3.
Reattach each of the rack mounting brackets to the recessed wall mount position (Figure 7-6).
4.
Install the Hub in the rack using the rack mounting screws.
5.
Tighten the mounting screws.
Help Hot Line (U.S. only): 1-800-530-9960 7-21
CONFIDENTIAL
Fusion Installation Procedures
Installing a Fusion Expansion Hub Directly to the Wall
To install the Hub directly to the wall:
1.
Pre-install 3/4” plywood to the wall.
2.
Mount both of the rack mounting brackets using #10-32 machine screws (refer to illustration Figure 7-7).
3.
Attach the Hub to the wall so the mounting brackets are orientated at the top and bottom of the wall mounted hub. (Refer to Figure 7-8.)
Figure 7-7
Using Hub Rack-Mounting Brackets for Direct Wall Installation
7-22 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
Figure 7-8
Installing Directly to the Wall
D-620610-0-20 Rev A
NOTE: Leave the dust caps on the fiber ports until you are ready to connect the fiber optic cables.
Installing an Optional Cable Manager in the Rack
• Using the screws provided, fasten the cable manager to the rack, immediately above or below the Expansion Hub.
Powering On the Expansion Hub
1.
Connect the AC power cord to the Expansion Hub.
2.
Plug the power cord into an AC power outlet.
Help Hot Line (U.S. only): 1-800-530-9960 7-23
CONFIDENTIAL
Fusion Installation Procedures
3.
Turn on the power to the Expansion Hub and check that all the LED lamps are functioning properly.
Upon power-up, the LEDs blinks for five seconds as a visual check that they are functioning. After the five-second test:
• The
POWER
and
UL STATUS
LEDs should be green.
– If the uplink fiber is not connected, the
UL STATUS
LED turns red indicating
that there is no communication with the Main Hub.
• The
E-HUB STATUS
and
DL STATUS
LEDs should be red.
• All port LEDs should be off because no RAUs are connected yet.
Connecting the Fiber Cables to the Expansion Hub
Considerations:
• Before connecting the fiber cables, confirm that their optical loss does not exceed 3 dB optical budget. RL is less than -60dB.
• If fiber distribution panels are used, confirm that the total optical loss of fiber cable, from the Main Hub through distribution panels and patch cords to the Expansion Hub, does not exceed the optical budget.
• Make sure the fiber cable’s connectors are SC/APC (angle-polished).Using any other connector type will result in degraded system performance and may damage the equipment. (You can use an SC/APC pigtail if the fiber cable’s connectors are not SC/APC, refer to “Fusion Splicing of Fiber and Pigtail” on page 7-37, or replace the connectors.)
NOTE: Observe all Fiber Port Safety Precautions listed in Section 7.2.3 on page 7-5.
To connect the fiber cables:
The fiber cable is labeled with either 1 or 2, or is color-coded. For proper connection between the Main Hub ports and the Expansion Hub ports, refer to the numbering or color-coded connections you recorded when installing the Main Hub(s).
If the fiber jumper is labeled with 1 or 2:
1.
Connect 2 to
The
DL STATUS
not, there is a downlink problem. Make sure you are connecting the correct cable to the port.
2.
Connect 1 to
The
UL STATUS
take up to 20 seconds to establish communication.
The Expansion Hub’s it the frequency band command.
7-24 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
DOWNLINK
on Expansion Hub.
LED should turn green as soon as you connect the fiber. If it does
UPLINK
on Expansion Hub.
LED turns green on the first Main Hub communication. It may
E-HUB STATUS
LED turns green when the Main Hub sends
D-620610-0-20 Rev A
Fusion Installation Procedures
If the
UL STATUS
and
E-HUB STATUS
LEDs do not turn green/green, check the
Main Hub LEDs. Refer to page 7-18, item 2 in Table 7-5.
If the fiber jumper is color-coded (for example, “blue” or “red”):
1.
Connect “red” to
The
DL STATUS
DOWNLINK
on Expansion Hub.
LED should turn green as soon as you connect the fiber. If it does not, there is a downlink problem. Make sure you are connecting the correct cable to the port.
2.
Connect “blue” to
The
UL STATUS
UPLINK
on Expansion Hub.
LED turns green on the first Main Hub communication. It may take up to 20 seconds to establish communication.
The Expansion Hub’s
E-HUB STATUS
LED turns green when the Main Hub sends
it the frequency band command.
If the
UL STATUS
and
E-HUB STATUS
LEDs do not turn green/green, check the
Main Hub LEDs. See page 7-18, item 2 in Table 7-5.
Connecting the 75 Ohm CATV Cables
Considerations:
• Verify that the cable has been tested and the test results are recorded. This informa­tion is required for the As-Built Document.
• Verify that only captive centerpin F connectors are used on the solid copper center conductor CATV cable from CommScope (or equivalent).
• Verify that the CATV cable is labeled with:
• Fusion Expansion Hub port number being used
• RAU identifier
• Carrier (for multiple operator systems)
To connect the CATV cables:
1.
Connect the CATV cables to the F ports according to the labels on the cables.
The
STATUS
LEDs should be off because the RAUs are not connected at the other
end of the CATV cable.
2.
Record which cable you are connecting to which port (that is, from the label on the cable).
This information is required for the As-Built Document.
3.
Tie-off the cables or use the optional cable manager to avoid damaging the con­nectors because of cable strain.
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960 7-25
CONFIDENTIAL
Fusion Installation Procedures
Troubleshooting Expansion Hub LEDs During Installation
• All Expansion Hub
PORT
LEDs with RAUs connected should indicate Green/Red. This indicates that the RAU is powered on and communication has been estab­lished.
• The Expansion Hub
Table 7-6
During Installation LED State Action Impact
1.
Expansion
POWER
Off Check AC power; make sure the Hub power is On and no RAUs are connected
PORT
LEDs are on but
didn’t blink through
all states.
PORT
Flashing Red
(6 PPM)
UL STATUS
Red, after power-up
blink
2.
Expansion
UL STATUS
DL STATUS
PORT
Red
Red Check the downlink fiber for opti-
Off Check the CATV cable. Power is not getting to the Hub power is On and RAUs are
PORT
Flashing Red
(60 PPM) connected
PORT
Red Use AdminBrowser to determine
Troubleshooting Expansion Hub LEDs During Installation
UL STATUS
LED should be Green.
The Expansion Hub is not
Expansion Hub power-on switch
powering on.
is on; replace the Expansion Hub.
Replace the Expansion Hub. The Microcontroller is not
resetting properly; flash memory corrupted.
Port unusable; replace the Expan­sion Hub when possible.
Current sensor fault; do not use the port.
Replace the Expansion Hub. The Expansion Hub laser is
not operational; no uplink between the Expansion Hub and Main Hub.
Check the Main Hub LEDs Refer to page 7-18, item 2 in
No communication with Main Hub.
Table 7-5.
Use AdminBrowser to determine the problem.
No downlink between the cal power; verify that the cables are connected to correct ports
Expansion Hub and Main
Hub. (that is, uplink/downlink)
Check the Main Hub LEDs. Refer to page 7-18, item 2 in Table 7-5.
RAU.
Test the CATV cable. If the cable tests OK, try another port. If the second port’s LEDs are Red/Off, replace the RAU. If the second RAU doesn’t work; replace the Expansion Hub.
Power levels to RAU are not
correct; communications are
not established.
If the second port works, flag
the first port as unusable;
replace EH when possible.
RAU is off-line. the problem.
7-26 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
7.4.3 Installing RAUs
CAUTION: Install RAUs in indoor locations only. Do not con-
nect an antenna that is installed in an outdoor location to an RAU. For outdoor installations, a protective enclosure is required.
Installing RAUs
Mount all RAUs in the locations marked on the floor plans.
Considerations:
• Install 800 iDEN and 850/1900 MHz RAUs so that their antennas will be separated by enough space to reduce signal interference between the 800 and 850 bands. Refer to Section , “800/850 MHz Isolation Requirements,” on page 7-27 for rec­ommended distance between antennas.
• You can place the unit, without its fastening hardware, on a flat surface, such as a shelf, desk, cabinet, or any other horizontal surface that allows stable placement with the mounting base facing down to the mounting surface. For mounting to other locations (that is, walls, ceilings, poles) the RAU must be securely mounted using the 4 slotted mounting holes provided with #6 diameter fasteners. This method of mounting must securely hold a minimum of 7 lbs. load.
• Attach the RAU securely to a stationary object (that is, a wall, pole, or ceiling tile).
• For proper ventilation:
• Keep at least
• Do not stack RAUs on top of each other.
• Always mount the RAU with the solid face (containing the mounting holes) against the mounting surface.
76 mm (3 in.)
Fusion Installation Procedures
clearance around the RAU to ensure proper venting.
D-620610-0-20 Rev A
Installing Passive Antennas
Refer to the manufacturer’s installation instructions to install passive antennas.
Location
Passive antennas are usually installed below the ceiling. If they are installed above the ceiling, you must consider the additional loss due to the ceiling material when estimating the antenna coverage area.
800/850 MHz Isolation Requirements
When deploying any RF system, give special attention to preventing receiver block­ing or desensitization by out-of-band transmitters. Typically, sharp filters in the receiver front-end will reduce the interfering transmitters to tolerable levels. In select cases, the interferers may occupy a frequency band that is directly adjacent to the receiving band and cannot be adequately rejected by filtering. The only recourse in
Help Hot Line (U.S. only): 1-800-530-9960 7-27
CONFIDENTIAL
Fusion Installation Procedures
850
850
850
Cellular
MHub
FSN-809019-1 RAU
FSN-8519-1 RAU
850
Cellular
RAU
850
EHub
Cellular
these situations is to provide sufficient isolation by physically separating the interfer­ing transmitters and receivers.
iDEN occupies spectrum at both 800 MHz and 900 MHz (Tx:806–825/Rx:851–870 and Tx:896–901/Rx:935–940), while the Cellular A and B carriers share a single 850 MHz block (Tx:869–894/Rx:824–849). The combination of these frequency bands, 800/900 MHz iDEN and 850 MHz Cellular, result in uplink (BTS receive) bands that are adjacent to downlink (BTS transmit) bands. Figure 7-9 depicts these nearly con­tiguous bands, with arrows indicating the interfering downlink and receiving uplink bands.
Figure 7-9
800/850 MHz Spectrum
Installation of an in-building distributed antenna system (DAS) to provide coverage for both 800/900 MHz iDEN and 850 MHz Cellular must account for these down­link-to-uplink interference issues and provide adequate isolation.
LGC offers the following guidelines toward achieving the proper amount of isolation when deploying LGC Wireless Unison DAS products.
Figure 7-10
Guideline for Unison RAU Antenna Placement
800 MHz iDEN Downlink and 850 MHz Cellular Uplink
A 2 MHz frequency gap (851 – 849 MHz) separates the 800 iDEN downlink and 850 Cellular uplink frequency bands. Because of this narrow spacing, 800 iDEN down­link intermodulation products may fall within the 850 Cellular uplink band. In addi­tion, 800 iDEN downlink signals near the lower edge of the band at 851 MHz may
7-28 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Fusion Installation Procedures
cause the 850 Cellular uplink automatic level control (ALC) circuitry in the RAU to engage and thereby reduce uplink gain.
To prevent either of these conditions, use the following guidelines:
• In-band 800 iDEN intermodulation products < -90dBm
• Lower frequency 800 iDEN signals < –30dBm for Fusion
Given a typical DAS configuration (4 iDEN carriers, omni-directional antennas, line of sight), these guidelines translate to an antenna spacing (d1) of 6 – 9 meters.
850 MHz Cellular Downlink and 900 MHz iDEN Uplink
A 2 MHz frequency gap (896 – 894 MHz) separates the 850 Cellular downlink and 900 iDEN uplink frequency bands. Because of this narrow spacing, 850 Cellular downlink intermodulation products may fall within the 900 iDEN uplink band. In addition, 850 Cellular downlink signals near the upper edge of the band at 894 MHz may cause the 900 iDEN uplink ALC to engage and thereby reduce uplink gain.
To prevent either of these conditions, use the following guidelines:
• In-band 850 Cellular intermodulation products < -90dBm
• Upper frequency 850 Cellular signals < –30dBm for Fusion
Given a typical DAS configuration (6 CDMA carriers for Fusion, omni-directional antennas, line of sight), these guidelines translate to an antenna spacing (d2) of 8-14 meters.
Spacing between RAUs FSN-8519-1 and FSN-809019-1 should be in a range of from 8 to 14 meters.
Connecting the Antenna to the RAU
Connect a passive multi-band antenna to the N connector on the RAU using coaxial cable with the least amount of loss possible.
CAUTION: Firmly hand-tighten the N connector – DO NOT over-tighten the connector.
Connecting the CATV Cable
Considerations:
• Verify that the cable has been tested and the test results are recorded. This informa­tion is required for the As-Built Document.
• Verify that only captive centerpin 75 Ohm Type-F connectors are used on the solid copper center conductor CATV 75 Ohm cable.
• Verify that the CATV cable is labeled with:
D-620610-0-20 Rev A
Help Hot Line (U.S. only): 1-800-530-9960 7-29
CONFIDENTIAL
Fusion Installation Procedures
• Fusion Main Hub port number being used
• RAU identifier
• Carrier (for multiple operator systems)
To connect the CATV cable:
1.
Connect the CATV cables to the F female port on the RAU according to the label on the cable.
Power is supplied by the Fusion Main Hub over the CATV cable conductors. Upon power up, the LEDs will blink for two seconds as a visual check that they are functioning. After the two-second test:
• The
LINK
LED should be green indicating it is receiving power and communi-
cations from the Fusion Main Hub.
• The
ALARM
LED should be red until the Fusion Main Hub issues the band
command, within about 20 seconds, then it should be green.
2.
Record which cable you are connecting to the RAU (from the label on the cable).
This information is required for the As-Built Document.
3.
Tie-off cables or use the optional cable manager to avoid damaging the connectors because of cable strain.
7.4.3.1 Troubleshooting Using RAU LEDs During Installation
• The
LINK
LED should be green and remain green for longer than 90 seconds. The
ALARM
Table 7-7
During Installation LED State Action Impact
The RAU is connected to the Fusion Expan­sion Hub, which is powered on
LINK
ALARM
LINK
ALARM
LINK
ALARM
LEDs are red when the system band has not been programmed.
Troubleshooting RAU LEDs During Installation
Off Check CATV cable. No power to the RAU.
Off
Green • Check CATV cable
Red
Red from green, after cables are connected for 60 seconds
Red
• Check Hub LEDs Refer to page 7-26, item 2 in Table 7-6.
• Use AdminBrowser to determine the problem.
• Check CATV cable.
• Check the Hub LEDs.
• Use AdminBrowser to determine the problem.
The RAU is off-line.
No communications between the RAU and the Hub.
7-30 InterReach Fusion Installation, Operation, and Reference Manual
CONFIDENTIAL
D-620610-0-20 Rev A
Loading...
+ 94 hidden pages