ACV E-tech P 57, E-tech P 115, E-tech P144, E-tech P201, E-tech P 259 INSTALLATION OPERATING AND SERVICING INSTRUCTIONS

57 - 115 - 144 - 201 - 259 [Tri phase]
Installation, operating and
servicing instructions
ENGLISHFRANCAISNEDERLANDSESPAÑOLITALIANODEUTSCH
664Y3500
EN • 1
INDEX
WARNINGS 3
Who should read these instructions 3 Symbols 3
ENGLISHFRANCAISNEDERLANDSESPAÑOLITALIANODEUTSCH
Recommendations 3 Importants notes 3
INTRODUCTION 4
Description of the specifications 4 Casing 4 Heating body 4 Heating element
Connection 4 Control 4 Electrical protection 4
INSTRUCTIONS 5
User data 5 Setting up 5 Heating system pressure 5 Control panel legend 5
TECHNICAL CHARACTERISTICS 6
Electrical data 7 Power 7 Nominal current per phase 7
s 4
INSTALLATION : GENERAL 8
Dimensions 8 Installation room 8 Boiler room 8 Frost protection 8 Connecting to the system 8
INSTALLATION : HYDRAULIC 9
Heating connection 9 Heating connection + DWL 9
INSTALLATION : ELECTRIC SUPPLY 10
General safety rules 10 Important 10
Electrical connections 10 Sizing of supply wires 11 Power variation (kW) relative to voltage
Wiring diagrams 12 Power limitation 13 Powers wiring / Model : E-Tech P / 57 14 Powers wiring / Model : E-Tech P / 115 15 Powers wiring / Model : E-Tech P / 144 16 Powers wiring / Model : E-Tech P / 201 18 Powers wiring / Model : E-Tech P / 259 20
11
COMMISSIONING 22
Commissioning - Water 22 Commissioning - Electrical 22 Starting the boiler 22
22
MAINTENANCE 23
SPARE PARTS
664Y3500
EN • 2
See at the end of this manual
WARNINGS
WHO SHOULD READ THESE INSTRUCTIONS
These instructions should be read by:
- the specifying engineer
- the installer
- the user
- the service engineer
SYMBOLS
Essential instruction for the correct operation of the installation.
Essential instruction for the safety of persons and the environment.
Danger of electrocution.
IMPORTANTS NOTES
ENGLISHFRANCAISNEDERLANDSESPAÑOLITALIANODEUTSCH
The manufacturer reserves the right to change the
technical characteristics and specification of its products without notice.
The availability of certain versions and their accessories
can vary following the market.
Warning : Do not switch ON if there is a possibility that the water in heater is frozen.
Danger of burns
RECOMMENDATIONS
• These instructions are an integral part of the equipment to which they relate and must be handed to the user.
• The product must be installed and serviced by qualified engineers in accordance with the regulations in force.
• The manufacturer declines all liability for any damage caused as a result of incorrect installation or in the event of the use of appliances or accessories that are not specified by the manufacturer.
• Any failure to follow instructions relating to tests and test procedures may result in personal injury or risks of pollution.
• It is important to switch the boiler off from the external switching device before carrying out any work.
• There are no user parts inside the control panel.
• The installation must be in accordance with the current standards.
664Y3500
EN • 3
INTRODUCTION
DESCRIPTION OF THE SPECIFICATIONS:
This floor standing electric boiler is available in 5 models :
ENGLISHFRANCAISNEDERLANDSESPAÑOLITALIANODEUTSCH
- Model 57 with a power of 57,6 kW
- Model 115 with a power of 115,2 kW
- Model 144 with a power of 144 kW
- Model 201 with a power of 201,6 kW
- Model 259 with a power of 259,2 kW
The power circuit is supplied with 400 Volt tri phases without neutral. The control circuit is supplied with 230 Volt single phase.
CASING
The boiler is protected by a steel casing that has a red stove enamelled finish.
HEATING BODY
The boiler heating body is constructed from mild steel with welded joints. It is hydraulic tested at a pressure of 5,2 bar (maximum working pressure = 4 bar).
HEATING ELEMENTS
Immersion heaters, constructed from stainless steel Incoloy 800 are mounted in the front of the boiler, provide the heating source to the boiler.
CONNECTION
The boiler is suitable for connection to most heating and water process systems, with a maximum working pressure of 4 bars and a maximum temperature of 90°C. It can also be used in multiple boiler installations allowing greater outputs to be achieved.
The boiler and connection glands are provided for the power supply, the control supply and optional external controls.
CONTROL
The boiler is equipped with an electronic sequencing control that constantly adapts the power required thanks to a four stage modulation. The boiler is commonly controlled by an external contact (i.e. room thermostat). The maximum power can be limited to 25%, 50% or 75% by moving electrical bridges.
ELECTRICAL PROTECTION
The control circuit is protected by an internal 3 Amp MCB. The power circuit is protected at its input by 3 power fuses. Moreover, each contactor - supplying a pair of electric stars (28,8kW) - is protected by an automatic thermal and magnetic safety relay.
4
5
1. Control panel
2. Heating elements
3. Contactor and safety relays
4. Optional controller
5. Control circuit
6. Main fuses and power connections
7. Removable access panel
1
2
6
3
7
664Y3500
EN • 4
INSTRUCTIONS
USER DATA
All user controls are situated on the front panel of the boiler, there are no user controls inside the boiler casing. The following instructions assume that the boiler has been commissioned, and that the system is filled with water and has been fully vented.
SETTING UP
• Before switching on any electrical supplies to the boiler ensure that the combined temperature and pressure gauge reads at least 1 bar and the control thermostat is set to the desired temperature.
• If any other auxiliary controls are fitted e.g. programmer, room thermostats, cylinder thermostats etc, consult appropriate manufacturers’ instructions to switch these on.
• Switch the winter/summer switch to winter position.
• Switch on any local means of isolation to boiler.
Ensure all the jacket panels are secured before
switching on electrical supply from the external isolator.
• Switch the boiler on using the ON/OFF switch (a test of the lights is done).
• After a short period of time the boiler temperature should start to rise, indicated on combined temperature and pressure gauge. The modulation level is displayed on the front panel by the stage indicator lights. If the boiler fails to operate, the overheat safety thermostat should be checked.
Access to the thermostat reset button is obtained by unscrewing
(anti-clockwise) the domed button cover on the front panel (a screwdriver is not required).The reset button can then be seen - press the button, a click should be heard and the button is reset. If no click was heard the device is not at fault and further investigation is required by a suitably qualified engineer.
• The external programmer can now be set to allow on/off periods as desired. The ON/OFF switch should be left in the ON position during normal use.
• As with most boilers and heating appliances the casing and pipework can get hot during normal running so the boiler must not be covered and the surrounding area must be kept clear.
HEATING SYSTEM PRESSURE
The CH pressure must be a minimum of 1 bar and must be checked by the end user on a regular basis. If the pressure drops under 0.5 bar, the integrated water pressure switch blocks the appliance until the pressure in the system returns to a level above 0.8 bar. The installer must fit an external filling loop to the system. For more information, please ask your installer when the system is delivered. A pressure safety valve is provided with the appliance. If the system pressure exceeds 4 bars, this valve opens and drains the water from the system. In this case, please contact your installer.
CONTROL PANEL LEGEND
1. Control thermostat : 1 = 25°C 2 = 40°C 3 = 55°C 4 = 70°C 5 = 85°C
2. ON/OFF switch
3. Summer/Winter switch
4. Manual reset high limit thermostat
5. Overheating warning light
6. Minimum water pressure warning light
7. Combined temperature and pressure gauge
ENGLISHFRANCAISNEDERLANDSESPAÑOLITALIANODEUTSCH
The power level indicator will automatically light on and
off during normal boiler operation, depending on boiler temperature.
• If the boiler is not in regular daily use during cold periods, it is recommended that it is fitted with a frost sensing thermostat to prevent the system from freezing.
4 5 6 7 8
8. Power level indicators
9. Optional internal controller
664Y3500
1 2 3 9
EN • 5
TECHNICAL CHARACTERISTICS
ENGLISHFRANCAISNEDERLANDSESPAÑOLITALIANODEUTSCH
Model 57 115 144 201 259
Power 57,6 kW 115,2 kW 144 kW 201.6 kW 259,2 kW
Nominal supply voltage
Power circuit 3 x 400 V 3 x 400 V 3 x 400 V 3 x 400 V 3 x 400 V
Control circuit
Heating element type 4 x 3 x 2.4 kW 4 x 3 x 2.4 kW 4 x 3 x 2.4 kW 4 x 3 x 2.4 kW 4 x 3 x 2.4 kW
Number of elements 24579
Ohmic value of single resistance (2,4 kW)
Water capacity (Litres)
Max. working pressure (bars) 44444
Min. working pressure (bars) 0.8 0.8 0.8 0.8 0.8
Max. working temperature (°C)
Hydraulic pressure drop (mbar) [ΔT = 10°C]
1 x 230 V
50/60 Hz
22,0 Ohm 22,0 Ohm 22,0 Ohm 22,0 Ohm 22,0 Ohm
60 60 60 102 102
90 90 90 90 90
20 79 123 20 33
1 x 230 V
50/60 Hz
1 x 230 V
50/60 Hz
1 x 230 V
50/60 Hz
1 x 230 V
50/60 Hz
Heating connection 2” [F] 2” [F] 2” [F] DN 100 (*) DN 100 (*)
Height (mm) 1495 1495 1495 1495 1495
Width (mm) 542 542 542 542 542
Depth (mm) 567 567 567 567 567
Weight empty (kg) 110 123 131 187 200
(*) DN100 fl anges to be welded
664Y3500
EN • 6
TECHNICAL CHARACTERISTICS
POWER
Models
E-Tech P / 57 14,4 14,4 14,4 14,4 57,6
E-Tech P / 115 28,8 28,8 28,8 28,8 115,2
E-Tech P / 144 36,0 36,0 36,0 36,0 144,0
E-Tech P / 201 50,4 50,4 50,4 50,4 201,6
E-Tech P / 259 64,8 64,8 64,8 64,8 259,2
Models
Power (kW)
Stage 1
Stage 1
(A)
Power (kW)
Stage 2
NOMINAL CURRENT PER PHASE
Stage 2
(A)
Power (kW)
Stage 3
Stage 3
(A)
Power (kW)
Stage 4
Stage 4
(A)
Total Power
(kW)
Total current
per phase
(A)
ENGLISHFRANCAISNEDERLANDSESPAÑOLITALIANODEUTSCH
E-Tech P / 57 20,9 20,9 20,9 20,9 83,6
E-Tech P / 115 41,7 41,7 41,7 41,7 166,8
E-Tech P / 144 62,7 62,7 41,8 41,8 209
E-Tech P / 201 83,5 83,5 62,6 62,6 292,2
E-Tech P / 259 83,5 104,4 83,5 104,4 375,8
664Y3500
EN • 7
DIMENSIONS
ENGLISHFRANCAISNEDERLANDSESPAÑOLITALIANODEUTSCH
Models
E-Tech P / 57 1495 567 550 183 542 125 2” [F]
E-Tech P / 115 1495 567 550 183 542 125 2” [F]
E-Tech P / 144 1495 567 550 183 542 125 2” [F]
E-Tech P / 201 1495 567 1100 183 542 125 DN 100
E-Tech P / 259 1495 567 1100 183 542 125 DN 100
INSTALLATION : GENERAL
A
mm
B
mm
C
mm
D
mm
B
E
mm
F
mm Heating connection
F
A
INSTALLATION ROOM
The minimum clearance around the appliance must comply with the figure shown opposite.
BOILER ROOM
• Electric boilers must be installed in boiler rooms complying with the relevant technical standards and applicable regulations.
• The appliance should never be installed outdoors, because it has not been designed for and is not equipped with automatic defrosting systems.
• If possible, install the boiler above the ground level, to reduce the risk of flooding the electrical components.
C
E
D
TOP VIEW
500 mm
FROST PROTECTION
The boiler is NOT fitted with frost protection. If the boiler is
being installed in a position where freezing could take place, then a suitable external frost thermostat should be fitted.
CONNECTING TO THE SYSTEM
The boiler is designed to operate on a sealed system (ie. no open vent or feed and expansion tank). An adequate expansion vessel, sized accordingly must be installed in the system.
664Y3500
500 mm
EN • 8