v This manual should be passed on to the end user.
v The contents of this manual are subject to change without prior notice.
v All rights reserved.
v ABUS gives no warranty of any kind with regard to this manual, including, but not limited to, fitness for
a particular purpose.
vIf any question arises or errors are found, or if any information is missing from this manual, please
M94
inform your supplier or inform at info@abusek.com
vThe specifications mentioned in this manual are limited to those for the standard type under the
specified model number break-down and do not necessarily apply for customized instruments.
vPlease note that changes in the specifications, construction, or component parts of the instrument
may not immediately be reflected in this manual at the time of change.
vIf the customer or any third party is harmed by the use of this product, ABUS assumes no
responsibility for any such harm owing to any defects in the product which were not predictable, or for
any indirect damages.
vThe integral modules specifically HART module are not manufactured by ABUS.
Although Warning hazards are related to personal injury, and Caution hazards are associated with
equipment or property damage, it must be understood that operation of damaged equipment could, under
certain operational conditions, result in degraded process system performance leading to personal injury
or death. Therefore, comply fully with all Warning and Caution notices.
Information in this manual is intended only to assist our customers in the efficient operation of our
equipment. Use of this manual for any other purpose is specifically prohibited and its contents are not to
be reproduced in full or part without prior approval of Technical Communications Department, ABUS
Technologies.
HEALTH AND SAFETY
To ensure that our products are safe and without risk to health, the following points must be noted:
1. The relevant sections of these instructions must be read carefully before proceeding.
2. Warning labels on containers and packages must be observed.
3. Installation, operation, maintenance and servicing must only be carried out by suitably trained
personnel and in accordance with the information given. Any deviation from these instructions will
transfer the complete liability to the user.
4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when
operating in conditions of high pressure and/or temperature.
5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept
dry. Normal safe handling procedures must be used.
6. When disposing of chemicals ensure that no two chemicals are mixed.
Safety advice concerning the use of the equipment described in this manual or any relevant
hazard data sheets (where applicable) may be obtained from the Company address on the back cover,
together with servicing and spares information.
The ABUS DP Series features high performance with high degree of precision.
Differential pressure measurement can be used to measure flow, level, density and viscosity.
This versatile primary measurement can provide high accuracy results even in harsh
environmental conditions. It is considered on the basis of the proven and reliable sensing
technology and extensive digital technology.
16-bit single chip is adopted as its core element, with its powerful function and highspeed processing capacity, ensures the excellent accuracy with stability of the transmitter. The
whole design frame focuses on its reliability, stability and high precision, meeting the growing
demand of on-site industrial use. To achieve this goal, digital signal processing is used by the
software to ensure minimum disturbance effects and zero point stability. Meanwhile, it has the
Zero Stability Capacity (ZSC) and Temperature Supplementing Capacity (TSC).
The powerful interface guarantees an excellent interaction rarely needing manual
operator. Keypad operation can accomplish the basic settings of zero, range setting, damping
setting under the circumstances of no standard pressure, and proving to be very convenient for
the on-site adjustments.
By connecting with module RS485, it can realize the remote transmission of digital signal
or the building up of RS485 industrial LAN.
Transmitter has an optional HART module. Transmitter added the HART module has
HART communication capabilities, with the conventional operations being controlled by the
manual operator. Transmitter can be widely used in the sectors such as petroleum, chemical,
iron & steel, power supply, light industry and environmental protection, capable of realizing the
measurement of various pressures, differential pressures, flows and fluids, can adapt for all kinds
of harsh and hazardous environment and corrosive processes.
6 Name plate 19 Zero alignment plate
7 Housing body 20 Housing body lockup bolt
8 Meter head 21 Parallel wires
9 Mounting bolts of meter head 22 Circuit board
18 Position code plate
10 Meter head cover 23 Nut M10
11 Drain/ vent valve 24
As indicated in the working principle diagram, the outside pressure or differential pressure
will cause some change in the sensor capacitance value. Through the digital signal conversion, it
will change into the frequency signal, which is sent to the microprocessor. After the calculation by
microprocessor, a current control signal will be output to the current control circuit, converted into
analogue 4-20mA current output. Meanwhile, the microprocessor is responsible for the
interactive and other actions (display and setting). The communication port used for digital
communication needs the special port of our company. HART module will realize the transmitter
HART communication.
Output Signal: 4 ~ 20mA DC, 2-Wire System with Digital communication,
Reference Accuracy: ±0.075%
Range ability 100 : 1
Overall Performance: ± 0.1 % (for range of 1/10 of max allowed span) including
comprehensive inaccuracy of linearity, changing difference and
repeatability.
Stability:±0.15% of the span; for Draft Ranges, ±0.25% of the span.
Start-Up time: Max 2 seconds for minimum damping.
Volume Change: Less than 0.16cm
Response Time: Less that 100 ms
Damping: Electrical damping is 0 ~ 32 seconds, continually adjustable at
an interval of 0.1 second. Sensitive components have 0.2
seconds constant damping time. (Span 3 is 0.4 seconds)
Functions: PushButton configurable Linear/Square root
Effect of Temperature: Zero Inaccuracy: Max. ±0.25% of span for each 50F (28°C).
Vibration Effect: At time of 0 ~ 200Hz for shock frequency on any direction, the
error is 0.05%/g of the highest one.
3
.
Power Effect: Less than output range by ±0.005%/V.
ABUS TECHNOLOGIES INC.
6
Mounting Orientation Effect: Zero drifts no more than 0.24kPa. No effect for movement
parallel to diaphragm. The error could be resolved by quick Zero
reset pushbutton on the instrument.
Power Voltage: 12V ~ 45V DC
Intrinsically safe/explosion-proof products with max 30 VDC
should be powered by safe Barrier
M94
Parameters for intrinsically safety: U
≤ 28V DC,
0
type outsourcing safe barrier I0 ≤ 30mA
P0 ≤ 0.84W
Physical Parameters:
O Ring of Contacting Medium: Viton / Glass Filled PTFE
Filling liquid: Silicone Oil / Inert Gas
Bolt: Cadmium plated carbon steel.
Outer shell or electronic circuit: Low Cu Al.
O shaped seal ring: Acrylotrile-butadiene rubber, fluorine rubber polyurethane.
NOTE: Please refer to Ordering Table for Flange connector, Exhaust/Vent valves and Isolation
Diaphragm Material options
Pressure Connection Part: ¼ - 18 NPT for joint thread in pressure room,
½ - 14 NPT for joint thread in pressure guiding joint.
Zero Shift : push key S & Z at the same time (key S on the left while key Z on the right) for 6
seconds, the screen indicates “Hart”, means zero and span adjustment status is activated; push
key Z for 5 seconds, “Hart” on the screen disappeared; zero shifts successfully and exits the
status of activation.
Span Shift: push key S & Z at the same time (key S on the left while key Z on the right) for 6
seconds, the screen indicates “Hart”, means zero and span adjustment status is activated; after
confirming the pressure of equipment is span pressure, push key S for 6 seconds; then “Hart” on
the screen disappeared; span shifts successfully and exits the status of activation.
Note: After entering the status of activation, if you don’t want to adjust, push key S & Z together;
after loosing the key, “Hart” on the screen disappears; it means having exit the status of
activation
2. Parameter Setting
2-1 keys : Push key S & Z = exit key; exit key comes into force after loosing key S & Z; push key
Z for 4 seconds to shift
2-2 Parameters : After pushing key S for 6 seconds, the screen indicates “PASS”; then push key
Z, the screen indicates value and the cursor flickers. The flickering bit is modifier bit; push key Z
the value increases 1 but not carry. Push key Z for 4 seconds the cursor shifts. Follow the above
mentioned operation to revise the value to be 160, then push key S to enter adjustment procedure
of next parameter. Meanings of parameters are as follows
.
M94
:
yes/no
Hotkey: push key Z for 6 seconds to do zero trimming
Note: Please operate carefully for italic part parameters; make sure correct value of pressure
forced on equipment
1
6
Password Verification, PW: 160
Process value to 20 mA (full scale value)
Process Value to 4 mA (zero value)
Transmitting function, “=0” stands for linearity, “=1” stands for
evolution
Indicating units, 0=KPa, 1=KPa, 2=KPa, 4=KPa, 6=Pi, 7=bar,
8=KPa, 9=KPa, 11=Pa, 12=KPa, 13=KPa, 15=MPa, 16=mA,
17=%, 18=S, 19=m3, 20=t/h
Damping time, max limited value is 30 s when program runs
Low point trimming. Process value adjusted to input value; after
pushing key Z revise low point trimming pressure value; don’t
push key Z if you don’t want to adjust; directly push key S to
enter next parameter
High point trimming. Process value adjusted to input value;
after pushing key Z revise high point trimming pressure value;
don’t push key Z if you don’t want to adjust; directly push key S
to enter next parameter
Hart. Three-point linearization and trimming data initialization
1 Rotating Display
2 Bright White Backlit Display
3 Bar Graph Display
4 Display in various Engineering Units
5 Zero Button
6 Span Button
5
ABUS TECHNOLOGIES INC.
8
3. ELECTRICAL CONNECTIONS
Electrical Port: :NPT1/2 load resistance of cable sealed connector: (4-20mA)
− 14
=
where: U is power voltage, RD is cable internal resistance
0.02
−
M94
(Note 1: User can install the distributor or safe barriers per the on-site and design
requirements. For details, see the usage of distributor and safe barrier.)
It is recommended to choose the explosion-proof impulse terminal with the cable
diameter of ö8 – 12. The connection terminal is set with test terminal, convenient for the online
test of the operator.
Signal terminal is situated in a separate housing of the electrical box. Screw up the meter
cover for wiring. The upper end is for signal, while the lower end is for test meter. Fig. 2-13
indicated the terminal location. The test terminal is used for connecting any optional indicator
ABUS TECHNOLOGIES INC.
9
head or test. The power supply goes to the transmitter through the signal line, with no need of
Special Attention
:
additional wiring.
Do not connect the power signal line to the test terminal; otherwise the
diode inside the test terminal would be destroyed
In case of the diode being damaged unfortunately, connecting the test terminal can keep
the transmitter working on, except the indicator unable to connect.
No need to shield the signal wire, and litz wire can be used for better effect. Do not lay
together the signal wire and other power wires, to get near to the strong electricity equipment.
The wiring orifice on the housing body of transmitter should be sealed or inserted in a
plug smeared with seal glue to prevent the humidity being accumulated in the housing. In the
case of the wiring not being sealed, the transmitter should be mounted with the wiring orifice
upside down to discharge the moisture.
The signal line may ignore the grounding (hanging) or get to ground at any point on the
loop line. The transmitter housing can have grounding or not, and the power has no need of
being stabilized, even if the power ripples has a peak-to-peak value of 1V. And the output ripples
of transmitter can also be ignored.
Since the transmitter gets grounded by way of capacitance coupling, it is not appropriate
to use a high-voltage mega-ohm meter to check the insulation resistance. The voltage used for
checking the line should be no more than 100 V.
The transmitter circuitry is designed as intrinsic safe circuitry, limiting the output current
below 30 mA DC (35 mA DC under the condition of high temperature or high voltage).
Intrinsically Safety Type Explosion Proof Transmitter System Wiring Diagram
M94
li: 30mA Uo ≤ 28V DC
Pi: 0.84W lo ≤ 30mA
Po ≤ 0.84W
Note: See GB3836, 4-2000 standard for the definitions of Um, Uo, lo, Po, Ui, li, Pi
The connection wire or cable between safe barrier and transmitter has a largest allowed
distribution capacitance of no more than 0.02µF and the largest allowed distribution inductance
of not more than 2.0mH.
L12 CS CD-plating 316 L SS 316 L SS
L13 CS CD-plating Hastelloy C Hastelloy C
L14 CS CD-plating Monel Monel
L15 CS CD-plating 316 L SS Tantalum
L22 is the Part of
Standard equipment
L22* 316 L SS 316 L SS 316 L SS
L23 316 L SS 316 L SS Hastelloy C
L24 316 L SS 316 L SS Monel
L25 316 L SS 316 L SS Tantalum
L33 Hastelloy C Hastelloy C Hastelloy C
L35 Hastelloy C Hastelloy C
Tantalum
L44 Monel Monel Monel
D Digital Backlit LCD Indicator(with programming keys)
B1 Bend bracket for pipe mounting (2” pipe)
B2 Bend Bracket for plate mounting
B3 Flat bracket for pipe mounting (2” pipe)
Weather proof is the
Standard equipment
D1 Side exhaust/vent valve of flange on top
D2 Side exhaust/vent valve of flange on bottom
L12 CS CD-plating 316 L SS 316 L SS
L13 CS CD-plating Hastelloy C Hastelloy C
L14 CS CD-plating Monel Monel
L15 CS CD-plating 316 L SS Tantalum
L22* 316 L SS 316 L SS 316 L SS
L23 316 L SS 316 L SS Hastelloy C
L24 316 L SS 316 L SS Monel
L25 316 L SS 316 L SS Tantalum
L33 Hastelloy C Hastelloy C Hastelloy C
L35 Hastelloy C Hastelloy C
L44 Monel Monel Monel
D Digital Backlit LCD Indicator(with programming keys)
B1 Bend bracket for pipe mounting (2” pipe)
B2 Bend Bracket for plate mounting
B3 Flat bracket for pipe mounting (2” pipe)
D1 Side exhaust/vent valve of flange on top
D2 Side exhaust/vent valve of flange on bottom
W* WeatherProof Type
150lb flange: 15kg/cm2 (at 37° filled with silicon oil)
300lb flange: 30kg/cm2 (at 37° filled with silicon oil)
Connecting Fitting for Process Pressure
High-pressure side : 3” or 4” 150lb flange or 300lb flange
Low-pressure side : The connecting thread of the flange is 1/4-18NPT (taper-pipethread)
The connecting thread of the joint is ½-14NPT (taper-pipe-thread)
FLANGE SIZE (MM) BOLT HOLE (MM)
Code Size Specification Diameter A B C Amount Diameter Distribution