DFM44E Series
Installation Instructions
System Requirements:
Win 95b/98/Me/2000/XP
Resolution: 1024 x 768
32MB RAM
Copyright © 2003. Maxitrol Company. All Rights Reserved.
23555 Telegraph Rd.
Southfield, MI 48034
248.356.1400
Read Before Installation
DFME DFME
DFME
DFME DFME
Proper DFME operation can only be achieved by completing a full setup routine before operation.
Before installing Temperature Controller and Software, read the entire installation instruction manual to ensure proper and successful operation.
AmplifAmplif
Amplif
AmplifAmplif
ier MUST be poier MUST be po
ier MUST be po
ier MUST be poier MUST be po
ww
w
ww
erer
er
erer
ed fred fr
ed fr
ed fred fr
om it’om it’
om it’
om it’om it’
s os o
s o
s os o
wn sewn se
wn se
wn sewn se
parpar
par
parpar
aa
te 24 te 24
a
te 24
aa
te 24 te 24
VV
V
VV
AA
C 40 C 40
A
C 40
AA
C 40 C 40
VV
V
VV
A trA tr
A tr
A trA tr
ansfansf
ansf
ansfansf
oror
or
oror
mermer
mer
mermer
..
.
..
DFME Product Description
Temperature Controller for use with Recirculating Direct Gas-Fired Modulating Air Heaters in accordance with applicable
specifications of ANSI Z83.18.
DFM44E System Requirements
ADFM44E Amplifier (Ambient Operating Temperatures: -40°F (-40°C) to 158°F (70°C))
TDFM44 Selector (40°F - 95°F)
TS394-2B-4 Return Air Sensor
TS394-2B-4 Outdoor Air Sensor
TS194Q Discharge Air Sensor
MT Series Mixing Tube
M/MR212 Series Modulating Gas Valve
Software CD-ROM
Signal from Airflow Measuring Device or Outside Air Damper (not supplied)
Laptop or PC with Windows 95b/98/Me/2000/XP (32 MB RAM minimum) (not supplied)
Patch Cable w/ RJ45 connectors (both ends) (not supplied)
Serial Cable (DB9M to DB9F) (not supplied)
Separate 24 VAC 40 VA Power Supply (not supplied)
Accessories
Airflow Measuring Device (available)
Note: Auto-Calibrate feature requires Airflow Measuring Device with 0-10 VDC output.
Features
Low Fire Start Timer (standard on all versions)
Unoccupied Mode (standard on all versions)
1-24 VDC N.O. Relay (1 W max) required (not supplied)
Mild Weather Thermostat (version 2.2)
1-24 VDC N.O. Relay (1 W max) required (not supplied)
Freeze Thermostat (version 2.3)
1-24 VDC N.O. Relay (1 W max) required (not supplied)
Mild Weather and Freeze Thermostat (version 2.4)
2-24 VDC N.O. Relays (1 W max) required (not supplied)
TSDFM44 Remote Room Sensor (optional on all versions)
2
Form Instr 44E2.4
@ 2003, Maxitrol Company, 23555 Telegraph Rd., Southfield, MI 48034
www.maxitrol.com, 248.356.1400
Step1: Hardware Installation Instructions
After each component has been located and mounted,
set dipswitches and make wire connections according
to Diagrams 1 and 2.
Items Needed
3/16” Drill Bit
Mounting Template (included)
ADFM44E Connections
Diagram 1
Separate
Power Supply
24 VAC 40 VA
(See Note 1)
M/MR212
Modulating
Gas Valve
On Board
24 VDC Relay
Power Output
(See Note 4)
Serial Cable
Connection
to PC/Laptop
(12 ft maximum)
J1
Patch Cable w/ RJ45
connection (both ends) to
TDFM44 Selectrastat
(See Diagram 2 for maximum
lengths.)
ADFM44E
SW1
A
SW1 #4
ON
OFF
J3
J4
SW2
Low Fire Start Timer
Timing
Timing begins when 24 VAC is present at J1.
Timing begins when 24 VAC is present at J7 and J1.
J5/J6
J7
J8
Note 1:
Maxitrol ADFM44E amplifiers have full wave rectifiers (diodes). DO NOT connect any other external devices requiring 24 VAC to the same
transformer powering the ADFM44E amplifier (J1) doing so will destroy the ADFM44E amplifier and void the warranty.
24 VAC supply power (J1) with customer supplied relay (1 W max) may be used as input (J7) to begin Low Fire Start Timer.
Form Instr 44E2.4
@ 2003, Maxitrol Company, 23555 Telegraph Rd., Southfield, MI 48034
www.maxitrol.com, 248.356.1400
3
A
Note Polarity
0-10 VDC Airflow
Measuring Device
(used for Auto-Calibrate
only)
Temperature Sensors
View A
Damper Position
Feedback or
Continuous Airflow
Measuring Device
24 VAC Input to
Low Fire Start Timer
(see Note 1 and SW1)
Note
Polarity
External
Matching
Resistor
(see Note 3)
Note 2:
This connection is for direct
attachment of TSDFM44 to
ADFM44E board only. See
diagram 2, C.
When properly connected, the resistance
or voltage measured across the feedback
connection (J5) should increase as the
outside air damper opens. Similarly, the
resistance or voltage should decrease as
the outside air damper closes.
Switch SW2 is set as in chart for
the Damper or Continuous
Airflow Measuring Device
feedback being used.
Feedback
0 to 5V
0 to 10V
4 to 20 mA
135 ohm POT
500 ohm POT
10 K ohm POT
POT with EXT R
Relay Drive
SW2
#5, #6 ON
#5 ON
#4, #5 ON
#1 ON
#2 ON
#3 ON
ALL OFF
Freeze Thermostat
Mild Weather
Lockout
Unoccupied
Mode
Note 4:
Max. Coil Power = 1 W.
The corresponding relay
drive (J8) is at ground (24
VDC) when Mild Weather
Lockout, Freeze Thermostat
or Unoccupied Mode are
inactive.
Note 3:
If a damper feedback POT not having a value of 135, 500 or 10 K is used, an External Resistor equal to the POT value must be
connected to the AMPLIFIER (J6). Diagram 1, View A. ALL of SW2 should be OFF.
Form Instr 44E2.4
@ 2003, Maxitrol Company, 23555 Telegraph Rd., Southfield, MI 48034
www.maxitrol.com, 248.356.1400
4
Room Sensing Options
Diagram 2
Integral to TDFM44 Selectrastat
A. Temperature sensed by TDFM44 sensor:
Leave terminals #1 and #2 connected to sensing element.
Place SW1 #1 ON.
Terminal Connections
3, 4, 5 (see Note 5, page 6)
ADFM44E
(TDFM44 to ADFM44E connection: 120 ft maximum)
5
Form Instr 44E2.4
@ 2003, Maxitrol Company, 23555 Telegraph Rd., Southfield, MI 48034
www.maxitrol.com, 248.356.1400