ABB S800 Technical specifications

System pro M
Technical features
High performance MCBs - S800 series
2
TECHNICAL FEATURES S800U-Z S800U-K
Standards Characteristics available Rated current I Poles Rated operating voltage U (AC) 50/60Hz Rated interrupting in accordance with UL489
1-pole
2...4-pole
Ultimate short-circuit breaking capacity Icu in accordance with IEC 60947-2
(AC) 50/60 Hz 240/415V 1-pole (AC) 50/60 Hz 240/415V 2 ...4-pole
Service short-circuit capacity Ics in accordance with IEC 60947-2
(AC) 50/60 Hz 240/415V 1-pole (AC) 50/60 Hz 240/415V 2 ...4-pole
Conductor type Wire range 10...100A Tightening torque Mounting position Permissible ambient temperature for operations Type of protection
Contacts Certifications Standards
n
e
[A] 10...100
[V] 240
[kA] 30 [kA] 50
[kA] 30 [kA] 50
[kA] 25 [kA] 40
[°C] -25...+60
UL489, CSA 22.2 No. 5-02, IEC 60947-2
Z
1...4
Single conductor copper only
UL listed circuit breaker (File 312425)
8-1AWG
31 in.lbs. (3.5Nm)
any
IP20
IP40 (only actuation side)
cadmium free
CSA 22.2 No. 5-02
S800
K
Magnetic release 4xI Magnetic release 8xI
n
n
2/80
ABB
Loading...