ABB S500 UL 1077 Catalog Page

S500 series
UL 1077
Description
The S500 high performance MCB offers a compact solution to circuit protection. The S500 devices are UL tested current limiting and DIN rail mounted. The S500 is available with application­specific trip characteristics to provide maximum circuit protection.
Features
− High breaking capacity
− Fast breaking time (2.3 - 2.5 ms)
− Adjustable trip unit
− DIN rail mounting
− Finger safe terminals The breakers offer thermal-magnetic trip protection according to B and K characteristics.
− Multi-functional terminals
− Wide range of accessories
− UL 1077 recognized 600 VAC and 600 VDC versions For the worldwide market, the breakers carry CSA, IEC, CE and many other agency approvals.
− UL1077 AC adjustable K
− UL1077 DC adjustable B, K
− UL File #E167556
− IEC #E60497-2
S500 S500UC
Amperage 0.1-45 A 0.1-63 A Voltage 600Y/347 VAC 1 pole 250 VDC
Poles 1, 2, 3 1, 2, 3, 4 Trip characteristics K B, K Interrupting ratings Up to 30 kA: UL 1077
Auxilliary contacts Yes Yes Bell alarm Yes Yes Shunt trip No No Undervoltage release No No Busbar Yes Yes
2 pole 500 VDC 3 pole 600 VDC 4 pole 600 VDC
30 kA: UL 1077 30 kA: CSA C22.2
68 Miniature Circuit Breakers | US Catalog
S500UC-K
Supplemental protectors—UL 1077, CSA 22.2, IEC
Number of poles
1
2
Rated current
I
n
A Catalog number Number of poles
0.1-0.15 S501UC-K0.15
Rated current
I
n
A Catalog number
0.1-0.15 S503UC-K0.15
0.14-0.21 S501UC-K0.21 0.14-0.21 S503UC-K0.21
0.2-0.3 S501UC-K0.3 0.2-0.3 S503UC-K0.3
0.28-0.42 S501UC-K0.42 0.28-0.42 S503UC-K0.42
0.38-0.58 S501UC-K0.58 0.38-0.58 S503UC-K0.58
0.53-0.8 S501UC-K0.8 0.53-0.8 S503UC-K0.8
0.73-1.1 S501UC-K1.1 0.73-1.1 S503UC-K1.1 1-1.5 S501UC-K1.5 1-1.5 S503UC-K1.5
1.4-2.1 S501UC-K2.1 1.4-2.1 S503UC-K2.1 2-3 S501UC-K3 2-3 S503UC-K3
2.8-4.2 S501UC-K4.2 2.8-4.2 S503UC-K4.2
3
3.8-5.8 S501UC-K5.8 3.8-5.8 S503UC-K5.8
5.3-8 S501UC-K8 5.3-8 S503UC-K8
7.3-11 S501UC-K11 7.3-11 S503UC-K11 10-15 S501UC-K15 10-15 S503UC-K15 14-20 S501UC-K20 14-20 S503UC-K20 18-26 S501UC-K26 18-26 S503UC-K26 23-32 S501UC-K32 23-32 S503UC-K32 29-37 S501UC-K37 29-37 S503UC-K37 34-41 S501UC-K41 34-41 S503UC-K41 38-45 S501UC-K45 38-45 S503UC-K45
0.1-0.15 S502UC-K0.15
0.1-0.15 S504UC-K0.15
0.14-0.21 S502UC-K0.21 0.14-0.21 S504UC-K0.21
0.2-0.3 S502UC-K0.3 0.2-0.3 S504UC-K0.3
0.28-0.42 S502UC-K0.42 0.28-0.42 S504UC-K0.42
0.38-0.58 S502UC-K0.58 0.38-0.58 S504UC-K0.58
0.53-0.8 S502UC-K0.8 0.53-0.8 S504UC-K0.8
0.73-1.1 S502UC-K1.1 0.73-1.1 S504UC-K1.1 1-1.5 S502UC-K1.5 1-1.5 S504UC-K1.5
1.4-2.1 S502UC-K2.1 1.4-2.1 S504UC-K2.1 2-3 S502UC-K3 2-3 S504UC-K3
2.8-4.2 S502UC-K4.2 2.8-4.2 S504UC-K4.2
4
3.8-5.8 S502UC-K5.8 3.8-5.8 S504UC-K5.8
5.3-8 S502UC-K8 5.3-8 S504UC-K8
7.3-11 S502UC-K11 7.3-11 S504UC-K11 10-15 S502UC-K15 10-15 S504UC-K15 14-20 S502UC-K20 14-20 S504UC-K20 18-26 S502UC-K26 18-26 S504UC-K26 23-32 S502UC-K32 23-32 S504UC-K32 29-37 S502UC-K37 29-37 S504UC-K37 34-41 S502UC-K41 34-41 S504UC-K41 38-45 S502UC-K45 38-45 S504UC-K45
10,000
5000
1000
500
100
50
10
5
1
0.5
0.1
seconds
0.05
0.01
1 2 3 5 10 20 30
multiple of rated current
DC
US Catalog | Miniature Circuit Breakers 71
Loading...