S4 N 250 B W - 2 xxx
Isomax
Molded case circuit breakers
S3 – S8
Isomax
MCCBs
15
Accessories (added in alpha-numeric order)
A = Auxiliary Switch
BA = Bell Alarm
BA3 = Bell Alarm (S6/S7 only)
S_ = Shunt trip with voltage code
U_ = Undervoltage release with voltage code
Number of poles
-2 = 2 pole
-4 = 4 pole
None = 3 pole
Type connectors
W = None
Trip unit function
B = LI F = LSIG/K
C = LSI H = LSIG/D
D = Molded Case Switch (MCS) J = LSIG/DT
E = LSIG K = LSIG/DTK
T = Thermal-magnetic – 10X Mag M = Magnetic only (MCP)
G = Thermal-magnetic – 2.5 - 3X Mag 2
Current rating
015 = 15A
250 = 250A
400 = 400A
1200 = 1200A
1
15
Interrupting rating
class
B = Basic (240VAC)
N = Normal
H = High
L = Extra High
BQ = Basic, 100% rated
NQ = Normal, 100% rated
HQ = High, 100% rated
LQ = Extra High, 100% rated
D = Special molded case switch
(No trip IEC)
Frame size
S3 = 150 / 225A S6 = 600 / 800A
S4 = 250A S7 = 1200A
S5 = 400A
Low Voltage Products & Systems 15.65
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 000 023 C0201
1 Consult ABB for factory installed accessories.
2 Consult ABB for availability.
Isomax
MCCBs
15
S7
1200A, 600 VAC
Electronic trip type
Standard S7 package includes com plete cir cuit breaker and mount ing hard ware.
Order cable lugs or other connection scheme as a sep a rate item.
H x W x D
15.98" x 8.27" x 5.45"
S7
General
The S7 breaker family is a 1200A frame utilizing a mi cro pro ces sor based
overcurrent pro tec tive trip sys tem. In the 1200A version, the trip unit is adjustable
from 480A up to 1200A without the addition of any parts or rating plugs. As
standard, the S7 includes adjustable long time func tion for overload protection
and ad just able in stan ta neous func tion for short circuit protection.
Versions
To meet all application needs, the S7 is available in various versions:
B = Adjustment LI
C = Adjustment LSI
E = Adjustment LSIG
Q = 100% UL rated
D = Molded case switch
M = Magnetic only (MCP)
Trip functions
These tripping functions are avail able:
L = Long time I = In stan ta neous
S = Short time G = Ground fault
Performance level
Each version is also avail able in different maximum fault in ter rupt ing levels
H = High
L = Extra high (IEC only)
Number of poles
15
In UL/CSA version, the S7 is available as in two pole or three pole version, both
with the same dimensions. A four pole version is also avail able in a UL/IEC form.
For price estimate, add 35% to list price of selected three pole, contact ABB
Control.
Accessory mounting
Internal ac ces so ries are UL/CSA approved for both factory or fi eld in stal la tion.
Accessories require control ca ble con nec tors. Shunt trips or UVR's mount in the
left cavity. Auxiliary or bell alarm switches mount in the right cavity.
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
Voltage H
240VAC 100
480VAC 65
600VAC 50
IEC-947 Interrupting capacity (kA RMS)
Voltage H L
230VAC 100 200
380/400/415VAC 65 100
440VAC 55 80
500VAC 45 70
690VAC 25 35
Reverse feeding
All versions of the S7 family are suitable for reverse feed ap pli ca tions.
Molded case switches
UL489 switches in clude no overcurrent protection except for a high in stan ta neous
trip mechanism for self pro tec tion. IEC type molded case switches with no trip
pro tec tion are also avail able.
1 Consult factory
15.82 Low Voltage Products & Systems
1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule S7