Factory installation Field installation
Voltage Catalog number List Catalog numbers List
suffi x
24VDC SA
120VAC SB K5SB K7SB
For remote opening of circuit breaker and includes internal cut-off switch to protect solenoid. All shunt trips are left pole
mounted and can not be used with UVRs. Except for 12VDC, all shunt trips are approved for use in GF systems. Shunt trips
must be ordered with correct connector.
1 price adder S3 – S4 – S5 S6 – S7 price
1 price adder S3 – S4 – S5 S6 – S7 price
K5SA K7SA
$ 430
15
$ 415
S5 with K5S2
K5U1
K6C-SUP
Shunt trip connectors (required)
circuit breaker
Fixed mounted All included K6C-SU K7C-SU
Plug-in/Draw-out All included K6C-SUP K7C-SUP
Will trip CB when connected voltage drops to 35-70% of UVR voltage rating. Will allow CB to close (ON) when voltage is
approximately 85% of rated voltage. All UVRs are left pole mounted and can not be used with shunt trips. UVRs must be
ordered with correct connector.
1 price adder S3 – S4 – S5 S6 – S7 price
Undervoltage release connectors (required)
circuit breaker
Fixed mounted All included K6C-SU K7C-SU
Plug-in/Draw-out All included K6C-SUP K7C-SUP
Electrical specifi cations – UVR & low power shunt trips
V
24, 48, 125, 250 VDC –
For S3-S5 6 VA~/3W–
P Continuous duty
For S6-S7 10 VA~/4W–
Type Factory
24, 120, 240, 480 VAC ~ 50/60 Hz
Voltage
installation
1
S3 – S4 – S5 – S6 S7 List price
Field kit catalog number
$ 15
15
1 For factory installation add suffi x given to end of circuit breaker catalog number per accessory format.
Low Voltage Products & Systems 15.89
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 000 023 C0201
Discount schedule SA
Isomax
MCCBs
15
Electrical accessories
Auxiliary contacts
S3 – S7
Auxiliary contacts — S3 – S7
Factory installation Field installation
Contacts Catalog number List
suffi x
2 Form Cs A $ 275 K5AS K7AS $ 260
1 BA & 1 C BA
1 B BA & 1A+1B BA3 — K7BA-3
The auxiliary contacts are accessory contacts for the in di ca tion of circuit breaker open-closed or tripped. Bell alarm contacts
(B.A.) can be used to indicate circuit breaker tripping. All contacts are right pole mounted.
1
price adder S3 – S4 – S5 S6 – S7 price
Catalog numbers
K5BA K7BA
365
List
350
15
K5AS
K6C-ABP
Auxiliary contact connectors (required) — S3 – S7
Type Factory
circuit breaker
Fixed mounted All included K6C-AB K7C-AB
Plug-in/Draw-out All included K6C-ABP K7C-ABP
Electrical specifi cations
Voltage Maximum contact amperage rating
125 VDC 0.3 A
250 VDC 0.15 A
250 VAC 6 A
N.O. = contact is open as circuit breaker is open
N.C. = contact is closed when circuit breaker is open
B.A. = will open/close only when circuit breaker trips
Voltage
installation
1
S3 – S4 –- S5 – S6 S7 List price
Field kit catalog number
$ 15
S5 with K6C-AB
1 For factory installation add suffi x given to end of circuit breaker catalog number per accessory format.
2 Not UL approved for fi eld installation.
15.90 Low Voltage Products & Systems
1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule SA
K5M2
S4 with K5M2
Electrical accessories
Isomax
MCCBs
Motor operators, stored energy motor operators
S3 – S7
For remote control of circuit breaker opening and closing.
Complete with manual op er at ing lever, padlock device and emergency opening push-button.
When ordering the con nec tor always specify type and ver sion of the circuit-break er.
The following options are also available:
– key lock for open position
– key lock for open position of two or more circuit breakers (using the same key for groups of circuit breakers)
Motor operator connectors (required)
Type Field kit catalog number List
circuit breaker
Fixed mounted All K6C-M
Plug-in/Draw-out All K6C-MP
• Stored-energy motor operator with springs automatically pre-loaded by motor.
• Complete with shunt opening and closing release, and com part ment door fl ange.
• When ordering the connector always specify type and version of the circuit-breaker.
• The following options are also available:
– key lock for open position
– key lock for open position of two or more circuit-breakers (using the same key for groups of circuit-break ers).
S6 S7
price
$ 2407
Stored-energy motor operator connectors (required)
Type
circuit breaker
Fixed mounted All K6C-M K7C-M
Plug-in/Draw-out All K6C-MP K7C-MP
Electrical specifi cations
120, 240 VAC ~ 50/60 Hz
V
24, 48, 125, 250 VDC –
P inrush 660 VA~/600W–
P normal 180 VA~/180W–
Close time 0.09 s
Open time 1.2 s
Reset time 2.0 s
Field kit catalog number
Voltage
S6 S7 price
List
$ 15
15
S7 with K7M4
Low Voltage Products & Systems 15.91
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 000 023 C0201
Standard cable lugs, for use on line and load side of circuit breaker. Suitable for use with Cu or Al. Special versions available
with taps and screws for control wire connection. Note: S6 and S7 lugs are Al9Cu (90°C); all others Al7Cu (75°C).
For adding onto standard circuit breaker front terminals, extending available connection area for user termination. Suitable
for spaded cable or bus connection. S3 – S5 include terminal covers.
Saddle cable lug kits (Cu cable only)
Suitable for Max Wire Set of 6 List
use with amps range catalog number price
These special non-aluminum cable lugs are for use with copper cable. Lugs are intended for use with copper cable or where
non-aluminum connectors are required (marine, salt or corrosive environments).
Rear cable lug kits (Cu cable only)
Suitable for Max Wire Set of 6 List
use with amps range catalog number price