ABB S3, S4, S5, S6, S7 Catalog Page

...
S4 N 250 B W - 2 xxx
Isomax
Molded case circuit breakers S3 – S8
Isomax
MCCBs
15
Accessories (added in alpha-numeric order)
A = Auxiliary Switch BA = Bell Alarm BA3 = Bell Alarm (S6/S7 only) S_ = Shunt trip with voltage code U_ = Undervoltage release with voltage code
Number of poles
-2 = 2 pole
-4 = 4 pole None = 3 pole
Type connectors
W = None
Trip unit function
B = LI F = LSIG/K C = LSI H = LSIG/D D = Molded Case Switch (MCS) J = LSIG/DT E = LSIG K = LSIG/DTK T = Thermal-magnetic – 10X Mag M = Magnetic only (MCP) G = Thermal-magnetic – 2.5 - 3X Mag 2
Current rating
015 = 15A 250 = 250A 400 = 400A 1200 = 1200A
1
15
Interrupting rating class
B = Basic (240VAC) N = Normal H = High L = Extra High BQ = Basic, 100% rated
NQ = Normal, 100% rated HQ = High, 100% rated LQ = Extra High, 100% rated D = Special molded case switch
(No trip IEC)
Frame size
S3 = 150 / 225A S6 = 600 / 800A S4 = 250A S7 = 1200A S5 = 400A
Low Voltage Products & Systems 15.65
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 000 023 C0201
1 Consult ABB for factory installed accessories. 2 Consult ABB for availability.
Isomax
MCCBs
15
S3B
S3
150/225A Standard thermal-magnetic
S3N S3H S3L
H x W x D
6.70" x 4.13" x 4.07"
Standard S3 package in cludes complete cir cuit break er and mount ing hard ware. Order cable lugs as a separate item, standard copper/ aluminum (Cu/Al) lugs are no charge when or dered with breaker.
General
The S3 breaker family ranges from 15 through 225 amperes. The S3 trip mech a nisms are non-interchangeable and use sen si tive elec tro mag net ic relays for overcurrent trip pro tec tion. Heat sensitive bimetals are used for ther mal over cur rent protection. Short circuit cur rent protection begins at 10 times the
ther mal rating of the breaker and uses a magnetic coil principle.
Versions
To meet all application needs, the S3 is available in various versions: T =Thermal-magnetic
Q =100% UL rated D = Molded case switch M = Magnetic only (MCP)
G = 3X Mag (100 - 225A 3-pole only)
Performance level
Each version is also available in different maximum fault in ter rupt ing levels B = 240VAC
N = Normal H = High
L = Extra high
Number of poles
In UL/CSA form, the S3 is avail able in two pole or three pole versions, both with the same dimensions. A four pole ver sion is also available in UL/ IEC form. For price estimate, add 35% to list price of selected version three pole breaker,
contact ABB Control for details.
15
Accessory mounting
Internal accessories are UL/CSA ap proved for both factory or fi eld installation. Accessories require control ca ble con nec tors. Shunt trips or UVR's mount in the
left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S3 family are suitable for reverse feed applications.
Molded case switches
UL489 switches in clude no overcurrent pro tec tion except for a high in stan ta neous trip mech a nism for self protection. IEC type molded case switches with no trip pro tec tion are also available.
UL/CSA Interrupting capacity (kA RMS) UL489 / CSA C22.2
Voltage N H L
240VAC 65 100 150 480VAC 25 50 85 600VAC 14 14 25 500VDC 35 50 65 600VDC 20 35 50
1
IEC-947 Interrupting capacity (kA RMS)
Voltage N H L
230VAC 65 100 170 380/400/415VAC 35 65 85 440VAC 30 50 65 500VAC 25 40 50 690VAC 14 18 20 500VDC 35 50 65 750VDC 20 35 50
1 15-30A are 65kA at 480VAC
15.66 Low Voltage Products & Systems
1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
Discount schedule S3
S3
Isomax
MCCBs
150/225A Standard thermal-magnetic
S3B
240VAC trip catalog number price catalog number price
175A 1750A S3B175TW-2 S3B175TW S3B 150kA 200A 2000A S3B200TW-2 $ 460 S3B200TW $ 590 225A 2250A S3B225TW-2 S3B225TW
S3N
480VAC trip catalog number price catalog number price
15A 500A S3N015TW-2 S3N015TW 20A 500A S3N020TW-2 S3N020TW 25A 500A S3N025TW-2 S3N025TW 30A 500A S3N030TW-2 35A 500A S3N035TW-2 S3N035TW 40A 500A S3N040TW-2 S3N040TW 50A 500A S3N050TW-2 S3N050TW S3N 25kA 60A 600A S3N060TW-2 S3N060TW
70A 700A S3N070TW-2 S3N070TW 80A 800A S3N080TW-2 90A 900A S3N090TW-2 S3N090TW 100A 1000A S3N100TW-2 S3N100TW
125A 1250A S3N125TW-2 S3N125TW 150A 1500A S3N150TW-2 S3N150TW 175A 200A
225A1 2250A S3N225TW-2 S3N225TW
IC at
Breaker
Breaker
Magnetic 2 pole, 240VAC List 3 pole, 240VAC List
Rating
IC at
Rating
1
1750A S3N175TW-2 911 S3N175TW 1131
1
2000A S3N200TW-2 S3N200TW
Magnetic 2 pole, 600VAC/500VDC List 3 pole, 600VAC/DC List
S3N030TW
$ 316
S3N080TW
407
15
$ 413
504
S3H
Breaker
480VAC trip catalog number price catalog number price
15A 500A S3H015TW-2 S3H015TW 20A 500A S3H020TW-2 S3H020TW 25A 500A S3H025TW-2 S3H025TW 30A 500A S3H030TW-2 35A 500A S3H035TW-2 S3H035TW 40A 500A S3H040TW-2 S3H040TW 50A 500A S3H050TW-2 S3H050TW S3H 50kA 60A 600A S3H060TW-2 S3H060TW
70A 700A S3H070TW-2 S3H070TW 80A 800A S3H080TW-2 90A 900A S3H090TW-2 S3H090TW 100A 1000A S3H100TW-2 S3H100TW
125A 1250A S3H125TW-2 S3H125TW 150A 1500A S3H150TW-2 S3H150TW 175A 200A
225A1 2250A S3H225TW-2 S3H225TW
IC at
Rating
1
1750A S3H175TW-2 1376 S3H175TW 1586
1
2000A S3H200TW-2 S3H200TW
Magnetic 2 pole, 600VAC/500VDC List 3 pole, 600VAC/DC List
S3H030TW
$ 527
S3H080TW
617
$ 619
702
S3L
Breaker
480VAC trip catalog number price catalog number price
15A 500A S3L015TW-2 S3L015TW 25A 500A S3L025TW-2 S3L025TW
30A 500A S3L030TW-2 S3L030TW 35A 500A S3L035TW-2 S3L035TW
40A 500A S3L040TW-2 50A 500A S3L050TW-2 S3L050TW 60A 600A S3L060TW-2 S3L060TW
S3L 80A 800A S3L080TW-2 90A 900A S3L090TW-2 S3L090TW 100A 1000A S3L100TW-2 S3L100TW
125A 1250A S3L125TW-2 1818 S3L125TW 2260 150A 1500A S3L150TW-2 S3L150TW
175A1 1750A S3L175TW-2 S3L175TW 65kA 200A
225A1 2250A S3L225TW-2 S3L225TW
IC at
Rating
65k
70A 700A S3L070TW-2 S3L070TW
85kA
20A 500A S3L020TW-2
Magnetic 2 pole, 600VAC/500VDC List 3 pole, 600VAC/DC List
S3L020TW
$ 634
S3L040TW
634
S3L080TW
816
1
2000A S3L200TW-2 1818 S3L200TW 2260
$ 824
824
1010
15
1 480VAC maximum
Low Voltage Products & Systems 15.67
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 000 023 C0201
Discount schedule S3
S3
Isomax
MCCBs
15
S3NQ
480VAC trip catalog number price
S3HQ
480VAC trip catalog number price
15
IC at
Breaker
15A 500A S3NQ015TW 20A 500A S3NQ020TW 25A 500A S3NQ025TW 30A 500A S3NQ030TW $ 459 35A 500A S3NQ035TW 40A 500A S3NQ040TW 50A 500A S3NQ050TW
S3NQ 70A 700A S3NQ070TW 80A 800A S3NQ080TW 560 90A 900A S3NQ090TW 100A 1000A S3NQ100TW
125A 1250A S3NQ125TW 150A 1500A S3NQ150TW 175A1 1750A S3NQ175TW 1257 200A1 2000A S3NQ200TW 225A1 2250A S3NQ225TW
IC at
Breaker
15A 500A S3HQ015TW 20A 500A S3HQ020TW 25A 500A S3HQ025TW 30A 500A S3HQ030TW 35A 500A S3HQ035TW 40A 500A S3HQ040TW 50A 500A S3HQ050TW S3HQ 50kA 60A 600A S3HQ060TW
70A 700A S3HQ070TW 80A 800A S3HQ080TW 90A 900A S3HQ090TW 100A 1000A S3HQ100TW
125A 1250A S3HQ125TW 150A 1500A S3HQ150TW 175A1 1750A S3HQ175TW 1762 200A1 2000A S3HQ200TW 225A1 2250A S3HQ225TW
150/225A 100% UL rated
Magnetic 3 pole 600VAC/DC List
Rating
60A 600A S3NQ060TW
25kA
Magnetic 3 pole List
Rating
$ 688
780
S3LQ
480VAC trip catalog number price
Note: When applied cor rect ly, UL tested 100% equipment rated breakers may be applied at full rating rather than on the sizing rules of the NEC where breakers and cable are sized based on actual con tin u ous load current divided by 80%. This 100% rating can save the user the cost of larger cable or bus bar. Please consult the NEC for details and other design factors needed for this application.
1 480VAC maximum
15.68 Low Voltage Products & Systems
1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
IC at
Breaker
15A 500A S3LQ015TW 25A 500A S3LQ025TW
30A 500A S3LQ030TW 35A 500A S3LQ035TW
40A 500A S3LQ040TW 50A 500A S3LQ050TW 60A 600A S3LQ060TW
S3LQ 85kA 70A 700A S3LQ070TW 80A 800A S3LQ080TW 90A 900A S3LQ090TW 100A 1000A S3LQ100TW
125A 1250A S3LQ125TW 150A 1500A S3LQ150TW 175A1 1750A S3LQ175TW 2511 200A1 2000A S3LQ200TW 225A1 2250A S3LQ225TW
20A 500A S3LQ020TW
65kA
Magnetic 3 pole List
Rating
$ 916
1123
Discount schedule S3
S3
Isomax
MCCBs
150/225A, 600VAC
15
Magnetic only (MCP)
Magnetic only circuit breakers are instantaneous trip only devices which are Un der writ ers Lab o ra to ries Recognized. MCPs must be used with some other device that will provide over load protection.
Interruption
Typ e
capacity trip catalog number price
240VAC 35kA 3 12 36 S3N003MW 480VAC 18kA 5 20 – 60 S3N005MW 600VAC 10kA 10 40 – 120 S3N010MW
240VAC 35kA $ 568 480VAC 18kA 25 100 – 300 S3N025MW S3N 600VAC 10kA
150 600 – 1500 S3N150MW 929
Interruption
Typ e
capacity trip catalog number price
240VAC 50kA 3 12 36 S3L003MW 480VAC 25kA 5 20 – 60 S3L005MW 600VAC 10kA 10 40 – 120 S3L010MW
$ 710 240VAC 50kA 480VAC 25kA 25 100 – 300 S3L025MW S3L 600VAC 10kA
150 600 – 1500 S3L150MW 1910 480VAC 65kA 200 2 800 – 2400 S3L200MW 1910
240VAC 75kA 480VAC 35kA 600VAC 14kA
240VAC 150kA 480VAC 85kA 600VAC 25kA
50 200 – 600 S3N050MW 633 100 400 – 1200 S3N100MW 763 125 500 – 1500 S3N125MW 929
50 200 – 600 S3L050MW 710 100 400 – 1200 S3L100MW 843 125 500 – 1500 S3L125MW 1910
Magnetic 3 pole List
Amps
Magnetic 3 pole List
Amps
Molded case switches
Interruption
Typ e
capacity 3 trip catalog number price
S3B-D 240VAC 150KA 225 2250A S3B225DW $ 410 240VAC 100kA
480VAC 50kA S3H-D 600VAC 14kA 150 1500A S3H150DW 892 500VDC 65kA 225 2 2250A S3H225DW 1254 600VDC 50kA
Non-UL switches without overcurrent protection
Withstand rating
600VAC 6.5kA
Magnetic 3 pole List
Amps
100 none S3D100W 531 160 none S3D160W 892 250 none S3D250W 1393
Connection options
Wire Set of 2 List Set of 3 List Type range
CU/AL front lugs 14AWG – 2AWG 60 K3TA-2 $ 4 K3TA $ 6 CU/AL front lugs 14AWG – 1/0 100 K4TB-2 4 K4TB 6 CU/ALfront lugs 2AWG – 4/0 150 K4TC-2 4 K4TC 6 CU/AL front lugs 4AWG – 300kcmil 225 K4TD-2 10 K4TD 15
CU front lugs (saddle) 14AWG – 250kcmil 250 K4TES 30 CU rear lugs 6AWG – 250kcmil 250 K4TER
Extended front bar 250 K4ET-250 46
Amps
catalog number price catalog number price
Set of 6
catalog number
15
1 Suggested lugs for circuit breaker up to amps shown. Cable size and type determine maximum amperage. 2 480VAC maximum. 3 With fuse or MCCB protected circuit.
Low Voltage Products & Systems 15.69
ABB Inc. • 888-385-1221 • www.abb-control.com 1SXU 000 023 C0201
Discount schedule SM – S3 MCPs only Discount schedule S3 – Circuit breakers Discount schedule SA – Lugs
Loading...