ABB S280UC Catalog Page

System pro M
S200 Series
14
UL 1077 VDE 0660
K
S280UC
500 VDC Supplemental protectors
14
S281UC-K, 1 pole
S282UC-K, 2 pole
S283UC-K, 3 pole
Rated Catalog List Delivery current number price class
qty
Sugg.
order
Wgt. oz.
(1 pc.)
1 pole
0.2 S281UC-K0.2 $ 104
0.3 S281UC-K0.3 104
0.5 S281UC-K0.5 104
0.75 S281UC-K0.75 1 S281UC-K1 104
1.6 S281UC-K1.6 104 2 S281UC-K2 104 3 S281UC-K3 104 4 S281UC-K4 104 6 S281UC-K6 104 B 10 4.6 8 S281UC-K8 104 10 S281UC-K10 104 16 S281UC-K16 104 20 S281UC-K20 104 25 S281UC-K25 108 32 S281UC-K32 110 40 S281UC-K40 116 50 S281UC-K50 136 63 S281UC-K63 152
104
2 pole
0.2 S282UC-K0.2 242
0.3 S282UC-K0.3 242
0.5 S282UC-K0.5 242
0.75 S282UC-K0.75 242 1 S282UC-K1 242
1.6 S282UC-K1.6 242 2 S282UC-K2 242 3 S282UC-K3 242 4 S282UC-K4 242 B 5 9.2 6 S282UC-K6 242 8 S282UC-K8 242 10 S282UC-K10 242 16 S282UC-K16 242 20 S282UC-K20 242 25 S282UC-K25 248 32 S282UC-K32 256 40 S282UC-K40 266 50 S282UC-K50 312 63 S282UC-K63 348
Rated Catalog List Delivery current number price class
qty
Sugg.
order
3 pole
0.2 S283UC-K0.2 $ 370
0.3 S283UC-K0.3 370
0.5 S283UC-K0.5 370
0.75 S283UC-K0.75 370 1 S283UC-K1 370
1.6 S283UC-K1.6 370 2 S283UC-K2 370 3 S283UC-K3 370 4 S283UC-K4 370 6 S283UC-K6 370 8 S283UC-K8 370 10 S283UC-K10 370 16 S283UC-K16 370 20 S283UC-K20 370 25 S283UC-K25 382 32 S283UC-K32 408 40 S283UC-K40 448 50 S283UC-K50 472 63 S283UC-K63 534
B 3 13.9
Delivery Class
A - Standard item, stock to 2 weeks lead time B - Stock to 4 weeks lead time C - 6 to 8 week lead time
Wgt. oz.
(1 pc.)
Direct current applications
The S280UC differs from standard miniature circuit breakers in that the UC versions include a permanent magnet which aids in the extinguishing of the arc during medium and high level faults. It is necessary to observe the correct polarity and current direction when connecting the UC breakers. Two examples of correct connection are shown below.
10,000
5000
1000
500
100
50
10
5
1
0.5
0.1
seconds
0.05
0.01 1 2 3 5 10 20 30
multiple of ratedcurrent
DC
Termination points are marked on all UC type MCBs, points one (1) and four (4) are negative and points two (2) and three (3) are positive. Four pole breakers are also available for voltage reversal applications.
14.12 Low Voltage Products & Systems
1SXU 000 023 C0201 ABB Inc. • 888-385-1221 • www.abb-control.com
UC-K
250VDC 500VDC
Single Pole
L- L+
-1 2
+
Discount schedule CB7
Maximum voltage between leads
S281UC
LOA
D
-+
Two Pole
L- L+
S282UC
L- L+
-1
-1
+2
+2
LOAD
- +
LOAD
-+
3+ 4-
3+ 4-