System pro M
Technical data
Industrial Miniature Circuit-Breakers
S 220 series
No. of poles: 1-, 2- and 3-pole
specifications: IEC 60947-2, EN 60898-1,
VDE 0641 T11
rated current In: 0.2 to 63 A
internal nominal internal resistance power loss
resistance: current per pole per pole
/A m W
I
n
0.2 32000 1.3
0.3 13500 1.2
0.5 6400 1.6
0.75 2900 1.6
1 1400 1.4
1.6 630 1.6
2 420 1.7
3 160 1.4
4 120 1.9
6 47 1.7
8 34 2.2
10 9.6 1
16 7.6 2.0
20 5.1 2.1
25 4.4 2.8
32 3.3 3.4
40 2.6 4.2
50 1.7 4.3
63 1.6 6.4
connection: individual or busbar
terminals: combined box terminal with
M5 screw
connection capacity (Cu): 1 x 25 mm
2
or 2 x 10 mm
2
for finely stranded to massive
conductors
min. cross section 1 mm
2
protection according to
IEC 60529, EN 60529, VDE 0470: IP 20
size: DIN 43 880, frame size 1
depth of device: 83 mm
dimensions: see illustrations on page 15
mounting position: optional
fixing: snap-on onto DIN rails-
EN 60 715, 35 mm width,
screw fixing by means of
mounting plate(see
Accessories)
climatic resistance: constant climate
according to DIN 40 046 23/83, 40/93, 55/20 (°C/Rh)
or, as applicable, IEC 60068: alternating climate (24 h cycle)
25/95 – 40/93 (°C/Rh)
ambient temperature: T
+ 55 °C, T
max
– 25 °C
min
shock resistance: 10 g at least 20 impacts
shock duration 13 ms
vibration resistance: 5 g, at least 30 minutes
mechanical service life: 20,000 operations
service life at rated load 20,000 operations, I
and operating voltage: 4,000 operations, I
0,2 … 32 A
n
40 … 63 A
n
specifications: VDE 0660, IEC 60 947-2
operating voltage Un: 1-pole 400/690 V 60 V ...—
multi-pole 690 V 110 V ...—
The tripping values for electromagnetic trip
releases are valid for AC values from 16
60 Hz. Deviating frequencies or DC current
will cause the tripping characteristics to
change as is indicated in the table on page 6.
min. rated 12 V , 12 V ...—
voltage U
insulation group C at 500 V
acc. to former VDE 0110: B at 750 V
: (with respect to contact stability)
Bmin
compareable to
}
overvoltage category III
pollution degree 2
trip-free mechanism: miniature circuit-breaker
and auxiliary switch
housing: plastic, gray RAL 7035
operating lever: black, in ON and OFF position
sealable;
lockable with lock adapter
(see Accessories)
2
/3 to
Auxiliary switch S 220-H 11
terminal: M 3.5 screw
with captive clamping
washer
connection capacity (Cu): 2 x 0.75 … 2.5 mm
… 1.5 mm
with connector sleeve
permanent currentI
rated current I
:5 A
th2
at: 220 V :5 A
n
400 V :2 A
60 V ...—: 2 A
110 V ...— : 1.5 A
250 V ...—: 1 A
min. switching capacity: 5 VA
2
2
5