ABB S200U, S200UP, SU200PR, S200UDC Technical Data

Technical data
S200U, S200UP, SU200PR & S200UDC UL 489, CSA 22.2 No. 5
Miniature
circuit breakers
S200
Technical data
Specifications: UL 489, C 22.2 No. 5, IEC 60947-2 UL 489, VDE 0660 UL File-Number: E 212323, UL, Current limiting series ratings E212323, UL No. of poles: 1, 2, 3 & 4 1, 2 Tripping characteristics: K, Z K K, Z Rated current: 0.2 (K) 0.5 (Z) ... 63 A 0.2 (K) 0.5 (Z) ... 25 A 0.2 ... 63A 1 - 63 A
Rated voltage:
Short circuit capacity: 10 kA 14 kA Frequency: 50/60 Hz 50/60 Hz Degree of protection: IP 20 Mounting position: Vertical and horizontal Any Vertical and horizontal Fixing: 35 mm DIN rail 35 mm DIN rail Clamps only for Cu: 18-4 AWG (0.75 … 25 mm Service life, mech. and at rated
load:
Tightening torque: 25 in. lbs (2.8 Nm) 25 in. lbs (2.8 Nm)
Ambient temperature: – 25 °C … + 55 °C/– 13 °F … + 131 °F
Shock resistance: 30 g at least 2 impacts shock, duration 13 ms 25 g, 2 shocks - 13ms
S200U S200UP SU200PR S200UDC
Single pole: 277VAC (<=35A);
Single pole: 240VAC
Multi pole: 240VAC
20,000 operations
Single pole: 277VAC
Multi pole: 480Y/277VAC
2
) 18-4 AWG (0.75 … 25 mm2)
240VAC (>35A)
Multi pole: 480Y/277VAC (<=35A);
240VAC (>35A)
IP20, IP40 in enclosure w/cover
6000 operations (AC)
1 cycle (1s-ON, 9S-OFF)
20,000 operations
– 25 °C … + 55 °C/– 13 °F …
30 g at least 2 impacts shock,
1P: 60 V DC
2P:125 V DC 1
IP 20
+ 131 °F
duration 13 ms
Auxiliary contact S2C-H6RU and S2C-S6RU
Rated current: 10
Rated voltage AC / DC: 24 Contact: 1 pole double throw Connection capacity mm Tightening torque: 11 in.Ibs (1.2 Nm) Shock resistance acc. to DIN IEC 68-2-6: 5 g, 20 frequency cycles 5...150...5 Hz at 24 VAC/DC, 5 mA auto-reclosing < 10 ms Mechanical service life: 10,000 operations
Shunt trip Type
Rated voltage AC
Max. release duration ms < 10 < 10 Min. release voltage AC
Consumption on release AC
Coil resistance Terminals AWG/mm Tightening torque in.Ibs/Nm 18 / 2 18 / 2
2
18 – 14 AWG (0.75…2.5 mm2)
S2C-A1U S2C-A2U
DC
DC
DC
V V
V V
VA VA
Ω
2
12 ... 60 12 ... 60
7
10
40 ... 200 40 ... 200
3.7 225
18…6 / 0.75 – 16 18…6 / 0.75 – 16
110 ... 415 110 ... 250
55 ... 210 55 ... 110
15
55
80
1 Poles connected in series.
Low Voltage Products & Systems 15.13
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A
Miniature
S200
circuit breakers
Technical data
S200U, S200UP, SU200PR & S200UDC UL 489, CSA 22.2 No. 5
Internal resistance and power loss
Internal resistance per pole in mz, power loss per pole in W.
Type Rated
S200U
S200UP
current
A
0.2 42500 1.7
0.3 20000 1.8
0.5 6340 1.6 10100 2.5
0.75 2500 1.4 – 1 1400 1.4 2270 2.3
1.6 625 1.6 1100 2.8
2 460 1.8 619 2.5 3 211 1.9 211 1.9 4 163 2.6 163 2.6
6 67 2.4 104 3.7 8 45 2.9 55 3.5 10 19 1.9 21 2.1
13 – 16 8.2 2.1 10.9 2.8
20 7.3 2.9 7.3 2.9
25 5.6 3.5 5.6 3.5 32 4.1 4.2 4.1 4.2 40 4.0 6.4 4.0 6.4
50 1.2 3.0 1.8 4.4 63 1.3 5.2 1.3 5.2
Device series
K
mz
W
SU200PR
Rated current Internal resistance per pole
A
0.2 25300 1.01
0.3 13700 1.23
0.5 4740 1.19
15
4)
specic conditions and are therefore to be considered as typical values.
0.75 2067 1.16
1 1270 1.27
1.5 610 1.56
2 442 1.77
3 140 1.26
4 109 1.75
5 50 1.26
6 54 1.94
8 22 1.41
10 18.2 1.82
13 14.8 2.50
15 8.1 1.83
16 11.1 2.83
20 8.5 3.40
25 5.5 3.43
30 3.8 3.39
32 4.6 4.70
35 3.9 4.76
40 2.8 4.40
50 1.7 4.25
60 1.7 6.18
63 1.9 7.56
Internal resistances and power loss are subject to application-specic and environment-
m
1)
Power loss per pole
Device series
Z
mz
W
Type Rated
W
S200UDC
1)
current
A
1 1400 1.4 2270 2.3
1.6 625 1.6 1100 2.8
2 460 1.8 619 2.5 3 211 1.9 211 1.9 4 153 2.6 163 2.5
6 67 2.4 104 3,7 8 45 2.9 55 3.5
10 19 1.9 21 2.1
13 – 16 8.2 2.1 10.9 2.8
20 7.3 2.0 7.3 2.9
25 5.6 3.5 5.6 3.5 32 4.1 4.2 4.1 4.2 40 4.0 6.4 4.0 6.4
50 1.2 3.0 1.8 4.4 63 1.3 5.2 1.3 5.2
Device series
K
mz
Device series
Z
W
mz
W
15.14 Low Voltage Products & Systems
1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Loading...
+ 1 hidden pages