Data Sheet
System pro M compact®
Supplementary protector S 200 PR
for ring-tongue applications acc. to UL1077
2CDC021026S0011
The S 200 PR is a high-performance
supplementary protector with ring
cable lug connections conforming to
UL, CSA, and IEC standards. The
integrated captive connecting screws
simplify the connection of electric lines,
provides extra protection and saves
time. This supplementary protector is
a valuable addition to the well-known
®
system pro M compact
range which
allow most of the UL1077, CSA 22.2
No. 235 and IEC-approved components
to be combined effortlessly with the new
model line.
2CDC021016S0012
Standards and approvals
Standards
UL 1077
CSA 22.2. No. 235
IEC/EN 60947-2
Approvals
UL 1077 US
CSA 22.2 No.235 CA
VDE DE
Supplementary protector S 200 PR
Technical data
General Data
Standards UL1077, CSA 22.2 No. 235, IEC/EN 60947-2
Poles 1P, 2P, 3P, 4P
Rated current I
Rated frequency f 50/60 Hz
Tripping characteristics K
IEC/EN 60947-2
Rated operational voltage U
Power frequency recovery voltage U
Min. operating voltage 12 V AC
Rated insulation voltage U
Rated ultimate short-circuit breaking capacity I
Rated service short-circuit breaking capacity I
Overvoltage Category III
Pollution Degree 2
Rated impulse withstand voltage U
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics 20 °C
Electrical endurance I
UL / CSA
Rated voltage 1P: 277 V AC, 2 ... 4P: 480Y/277 V AC
Rated interrupting capacity 10 kA
Application Ring tongue terminal, not for general use
Reference temperature for tripping characteristics 25 °C
Electrical endurance 6,000 ops. (AC), 1 cycle (1s.-ON, 9s.-OFF)
Mechanical data
Housing Insulation group I, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Real CPI (green OFF / red ON)
Protection degree acc. to EN 60529 IP20, IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g - 2 shocks - 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5g - 20 cycles at 5 ... 150 ... 5 Hz at 0.8 I
Environmental conditions acc. to DIN EN 60068-2-30 28 cycles with 55 °C/90-96 % and 25 °C/95-100%
Ambient temperature -25 ... +55 °C
Storage temperature -40 ... +70 °C
Installation
Terminal Ring Tongue Terminal
Cross section of conductors (top/bottom) 18 - 4 AWG
Torque 2.8 Nm
Screw driver No. 2 Pozidrive
Mounting On DIN rail 35 mm, acc. to EN 60 715 by fast clip
Mounting position any
Supply side top or bottom
Dimensions and weight
Mounting dimensions acc. to DIN 43880 Mounting dimension 1
Pole dimensions (H x D x W) 100 x 69 x 17.5
Pole weight approx. 125 g
Combination with auxiliary elements
Integrated auxiliary switch No
Signal contact/auxiliary switch, shunt trip, undervoltage release Ye s
0.2 - 63 A
n
1P: 230 V AC, 2 ... 4P: 400 V AC
n
max
i
cu
cs
(1.2/50µs) 4 kV (test voltage 6.2 kV at sea level; 5 kV at 2000 m)
imp
1P: 253 V AC, 2 ... 4P: 440 V AC
250 V AC (phase to ground), 500 V AC (phase to phase)
15 kA
11.2 kA (≤40 A); 7.5 kA (>40 A)
≤ 25 A: 20,000 ops., In > 25 A: 10,000 ops.
n
25 in-Ibs.
n
2 - 2CDC002138D0201
Supplementary protector S 200 PR
Tripping characteristic, internal resistance and power loss
Tripping characteristic K
Rated current Thermal release
Currents:
conventional
non-tripping
current
I
n
0.5 to 63 A 1.05 · I
1)
The thermal releases are calibrated to a nominal reference ambient temperature; for K the reference value is 20 °C.
In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise.
2)
The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency.
3)
As from operating temperature (after I1 > 1 h or, as applicable, 2 h)
I
1
1.05 · I
n
n
1)
conventional
tripping
current
I
2
1.2 · I
n
1.2 · I
n
Electromagnetic release
Tripping time Currents:
hold
current
surges
> 1 h
< 1 h not applicable
> 2 h
< 1 h
3)
10 · I
n
2)
trip
at least at
14 · I
n
Tripping time
> 0.2 s
< 0.2 s
K characteristic
Internal resistance and power loss
2CDC 022 005 F0211
4)
environment-specific conditions and are therefore to be considered as typical
values.
Rated current Internal resistance
per pole
A
mΩ
4)
Power loss
per pole
4)
W
0.2 25300 1.01
0.3 13700 1.23
0.5 4740 1.19
0.75 2067 1.16
1 1270 1.27
1.5 610 1.56
2 442 1.77
3 140 1.26
4 109 1.75
5 50 1.26
6 54 1.94
8 22 1.41
10 18.2 1.82
13 14.8 2.50
15 8.1 1.83
16 11.1 2.83
20 8.5 3.40
25 5.5 3.43
30 3.8 3.39
32 4.6 4.70
35 3.9 4.76
40 2.8 4.40
50 1.7 4.25
60 1.7 6.18
63 1.9 7.56
Internal resistances and power loss are subject to application-specific and
2CDC002138D0201 - 3