ABB S 200 M UC Catalog

System pro M compact®
Miniature Circuit Breaker S 200 M UC for DC and AC applications
2CDC021031S0011
The miniature circuit breaker S 200 M UC extends the established ABB System pro
M
compact® product range with an MCB for DC and AC applications. The S 200 M UC has an impressive performance range with multiple approvals. Its high inbuilt short circuit breaking capacity across the entire model line, flexible AC and DC application, and approval and compliance in accordance with all major international and local standards make it truly unique.
M
All current System pro
compact® accessories can be easily combined with the new model line. Whether warehousing or project engineering, planning, installing or maintaining your equipment, the S 200 M UC is a simple and flexible solution.
2CDC021033S0011
Standards
IEC/EN 60898-2
IEC/EN 60947-2
UL 1077
GB 10963.2 (on request)
GB 14048.2 (on request)
Approvals
VDE DE
UL 1077 US
CSA 22.2 NO.235 CA
CCC PRC (on request)
GL DE (on request)
BV FR
LRS GB
DNV NO
RINA IT
SABS SA (on request)
CCS PRC (on request)
RMRS RU
EAC RU
GOST Fire RU
IMQ IT
KEMA NL
Miniature Circuit Breaker S 200 M UC
Technical Data
General Data
Standards IEC/EN 60898-2, IEC/EN 60947-2, UL1077, CSA 22.2 No. 235
Poles 1P, 2P, 3P, 4P
Rated current I
Rated frequency f 0/50/60 Hz
Rated insulation voltage U
Overvoltage category III
Pollution degree 2
IEC/EN 60898-2
Tripping characteristics B, C
Rated operational voltage U
Max. power frequency recovery voltage U
Min. operating voltage 12 V AC – 12 V DC
Rated short-circuit capacity I
Energy limiting class (B, C up to 40A) 3
Rated impulse withstand voltage U
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics 30 °C
Electrical endurance I
IEC/EN 60947-2
Tripping characteristics B, C, K, Z
Rated operational voltage U
Max. power frequency recovery voltage U
Min. operating voltage 12 V AC – 12 V DC
Rated ultimate short-circuit breaking capacity I
Rated service short-circuit breaking capacity I
Rated impulse withstand voltage U
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics B, C
K, Z
Electrical endurance I
UL 1077/CSA 22.2 No. 235
Tripping characteristics C, K, Z
Rated voltage 1P: 277 V AC, 250 V DC
Rated interrupting capacity 6 kA (AC); 10 kA (DC)
Application Supplemental protection, for general use. TC1, OL0, SC:U1
Reference temperature for tripping characteristics 25 °C
Electrical endurance 6,000 ops., 1 cycle (1s.-ON, 9s.-OFF)
0.2 - 63 A
n
i
1P: 230 V AC, 220 V DC
n
253 V AC (phase to ground), 440 V AC (phase to phase)
2P: 400 V AC, 440 V DC
3...4P: 400 V AC*
max
1P: 253 V AC, 250 V DC
2P: 440 V AC, 500 V DC
3...4P: 440 V AC*
cn
(1.2/50µs) 4 kV (test voltage 6.2 kV at sea level; 5 kV at 2,000 m)
imp
e
10 kA
≤ 25 A: 20,000 ops. (AC), In > 25 A: 10,000 ops. (AC); 1,000 ops. (DC)
n
1P: 253 V AC, 220 V DC
2...4P: 440 V AC, 440 V DC
max
1P: 266 V AC, 250 V DC
2...4P: 462 V AC, 500 V DC
cu
≤40 A: 10 kA (AC); 10 kA (DC)
>40 A: 6 kA (AC); 10 kA (DC)
cs
≤40 A: 7.5 kA (AC); 10 kA (DC)
>40 A: 6 kA (AC); 10 kA (DC)
(1.2/50µs) 4 kV (test voltage 6.2 kV at sea level; 5 kV at 2,000 m)
imp
55 °C
20 °C
≤ 25 A: 20,000 ops. (AC), In > 25 A: 10,000 ops. (AC); 1,500 ops. (DC)
n
2...4P: 480Y/277 V AC, 500 V DC
2 1SXU400144L0201 | Miniature Circuit Breaker S 200 M UC
Miniature Circuit Breaker S 200 M UC
Technical Data
Mechanical data
Housing Insulation group I, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Real CPI (green OFF/red ON)
Protection degree acc. to DIN EN 60529 IP20, IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g - 2 shocks - 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5 g - 20 cycles at 5 ... 150 ... 5 Hz at 0.8 I
Environmental conditions (damp heat cyclic)
acc. to IEC/EN 60068-2-30
Ambient temperature -25 ... +55 °C
Storage temperature -40 ... +70 °C
Installation
Terminal Fail-safe bi-directional cylinder-lift terminal
Cross-section of conductors (top/bottom) Solid, stranded: 35 mm² / 35 mm²
Cross-section of busbars (top/bottom) 10 mm² / 10 mm²
Torque IEC 2.8 Nm
UL 18 in-Ibs.
Screwdriver No. 2 Pozidriv
Mounting On DIN rail 35 mm, acc. to EN 60715 by fast clip
Mounting position Any
Supply Please note polarity of device
Dimensions and weight
Mounting dimensions acc. to DIN 43880 1
Pole dimensions (H x D x W) 85 x 69 x 17.5
Pole weight Approx. 125 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal contact Yes
Shunt trip Yes
Undervoltage release Ye s
Motor operating device Yes
28 cycles with 55 °C/90-96 % and 25 °C/95-100 %
flexible: 25 mm
14 – 4 AWG (Cu only)
14 – 8 AWG
2
/ 25 mm
2
n
Miniature Circuit Breaker S 200 M UC | 1SXU400144L0201 3
Miniature Circuit Breaker S 200 M UC
Tripping characteristics
B characteristic C characteristic
K characteristic
2CDC022015F0214
2CDC022017F0214
Z characteristic
4 1SXU400144L0201 | Miniature Circuit Breaker S 200 M UC
2CDC022010F0211
2CDC022060F0211
Miniature Circuit Breaker S 200 M UC
Derating
For installations of miniature circuit breakers at temperatures other than the referenced value and installations of several miniature circuit breakers directly side by side, derating factors must be considered.
Deviating ambient temperature
The rated value of the current of a miniature circuit breaker refers to a temperature of 20 °C for circuit-breakers with characteristics K and Z and 30 °C for characteristics B and C. The following table contains the derating of load capability of S 200 M UC MCBs with temperatures from -40 °C to 70 °C for the curves B, C, K, and Z.
Tripping Rated Maximum operating current at ambient temperature T
characteristics current
I
n
A - 40 - 30 - 20 - 10 0 10 20 30 40 50 60 70
B, C 0.5 0.61 0.59 0.58 0.56 0.55 0.53 0.52 0.50 0.49 0.47 0.46 0.44
1.0 1.21 1.18 1.15 1.12 1.09 1.06 1.03 1.00 0.97 0.94 0.91 0.88
1.6 1.94 1.89 1.84 1.79 1.74 1.70 1.65 1.60 1.55 1.50 1.46 1.41
2.0 2.42 2.36 2.30 2.24 2.18 2.12 2.06 2.00 1.94 1.88 1.82 1.76
3.0 3.63 3.54 3.45 3.36 3.27 3.18 3.09 3.00 2.91 2.82 2.73 2.64
4.0 4.84 4.72 4.60 4.48 4.36 4.24 4.12 4.00 3.88 3.76 3.64 3.52
6.0 7.26 7.08 6.90 6.72 6.54 6.36 6.18 6.00 5.82 5.64 5.46 5.28
8.0 9.68 9.44 9.20 8.96 8.72 8.48 8.24 8.00 7.76 7.52 7.28 7.04
10.0 12.10 11.80 11.50 11.20 10.90 10.60 10.30 10.00 9.70 9.40 9.10 8.80
13.0 15.70 15.30 15.00 14.60 14.20 13.80 13.40 13.00 12.60 12.20 11.80 11.40
16.0 19.40 18.90 18.40 17.90 17.40 17.00 16.50 16.00 15.50 15.00 14.60 14.10
20.0 24.20 23.60 23.00 22.40 21.80 21.20 20.60 20.00 19.40 18.80 18.20 17.60
25.0 30.30 29.50 28.80 28.00 27.30 26.50 25.80 25.00 24.30 23.50 22.80 22.00
32.0 38.70 37.80 36.80 35.80 34.90 33.90 33.00 32.00 31.00 30.10 29.10 28.20
40.0 48.40 47.20 46.00 44.80 43.60 42.40 41.20 40.00 38.80 37.60 36.40 35.20
50.0 60.50 59.00 57.50 56.00 54.50 53.00 51.50 50.00 48.50 47.00 45.50 44.00
63.0 76.20 74.30 72.50 70.60 68.70 66.80 64.90 63.00 61.10 59.20 57.30 55.40
K, Z
0.5 0.59 0.58 0.56 0.55 0.53 0.52 0.50 0.49 0.47 0.46 0.45 0.44
1.0 1.18 1.15 1.12 1.09 1.06 1.03 1.00 0.97 0.94 0.91 0.88 0.85
1.6 1.89 1.84 1.79 1.74 1.7 1.65 1.60 1.55 1.50 1.46 1.42 1.38
2.0 2.36 2.3 2.24 2.18 2.12 2.06 2.00 1.94 1.88 1.82 1.77 1.72
3.0 3.54 3.45 3.36 3.27 3.18 3.09 3.00 2.91 2.82 2.73 2.65 2.57
4.0 4.72 4.60 4.48 4.36 4.24 4.12 4.00 3.88 3.76 3.64 3.53 3.42
6.0 7.08 6.90 6.72 6.54 6.36 6.18 6.00 5.82 5.64 5.46 5.30 5.14
8.0 9.44 9.20 8.96 8.72 8.48 8.24 8.00 7.76 7.52 7.28 7.06 6.85
10.0 11.80 11.50 11.20 10.90 10.60 10.30 10.00 9.70 9.40 9.10 8.83 8.57
13.0 15.30 15.00 14.60 14.20 13.80 13.40 13.00 12.60 12.20 11.80 11.45 11.11
16.0 18.90 18.40 17.90 17.40 17.00 16.50 16.00 15.50 15.00 14.60 14.16 13.74
20.0 23.60 23.00 22.40 21.80 21.20 20.60 20.00 19.40 18.80 18.20 17.65 17.12
25.0 29.50 28.80 28.00 27.30 26.50 25.80 25.00 24.30 23.50 22.80 22.12 21.46
32.0 37.80 36.80 35.80 34.90 33.90 33.00 32.00 31.00 30.10 29.10 28.23 27.38
40.0 47.20 46.00 44.80 43.60 42.40 41.20 40.00 38.80 37.60 36.40 35.31 34.25
50.0 59.00 57.50 56.00 54.50 53.00 51.50 50.00 48.50 47.00 45.50 44.14 42.82
63.0 74.30 72.50 70.60 68.70 66.80 64.90 63.00 61.10 59.20 57.30 55.58 53.91
°C
Influence of adjacent devices
If several miniature circuit breakers are installed directly side by side with high load on all poles, a correction factor must be applied to the rated current (see table). If distance pieces are used, the factor does not apply.
No. of adjacent devices Factor F
1 1
2, 3 0.9
4, 5 0.8
≥ 6 0.75
Miniature Circuit Breaker S 200 M UC | 1SXU400144L0201 5
Loading...
+ 11 hidden pages